Yokogawa VJSS User Manual

User’s Manual
Model VJSS High/Low Signal Selector
(Isolated Single-output and Isolated Dual­output Types)
Thank you for purchasing the JUXTA Signal Conditioner. Please read through this manual before use for correct handling.
2nd Edition Mar. 2012 (YK)
Network Solutions Business Division
2-9-32, Naka-cho Musashino-shi, Tokyo 180-8750 Japan Phone: +81-422-52-7179 Facsimile: +81-422-52-6973
CAUTIONARY NOTES FOR SAFE USE OF THE PRODUCT
This User’s Manual should be carefully read before installing and operating the product. The following symbol is used on the product and in this manual to ensure safe usage.
This symbol is displayed on the product when it is necessary to refer to the User’s Manual for information on personal and instrument safety. This symbol is displayed in the User’s Manual to indicate precautions to avoid danger to the operator, such as an electric shock.
The following symbols are used only in this manual.
Note
Draws attention to essential information for understanding the operations and/or functions of the product.
CHECKING PRODUCT SPECIFICATIONS AND PACKAGE
(1) Checking the Model and Product Specications
Check that the model and specications indicated on the nameplate attached to the main unit are as ordered.
(2) Packaged Items
Check that the package contains the following items: VJSS: 1 Tag number label: 1 Shunt resistor (for current input): 2 User's Manual (this manual)
MODEL AND SUFFIX CODES
Model Sufx codes Description VJSS Selection rule Output conguration Power supply 6 100-240 V AC/DC
Input signal A 4 to 20 mA DC
Output-1 signal A 4 to 20 mA DC
Output-2 signal A 4 to 20 mA DC
Options /SN Without socket
*1 Operating range: 85-264 V *2 Operating range: 12-36 V *3 DC voltage signal or DC current signal
-   -  0/
-H Selects “high” signals
-L
1 Single 2 Dual
7 15-30 V DC
6 1 to 5 V DC
B 2 to 10 mA DC C 1 to 5 mA DC D 0 to 20 mA DC E 0 to 16 mA DC F 0 to 10 mA DC G 0 to 1 mA DC 1 0 to 10 mV DC 2 0 to 100 mV DC 3 0 to 1 V DC 4 0 to 10 V DC 5 0 to 5 V DC 6 1 to 5 V DC 7 −10 to 10 V DC Z (Custom order)
6 1 to 5 V DC N None
0 Always 0
High/Low Signal Selector
Selects “low” signals
Blank: With socket
[STYLE: S3]
(*2)
(*3)
(*1)
GENERAL
The VJSS is a compact, plug-in high/low signal selector that selects the higher or lower of two DC input signals and converts it into an isolated DC voltage or DC current signals.
1
1. MOUNTING METHOD
Mounting
External receiving resistor
Note
Insert/pull out the main unit into/from the socket vertically to the face of socket. Otherwise the terminals are bent and it may cause a bad contact.
Wiring should be connected to the terminals on the socket of the product. The terminals for external connections are of M3 screws. Use crimp-on terminal lugs for connections to the terminals.
Recommended cables: A nominal cross-sectional area of
0.5 mm2 or thicker for signal cables, and that of 1.25 mm2 or thicker for power cables.
1.1 Wall Mounting
Loosen the main unit-xing screw of the product and pull out the main unit from the socket. Fix the socket on the wall with screws. Next, insert the main unit into the socket and fasten the main unit with the main unit-xing screw.
Main unit
1.2 DIN Rail Mounting
Insert a DIN rail into the upper part of the DIN rail groove on the rear of the socket, and then slide the slide lock at the lower part of the socket upwards until the socket is xed into position as shown below
1.3 Mounting Using
When using a multi-mounting base, see the User’s Manual for VJCE (VJCE Mounting Base).
1.4 Using a Duct
When using a wiring duct, install the duct at leaset 30 mm away from the top and bottom faces of the main unit.
2. INSTALLATION LOCATION
• Avoid the following environments for installation locations: Areas with vibration, corrosive gases, dust, water, oil, solvents, direct sunlight, radiation, a strong electric eld, and/or a strong magnetic eld, altitude of more than 2000m above sea level.
• If there is any risk of a surge being induced into the power line and/or signal lines due to lightning or other factors, a dedicated lightning arrester should be used as protection for both this converter and a eld-installed device.
• Operating temperature/humidity range: 0 to 50C/5 to 90%RH (no condensation)
screws
Main unit-fixing screw
DIN rail
Threaded hole for fixing the main unit
Mounting Dimensions
Socket
59±0.3
Push
(Rear of socket)
29.5 or more
22±0.2
Fit into here
DIN rail
DIN rail
Slide look
Unit: mm
2-M4 or 2-ø4.5 or more
(Shunt resistor for current input)
Input-1
+
R
Input-2
+
R
R: External receiving resistor
for current input
Note
● Do not use output-2 for the single-output type.
● The power line and input/output signal lines should
be installed away from noise-generating sources. Other wise accuracy cannot be guaranteed.
● The grounding resistance must be 100 Ω (JIS
Class D grounding). The length and thickness of the grounding cable should be as short and thick as possible. Directly connect the lead from the ground terminal (terminal no. 8) of the product to the ground. Do not carry out daisychained inter-ground terminal wiring
● Use of the product ignoring the specications may
cause overheating or damage. Before turning on the power, ensure the following:
Power supply voltage and input signal value applied to
The external wiring to the terminals and wiring to ground
● Do not operate the product in the presence of
ammable or explosive gases or vapors. To do so is highly dangerous.
● The product is sensitive to static electricity;
exercise care in operating it. Before you operate the product, touch a nearby metal part to discharge static electricity.
● For 15-30 V DC (±20%) power supply, as a safety
measure, always install a circuit breaker (an IEC 60947-compatible product, 1 A, 30 V DC) in an easily accessible location near the instrument. Moreover, provide indication that the switch is a device for turning off the power to the instrument.
3 2
1
56
1
3
4
6
4
789
1011
Power Supply
1110 8
N
L+
GND
Output-2
+
2
5
Output-1
+
7
9
the product should meet the required specications.
are as specications.
3. EXTERNAL WIRING
WARNING
Be sure to turn OFF the power supply before wiring to avoid the risk of electric shock. Use a tester or similar device to ensure that no power is being supplied to a cable to be connected.
2
IM 77J01S11-01E 2nd Edition Mar, 02. 2012-00
4. DESCRIPTION OF FRONT PANEL
How to connect with the setting tool
4.1 Front Panel
The communications connector in the front panel is used for setting up parameters through a PC (VJ77 PC-based Parameters Setting Tool) or the Handy Terminal.
Connector for
communication
4.2 Connector for Communication
Use the connector for communication when setting the parameters using a PC (VJ77 Parameters Setting Tool) or the Handy Terminal
JUXTA communication cable with 5-pin connector (F9182EE)
JHT200 Handy Terminal
PC which is installed with the VJ77
• Use the VJ77 of version R1.04 or later.
• The modular jack conversion adapter does not come with the JHT200 Handy Terminal. It is sold separately.
[Provided with VJ77 and JHT200]
Dedicated cable (E9786WK) [Provided with VJ77]
5. SETTING PARAMETERS
Set the parameters using a PC (VJ77 Parameter Setting Tool) or the Handy Terminal. Refer to “6. LIST OF PARAMETERS” in this manual and the User’s Manual for VJ77 PC-based Parameters Setting Tool (IM 77J01J77-01E) or the User’s Manual for JHT200 Handy Terminal (IM JF81-02E). Parameters are indicated inside the [ ].
Setting High Selector/Low Selector
Set the high selector or low selector in the xed constant [H01:CONST].
High selector: H01=100.0
Low selector: H01=0.000
Note
Do not change the parameter set value of the other than above.
Modular jack conversion adapter (E9786WH) [Provided with VJ77]
Dedicated adapter (E9789HA) [Provided with VJ77]
6. LIST OF PARAMETERS
Parameter Display Item
MODEL Model TAG NO Tag No. SELF CHK Self-check result
A DISPLAY1 Display 1
A01 INPUT1 Input value 1 A02 INPUT2 Input value 2 A05 OUTPUT1 Output value 1 A06 OUTPUT2 Output value 2 A11 T1 Temporary memory 1 A12 T2 Temporary memory 2 A13 T3 Temporary memory 3 A14 T4 Temporary memory 4 A15 DI Digital input A16 DO Digital output A17 LOAD Load factor A54 STATUS Status A56 REV NO REV No. A58 MENU REV MENU REV A60 SELF CHK Self-check result
B DISPLAY2 Display2
B01 INPUT1 Input value 1 B02 INPUT2 Input value 2 B05 OUTPUT1 Output value 1 B06 OUTPUT2 Output value 2 B11 T1 Temporary memory 1 B12 T2 Temporary memory 2 B13 T3 Temporary memory 3 B14 T4 Temporary memory 4 B15 DI Digital input B16 DO Digital output B17 LOAD Load factor B60 SELF CHK Self-check result
D SET (I/O) Setting (I/O)
D01 TAG NO.1 Tag No.-1 D02 TAG NO.2 Tag No.-2 D03 COMMENT1 Comment-1 D04 COMMENT2 Comment-2 D20 INP TYPE Input type D22 IN RESIST Input resistor D27 INPUT1 L_RNG Input-1 low range D28 INPUT1 H_RNG Input-1 high range D29 INPUT2 L_RNG Input-2 low range D30 INPUT2 H_RNG Input-2 high range D38 OUT1 L_RNG Output-1 low range D39 OUT1 H_RNG Output-1 high range D40 OUT2 L_RNG Output-2 low range D41 OUT2 H_RNG Output-2 high range D46 PRGM SELECT Program selection D47 CYCLE TIME Computation cycle D60 SELF CHK Self-check result G PROGRAM Program G01 PROGRAM Program G02 PROGRAM Program ↓ ↓ G59 PROGRAM Program G60 SELF CHK Self-check result
H CONST Fixed constant
H01 CONST Fixed constant H02 CONST Fixed constant
↓ H59 CONST Fixed constant H60 SELF CHK Self-check result
P ADJUST Adjustment
P08 IN1 ZERO ADJ Input-1 zero adjustment P09 IN1 SPAN ADJ Input-1 span adjustment P10 IN2 ZERO ADJ Input-2 zero adjustment P11 IN2 SPAN ADJ Input-2 span adjustment P26 OUT1ZERO ADJ Output-1 zero adjustment P27 OUT1SPAN ADJ Output-1 span adjustment P28 OUT2ZERO ADJ Output-2 zero adjustment P29 OUT2SPAN ADJ Output-2 span adjustment P60 SELF CHK Self-check result
Q TEST Test
Q03 OUT1 TEST Forced output-1 Q04 OUT2 TEST Forced output-2 Q60 SELF CHK Self-check result
*1 The displayed status is to let the service staff know the past
records of the product.
*2 There are items not displayed depending on what output-2 is
specied.
*3 The parameters are the items to be set at the factory.
*1
*2
*1
*1
*3
*3
*3
*3
*3
*3
*3
*3
*3
*3
*3
*3
*3
*3
*3
*3
*3
*3
*3
3
IM 77J01S11-01E 2nd Edition Mar, 02. 2012-00
7. MAINTENANCE
External receiving resistor
The product starts running immediately when the power is turned on; however, it needs 10 to 15 minutes of warm-up before it meets the specied performance.
7.1 Calibration Apparatus
• Two DC voltage/current standard (Yokogawa 7651 or the equivalent)
• A digital multimeter (Yokogawa 7561 or equivalent)
• A precision resistor of 250 Ω ±0.01%, 1W
• Setting tool for adjustment (Refer to “4.2 Connector for
Communication” in this manual.)
7.2 Calibration Procedure
1. Connect the instruments as shown below.
(Shunt resistor for current input)
Input-1
Input-2
+
1
Ri
3
+
4
Ri
6
Voltage and current generator
Voltage and current generator
Ri: External receiving resistor
for current input
2. For the high signal selector: VJSS-H□□-□□□0 Apply the input signal equivalent to -5 to 0% of the input span to one of two inputs of the converter from a voltage current source. For the low signal selector: VJSS-L □□ - □□□ 0 Apply the input signal equivalent to 100 to 105% of the input span to one of two inputs of the converter from a voltage current source.
3. Apply the input signal equivalent to 0, 25, 50, 75, and 100% of the input span to one of two inputs of the converter from a voltage current source.
4. Check to see the corresponding output voltages are 0, 25, 50, 75, and 100% respectively and within the specied accuracy rating. “R” is used for current output.
• Use the setting tool (VJ77 Parameter Setting Tool or JHT200 Handy Terminal) to adjust the input/output signals.
Input Adjustment Procedure
(1) Input the value equivalent to 0% value of the input range to
the high/low signal selector.
(2) Call the display item (A: DISPLAY1) to check the input value
in A01: INPUT1.
(3) If the adjustment is necessary, call the adjustment item (P:
ADJUST).
(4) Select P08: IN1 ZERO ADJ to enter the adjustment mode.
Select EXECUTE (adjustment) for adjustment. (If RESET is selected, the adjusted value is reset to the factory-set default.)
(5) Input the value equivalent to 100% value of input range. (6) Call the display item (A: DISPLAY1) to check the input value
in A01: INPUT1.
(7) If the adjustment is necessary, call the adjustment item (P:
ADJUST).
(8) Select P09: IN1 SPAN ADJ to enter the adjustment mode.
Select EXECUTE (adjustment) for adjustment. (If RESET is selected, the adjusted value is reset to the factory-set default.)
• Input-2 can be adjusted by the same operation as the above.
3 2
1
56
4
789
1011
Power Supply
1110 8
N
L+
Ro: For current output using
GND
Output-2
2
+
DMM
R
5
Output-1
+
7
R
DMM
9
250 Ω precision resistor
Output Adjustment Procedure
(1) When adjusting 0% value of output, call the adjustment item
(P:ADJUST) to select [P26:OUT1ZERO ADJ].
(2) If there is a positive deviation, correct it by setting a negative
value to offset the deviation. If there is a negative deviation, correct it by setting a positive value.
*: The 100% value of output-1 and the 0%/100% value of
output-2 can be adjusted by the same operation as the above. For adjustment using a setting tool, refer to the User’s Manual for each setting tool and “6. LIST OF PARAMETERS” in this manual. User’s Manual for VJ77 [Document No.: IM 77J01J77-01E]; however, use the VJ77 of version R1.04 or later. User’s Manual for JHT200 [Document No.: IM JF81-02E]
SAFETY AND EMC STANDARDS
CAUTION
This instrument is for Measurement Category I (CAT.I). Do not use it for measurements in locations falling under Measurement Categories II, III, and IV.
Internal Wiring
Entrance Cable
IV
III
Outlet
I
Measurement
Description Remarks
category
I CAT.I For measurements performed
on circuits not directly connected to MAINS.
II CAT.II For measurements performed
on circuits directly connected to the low-voltage installation.
III CAT.III For measurements performed in
the building installation.
IV CAT.IV For measurements performed
at the source of the low-voltage installation.
An analog input signal is measurement category I (CAT.I). Rated transient overvoltage: 1500 V
Note This is a reference safety standard value for
Measurement Category I of IEC/EN/CSA/UL61010-1. This value is not necessarily a guarantee of instrument performance.
EMC standards: Complies with EN61326.
The above conformed instrument is only for voltage of 15 to 30 V DC.
* The instrument continues to operate at a measurement
accuracy of within ±20% of the range during testing.
II
T
Appliances, portable equipments, etc.
Distribution board, circuit breaker, etc.
Overhead wire, cable systems, etc.
(Note)
4
IM 77J01S11-01E 2nd Edition Mar, 02. 2012-00