Yokogawa CW500 Specifications

A Clear Path to Electrical Power Excellence!
CW500
Power Quality Analyzer
Bulletin CW500-01EN
Electrical power measurement is a key for innovation.
The Yokogawa CW500 is a portable power meter that utilizes a current clamp sensor for use in the eld enabling consumption and power quality measurement of the power line.
By the navigation screen of the unit, the connection setting and detail setting of the unit is simple and direct by following the screens.
Keys which directly turn on desired measuring screens allow comfortance at the use of eld.
Stored measured data are easily accessed by a click on the le with included PC software.
Simplied power measuring – Several direct
keys keep you simple and direct access to Voltage/ Current/Power/Power factor/ Phase Angle/Frequency/ Integrated power/Demand by values or by a trend graph.
Firmly capture line power quality issue –
Captures short period power malfunction conforming IEC 6100-4-30 Class S.
User support – Function of
Quick Start Guide to support secure wiring and setting of units.
Features
Power Measure and Logging
Power Quality Measuring
User Support
Analysis of Data and Report Generation
Power Measuring and Logging
Simultaneously measures 3 CH Voltage input, 4 CH current
clamp-on probe input, 2 CH DCV input.
Displays value list or trend graph screen of Instantaneous/
Average/Maximum/Minimum of Voltage/Current/Power/Power factor/Phase Angle/Phase Advanced Capacitance Calculation and DCV input.
Integration Value of Active/
Reactive/Apparent Energy is each displayed by consumption and generation.
Demand value can be
monitored by screens of present power consumption compared to aimed demand power value.
User Support
Quick Start Guide Function:
Start Guide Function supports secure wiring and setting
before measuring.
Automatically recognize the type of current clamp-on probe.
Vector Display:
Indicates Voltage and Current phase difference and values
between input channels of voltage and current.
Checks whether the wiring is appropriate or not.
Power Quality Measuring
Analysis of Data and Report Generation
Measure Temporary Malfunction of Power Line
Captures temporary malfunction phenomena of power
line which causes malfunction or destruction of devices by types (Voltage swell, Voltage dip, Voltage interruption, Transient overvoltage, inrush current) as an event by high sampling rate of 24 µs and RMS calculation.
Event data contains the type of malfunction, occurred
time or occurrence nish time, measured value and waveform of voltage and current of all channels for approx. 200 ms period.
Measurement method conforms to IEC standard 61000-
4-30 Class S
Measure Continuous Malfunction of Power Line
Harmonics
Measure and display graphs and list of up to the 50
Harmonic components of voltage, current and power for each phase and in total.
Waveform
Displays with up to 10 or 12 waveforms of voltage and
current for each CH.
Flicker
Measures, 1 minute icker (Pst, 1 min),
short icker (Pst) and long icker (Plt).
Unbalance rate
Displays voltage and current unbalance
rate on 3 phase wiring.
th
CW500Viewer (Included PC software)
Automatically generates graph and report by simple
clicking on a le data displayed on screen.
Uniform management of main unit settings
Realtime measuring by USB communication.
Types of data
Power data, Power quality event data, Main Unit Setting
data, Screen capture data.
Memory card and interface
SD Memory card, USB communication, Bluetooth
communication (Available for USA, Canada and Japan only)
Function
CW500Function
Power Measuring
Power line and Input Channel: 3 CH Voltage, 4 CH for Current Clamp Probe.
1P2W (up to 4 system), 1P3W (up to 2 system), 3P3W2current (up to 2 system), 3P3W3current, 3P4W
Power measuring item:
Instantaneous, Average, Maximum and Minimum values:
Voltage/Current/Power (Active, Reactive, Apparent)/Power factor/ Phase Angle/Frequency/Calculated Phase Shift Condensor/DC voltage value 2 CH.
Integration Value
Energy (Active, Reactive, Apparent) each by
consumption and generation
Demand (Occurrence of max. demand time, current
demand, estimated demand value)
Recording Interval Period:
1/2/5/10/15/20/30 second, 1/2/5/10/15/20/30 minute, 1 hour/2 hours
Recording method
Manual, time setting, period setting
List Display
Hems of measuring values can be selected with position.
Zoom Display
Zoom display can be selected by 4 or 8 division.
Trend Graph
Trend graph of voltage/ current/power/power factor/frequency/ advanced phase condenser/DC voltage
4
Estimated Recording Length with 2 GB SD card.
Interval Power recording +Harmonics
1 sec. 13 days 3 days 1 min. Over 1 year 3 months
30 min. Over 10 years Over 7 years
The recording length shortens according to the number
of power quality events.
Only included SD memory card or dedicated SD
memory card is guaranteed.
Various Measuring Screen
List display, Zoom display by 4 or 8 division,
Trend graph display
Integration Value Display for Energy
Demand List display of value,
Demand Graph display for change of period, Demand Graph display for whole recording
Energy Display
List of Active, Apparent, Reactive by consumption or generation
5
Analysis and Report of recorded data
Demand measuring
Demand is the average power value of a specic period (usually 30 minutes). Contract with the power supplier conditionally concerns the maximum average power value between period for the consumption fee. This function supports how to maintain within the target consumption by monitoring the estimated demand value to the setting rate, with the maximum demand value.
List of Demand Value
Graph display of change on specic period
When the estimated demand value line is displayed inside this area, it mean that the demand value will be over the target value.
Analysis and report is enabled by simply clicking on the desired data on software screen. Analysis is capable by trend graph, average, maximum and minimum value of voltage, current, power, power factor. Report generating could be set by day time, night time, working day, off day or monthly period. Additionally energy data to quantity of crude oil barrels, or to CO
can be converted.
2
Trend analysis graph
Sample of report
Estimated demand value
Graph display of whole demand trend
Max. demand value
Aimed target demand value