Thank you for purchasing the CX1000. This manual describes the functions (excluding
the communications functions), installation and wiring procedures, operating procedures,
and handling precautions of the CX1000. To ensure correct use, please read this
manual thoroughly before beginning operation. The following four manuals are also
provided in addition to this manual. Read them along with this manual.
Electronic Manuals Provided on the Accompanying CD-ROM
Manual TitleManual No.Description
CX1000/CX2000IM 04L31A01-17EDescribes the communications functions of the
Communications InterfaceCX1000/CX2000 using the Ethernet/serial
interface.
User’s Manual
DAQSTANDARD for CXIM 04L31A01-61EDescribes the functions and operating
User’s Manualprocedure of the software “DAQSTANDARD
for CX” that comes with the package.
Paper Manuals
Manual TitleManual No.Description
CX1000 Installation andIM 04L31A01-73EDescribes concisely the installation
Connection Guideprocedures and wiring procedures of the
CX1000.
Precautions on the Use ofIM 04L31A01-72EPrecautions regarding the use of the CX1000/
the CX1000/CX2000CX2000. The same information is written on
pages ii and iii of this user’s manual.
• This manual describes the CX1000, style number “S1.”
• The contents of this manual are subject to change without prior notice as a result of
continuing improvements to the instrument’s performance and functions. Note that
the program control operation described in this manual is not supported by this
version of the CX1000. Therefore, the information regarding the program control
operation may not be correct.
• Every effort has been made in the preparation of this manual to ensure the accuracy of
its contents. However, should you have any questions or find any errors, please contact
your nearest YOKOGAWA dealer as listed on the back cover of this manual.
• Copying or reproducing all or any part of the contents of this manual without the
permission of Yokogawa Electric Corporation is strictly prohibited.
• The TCP/IP software of this product and the document concerning the TCP/IP
software have been developed/created by YOKOGAWA based on the BSD
Networking Software, Release 1 that has been licensed from the Regents of the
University of California.
• Microsoft, MS-DOS, Windows, and Windows NT are either registered trademarks
or trademarks of Microsoft Corporation in the United States and/or other countries.
• Zip is either a registered trademark or trademark of Iomega Corporation in the
United States and/or other countries.
• Adobe and Acrobat are trademarks of Adobe Systems incorporated.
• Company and product names that appear in this manual are trademarks or registered
trademarks of their respective holders.
• Read this manual thoroughly and have a clear understanding of the product before operation.
• This manual explains the functions of the product. YOKOGAWA does not guarantee that the product will suit
a particular purpose of the user.
• Under absolutely no circumstances may the contents of this manual be transcribed or copied, in part or in
whole, without permission.
• The contents of this manual are subject to change without prior notice.
• Every effort has been made in the preparation of this manual to ensure the accuracy of its contents.
However, should you have any questions or find any errors or omissions, please contact your nearest
YOKOGAWA dealer.
Precautions Related to the Protection, Safety, and Alteration of the Product
• The following safety symbols are used on the product and in this manual.
“Handle with care.” (To avoid injury, death of personnel or damage to the instrument, the
operator must refer to the explanation in the manual.)
Functional ground terminal. (Do not use this terminal as a protective ground terminal.)
Protective grounding terminal
Alternating current
• For the protection and safe use of the product and the system controlled by it, be sure to follow the
instructions and precautions on safety that are stated in this manual whenever you handle the product.
Take special note that if you handle the product in a manner that violate these instructions, the protection
functionality of the product may be damaged or impaired. In such cases, YOKOGAWA does not
guarantee the quality, performance, function, and safety of the product.
• When installing protection and/or safety circuits such as lightning protection devices and equipment for
the product and control system or designing or installing separate protection and/or safety circuits for
fool-proof design and fail-safe design of the processes and lines that use the product and the control
system, the user should implement these using additional devices and equipment.
• If you are replacing parts or consumable items of the product, make sure to use parts specified by
YOKOGAWA.
• This product is not designed or manufactured to be used in critical applications that directly affect or
threaten human lives. Such applications include nuclear power equipment, devices using radioactivity,
railway facilities, aviation equipment, air navigation facilities, aviation facilities, and medical equipment. If
so used, it is the user’s responsibility to include in the system additional equipment and devices that
ensure personnel safety.
• Do not modify this product.
iiIM 04L31A01-03E
Safety Precautions
WARNING
Power Supply
Ensure that the source voltage matches the voltage of the power supply before turning ON the
power.
Protective Grounding
Make sure to connect the protective grounding to prevent electric shock before turning ON the
power.
Necessity of Protective Grounding
Never cut off the internal or external protective earth wire or disconnect the wiring of the protective
earth terminal. Doing so invalidates the protective functions of the instrument and poses a potential
shock hazard.
Defect of Protective Grounding
Do not operate the instrument if the protective earth or fuse might be defective. Make sure to
check them before operation.
Do Not Operate in an Explosive Atmosphere
Do not operate the instrument in the presence of flammable liquids or vapors. Operation in such
environments constitutes a safety hazard.
Do Not Remove Covers
The cover should be removed by YOKOGAWA’s qualified personnel only. Opening the cover is
dangerous, because some areas inside the instrument have high voltages.
External Connection
Connect the protective grounding before connecting to the item under measurement or to an
external control unit.
Damage to the Protective Structure
Operating the CX1000 in a manner not described in this manual may damage its protective structure.
Exemption from Responsibility
• YOKOGAWA makes no warranties regarding the product except those stated in the WARRANTY that is
provided separately.
• YOKOGAWA assumes no liability to any party for any loss or damage, direct or indirect, caused by the
user or any unpredictable defect of the product.
Handling Precautions of the Software
• YOKOGAWA makes no warranties regarding the software accompanying this product except those
stated in the WARRANTY that is provided separately.
• Use the software on a single PC.
• You must purchase another copy of the software, if you are to use the software on another PC.
• Copying the software for any purposes other than backup is strictly prohibited.
• Please store the original media containing the software in a safe place.
• Reverse engineering, such as decompiling of the software, is strictly prohibited.
• No portion of the software supplied by YOKOGAWA may be transferred, exchanged, sublet, or leased for
use by any third party without prior permission by YOKOGAWA.
IM 04L31A01-01E
iii
Checking the Contents of the Package
Unpack the box and check the contents before operating the instrument. If some of the
contents are not correct or missing or if there is physical damage, contact the dealer
from which you purchased them.
CX1000
When you open the operation cover on the front panel, a name plate is located on the
back side of the cover. Check that the model name and suffix code given on the name
plate on the rear panel match those on the order.
Open the operation
cover
STYLE
MODEL
SUFFIX
NO
STYLE
MODEL and SUFFIX
Model
CX1006
CX1206
External
storage
medium
Communication
interface
Displayed language
Options
*1
Suffix Code –2 (Ethernet + RS-422A/485 serial interface port) must be selected for the communication interface and
/CM1 (Green series communications) must be selected for the Optional Code.
*2
Includes the Modbus master/slave function. However, to use the Modbus master function, /M1 must be selected for the
Optional Code.
*3
Only one of the options can be specified on the CX1006. Cannot be specified on the CX1206.
*4
Suffix Code –1 (with RS-232 serial interface port) or –2 (with RS422/485 interface port) must be selected for the
communication interface. Either one can be specified on the CX1206. Ladder communication (/CM2) cannot be
specified on the CX1006.
*5
Either one can be specified on the CX1206.
Suffix CodeOptional CodeDescription
*1
Number of internal control loops: 0, number of inputs for measurement: 6 ch
Number of internal control loops: 2, number of inputs for measurement: 6 ch
–1
–2
–3
When contacting the dealer from which you purchased the instrument, please give them
the instrument number.
ivIM 04L31A01-03E
Standard Accessories
The standard accessories below are supplied with the instrument. Check that all
contents are present and that they are undamaged.
Checking the Contents of the Package
or
1
No. NamePart Number/Model Q’ty Note
1Terminal screws5M4
2Mounting bracketB9900BX2For panel mounting
3DAQSTANDARDCXA100-011Software for setting the CX and
4CX1000/CX2000B8700MA1CD-ROM containing the PDF files of this
5CX1000 Installation and IM 04L31A01-73E1Abridged paper manual
6Precautions on the Use IM 04L31A01-72E1Paper stating the precautions.
7External storage medium A1053MP1Zip disk (provided only when the external
2
for CXdisplaying data CD-ROM used to install
electronic manualmanual, the CX1000/CX2000
Connection Guide
of the CX1000/CX2000
3
Optional Accessories (Sold Separately)
The following optional accessories are available for purchase separately. When you
receive the order, check that all contents are present and that they are undamaged.
For information and ordering, contact your nearest YOKOGAWA dealer.
Part NamePart Number/ModelQ’tyNote
3.5" floppy disk7059 00102HD
Zip diskA1053MP1100 MB
ATA flash memory cardB9968PK124 MB (The size and model may
Shunt resistance4159 201250 Ω±0.1%
(for the screw terminal)4159 211100 Ω±0.1%
Mounting bracketB9900BX2
4
B9968PK1ATA flash memory card, provided only
4159 22110 Ω±0.1%
5
6
“DAQSTANDARD for CX”
Communication Interface User’s Manual,
DAQSTANDARD for CX User’s Manual,
and other files.
storage medium suffix code is “-2”)
when the external storage medium suffix
code is “-3” (the size and model may
change in the future)
change in the future. Check with your
YOKOGAWA dealer when ordering.)
7
IM 04L31A01-01E
v
How to Use This Manual
Structure of the Manual
This user’s manual consists of the following sections. For details on the communications
functions and the software “DAQSTANDARD for CX” provided with the package, see the
respective manuals (IM 04L31A01-17E and IM 04L31A01-61E).
ChapterTitle and Description
1Explanation of Functions
Describes in detail the functions of the instrument. The chapters that explain the
operation of the CX1000 only describe the operating procedures. For more detailed
information about the functions, see this chapter.
2Installation and Wiring
3Names of Parts, Display Modes, and Common Operations
4Control Function Related Setup Operations
5Program Control Related Setup Operations (Only on Models with the Program
6Operations during Control Operation
7Measurement Function Related Setup Operations
8Operations for Changing the Displayed Contents
9Data Save/Load Operations
10Computation and Report Function Related Operations (Only on Models with the
11Operations of Other Functions
12Troubleshooting
13Maintenance
14Specifications
AppendixDescribes the acquisition function of measured data to the internal memory, additional
Index
Describes the installation and wiring procedures of the CX1000.
Describes the names of the parts of the CX1000, the basic key operations, the basic
operations carried out initially, and how to use the external storage medium drive.
Describes setup operations related to the control function that are carried out before
starting control operations.
Control Option)
Describes the setup operations related to program control that are carried out before
starting control operations on models with the program control option.
Describes how to switch operation mode during control operation, how to change the
setpoints of setting mode, how to tune the control parameters, and the operations on the
program control screen (operations only on models with the option).
Describes how to set the PV input of the measurement function and alarms
(measurement alarms).
Describes how to change the operating display of both the control function and the
measurement function and the display format.
Describes how to write various data to the internal memory, how to save and load from
the external storage medium, and the file operations on the external storage medium.
Computation Function Option)
Describes how to set and execute operations related to the computation function and
report function of the computation function option.
Describes the USER key, key lock, login/logout of key operation, log display, and
remote input setting.
Describes the error messages and the troubleshooting measures of the CX1000.
Describes periodic inspection, calibration, and recommended replacement period for
worn parts.
Describes the specifications of the CX1000.
information on the computation and report functions, the ASCII file format, and initial settings.
Note
• This user’s manual covers information regarding CX1000s that have a suffix code for
language “-2” (English).
• For details on setting the displayed language, see
Danger. Refer to corresponding location on the instrument.
This symbol appears on dangerous locations on the instrument
which require special instructions for proper handling or use. The
same symbol appears in the corresponding place in the manual to
identify those instructions.
WARNING
CAUTION
Note
Symbols Used on Pages Describing Operating Procedures
On pages that describe the operating procedures in Chapter 3 through 11, the following
symbols are used to distinguish the procedures from their explanations.
[ ] ................Indicates character strings that appear on the screen.
Procedure
Calls attention to actions or conditions that could cause serious
injury or death to the user, and precautions that can be taken to
prevent such occurences.
Calls attentions to actions or conditions that could cause damage to
the instrument or user’s data, and precautions that can be taken to
prevent such occurrences.
Calls attention to information that is important for proper operation
of th instrument.
Example: [Space] soft key, [Volt]
This subsection contains the operating procedure used to carry out
the function described in the current section. All procedures are
written with inexperienced users in mind; experienced users may
not need to carry out all the steps.
IM 04L31A01-01E
Setup Items
Describes the details of the settings and the restrictions that exist with
the operating procedure. It does not give a detailed explanation of
the function. For details on the function, see chapter 1.
Appendix 7 Control Function Block Diagram ...................................................................... App-33
Appendix 8 Explanation of Engineering Units (EU and EUS)............................................. App-39
1
2
3
4
5
6
7
8
9
10
11
12
13
14
IM 04L31A01-01E
App
Index
xi
Chapter 1 Explanation of Functions
1.1CX1000 Overview
The CX1000 consists of a control function and a measurement function. The control
function executes control through PID control and ON/OFF control. The measurement
function displays and acquires measured data and control-output data.
Control Function
The CX1000 supports thee control modes: single-loop control, cascade control, and loop
control with PV switching. It can handle up to two loops of PID control. In addition, the
UT Series controllers made by Yokogawa M&C Corporation can be connected and
controlled simultaneously as external loops (four loops max.). You can check the control
status on the controller style and faceplate style displays and the hybrid style display that
is a mixture of the two styles. Furthermore, the overview display allows monitoring of all
control loops including external loops. In addition, the CX1000 provides auto-tuning of
PID constants as well as manual tuning, which enables you to adjust the control
parameters such as PID constants while checking the control status.
Measurement Function
In addition to the measured data for the control function, the CX1000 can acquire up to
six channels of measured data. The data can be displayed as waveforms, numeric
values, and bar graphs. The measured data along with the control data can be stored to
a floppy disk, Zip disk, or ATA flash memory card using the built-in drive.
Conceptual Input/Output Diagram
1
Explanation of Functions
PC
• Universal control output: for 2 loops
Select current, voltage pulse, or
relay output.
Select one from the following option
terminal blocks.
Measurement alarm output
(/A6 option)
Measurement alarm output +
FAIL/memory end output
(/A4F option)
PLC
(such as the FA-M3
by YOKOGAWA)
Measurement alarm
output + remote input/
output
(/A6R option)
Measurement alarm
output + FAIL/memory
end output + remote
input/output
(/A4FR option)
IM 04L31A01-03E
1-1
1.2Control Function Overview
Control Signal Input/Output
As shown in the following figure, the CX1000 can control up to two loops.
Control PV input
Control output
• Relay
• Voltage pulse
DISP/
ENTER
• Current
CX
The UT Series controllers made by Yokogawa M&C Corporation can be connected via
the serial interface and controlled simultaneously as external loops (four loops max.)
(see the
CX1000/CX2000 Communication Interface User’s Manual
Analog Input for Loop Control
PV input and remote setpoint input (RSP) are available as control signal inputs. You can
select thermocouple, resistance temperature detector, standard signal, or DC voltage for
both PV input and RSP input. The RSP input is used as a terget setpoint (SP). There
are five input terminals on the control/measurement input terminal block. The figure
below shows their assignments according to the number of loops used and the control
mode (see the
[Control mode setting]
During single-loop control
During cascade control
During loop control with
PV switching
You can apply scale conversion, bias, input filter, ten-segment linearizer bias, tensegment linearizer approximation, and square-root computation on the control signal
input. For thermocouple inputs, you can set reference junction compensation. In
addition, ratio setting can be specified against RSP inputs.
(number of analog inputs: 5)
[Up to 2 loops]
Controls
and
switches
······
• SSR
• Magnet switch
etc.
next page
).
LOOP2
21321
PV, PV1, PV2: PV input, (RSP): RSP input
(not used during program control), : unused terminal
Object of
control
(RSP)
LOOP1
(RSP)(RSP)
(RSP)
• TC
• RTD
etc.
).
Measurement input terminals
PVPV
PVPV
PV1PV1PV2PV2
Control Signal Output
The terminal provides universal output. Two loops can be controlled (except cascade control
which uses two loops for one control). The following types of control output can be selected.
• PID control output
• Time proportional PIDOutputs ON/OFF signals with a pulse width that is proportional
relay contact output:to the time as relay contact signals according to the computed
PID value.
• Time proportional PIDOutputs ON/OFF signals with a pulse width that is proportional to
voltage pulse output:the time as voltages according to the computed PID value.
• Current output (continuous Continuously outputs a current (analog signal) that is
PID control output):proportional to the computed PID value.
• On/off control relayOutputs on/off control relay contact signals according to the
contact output:polarity (positive/negative) of the deviation between the SP
and the PV.
1-2IM 04L31A01-03E
SP
PV
OUT
SP
PV
OUT
PV derivative type PID
(with output bump)
Deviation derivative type PID
(with output bump)
1.2 Control Function Overview
Control Methods
PID control and ON/OFF control are available. The following control modes can be
selected for both PID control and ON/OFF control.
Control Mode
In PID control, the following three control modes are available in relation to the PV input
selection.
• Single-loop control
Basic control consisting of a single system of controller CPU.
PV
PIDSP
OUT
• Cascade control
Control consisting of two systems of controller CPUs that use the primary control
output as the secondary control SP.
PV1
PIDSP
PV2
PID
OUT
• Loop control with PV switching
Single-loop control that is switched between two PV inputs (PV1 and PV2) according
to a specified condition.
PV1
PV2
1
Explanation of Functions
IM 04L31A01-03E
PIDSP
OUT
In PID control, you can also select the PID control mode.
PID Control Mode
Depending on the desired operation at the time the SP is changed, you can select the
PID control mode from below. The selections between the PV derivative type and
deviation derivative type as well as the presence or absence of the control output bumps
are automatically made according to the PID control mode and operation mode (fixedpoint control or program control).
• Standard PID control
Controlled so that the control output reaches the new SP quickly after the SP is
changed.
• Fixed-point control
Select this mode if you wish to avoid the control OUT from reacting sensitively to the
SP change causing a disturbance in the control such as in the case with a continuous
fixed-point control.
PV derivative type PID (without output bump) PV derivative type PID (with output bump)
SP
SP
PVOUT
PV
OUT
1-3
1.2 Control Function Overview
Control Parameters
The following control parameters are available. For each group, you can enter up to
eight sets of SPs and PID parameters as underlined below.
SP,
value, relay hysteresis, control action direction, preset output, SP tracking, PV tracking,
setpoint limiter, output velocity limiter, auto/manual switching of the over-integration
prevention function (anti-reset windup), ON/OFF of the control output suppression
function, and SP ramp-rate.
PID Selection Method
The following two methods are available.
• Target setpoint selection method
PV
Rise according to the
setpoint ramp-up
SP1
(No.1 PID)
Switch from SP1 to SP3Switch from SP3 to SP1 Switch from SP1 to SP2
• Zone PID method
Maximum value of
measurement span
Reference point 6
Reference point 5
Reference point 4
Reference point 3
Reference point 2
Reference point 1
Minimum value of
measurement span
Note
PID constant, control output limiter, ON/OFF of the shutdown function, manual reset
A group (up to 8 groups) consisting of a SP and PID parameters is registered to a PID
number (SP number). By specifying the SP number using keys on the front panel,
external contact input, or via communications, the SP and PID parameters are
switched.
SP3
(No.3 PID)
setting
Fall according to the
setpoint ramp-down
setting
SP1
(No.1 PID)
SPn: Target setpoint number
SP2
(No.2 PID)
Rise according to the
setpoint ramp-up
setting
Time
The measurement span is divided into a maximum of seven zones using reference
points. The optimum PID constant is preassigned to each zone, and the PID constant
(in actuality, other control parameters that are registered using the PID number are
included) is automatically switched according to the PV. This method is suited for
controlling equipment such as reactors in which the chemical reaction gain varies
depending on the temperature.
If the current PV is here, PID
constant of PID No. 5 is used
for control.
Change in the
PV.
• When performing program control operation on models with the program control option,
you will select between segment PID method (zone PID selection OFF) and zone PID
method.
• For a description on auto tuning, which automatically sets the optimum PID constant, see
section 1.12, “Tuning.”
No.7 PID
No.6 PID
No.5 PID
No.4 PID
No.3 PID
No.2 PID
No.1 PID
1-4IM 04L31A01-03E
1.2 Control Function Overview
Alarm Output
When the control action status matches the preset status (up to 4 points per loop), the
CX1000 can output a relay contact signal from the control output terminal block or the DIO
expansion terminal block or display the alarm occurrence status on the screen. In relay
contact output, you can select and assign the type of alarm you wish to output at each
output terminal of the control output terminal block or the control DIO extension terminal
block.
Alarm Type
You can select the alarm type from below. For a detailed explanation on each alarm
output, see
section 1.10, “Control Alarm Related Settings.”
PV high-limit alarm, PV low-limit alarm, deviation high-limit alarm, deviation low-limit
alarm, deviation high & low limit alarm, deviation within high & low limits alarm, SP highlimit alarm, SP low-limit alarm, output high-limit alarm, and output low-limit alarm.
Alarm Hysteresis
You can set a hysteresis to the setpoints used in the activation and releasing of the alarm.
Example of PV high limit alarm
OFF
PV
Time
ON
Alarm setpoint
Hysteresis
Alarm ON
OFF
ON
OFF
1
Explanation of Functions
Alarm Standby
You can put the alarm output on standby at the initial stage of control operation until the
PV input reaches the SP.
PV
Power up
Normal
handling
Alarm Mode
You can set the condition for disabling the alarm output (such as when the operation is stopped).
FAIL Output/Self Diagnosis Output
In addition to the alarm output described above, the following relay contact signal for
failure detection can be output from the control output terminal block.
• FAIL output
Output when a failure is detected in the CX1000 CPU. When a failure is detected, the
CX1000 is put in the following condition.
Control: Stopped (preset output if in the middle of operation, control output is off or
0% when power is turned ON)
• Self diagnosis output
Output when an input burnout, A/D converter failure, or RJC failure occurs. If an input
burnout or A/D converter failure is detected, the control output is set to the preset
output value. For RJC, PID control continues as though RJC is 0 °C.
Normal
Alarm is not output during this
period even if the PV is below
the alarm low limit.
Failure
Alarm output ON
Hysteresis
Alarm low limit value
Time
IM 04L31A01-03E
1-5
1.2 Control Function Overview
Control Operation Mode
The following control operation switching is available. The control operation can be
switched using keys on the CX1000 control group display (see
inputs, or via communications. For a description of the control operation modes on
models with the program control option, see “
control function block diagram in the explanation below is a simplified one. For a
detailed control function block diagram for each control mode, see appendix 7.
Switching between Remote (REM) and Local (LOC)
Select whether control is executed using the SPs set on the CX1000 or using the
external analog signal (RSP) as the SP.
PV inputRSP input
PV
SP
Local
(LOC)
Controller CPU
RSP
Remote
(REM)
(Analog signal)
Program Control
page 1-12
), using contact
” in the next section. The
Control output
OUT
Switching between Auto (AUT), Manual (MAN), and Cascade (CAS)
When set to auto, the control output value (OUT) is computed from the deviation between the PV
input and the SP. When set to manual, the control output value (OUT) that is set manually is
used rather than the computed control output value (OUT). Switching to “cascade (CAS)” is
possible only when the control mode is set to “cascade control.” In cascade control, the primary
PID control output is used as the SP of the secondary PID control.
Switching between Run (RUN) and Stop (STP)
When the operation is stopped, the control output value (OUT) is set to the preset value.
Single-loop control
Manual operation
Manual (MAN)
Preset output
Stop (STP)
PV input
PV
Controller CPU
Output limiter
Run (RUN)
Control output
SP
Auto (AUT)
OUT
Cascade control
PV input 1
(Cascade primary)
PV1PV2
Controller CPU 1
Cascade
Manual (MAN)
SP1
PV input 2
(Cascade secondary)
SP2
Auto/
Manual
Controller CPU 2 Manual operation
Cascade/
Auto
(CAS/AUT)
Output limiter Preset output
Run (RUN)Stop (STP)
Control output
OUT
Enabling/Disabling Auto-Tuning
In PID control, the optimum PID constant is set automatically when auto-tuning (see
page 1-52
) is performed. Auto-tuning is possible only during auto operation.
Contact Input
Contact input can be used to carry out operations such as running/stopping operation,
switching operation modes, changing SPs, switching PV inputs (during loop control with
PV switching). For a description on the possible operations, see “Contact Input
Information Registration” on
1-6IM 04L31A01-03E
page 1-23
.
1.2 Control Function Overview
Program Control (Optional Function)
This function is used to ramp-up or ramp-down the SP according to a program pattern. You can
set multiple program patterns (up to 30) and switch among them according to the operating
condition. A program pattern consists of multiple program segments.
There are two methods in selecting the PID constant in program control. One is the
“segment PID method” in which the PID constant is switched every segment according to
the program pattern setting; the other is the “zone PID method” in which the PID
This function cannot be used on the current version of the CX1000.
The infomation given here may change in the future.
constant is automatically switched according to the PV. The “segment PID method” is
used when a different PID constant is required in the same PV region when the
temperature is rising and when the temperature is falling.
Segment PID method
PV
1000.0
500.0
0.0
SEG1SEG2SEG3SEG4SEG5SEG6SEG7
No.2 PID
Setting the Operation for Program Control
Settings include the number of repetitions of the program pattern (repeat function), delay
function (wait function) for the case when the PV cannot follow up the SP, and alarm
output/event output assignments (contact output assignments) according to the program
progression.
Operation Mode during Program Control
The following 4 types of operation modes are available.
• Program operation mode
Condition in which control is carried out according to the program pattern.
• Hold operation mode
Condition in which program operation is paused.
• Reset mode
Condition in which program operation is stopped. All event outputs are cleared (off).
• Local operation mode
Mode in which fixed-point control is performed independently from the program
operation condition.
No.1 PIDNo.3 PID
The PID constant of PID No. 1
is used in the 5th segment (SEG5).
1
Explanation of Functions
IM 04L31A01-03E
RESET
Reset mode
RESET
Program operation modeHold operation mode
Since the remote input cannot be used for the SP during program control, there is no
remote/local switching operation.
RUN
RUN per
loop
Release HOLD
HOLD
Program operation
Local operation mode
LOC
1-7
/
1.2 Control Function Overview
Flow of Setup Procedure
Below is a standard flow of setup procedure in executing control for the first time using
auto operation.
Power ON
Initial settings include the following
parameters.
Set SP
Set relay hysteresis
Set other control
parameters
Set alarm-related
parameters
Operating condition
Stop control
Initial settings
PID control or
ON/OFF control?
Set SP
Section 1.10
Set PID parameters
Set alarm-related
parameters
Start a test run
Operating condition
Adjust control
Start actual operation
Initial settings
Basic control settings
PV input related settings
Contact input/output
*
*
Set in
"Control Output Type"
PID controlON/OFF control
of basic control settings
related settings
Control output
suppression
→ Section 1.3
→ Section 1.4
→ Section 1.5
→ Section 1.6
→ Section 1.7
→ Section 1.10
• Auto tuning
• Manual tuning → Section 1.12
• Other adjustments
(Parameters that cannot be changed
during operation → section 6.1)
When using program control, set the items that include “Program control: On” in “Basic
control settings” indicated above. Then, carry out the following settings in addition to
“Target setpoint/PID parameter settings.”
Settings for program control
This function cannot be used on the current version of the CX1000.
The infomation given here may change in the future.
Pattern initial setting
Wait operation setting
Pattern start setting
Program pattern setting
Event setting
Event output setting
Repeat action setting
Operation start time
Start segment number
*
The operation start time and start segment number is set using key
operations on the operation screen.
→ Section 1.11
Pattern initial setting:
Set the pattern numbers, pattern off/on, number of
segments used, segment assignment method, and
edit segment number.
Wait operation setting:
Set wait zone off/on, wait zone settings, and timer.
Pattern start setting:
Set starting target setpoint and start code (operation
start condition).
Program pattern setting:
Set segment numbers, ramp/soak, final target setpoint,
segment time, ramp-rate-time unit, ramp-rate, segment
PID group numbers, operation at the time of segment
switching, wait operation type, and wait numbers.
Event setting:
Set event types, loop number/type/setpoint (only when
PV event is selected), time event ON/OFF, and ON time
OFF time (only when time event is selected).
Event output setting:
Set the event type, relay output ON/OFF, and relay
output number.
*
Repeat action setting:
Set the repeat function, number of repetitions, start
*
segment number, and end segment number.
1-8IM 04L31A01-03E
1.2 Control Function Overview
Switching Displays
Power ON
Operation display
MENU key
Soft keys
Operation mode
ESC key
Control setting mode
[Setting mode (Control)]
Menu
MENU key or
ESC key
Setup display
(#1 to #7
*
)
Control-related settings are entered in basic setting mode and control setting mode. In
addition, settings common to control and measurement are entered in the common and
measurement setting mode.
Display Transition Diagram
[End] soft key -> DISP/ENTER key
(This operation saves the settings made
in the basic setting mode.)
MENU key or ESC key
MENU key
Press the FUNC
key for 3 s
Soft keys
Common and measurement setting mode
[Set mode]
Press the FUNC
Menu
MENU key or
ESC key
Setup display
(#1 to #11)
key for 3 s
Soft keys
Basic setting
mode
Menu
ESC key
Setup display
(#1 to #12
**
)
1
Explanation of Functions
*
#1 to #8 when program control
is ON.
**
#1 to #11: Basic common and
measurement settings
#12: Basic control settings
Basic Control Setup Items in Basic Setting Mode
#1 Control action
PID number, control period, zone PID, restart mode, restart mode (program) (only on
models with the control option), initial PID, auto tuning, control mode, method (only
during loop control with PV switching), program control ON/OFF (only on models with
the program control option), and PID control mode.
#2 Input setting
Burnout and RJC.
#3 Contact input-registration
Contact input registration
#4 AUX
Remote setting, alarm mode, and SP number selection source.
#5 Output processing
Control output, cycle time, and analog-output type
#6 Relay
FAIL ON/OFF, self diagnosis ON/OFF, and relay action/behavior (energize/deenergize, hold/nonhold)
#7 Tuning setting
Tuning item selection
#8 External loop setting (For details on the settings, see the
Communication Interface User’s Manual
.)
CX1000/CX2000
Setup Items in the Control Setting Mode
#1 Control input range
Input type, mode, type, range, span, scale, unit, square root, low-cut, bias, filter, and ratio.
#2 Control alarm
Type, standby, relay output ON/OFF, and alarm value
IM 04L31A01-03E
1-9
1.2 Control Function Overview
#3 Operation-related parameters/Zone PID
#4 PID parameters
#5 Control group setting
#6 Ten-segment linearizer I/O
#7 Program control (only when program control is ON)
#8 Detailed setting (“#7” when program control is OFF)
Suppressing function, ramp-rate-time unit, SP ramp-down-rate/SP ramp-up-rate, tag,
tag comment, reference point (when zone PID is selected), switching hysteresis
(when zone PID is selected), and reference deviation (when zone PID is selected).
SP, PID constant, output limit, shutdown ON/OFF, manual reset, relay hysteresis
(only during ON/OFF control), reverse/direct, and preset output.
Group name, kind (internal loop/external loop/measurement channel), and number.
Input type, mode, and biasing or approximation input/output values.
#1Program parameter setting
Pattern initial setting, wait action setting, program start setting, program pattern
setting, event setting, and repeat action setting.
#2Event output setting
Event kind, relay output ON/OFF, number, and program pattern end signal relay
output ON/OFF.
#3AUX (Auto message, Display position)
Auto message for program Run/Reset and Program display position.
In operation mode, the following control operation displays can be shown.
• Control group display
This display is used to monitor the control status of multiple loops simultaneously
including external loops. You can select from three display styles as shown in the
display example in the figure below. If you include the measurement channels for the
measurement function in the group, you can also monitor the measured values on the
measurement channels at the same time on this display.
• Tuning display
This display is used to optimize (tune) the control parameters such as PID constants.
• Overview display
This display is used to monitor the alarm status of all control loops.
• DI/DO status display
Displays the ON/OFF status of the current contact input (DI) and contact output (DO).
• Control action summary display
Displays a log of control actions such as operation run/stop and auto/manual
operation switching.
On models with the program control function option, the following additional displays are
available: 1) the program operation display, which can show the pattern and current PV
accumulated on the screen during program operation and 2) the program event
summary display, which shows a log of time events and PV events that occurred during
program operation. Displays common with the measurement function include: 1) the alarm
summary display, which shows a log of alarm occurrence status and 2) the memory summary
display, which shows the file information of the internal memory. In addition, the values of PV,
SP, and OUT can be assigned to channels, and the trends of these channels can be displayed
along with the trends of measurement channels on the trend display of the measurement
function.
• Control group display
1
Explanation of Functions
Display Examples
IM 04L31A01-03E
• Tuning display
• Control operation summary display
Faceplate styleHybrid styleController style
• Overview display
• Trend display
• DI/DO status display
1-11
1.2 Control Function Overview
Saving Data
Acquisition to the Internal Memory
Along with the measurement data, the data of SPs, PVs and OUT, and event information
for control are acquired to the internal memory.
Saving Data to the External Storage Medium
You can save the data acquired in the internal memory to an external storage medium
(floppy disk, Zip disk, or ATA flash memory card).
Floppy disk
Communications
CX
1
6
26
21
16
11
2
7
27
22
17
12
DISP
3
8
4
9
5
10
/ENTER
28
23
18
13
29
24
19
14
30
25
20
15
• Control setup data
• Measurement setup data
Zip disk
ATA flash memory card
• Measured data
The following communications functions are available. For a description on the handling
of the communications function and the software “DAQSTANDARD for CX” that comes
with the package, see the respective manuals.
Communications with Controllers
The CX1000 can communicate with UT Series Controllers made by Yokogawa M&C
Corporation to transmit/receive control parameters and receive PV data. Up to four
external loops can be constructed.
CX
1
6
26
21
16
11
2
7
27
22
17
12
DISP
3
8
4
9
5
10
/ENTER
28
23
18
13
29
24
19
14
30
25
20
15
Controllers
Up to four units (four loops)
Communications with PLCs
The CX1000 can carry out ladder communications between PLCs (sequencers).
PLCs (such as the FA-M3 by YOKOGAWA)
CX
1
6
26
21
16
11
2
7
27
22
17
12
DISP
3
8
4
9
5
10
/ENTER
28
23
18
13
29
24
19
14
30
25
20
15
CX
11
16
21
26
6
1
12
17
22
27
7
2
8
3
9
4
10
5
DISP
/ENTER
13
18
23
28
14
19
24
29
15
20
25
30
Up to 32 units
Communications with PCs
The CX1000 can communicate with PCs.
• Modbus master/slave
CX
1
6
26
21
16
11
2
7
27
22
17
12
DISP
3
8
4
9
5
10
/ENTER
28
23
18
13
29
24
19
14
15
30
25
20
PC
• Dedicated protocol communications
with the PC (Command communications)
• Display settings/data of the CX using
“DAQSTANDARD for CX”
1-12IM 04L31A01-03E
1.2 Control Function Overview
1.3Basic Settings of Control
PID Group Number
You can set up to eight groups of control parameters (“PID parameters” on the setting
display) that you wish to change collectively through control. You set the number of
groups to be used from 1 to 8. For example, if you set a value of 4, the selectable PID
numbers will be 1 through 4. The parameters that are included in a single control
parameter group vary depending on the control method (“Control output” in the settings).
During PID control:SP, PID constant, output lower/upper limit, shutdown ON/OFF
(only when outputting 4-20 mA of current), manual reset, reverse/
direct, and preset output
During ON/OFF control: SP, relay hysteresis, reverse/direct, and preset output
Control Period
The following control periods can be selected:
250 ms (initial value), 500 ms, and 1 s.
The control period is common to all loops. When the A/D integral time is set to 100 ms,
the control period is fixed to 1 s.
The scan interval of control PV input is the same as the control period.
PID Selection Method (Zone PID ON/OFF)
Select either one from below. When program control is ON on models with the program
control option, the selection is between the segment PID method (zone PID OFF) and
the zone PID method.
In the target setpoint selection method, the operator can switch up to 8 SPs as
necessary. There are two methods in switching the SPs. One method is to specify
the SP number (SPs are registered to PID numbers (= SP numbers) along with PID
constants and other parameters) using keys on the front panel. The other is to use
external contact input or communications. The SP can be switched at any time.
During switching, the setpoint ramp-up-rate or setpoint ramp-down-rate setting is
activated. In addition, when a switch is made, control computation is performed using
the PID constant group that corresponds to the SP at that point.
PV
Rise according to
ramp-up setting
(No.1 PID)
the setpoint
SP1
Switch from SP1 to SP3 Switch from SP3 to SP1 Switch from SP1 to SP2
SP3
(No.3PID)
Fall according to
the setpoint
ramp-down setting
SP1
(No.1 PID)
1
Explanation of Functions
SPn: SP number
SP2
(No.2PID)
Rise according to the
setpoint ramp-up setting
Time
IM 04L31A01-03E
1-13
1.3 Basic Settings of Control
• Zone PID method
In the zone PID method, the measurement span is divided into a maximum of seven zones
using reference points. The optimum PID constant is preassigned to each zone, and the
PID constant (in actuality, other control parameters that are registered using the PID
number are included) is automatically switched according to the PV.
The number of reference points that can be specified is “PID group number – 2.” As shown in
the figure below, if the PID group number is 7, the number of reference points is 5. If the
number of reference points is 5, there are 6 zones. For example, if zones 1 through 6
correspond to PID numbers 1 through 6 and if the PV is within the zones of reference points 3
and 4, the control parameters of PID number 4 are selected. The control parameters of PID
number 7, which cannot be assigned to a zone, are selected when the deviation between the
SP and PV becomes greater than the preset reference deviation.
Maximum value of
measurement span
Reference point 5
Reference point 4
Reference point 3
Reference point 2
Reference point 1
Minimum value of
measurement span
If the current PV here,
control using thePID
constant of No. 4.
Restart and Restart for Program Control
Select how the CX1000 is to behave when an extended power failure occurs during control
operation (power failure period of 5 s or more) and the power recovers.
• Continue (initial setting):
Continue the operation before the power failure occurred.
• Manual operation:
Start from the manual operation condition.
• Auto operation (only during fixed-point operation):
Auto operation by continuing the operation before the power failure occurred.
• Reset (only during program operation):
Stop the program operation.
Change in the
PV.
No.6 PID
No.5 PID
No.4 PID
No.3 PID
No.2 PID
No.1 PID
Note
If the duration of the power failure is less than or equal to 2 s (a short power disruption), the
operation before the disruption continues. If the duration is between 2 to 5 s, the behavior for a
short power disruption or an extended power failure is carried out depending on the condition.
Initial PID
Select whether the initial PID constant in PID parameter settings (see
optimized to temperature control, pressure control, or flow control. Below are the initial
values of PID constants.
Initial values for temperature: P = 5.0%, I = 240 s, and D = 60 s.
Initial values for pressure/flow: P = 120.0%, I = 20 s, and D = 0 s.
page 1-28
) is
Control Mode
The following three control modes are available. The mode is selected for each control loop.
• Single-loop control
Basic control consisting of a single system of controller CPU.
PV
PIDSP
OUT
1-14IM 04L31A01-03E
1.3 Basic Settings of Control
Process value = 1–
• Cascade control
Control consisting of two systems of controller CPUs that uses the primary control
output as the secondary control SP. Continuous PID control is only possible for
primary control.
PV2
PID
OUT
SP
PV1
PID
• Loop control with PV switching
Single-loop control that switches between two PV inputs (PV1 and PV2) according to
the following conditions.
PV1
PV2
PIDSP
OUT
Input Switching Condition ([Method] on the setting display)
• Auto switching according to the PV range ([Range] on the setting display)
Switches PV inputs (PV1 and PV2) automatically according to the preset “PV
switching low-limit” and “PV switching high-limit” as shown in the following figure.
However, PV1 must be less than PV2.
PV range high limit
PV switching high limit
PV switching low limit
PV range low limit
PV
The PV value is computed using the following equation when “PV switching lower limit
< PV1 ≤ PV switching upper limit” and “PV switching lower limit ≤ PV2 < PV switching
upper limit.”
PV input 1 – PV switching low limit
PV switching high limit – PV switching low limit
• Auto switching according to the PV switching upper limit ([PVHigh] on the setting display)
The preset “PV switching upper limit” and PV1 are compared. Auto switching is
performed according to the following conditions. The switching hysteresis is
approximately 0.5% of the PV range span.
When PV1 ≤ PV switching upper value: Switch to PV1
When PV1 > PV switching upper value: Switch to PV2
• Switching through control input ([Signal] on the setting display)
Input is switched using “PV switching (loops 1 and 2)” (see page 1-23) as follows:
Contact input is OFF: Switch to PV1. Contact input is ON: Switch to PV2.
PV2
Process value according
to the equation
PV1
× PV input 1+× PV input 2
PV input 1 – PV switching low limit
PV switching high limit – PV switching low limit
1
Explanation of Functions
Program Control ON/OFF (only on models with the program control option)
Select whether to use the program control function. For a description on the settings for
program control, see
IM 04L31A01-03E
section 1.11, “Program Control Related Settings.”
1-15
1.3 Basic Settings of Control
PID Control Mode
There are two PID control modes: standard PID control mode and fixed-point control mode. To
control the output so that the PV reaches the new SP quickly after the SP is changed, select
“standard PID control mode.” To perform a continuous fixed-point control, select “fixed-point
control.” As shown in the figure below, the control behavior varies depending on the selected
PID control mode. There are two control methods: PV derivative type PID control method and
deviation derivative type PID control method. As shown in the figure below, the control method is
automatically selected. In addition, the presence or absence of the control output bump at the
point of change of the SP is automatically selected. When performing program control in
standard PID control mode on models with the program control option, deviation derivative type
PID control is used during operation (except during hold and soak) and on the secondary loop of
cascade control. For all other cases, PV derivative type PID control is used.
Type of PID
Control Mode
Standard PID
control mode
(Initial value)
Control MethodDescription of the Control Operation
PV derivative type PID
During operation in local
mode or auto mode
(only the primary side
during cascade control)
With bumps in the control
output at the time the SP
is changed
Deviation derivative
type PID
During operation in remote
mode (secondary side
during cascade control)
Employs a PV derivative type PID so that the output reaches
the new SP quickly after the target setpoint is changed. In PV
derivative type PID, the proportional terms (P) that are
proportional to the deviation that occurred due to the SP change
are output immediately, forcing the process value to quickly reach
the new SP.
SP
PV
By applying the derivative term (D) against the deviation that
occurs due to minute changes in the program pattern, the process
value quickly tracks the program pattern.
OUT
Fixed-point
control mode
With bumps in the control
output at the time the SP
is changed
PV derivative type PID
During operation in local
mode or auto mode
(only the primary side
during cascade control)
Without bumps in the
control output at the time
the SP is changed
PV derivative type PID
During operation in remote
mode (secondary side
during cascade control)
With bumps in the control
output at the time the SP
is changed
SP
PV
Use this function on continuous fixed-point control, if you do not
wish to disturb the PV caused by the sensitive reaction of the
control output (OUT) at the time the SP is changed.
In the case of "PV derivative type PID + no control output bumps,
" the output value (OUT) does not drastically change at the time
the SP is changed. The deviation is gradually eliminated using
only the integral term (I) against the deviationthat occurs.
SP
Use this function on the secondary loop of cascade control.
A stable control output is achieved without sensitively reacting to
the output of the primary loop.
SP
PV
OUT
OUT
OUT
PV
1-16IM 04L31A01-03E
Loading...
+ 326 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.