Yokogawa VJAK User Manual

User’s
/
Manual
IM 77J01A21-01E
Model VJAK Limit Alarm (DC Current Input Type) (with Transmitter Power Supply)
1. CAUTIONARY NOTES FOR SAFE USE OF THE PRODUCT
This user’s manual should be carefully read before installing and operating the product. The following symbol is used on the product and in this manual to eusure safe use.
This symbol is displayed on the product when it is necessary to refer to the users manual for infor­mation on personnel and instrument safety. This symbol is displayed in the users manual to indi­cate precautions for avoiding danger to the opera­tor, such as an electric shock.
The following symbols are used only in this manual.
IMPORTANT
Indicates that operating the hardware or software in a particular manner may cause damage or result in a system failure.
NOTE
Draws attention to essential information for under­standing the operations and/or functions of the product.
2.
CHECKING THE PRODUCT SPECIFICATIONS AND THE CONTENTS OF THE
(1) Model and Specifications Check
Check that the model and specifications indicated on the nameplate attached to the side face of the main unit are as ordered.
(2) Contents of the Package
Check that the package contains the following items:
VJAK: 1
User’s manual (this manual: IM 77J01A21-01E): 1
Accessories:
Tag number label: 1 sheet
PACKAGE
3. GENERAL
This plug-in type Limit Alarm for DC current input receives 4 to 20 mA DC current signal. It is used in combination with two­wire type transmitter.
Each parameter setting can be changed using a PC
(VJ77 PC-based Parameters Setting Tool) or the Handy Terminal (JHT200 ).
VJAK-0 2 - 0/T0
Model
Number of outputs 2: 2 outputs
Power supply 6: 100-240 V AC/DC 7: 15-30 V DC
Input signal A: 4 to 20 mA DC (Transmitter power supply: 24 to 28 V DC)
Output signal T: Alarm output (2 points of relay contacts)
Optional specification Blank: With socket
SN: Without socket
(Operating range: 85 to 264 V)
(Operating range: 12 to 36 V)
5. MOUNTING METHODS
5.1 Wall Mounting
Loosen the main unit-fixing screw to disconnect the main unit from the socket. Next, anchor the socket onto the wall with screws. Then, plug the main unit into the socket and se­cure the main unit with the main unit-fixing screw.
Main unit
Main unit-fixing screw
<Mounting Dimensions>
29.5 or more 22±0.2
59±0.3
2-M4 or 2-ø4.5 or more
Socket
Unit: mm
Hole for main unit-fixing screw
Mounting screws
Keep this manual in a safe place.
Network Solutions Business Divisiion
2-9-32, Naka-cho Musashino-shi, Tokyo 180-8750 Japan Phone: +81-422-52-7179 Facsimile: +81-422-52-6619
Fig.5.1
IM 77J01A21-01E
1st Edition : Aug. 2006 (YK)
2
5.2 DIN Rail Mounting
Locate the VJAK so that the DIN rail fits into the upper part of the DIN-rail groove at the rear of the socket, and fasten the socket using the slide lock at the lower part of the socket.
DIN rail
(Rear of the socket)
Push
DIN rail
Slide lock
Fit into
here
DIN
rail
Fig. 5.2
5.3 Using a Duct
Wiring duct should be installed at least 30 mm away from the top and bottom faces of the main unit.
6. INSTALLATION LOCATIONS
Avoid the following environments for installation locations: Areas with vibrations, corrosive gases, dust, water, oil, solvents, direct sunlight, radiation, a strong electric field, and/or a strong magnetic field.
If there is any risk of a surge being induced into the power line and/or signal lines due to lightning or other factors, a dedicated lightning arrester should be used as protection for both the product and a field-installed de­vice.
7. EXTERNAL WIRING
WARNING
To avoid the risk of an electric shock, turn off the power supply and use a tester or similar device to ensure that no power is supplied to a cable to be connected, before carring out wiring work.
Wiring should be connected to the terminals on the socket of the VJAK. The terminals for external connections are of M3 screws. Use crimp-on lugs for connections to the terminals.
It is recommended that signal wires have a nominal cross-sectional area of 0.5 mm2 or thicker, while the power cable has a nominal cross-sectional area of 1.25 mm2 or thicker.
Input signal
When using internal power supply
+
PS
+
COM
When using external power supply
1
3
+
Power supply
COM
L
+
N
GND
56
1011
1
4
789
Alarm-2 output
ALM2 (NO)
2
COM
5
Alarm-1 output
ALM1 (NO)
7
COM
9
3 2
1
3
44
10
11
8
IMPORTANT
Use of the product ignoring the specifications may cause overheating or damage. Before turning on the power, ensure the following: (a) Power supply voltage and input signal
value applied to the product should meet the required specifications.
(b) The external wiring to the terminals and
wiring to ground are as specifications.
Do not operate the product in the presence of flammable or explosive gases or vapors. To do so is highly dangerous.
The product is sensitive to static electricity; exercise care in operating it. Before you operate the product, touch a nearby metal part to discharge static electricity.
If an inductance (L) load such as auxiliary relays or solenoid valves is used, always insert a spark killer for diminishing sparks, such as a CR filter or a diode in parallel with the inductance load. Otherwise a malfunction or relay failure may occur. Refer to the following guidelines for a capacitor and resistor: Capacitor : 0.5 to 1 ␮F with respect to a contact
current of 1 A
Resistor: 0.5 to 1 Ω with respect to a contact
voltage of 1 V
The power line and input/output signal lines should be installed away from noise­generating sources. Otherwise accuracy cannot be guaranteed.
The grounding resistance must be 100 Ω (JIS Class D grounding). The length and thickness of the grounding cable should be as short and thick as possible. Directly connect the lead from the ground terminal (terminal no. 8) of the product to the ground. Do not carry out daisy-
chained inter-ground terminal wiring.
8. DESCRIPTION OF FRONT PANEL AND CONNECTION OF SETTING TOOLS
8.1 Front Panel
The communications connector on the front panel is used for setting up parameters using a PC (VJ77 PC-based Param­eters Setting Tool) or the Handy Terminal (JHT200). The alarm indicator lamps for alarm 1 and alarm 2 light up if an alarm occurs.
Communication connector
Alarm indicator lamp
(for alarm 1)
Alarm indicator lamp
(for alarm 2)
Fig. 8.1 Front Panel
ALM1
ALM2
When connecting the transmitter to the VJAK directly without using the transmitter power supply, connect [+] of the transmitter output to the terminal no. 3 and connect [ to the terminal no. 4.
All Rights Reserved. Copyright © 1999, Yokogawa M&C Corporation IM 77J01A21-01E 1st Edition : 2006.08.15-00
]
3
(
)
[
]
e
d
8.2 Connecting the Setting Tools
Connect the modular jack conversion adapter (E9786WH) to the JUXTA communication cable with 5-pin connector (F9182EE) and then connect this adapter to the communica­tion connector of JUXTA.
JUXTA communication cable with 5-pin connector (F9182EE)
JHT200 Handy Terminal
PC with th VJ77 installe
[Comes with VJ77 and JHT200]
Modular jack conversion adapter (E9786WH) [Comes with VJ77]
Dedicated adapter (E9789HA) [Comes with VJ77]
Dedicated cable
Comes with VJ77
E9786WK
Fig. 8.2 Connecting the Setting Tools
Note: The modular jack conversion adapter does not
come with the JHT200 Handy Terminal. It is sold separately.
9. SETTING PARAMETERS
Set the parameters using a PC (VJ77 PC-based Parameters Setting Tool) or the Handy Terminal (JHT200). Refer to the list of parameters in this manual and the users manual for VJ77 PC-based Parameters Setting Tool (IM 77J01J77-01E) or JHT200 Handy Terminal (IM JF81-02E).
9.1 Settings Related to Input
9.1.1 Square Root Extraction Function
Select SQR in D11: LINEARIZE to set with square root ex­traction function.
9.1.2 Low-cut Function
Set the low-cut point in D12: LOW CUT numerically when with square root extraction function is set.
Setting range: 0 to 100% of input range
Setting resolution: 0.1%
Output signal
(Y)
Y=X
9.2.2 Direction of Alarm Action
Select the direction of alarm-1 action and that of alarm-2 ac­tion from among HIGH ALM (high-limit alarm) and LOW ALM (low-limit alarm) in E05: ALM1 ACTION and E06: ALM2 AC­TION .
To activate alarm status when input signal ⱖ alarm
setpoint, select HIGH ALM.
To activate alarm status when input signal ⱕ alarm
setpoint, select LOW ALM.
9.2.3 Hysteresis
Set the alarm-1 and alarm-2 hysteresis in E09: HYSTER­ESIS1 and E10: HYSTERESIS2. Hysteresis is a value added to the alarm setpoint in order for an alarm status to be released (to normal) after the alarm status has been acti­vated. The alarm status will be released in the following con­ditions, depending on the direction of alarm action. * When HIGH ALM (high-limit alarm) is set: Alarm is re-
leased when input signal < (alarm setpoint - hysteresis).
* When LOW ALM (low-limit alarm) is set: Alarm is re-
leased when input signal > (alarm setpoint + hysteresis).
Setting range: 0 to 100% of input range
Setting resolution: 0.1%
9.2.4 Alarm ON Delay and Alarm OFF Delay
Set the alarm-1 and alarm-2 ON delays in E11: ON DELAY1 and E12: ON DELAY2 and then alarm-1 and alarm-2 OFF delays in E13: OFF DELAY1 and E14: OFF DELAY2. An alarm ON delay is the condition monitoring time from the establishment of alarm conditions to its output; an alarm OFF delay is the condition monitoring time from the establishment of return-to-normal conditions to its output.
Setting range: 0 to 999 seconds
Setting resolution: 1 second (However, about 0.2 sec-
ond is to be added to the set time to prevent wrong op-
eration.) For example, when an alarm ON delay is set to 1 second, alarm output is generated if alarm status continues for 1 sec­ond or more after the input value exceeds the alarm setpoint. Further, when an alarm OFF delay is set to 2 sec­onds, alarm output is released if normal condition continues for 2 seconds or more after the input value has returned to normal from the alarm status.
9.2.5 Direction of Relay Action
Select the direction of relay energizing in alarm-1 normal condition and alarm-2 normal condition from among NRM DE-ENERGIZED (de-energized under normal condition) and NRM ENERGIZED (energized under normal condition) in E15: RL1 ACTION and E16: RL2 ACTION.
0
Hysteresis (0.2% fixed)
Input signal (X)
Low-cut point
9.2 Settings Related to Alarm Output
9.2.1 Alarm Setpoint
Set the alarm setpoints of alarm 1 and alarm 2 in E03: SET POINT1 and E04: SET POINT2 numerically.
Setting range: 0 to 100% of input range
Setting resolution: 0.1%
IM 77J01A21-01E 1st Edition : 2006.08.15-00
10. DESCRIPTION OF ALARM ACTIONS
This chapter describes examples of alarm actions under the following conditions.
4
Item
Direction of alarm action
Parameter Setpoint Parameter Setpoint
E05 : ALM1 ACTION High-limit alarm E06 : ALM2 ACTION Low-limit alarm
Alarm 1 Alarm 2
Alarm setting E03 : SET POINT1 80% E04 : SET POINT2 15% Hysteresis E09 : HYSTERESIS1 10% E10 : HYSTERESIS2 5% Alarm ON delay E11 : ON DELAY1 1 sec E12 : ON DELAY2 3 sec Alarm OFF delay E13 : OFF DELAY1 2 sec E14 : OFF DELAY2 4 sec Description of alarm actions
The alarm is output if the condition where the input value is 80% or more of high­limit alarm continues for 1 second or more. After the alarm is output, when the condition where the input value is less than 70% of high-limit alarm continues for 2 seconds or more, the status returns to
The alarm is output if the condition where the input value is 15% or less of low-limit alarm continues for 3 seconds or more. After the alarm is output, when the condition where the input value is more than 20% of low-limit alarm continues for 4 seconds or more, the status returns to normal.
normal.
Alarm conditions established
Alarm conditions established
Normal conditions established
Normal conditions established
[1]: Alarm status does not continue for more than 1 second after the
High-limit alarm OFF
Alarm-1 OFF delay
alarm conditions are established at alarm 1.
[2]: Normal status does not continue for more than 2 seconds after the
normal conditions are established at alarm 1.
[3]: Alarm status does not continue for more than 3 seconds after the
alarm conditions are established at alarm 2.
[4]: Normal status does not continue for more than 4 seconds after the
normal conditions are established at alarm 2.
Alarm-1 setpoint (80%)
Alarm-1 hysteresis (10%)
Low-limit alarm ON
Alarm conditions
established
Alarm-2 ON delay
Alarm conditions
established
Normal conditions
established
Normal conditions
established
Low-limit alarm OFF
Alarm-2 OFF delay
[%]
100
80
60
High-limit alarm ON
[1] [2]
1 sec
Alarm-1 ON delay
2 sec
40
20 15
Alarm-1 action
Alarm-2 action
Alarm-2 hysteresis (5%)
0
Normal
Alarm-2 setpoint (15%)
Alarm
Normal Alarm
[3]
3 sec 4 sec
Normal
[4]
Elapsed time
1 sec
Normal
All Rights Reserved. Copyright © 1999, Yokogawa M&C Corporation IM 77J01A21-01E 1st Edition : 2006.08.15-00
11. LIST OF PARAMETERS
5
No. Item Display 01 Model MODEL 02 Tag No. TAG NO 03 Self-check result SELF CHK
Display items
A Display 1 DISPLAY1 A01 Input value INPUT1 A05 Output value 1 OUTPUT1 (*1) A07 Alarm-1 status ALM1 STATUS A08 Alarm-2 status ALM2 STATUS A54 Status STATUS (*2) A56 Rev No. REV NO A58 Menu Rev MENU REV A60 Self-check result SELF CHK Setting items (*3) D Setting (I/O) SET(I/O) D01 Tag no.1 TAG NO.1 D02 Tag no.2 TAG NO.2 D03 Comment 1 COMMENT1 D04 Comment 2 COMMENT2 D11 Linearize LINEARIZE D12 Low cut LOW CUT D38 Direction of output-1 action OUT1 DR (*1) D60 Self-check result SELF CHK
Adjusting items (*3) P Adjustment ADJUST1 P02 Zero adjustment of input 1 ZERO ADJ1 P03 Span adjustment of input 1 SPAN ADJ1 P12 0% adjustment of output 1 OUT1 0% (*1) P13 100% adjustment of output 1 OUT1 100% (*1) P60 Self-check result SELF CHK
*1 : The indications and settings of the parameters are not available. *2 : The status is displayed for service personnel to see history records. *3 : To call the parameter setting items D, E, P and Q using the JHT200 Handy Terminal, execute the following operation:
Press F1
D, E, P or Q key enters above.
ENTER
keys.
No. Item Display
B Display 2 DISPLAY2 B01 Input value INPUT1 B05 Output value 1 OUTPUT1 (*1) B07 Alarm-1 status ALM1 STATUS B08 Alarm-2 status ALM2 STATUS B60 Self-check result SELF CHK
E Setting (alarm output) SET(ALM) E03 Alarm-1 setting SET POINT1 E04 Alarm-2 setting SET POINT2 E05 Direction of alarm-1 action ALM1 ACTION E06 Direction of alarm-2 action ALM2 ACTION E09 Alarm-1 hysteresis HYSTERESIS1 E10 Alarm-2 hysteresis HYSTERESIS2 E11 Alarm-1 ON delay setting ON DELAY1 E12 Alarm-2 ON delay setting ON DELAY2 E13 Alarm-1 OFF delay setting OFF DELAY1 E14 Alarm-2 OFF delay setting OFF DELAY2 E15 Direction of alarm-1 relay action RL1 ACTION E16 Direction of alarm-2 relay action RL2 ACTION E60 Self-check result SELF CHK Test items (*3) Q Test TEST Q02 Forced output 1 OUT1 TEST (*1) Q04 Forced output (alarm 1) ALM1 TEST Q05 Forced output (alarm 2) ALM2 TEST Q60 Self-check result SELF CHK
IMPORTANT
Do not change the settings of the items marked (*1) in the List of Parameters above after the delivery of the prod­uct. Doing so may result in a malfunction or a system failure.
IM 77J01A21-01E 1st Edition : 2006.08.15-00
12. MAINTENANCE
The product enters the operable status as soon as the power is turned on, but requires 10 to 15 minutes of warm-up to meet the performance requirements.
12.1 Calibration Apparatus
Calibrator (Yokogawa Meters & Instruments’ CA71 or equivalent): 1
Setting tool for adjustment (Refer to “8.2 Connecting the Setting Tools in this manual.)
12.2 Calibration Procedure
(1) Connect the instruments as shown in Fig.12.1 and Fig.
8.2.
(2) Produce the input signal equivalent to 0% of the input
range from the calibrator to the product. Then, read the input value of Display items, A01: INPUT1 using the VJ77 or JHT200 and check that the input value is within the rated accuracy range. Take the same procedure for the input signal equivalent to 25, 50, 75 and 100% of the input range and check that the input values are within the rated accuracy range. For alarm output, check the relay action by the alarm in­dicator lamp or resistance of output terminals. If the input values are out of the rated accuracy range, adjust the input signal level referring to the user’s manual for VJ77 PC-based Parameters Setting Tool (IM 77J01J77-01E) or for JHT200 Handy Terminal (IM JF81­02E).
6
Input
With SINK current
+
Calibrator
Without SINK current
Calibrator
1
3
+
3
4
Power supply
L+
10
N–
11
GND
8
Fig. 12.1
3 2
1
56
4
789
1011
Alarm-2 output
ALM2 (NO)
2
COM
5
Alarm-1 output
ALM1 (NO)
7
COM
9
Calibrator
Calibrator
All Rights Reserved. Copyright © 1999, Yokogawa M&C Corporation IM 77J01A21-01E 1st Edition : 2006.08.15-00
Loading...