Yokogawa VJU7 User Manual

User’s
/ /
Manual
IM 77J01U07-01E
Model VJU7 Universal Temperature Converter (Isolated Single-output and Isolated Dual-output Types)
1. CAUTIONARY NOTES FOR SAFE USE OF THE PRODUCT
This user’s manual should be carefully read before installing and operating the product. The following symbol is used on the product and in this manual to eusure safe use.
WARNING
This symbol is displayed on the product when it is necessary to refer to the users manual for infor­mation on personnel and instrument safety. This symbol is displayed in the users manual to indi­cate precautions for avoiding danger to the opera­tor, such as an electric shock.
The following symbols are used only in this manual.
IMPORTANT
Indicates that operating the hardware or software in a particular manner may cause damage or result in a system failure.
NOTE
Draws attention to essential information for under­standing the operations and/or functions of the product.
4. MODEL AND SUFFIX CODES
VJU7-0 -
Model Number of outputs
1: 1 output 2: 2 outputs
Power supply 6: 100-240 V AC/DC 7: 15-30 V DC (Operating range: 12 to 36 V)
Input signal U: Thermocouple, RTD, mV signal
Output-1 signal A: 4 to 20 mA DC 6: 1 to 5 V DC Z: (Custom Order) DC current or voltage signal
Output-2 signal A: 4 to 20 mA DC 6: 1 to 5 V DC P: Communication function (RS-485) T: Alarm output (2 relay contacts) N: No output-2 signal
Optional specification Blank: With socket
SN: Without socket RJCN: Without RJC sensor
(Operating range: 85 to 264 V)
2.
CHECKING PRODUCT SPECIFICATIONS AND PACKAGED ITEMS
(1) Model and Specifications Check
Check that the model and specifications indicated on the nameplate attached to the side face of the main unit are as ordered.
(2) Contents of the Package
Check that the package contains the following items:
VJU7: 1
User’s manual (this manual: IM 77J01U07-01E): 1
Accessories:
Tag number label: 1 sheet
Range label: 1 sheet
RJC sensor (when /RJCN is not specified for the
optional specification): 1
3. GENERAL
This plug-in type Universal Temperature Converter receives thermocouple, RTD or mV signal and converts it into isolated DC voltage or current signal.
Settings of the input type (thermocouple, RTD or mV) and measurement range can be changed within the specified ranges.
One of DC voltage signal, DC current signal, communi­cation function (RS-485) and alarm output (2 relay con­tacts) can be selected for the output-2 signal.
Keep this manual in a safe place.
Network Solutions Business Divisiion
2-9-32, Naka-cho Musashino-shi, Tokyo 180-8750 Japan Phone: +81-422-52-7179 Facsimile: +81-422-52-6619
IM 77J01U07-01E ©Copyright Nov. 1999 4th Edition: Feb. 2007
2
5. MOUNTING METHODS
5.1 Wall Mounting
Loosen the main unit-fixing screw to disconnect the main unit from the socket. Next, anchor the socket onto the wall with screws. Then, plug the main unit into the socket and se­cure the main unit with the main unit-fixing screw.
Socket
Main unit
Main unit-fixing screw
<Mounting Dimensions>
29.5 or more 22±0.2
59±0.3
2-M4 or 2-ø4.5 or more
5.2 DIN Rail Mounting
Locate the VJU7 so that the DIN rail fits into the upper part of the DIN-rail groove at the rear of the socket, and fasten the socket using the slide lock at the lower part of the socket.
Fit into here
DIN rail
Push
DIN rail
Hole for main unit-fixing screw
Mounting screws
Unit: mm
(Rear of the socket)
Slide lock
DIN rail
6. INSTALLATION LOCATIONS
Avoid the following environments for installation locations: Areas with vibrations, corrosive gases, dust, water, oil, solvents, direct sunlight, radiation, a strong electric field, and/or a strong magnetic field.
If there is any risk of a surge being induced into the power line and/or signal lines due to lightning or other factors, a dedicated lightning arrester should be used as protection for both the product and a field-installed device.
7. EXTERNAL WIRING
WARNING
To avoid the risk of an electric shock, turn off the power supply and use a tester or similar device to ensure that no power is supplied to a cable to be connected, before carring out wiring work.
Wiring should be connected to the terminals on the socket of the VJU7. The terminals for external connections are of M3 screws. Use crimp-on lugs for connections to the terminals.
Be sure to use a compensating lead wire for thermo­couple input. Recommended cables: A nominal cross-sectional area of 0.5 mm2 or thicker for output signal cable, a nominal cross-sectional area of 1.25 mm2 or thicker for power cable and shielded twisted-pair cable (AWG24) for com­munication cable.
RJC sensor
Input signal
Make the wiring resistance of RTD input terminals 1 and 3 the same.
Recommended crimp-on lug size
(Unit: mm)
(Input type can be changed.)
mV
+
1
3
5.5 or less
(for thermocouple input)
RTD
Thermocouple
A
1
B
3
B
4
Power supply
Signal line
RJC sensor
Terminal screw
ø3.2 to 3.5
5.5 or more
RJC
L+
N–
GND
+
1
3
4
10
11
8
Ouptut-1 signal
Analog output
3 2
7
9
56
1011
+
Output-2 signal
Analog output
+
2
5
Alarm output
1
4
789
2
5
6
RS-485
B+
2
A–
5
6
COM
ALM1
(NO)
COM
ALM2
(NO)
5.3 Mounting Using a Multi-mounting Base
For mounting using a multi-mounting base, see the user’s manual for VJCE (VJ Mounting Base).
5.4 Using a Duct
Wiring duct should be installed at least 30 mm away from the top and bottom faces of the main unit.
IMPORTANT
Connect the RJC sensor at the correct position as shown above. Otherwise tempratures cannot be measured carrectly.
Conect the RJC sensor so that it overlaps the in­put signal line.
Handle the RJC sensor lead wire care to prevent disconnection.
All Rights Reserved. Copyright © 1999, Yokogawa M&C Corporation IM 77J01U07-01E 4th Edition Feb. 09, 2007-00
(
)
[
]
e
d
Use of the product ignoring the specifications may cause overheating or damage. Before turn­ing on the power, ensure the following:
(a)Power supply voltage and input signal value
applied to the product should meet the required specifications.
(b)The external wiring to the terminals and wiring to
ground are as specifications.
Do not operate the product in the presence of flammable or explosive gases or vapors. To do so is highly dangerous.
The product is sensitive to static electricity; ex­ercise care in operating it. Before you operate the product, touch a nearby metal part to dis­charge static electricity.
If an inductance (L) load such as auxiliary relays or solenoid valves is used, always insert a spark killer for diminishing sparks, such as a CR filter or a diode in parallel with the inductance load. Otherwise a malfunction or relay failure may oc­cur. Refer to the following guidelines for a ca­pacitor and resistor: Capacitor : 0.5 to 1 mF with respect to a contact
current of 1 A
Resistor: 0.5 to 1 W with respect to a contact
voltage of 1 V
The power line and input/output signal lines should be installed away from noise-generating sources. Otherwise accuracy cannot be guaran­teed.
The grounding resistance must be 100 W (JIS Class D grounding). The length and thickness of the grounding cable should be as short and thick as possible. Directly connect the lead from the ground terminal (terminal no. 8) of the prod­uct to the ground. Do not carry out daisy­chained inter-ground terminal wiring.
8. DESCRIPTION OF FRONT PANEL ND CONNECTION OF SETTING OOLS
8.1 Front Panel
The communications connector on the front panel is used for setting up parameters using a PC (VJ77 PC-based Param­eters Setting Tool) or the Handy Terminal (JHT200). The alarm indicator lamps for alarm 1 and alarm 2 light up if an alarm occurs. (The alarm indicator lamps are added only when the alarm output is specified for the output-2 signal.)
Communication connector
Alarm indicator lamp
(for alarm 1)
Alarm indicator lamp
(for alarm 2)
Fig. 8.1 Front Panel
8.2 Connecting the Setting Tools
Connect the modular jack conversion adapter (E9786WH) to the JUXTA communication cable with 5-pin connector (F9182EE) and then connect this adapter to the communica­tion connector of JUXTA.
ALM1
ALM2
3
JUXTA communication cable with 5-pin connector (F9182EE)
JHT200 Handy Terminal
PC with th VJ77 installe
Fig. 8.2 Connecting the Setting Tools
Note: The modular jack conversion adapter does not
9. SETTING PARAMETERS
Set the parameters using a PC (VJ77 PC-based Parameters Setting Tool) or the Handy Terminal (JHT200). Refer to the list of parameters in this manual and the users manual for VJ77 PC-based Parameters Setting Tool (IM 77J01J77-01E) or JHT200 Handy Terminal (IM JF81-02E).
NOTE
For the input sensor type, input type and tempera­ture unit, the default values of the input range, alarm setpoints and others are pre-defined accord­ing to the values to be selected. Set the parameters as follows.
1. Settings related to inputs: Set the parameters in
2. Before setting the parameters related to alarm
9.1 Settings Related to Input and Output
9.1.1 Input Sensor Type and Input Type
Select the input sensor type in D07: SENSOR TYPE. Select TC for thermocouple input, mV for mV input and RTD for RTD input. When you have selected TC in D07, select the TC type to use in D08: TC TYPE. When you have selected RTD in D07, select the RTD type to use in D09: RTD TYPE. Furthermore, for thermocouple or RTD input, select the tem­perature unit in D15: UNIT.
[Comes with VJ77 and JHT200]
Modular jack conversion adapter (E9786WH) [Comes with VJ77]
Dedicated adapter (E9789HA) [Comes with VJ77]
Dedicated cable
Comes with VJ77
come with the JHT200 Handy Terminal. It is sold separately.
E9786WK
order starting with (1).
(1) Input sensor type (2) Input type (3) Temperature unit for temperature input (4) Input hard range (5) Input range
output and making the adjustments such as wir­ing resistance correction and output correction, set the parameters described in 1 above. If setting the parameters (1) to (3) in 1 above af­ter setting the parameters related to alarm out­put or making the adjustment, the setpoint will be changed or the adjustment will be reset to the default.
IM 77J01U07-01E 4th Edition Feb. 09, 2007-00
4
9.1.2 Input Hard Range
Select the input hard range from among AUTO, HIGH, MIDDLE and LOW in D17: SELECT RANGE. In general, se­lect AUTO.
AUTO: Sets the most appropriate input hard range auto­matically with respect to the input range to be set.
HIGH: For RTD input, for a span of 130 Ω or more in an input range of 0 to 520 based on the reference resistane table.
MIDDLE: For thermocouple or mV input, for a span of
27.5 mV or more in an input range of 10 to 100 mV con­verted into thermoelectromotive force. For RTD input, for a span of 38.5 or more in an input range of 0 to 176 based on the reference resistane table.
LOW: For thermocouple or mV input, for a span of 10 mV or more in an input range of -2.5 to 25 mV converted into thermoelectromotive force.
NOTE
The conditions for the input hard range (HIGH, MIDDLE and LOW) are specified for operations within the range of accuracy rating. The input range may be set to a range not meeting these con­ditions, but take note of accuracy limitations. Simi­lar accuracy limitations exist even when AUTO is selected. For more information on accuracy limita­tions, see the general specifications of VJU7 (GS 77J01U07-01E).
9.1.3 Input Range
Set the 0% value of input range in D22: INPUT1 L_RNG and the 100% value of input range in D23: INPUT1 H_RNG nu­merically within the following specified range.
Input type
Thermocouple input Type K (CA) Type T (CC) Type E (CRC) Type J (IC) Type R Type S Type B Type N Type W3 Type W5
Pt100 (ITS-90) Pt100 (IPTS-68) JPt100 (JIS'89) Pt50 (JIS'81)
mV signal
*1: W97Re3-W75Re25 (tungsten 97% rhenium 3%-tungsten 75% rhenium 25%) The abbreviation of ASTM E988. *2: W95Re5-W74Re26 (tungsten 95% rhenium 5%-tungsten 74% rhenium 26%) The abbreviation of ASTM E988.
*1 *2
RTD input
mV input
9.1.4 Direction of Output Action
When output 1 and output 2 are analog outputs, the outputs can be reversed. Set the direction of output action in D38: OUT1 DR (output 1) and in D39: OUT2 DR (output 2). Select REVERSE for reverse action and DIRECT for direct action.
9.1.5 Wiring Resistance Correction
When an error occurs due to the influence of the input wiring resistance, the wiring resistance can be corrected automati­cally. Apply a stable input as shown below and select EX-
Operation guaranteed range
-200 to 1200 °C
-200 to 350 °C
-200 to 800 °C 0 to 750 °C 0 to 1600 °C 0 to 1600 °C 600 to 1700 °C
-200 to 1200 °C 0 to 2000 °C 0 to 2000 °C
-200 to 660 °C
-200 to 660 °C
-200 to 510 °C
-200 to 649 °C
-10 to 100 mV DC
ECUTE in P01: WIRING R. The correction is also required when the direction of burnout action is changed from UP (DOWN) to DOWN (UP) or the wiring for input is changed.
Thermocouple Input
VJU7
Short-circuit at the cable end.
VJ77
or
JHT200
RTD Input
VJ77
VJU7
Short-circuit at the cable end.
or
JHT200
mV Input
Voltage
generator
VJU7
Two signal lines are connected to the same terminal of one side.
VJ77
or
JHT200
9.2 Settings Related to Communication Function
Set the following parameters when the communication func­tion is specified for the output 2. For more information on communication functions, see the users manual for VJ Series Communication Functions (IM 77J01J11-01E).
9.2.1 Communication Protocol
Select the communication protocol from among PCLINK, PCLINK WITH SUM, MODBUS ASCII, MODBUS RTU and LADDER in F01: PROTOCOL.
9.2.2 Communication Address
Set the address number of the converter numerically in a range of 1 to 99 in F02: ADDRESS.
9.2.3 Baud Rate
Select the baud rate from among 1200, 2400, 4800 and 9600 bps in F03: BAUD RATE.
9.2.4 Parity
Select the parity from among NONE, EVEN and ODD in F04: PARITY.
9.2.5 Data Length
Select the data length from among 7 bits and 8 bits in F05: DATA LEN.
9.2.6 Stop Bit
Select the stop bit from among 1 bit and 2 bits in F06: STOP BIT.
9.2.7 Decimal Point Position
Number of decimals of input value (setting of D register [D0003]) can be set. Select the number of decimals from among 0 to 5 in F07: INPUT DEC PT.
All Rights Reserved. Copyright © 1999, Yokogawa M&C Corporation IM 77J01U07-01E 4th Edition Feb. 09, 2007-00
9.3 Settings Related to Alarm Output
Set the following parameters when the alarm output is speci­fied for the output 2.
9.3.1 Alarm Setpoint
Set the alarm-1 setpoint and alarm-2 setpoint numerically in E01: SET POINT1 and E02: SET POINT2 for thermocouple input and RTD input or in E03: SET POINT1 and E04: SET POINT2 for mV input. Set them in [°C] for temperature input or in [%] for mV input.
Setting range: 0 to 100% of input range
Setting resolution: 0.1°C (for thermocouple input and
RTD input), 0.1% (for mV input)
9.3.2 Direction of Alarm Action
Select the direction of alarm-1 action and that of alarm-2 ac­tion from among HIGH ALM (high-limit alarm) and LOW ALM (low-limit alarm) in E05: ALM1 ACTION and E06: ALM2 AC­TION.
To activate alarm status when input signal ⱖ alarm setpoint, select HIGH ALM.
To activate alarm status when input signal ⱕ alarm setpoint, select LOW ALM.
9.3.3 Hysteresis
Set the alarm-1 hysteresis and alarm-2 hysteresis numeri­cally in E07: HYSTERESIS1 and E08: HYSTERESIS2 for thermocouple input and RTD input or in E09: HYSTER­ESIS1 and E10: HYSTERESIS2 for mV input. Hysteresis is a value added to the alarm setpoint in order for an alarm status to be released (to normal) after the alarm status has been activated. The alarm status will be released in the following conditions, depending on the direction of alarm action. * When HIGH ALM (high-limit alarm) is set: Alarm is re-
leased when input signal < (alarm setpoint - hysteresis).
* When LOW ALM (low-limit alarm) is set: Alarm is re-
leased when input signal > (alarm setpoint + hysteresis).
Set them in [°C] for temperature input or in [%] for mV input.
Setting range: 0 to 100% of input range
Setting resolution: 0.1°C (for thermocouple input and
RTD input), 0.1% (for mV input)
9.3.4 Alarm ON Delay and Alarm OFF Delay
Set the alarm-1 ON delay and alarm-2 ON delay numerically in E11: ON DELAY1 and E12: ON DELAY2. Set the alarm-1 OFF delay and alarm-2 OFF delay numerically in E13: OFF DELAY1 and E14: OFF DELAY2. An alarm ON delay is a delay time from the establishment of alarm conditions to its output; an alarm OFF delay is a delay time from the establishment of return-to-normal conditions to its output.
Setting range: 0 to 999 seconds
Setting resolution:
is to be added to the set time to prevent wrong opera­tion.)
For example, when an alarm ON delay is set to 1 second, alarm output is generated if alarm status continues for 1 sec­ond or more after the input value exceeds the alarm setpoint. Furthermore, when an alarm OFF delay is set to 2 seconds, alarm output is released if normal condition contin­ues for 2 seconds or more after the input value has returned to normal from the alarm status.
9.3.5 Direction of Relay Action
Select the direction of relay energizing in alarm-1 normal condition and alarm-2 normal condition from among NRM DE-ENERGIZED (de-energized under normal condition) and NRM ENERGIZED (energized under normal condition) in E15: RL1 ACTION and E16: RL2 ACTION.
1 second (However, about 0.2 second
5
IM 77J01U07-01E 4th Edition Feb. 09, 2007-00
10. DESCRIPTION OF ALARM ACTIONS
This chapter describes examples of alarm actions under the following conditions.
6
Item
Direction of alarm action
Parameter Setpoint Parameter Setpoint
E05 : ALM1 ACTION High-limit alarm E06 : ALM2 ACTION Low-limit alarm
Alarm 1 Alarm 2
Alarm setting E03 : SET POINT1 80% E04 : SET POINT2 15% Hysteresis E09 : HYSTERESIS1 10% E10 : HYSTERESIS2 5% Alarm ON delay E11 : ON DELAY1 1 sec E12 : ON DELAY2 3 sec Alarm OFF delay E13 : OFF DELAY1 2 sec E14 : OFF DELAY2 4 sec Description of alarm actions
The alarm is output if the condition where the input value is 80% or more of high­limit alarm continues for 1 second or more. After the alarm is output, when the condition where the input value is less than 70% of high-limit alarm continues for 2 seconds or more, the status returns to
The alarm is output if the condition where the input value is 15% or less of low-limit alarm continues for 3 seconds or more. After the alarm is output, when the condition where the input value is more than 20% of low-limit alarm continues for 4 seconds or more, the status returns to normal.
normal.
Alarm conditions established
Alarm conditions established
Normal conditions established
Normal conditions established
[1]: Alarm status does not continue for more than 1 second after the
High-limit alarm OFF
Alarm-1 OFF delay
alarm conditions are established at alarm 1.
[2]: Normal status does not continue for more than 2 seconds after the
normal conditions are established at alarm 1.
[3]: Alarm status does not continue for more than 3 seconds after the
alarm conditions are established at alarm 2.
[4]: Normal status does not continue for more than 4 seconds after the
normal conditions are established at alarm 2.
Alarm-1 setpoint (80%)
Alarm-1 hysteresis (10%)
Low-limit alarm ON
Alarm conditions
established
Alarm-2 ON delay
Alarm conditions
established
Normal conditions
established
Normal conditions
established
Low-limit alarm OFF
Alarm-2 OFF delay
[%]
100
80
60
High-limit alarm ON
[1] [2]
1 sec
Alarm-1 ON delay
2 sec
40
20 15
Alarm-1 action
Alarm-2 action
Alarm-2 hysteresis (5%)
0
Normal
Alarm-2 setpoint (15%)
Alarm
Normal Alarm
[3]
3 sec 4 sec
Normal
[4]
Elapsed time
1 sec
Normal
All Rights Reserved. Copyright © 1999, Yokogawa M&C Corporation IM 77J01U07-01E 4th Edition Feb. 09, 2007-00
11. LIST OF PARAMETERS
7
No. Item Display 01 Model MODEL 02 Tag No. TAG NO 03 Self-check result SELF CHK
Display items
A Display 1 DISPLAY1 A01 Input value INPUT1 A05 Output value 1 OUTPUT1 A06 Output value 2 OUTPUT2 A07 Alarm-1 status ALM1 STATUS A08 Alarm-2 status ALM2 STATUS A54 Status STATUS (*1) A56 Rev No. REV NO A58 Menu Rev MENU REV A60 Self-check result SELF CHK Setting items (*2) (*3) D Setting (I/O) SET(I/O) D01 Tag no.1 TAG NO.1 D02 Tag no.2 TAG NO.2 D03 Comment 1 COMMENT1 D04 Comment 2 COMMENT2 D07 Input sensor type SENSOR TYPE D08 Thermocouple type TC TYPE D09 RTD type RTD TYPE D15 Unit UNIT D17 Input hard range selection SELECT RANGE D22 Input low range INPUT1 L_RNG D23 Input high range INPUT1 H_RNG D30 Burnout BURN OUT D38 Direction of output-1 action OUT1 DR D39 Direction of output-2 action OUT2 DR D60 Self-check result SELF CHK
Adjusting items (*3) P Adjustment ADJUST1 P01 Wiring resistance correction WIRING R P02 Zero adjustment of input 1 ZERO ADJ1 P03 Span adjustment of input 1 SPAN ADJ1 P12 0% adjustment of output 1 OUT1 0% P13 100% adjustment of output 1 OUT1 100% P14 0% adjustment of output 2 OUT2 0% P15 100% adjustment of output 2 OUT2 100% P60 Self-check result SELF CHK
*1 : The status is displayed for service personnel to see history records. *2 : Some items are not displayed depending on the selected input sensor type or output-2 specification. *3 : To call the parameter setting items D, E, F, P and Q using the JHT200 Handy Terminal, execute the following operation:
Press F1
D, E, F, P or Q key enters above.
ENTER
keys.
No. Item Display
B Display 2 DISPLAY2 B01 Input value INPUT1 B05 Output value 1 OUTPUT1 B06 Output value 2 OUTPUT2 B07 Alarm-1 status ALM1 STATUS B08 Alarm-2 status ALM2 STATUS B60 Self-check result SELF CHK
E Setting (alarm output) SET(ALM) E01 Alarm-1 setting SET POINT1 E02 Alarm-2 setting SET POINT2 E03 Alarm-1 setting SET POINT1 E04 Alarm-2 setting SET POINT2 E05 Direction of alarm-1 action ALM1 ACTION E06 Direction of alarm-2 action ALM2 ACTION E07 Alarm-1 hysteresis HYSTERESIS1 E08 Alarm-2 hysteresis HYSTERESIS2 E09 Alarm-1 hysteresis HYSTERESIS1 E10 Alarm-2 hysteresis HYSTERESIS2 E11 Alarm-1 ON delay setting ON DELAY1 E12 Alarm-2 ON delay setting ON DELAY2 E13 Alarm-1 OFF delay setting OFF DELAY1 E14 Alarm-2 OFF delay setting OFF DELAY2 E15 Direction of alarm-1 relay action RL1 ACTION E16 Direction of alarm-2 relay action RL2 ACTION E60 Self-check result SELF CHK
F Setting (communication) SET(COM)
F01 Communication protocol PROTOCOL F02 Address ADDRESS F03 Baud rate BAUD RATE F04 Parity PARITY F05 Data length DATA LEN F06 Stop bit STOP BIT F07 Decimal point position INPUT DEC PT F60 Self-check result SELF CHK Test items (*3) Q Test TEST Q01 ON/OFF of RJC RJC Q02 Forced output 1 OUT1 TEST Q03 Forced output 2 OUT2 TEST Q04 Forced output (alarm 1) ALM1 TEST Q05 Forced output (alarm 2) ALM2 TEST Q60 Self-check result SELF CHK
IM 77J01U07-01E 4th Edition Feb. 09, 2007-00
12. MAINTENANCE
The product enters the operable status as soon as the power is turned on, but requires 10 to 15 minutes of warm-up to meet the performance requirements.
12.1 Calibration Apparatus
Calibrator (Yokogawa Meters & Instruments CA71 or equivalent): 1
Temperature sensor (Yokogawa Meters & Instruments B9108WA or equivalent): 1
Digital Multimeter (Yokogawas 7561 or equivalent): 1
Precision resistor of 250 Ω ±0.01%, 1 W: 1
Setting tool for adjustment (Refer to 8.2 Connecting the Setting Tools in this manual.)
12.2 Calibration Procedure
(1) Connect the instruments as shown in Fig.12.1.
First adjust the output-1 signal and then the output-2 signal.
(2) Produce the input signal equivalent to 0, 25, 50, 75 and 100% of the input span from the calibrator. Check that the converters
output signals show voltages corresponding to 0, 25, 50, 75 and 100% within the rated accuracy range. If the output signal is out of the rated accuracy range, adjust the output signal level using the VJ77 PC-based Parameters Set­ting Tool or JHT200 Handy Terminal. Refer to the users manual for VJ77 PC-based Parameters Setting Tool (IM 77J01J77-01E) or for JHT200 Handy Terminal (IM JF81-02E).
8
Fig. 12.1
Thermocouple Input
Calibrator
Temperature sensor (B9108WA)
RTD Input
Calibrator
mV Input
Calibrator
+
1
3
RJC
4
A
1
B
3
B
4
+
1
3
3 2
56
1011
Power Supply
L+
N–
GND
Output 2
1
4
789
Analog output
2
5
R: 250 precision resistor for current output
Output 1
R
+
Digital
multimeter
ALM2 (NO)
2
COM
5
ALM1 (NO)
6
COM
5
Alarm 1
Calibrator
Alarm 2
Calibrator
Analog output
+
7
9
10
11
8
R: 250 precision resistor for current output
R
Digital
multimeter
All Rights Reserved. Copyright © 1999, Yokogawa M&C Corporation IM 77J01U07-01E 4th Edition Feb. 09, 2007-00
Loading...