Yokogawa MA7D User Manual

User’s Manual
Model MA7D Distributor (Dual-output and Unified Signal Type)
IM 77J04A07-02E
Please read through this User’s Manual before use for correct handling. Please keep this User’s Manual for future reference.
IM 77J04A07-02E
1st Edition Jul. 2003 (MC)
2nd Edition June 2004 (YK)
Network Solutions Business Divisiion
2-9-32, Naka-cho Musashino-shi, Tokyo 180-8750 Japan Phone: +81-422-52-7179 Facsimile: +81-422-52-6793
1. CAUTIONARY NOTES FOR SAFE USE OF THE PRODUCT
This User’s Manual should be carefully read before installing and oper­ating the product. The following symbol is used on the product and in this manual to ensure safe use.
This symbol is displayed on the product when it is necessary to refer to the Users Manual for information on personnel and instrument safety. This symbol is displayed in the Users Manual to indicate precautions for avoiding danger to the operator, such as an electric shock.
The following symbols are used only in this manual.
4.1 Wall Mounting
Remove the stoppers (top and bottom) from the product and pull out the main unit from the socket. Fix the socket on the wall using two M4 screws. Next, insert the main unit into the socket and fasten the main unit with the stoppers (top and bottom).
Main unit
IMPORTANT
Indicates that operating the hardware or software in a particular manner may cause damage or result in a system failure.
<Mounting Dimensions>
Socket
2-ø4.5 or 2-M4
NOTE
Draws attention to essential information for understanding the operations and/or functions of the product.
2.
CHECKING PRODUCT SPECIFICATIONS AND PACKAGED ITEMS
(1) Checking the Model and Product Specifications
Check that the model and specifications indicated on the nameplate attached to the side face of the main unit are as ordered.
4.2 DIN Rail Mounting
Insert a DIN rail into the upper part of the DIN rail groove on the rear of the socket, and then slide the slide lock at the lower part of the socket upwards until the socket is fixed into position as shown below.
(2) Packaged Items
Check that the packing carton contains the following items:
MA7D: 1
Spacer (used for DIN rail mounting): 1
User’s Manual (this manual: IM 77J04A07-02E): 1 copy
3. GENERAL
This plug-in type distributor is used in combination with a two-wire type transmitter to convert the transmitter’s 4 to 20 mA DC signals into 4 to 20 mA DC current or 1 to 5 V DC voltage signals.
40±0.2
DIN rail
4. MOUNTING METHOD
Pitch: 55 or more
5 or more
(51)
Push
Mounting
screws
(85)
Fit into here
DIN rail
Spacer
Stopper
Socket
Unit: mm
Note: (1) More than 5 mm interval is
required for side-by-side close mounting.
(2) Use the supplied spacer for
DIN rail mounting to keep 5 mm interval.
(Rear of the socket)
NOTE
Insert/pull out the main unit into/from the socket vertically to the face of socket. Otherwise the terminals are bent and it may cause a bad contact.
Slide lock
4.3 Using a Duct
When using a wiring duct, install the duct at leaset 20 mm away from the top and bottom faces of the main unit.
5. INSTALLATION LOCATIONS
Avoid the following environments for installation locations: Areas with vibration, corrosive gases, dust, water, oil, solvents, di­rect sunlight, radiation, a strong electric field, and/or a strong magnetic field
If there is any risk of a surge being induced into the power line and/or signal lines due to lightning or other factors, a dedicated lightning arrester should be used as protection for both this unit and a field-installed device.
6. EXTERNAL WIRING
WARNING
To avoid the risk of an electric shock, turn off the power supply and use a tester or similar device to ensure that no power is supplied to a cable to be connected, before carring out wiring work.
Wiring should be connected to the terminals on the socket of the prod­uct. The terminals for external connections are of M3.5 screws. Use crimp-on terminal lugs for connections to the terminals.
Recommended cables: A nominal cross-sectional area of 0.5 mm or thicker for signal cables, and that of 1.25 mm2 or thicker for power cables.
Power supply
L+
7
N–
8
GND
9
Output-2
+
10
11
8 7 6 5
10 11
1 2
Input
4
39
When using
internal
power supply
+
Output-1
1
2
PS+
COM
+
When using
external
power supply
4
5
6
Example to construct
Intrinsically Safe System
using Zener Barrier
4
+
+
5
6
4
5
6
7. PART NAMES OF FRONT PANEL
The figure below shows the MA7D with its front panel (cover) being open.
Output-1
Zero-adjustment volume
Span-adjustment volume
Output-2
Zero-adjustment volume
Span-adjustment volume
Power indicator lamp
Lit during power on
8. MAINTENANCE
The product starts running immediately when the power is turned on; however, it needs 10 to 15 minutes of warm-up before it meets the
2
specified performance.
8.1 Calibration Apparatus
A DC voltage/current standard (Yokogawa 7651 or the equivalent)
A digital multimater (Yokogawa 7561 or the equivalent)
A precision resistor of 250 ± 0.01%, 1 W
8.2 Calibration Procedure
(1) Connect the instruments as shown below. First adjust the output-1
signal and then the output-2 signal.
(2) Use the DC voltage/current standard and apply input signals
equivalent to 0, 25, 50, 75, and 100% of the input span to the product. Check to see the corresponding output voltages are 0, 25, 50, 75, and 100% respectively and within the specified accu­racy rating. “R” is used for current output.
If the output signals are out of the accuracy rating range, adjust the output signal level using the zero and span adjustment vol­umes on front face of the product.
IMPORTANT
The power line and input/output signal lines should be installed away from noise-generating sources. Other wise accuracy cannot be guaranteed.
The grounding resistance must be 100 Ω (JIS Class D grounding). The length and thickness of the grounding cable should be as short and thick as possible. Directly connect the lead from the ground terminal (terminal no.
9) of the product to the ground. Do not carry out daisy­chained inter-ground terminal wiring.
Use of the product ignoring the specifications may cause overheating or damage. Before turning on the power, ensure the following: (a) Power supply voltage and input signal value applied
to the product should meet the required specifications.
(b) The external wiring to the terminals and wiring to
ground are as specifications.
Do not operate the product in the presence of flammable or explosive gases or vapors. To do so is highly dangerous.
The product is sensitive to static electricity; exercise care in operating it. Before you operate the product, touch a nearby metal part to discharge static electricity.
Power supply
L
7
N
8
GND
9
Output-2
10
Digital
R
multimater
11
R: 250  precision resistor for current output
8 7 6 5
10 11
1 2
Input
With SINK current
4
DC voltge/ current
standard
5
Without SINK current
5
4
39
DC voltge/ current
standard
6
Output-1
1
Digital
R
multimater
2
R: 250  precision resistor for current output
2
IM 77J04A07-02E 2nd Edition June 01,2004-00