Yokogawa CW10 Specifications

LF CW10-EN
Features
AC / DC Power up to 600 kW
True RMS for AC .
Harmonics 1st to 25th order
Power fluctuation using the ACA Inrush and
Peak hold functions.
AC / DC Current max. 600 A
Frequency, Resistance, Continuity, Diode check,
Power factor.
Up to 9999 counts, approx. 37mm max. diameter of measurable conductor (the jaw opens approx. 45mm max.)
For Safety
CATIV 600V and CATIII 1000V compliant.
Useful Functions
Backlight on the display area turns on and a white LED automatically illuminates the front of jaw when clamping.
Non-contact Voltage Detection (Red LED lights up on detection).
Easy Operation with the Navigator key.
Low Pass Filter, Phase Detection, AC / DC
Auto Sense.
Power measurement example
LOAD
<URL : tmi.yokogawa.com>
SOURCE
Clamp-on Power Meter
A Simple Yet A Powerful Power Measuring Tool.
Subject to change without notice.
[Ed : 02/b] Copyright ©2011
Printed in Japan, 109(KP)
YOKOGAWA METERS & INSTRUMENTS CORPORATION
Global Sales Dept.
/Phone: +81-42-534-1413 Facsimile: +81-42-534-1438
E-mail: tm@cs.jp.yokogawa.com
YOKOGAWA CORPORATION OF AMERICA Phone: (1)-770-253-7000, Fax: (1)-770-254-0928 YOKOGAWA EUROPE B.V. Phone: (31)-88-4641000, Fax: (31)-88-4641111 YOKOGAWA ENGINEERING ASIA PTE. LTD. Phone: (65)-62419933, Fax: (65)-62412606
Inrush Current Measurement Method
Figure 1 Small motor Figure 2
Inrush AC current Displays RMS value of 100ms period.
Explanation
A function to measure inrush current is available. This function allows you to easily measure inrush current that occurs when starting a motor, relay, or the like. Just clamp the CW10 to the motor and set INRUSH before starting the motor to automatically measure and hold the inrush current that occured in 100 ms period (Figure 2).
What is inrush current?
Starting current or inrush current is the instantaneous electrical current that flows when the power is initially turned on.
Application
Specifications
Inrush current
Accuracy
23± 5°C, 80%RH or less Accuracy: ±(% of reading + digits)
Voltage
Rms-value detection
Function Range
Resolution
(Maximum reading)
Accuracy*
DCV
100 V 99.99 V
0.7% + 2
1000 V 999.9 V
ACV
100 V 99.99 V
1.0% + 5
50 ~ 500Hz
1000 V 999.9 V
LPF ACV
100 V 99.99 V
50 ≤ f ≤ 60Hz: 1.0% + 5
60 < f ≤ 400Hz: 5.0% + 5
1000 V 999.9 V
* DCV<1000digits: add 6digits to accuracy
ACV<1000digits: add 3digits to accuracy Maximum input voltage: 1000 Vrms, 1414.2 Vpk Input impedance: approx. 3.5MΩ, <100pF AC+DC Vrms accuracy=ACV accuracy + DCV accuracy
Crest factor effects
1.4 < CF ≤ 2.0: add 1.0% of reading to accuracy
2.0 < CF ≤ 2.5: add 2.5% of reading to accuracy
2.5 < CF ≤ 3.0: add 4.0% of reading to accuracy
Maximum input voltage: 690 Vrms CF=2 460 Vrms CF=3
Current
Rms-value detection
Function Range
Resolution
(Maximum reading)
Accuracy*
DCA
100 A 99.99 A 1.5% + 20
600 A 600.0 A*** 1.5% + 5*
ACA
100 A** 99.99 A
50 ≤ f ≤ 60Hz : 1.5% + 5*
60 < f ≤ 400Hz : 2.0% + 5*
600 A 600.0 A***
LPF ACA
100 A** 99.99 A
50 ≤ f ≤ 60Hz : 1.5% + 5
60 < f ≤ 400Hz: 5.0% + 5
600 A 600.0 A***
*The measured value <1000digits: add 5digits to accuracy **Input current ≥ 0.10A at 100 A range of ACA and LPF ACA ***600 A : Guaranteed accuracy (not maximum reading) Maximum input current: 600 Arms, 848.5Apk Conductor position effects: ±1.0% of reading AC+DC Arms accuracy=ACA accuracy + DCA accuracy
Crest factor effects
1.4 < CF ≤ 2.0: add 1.0% of reading to accuracy
2.0 < CF ≤ 2.5: add 2.5% of reading to accuracy
2.5 < CF ≤ 3.0: add 4.0% of reading to accuracy
Maximum input current: 420 Arms CF=2 280 Arms CF=3
Peak Hold (AC mode only)
Function Range
Resolution
(Maximum reading)
Accuracy
ACV
100 V 140.0 V
3.0% + 15
1000 V 1400 V
ACA
100 A 140.0 A
3.0% + 15
600 A 850 A
PEAK MAX: polarity+, polarity­Maximum input voltage and current: 1000 Vrms, 600 Arms Sine wave, ACV ≥ 5 Vrms, ACA ≥ 5 Arms, 50 to 400 Hz continuous wave
Frequency (Hz)
Function Resolution (Measuring range) Accuracy
100 Hz 20.00 to 99.99 Hz
0.5% + 31000 Hz 20.0 to 999.9 Hz
10 kHz 0.020 to 9.999 kHz
Maximum input voltage and current: 1000 Vrms, 600 Arms Input condition; 100 V range: 10 to 100 Vrms (Sine wave) 1000 V range: 100 to 1000 Vrms 100 A range: 10 to 100 Arms (<400Hz) 600 A range: 100 to 600 Arms (<400Hz) The measured value < approx. 10 Hz: 0.00Hz
Harmonic Measurement
Individual Harmonic
Harmonic order Resolution (Maximum reading) Accuracy
1st to 12th (h01- h12)
99.9 %
5% + 10
13th to 25th (h01- h12) 10% + 10
Maximum input voltage and current: approx. 1000 Vrms, 600 Arms The “rdy” is displayed at ACV < 10 Vrms, ACA < 10 Arms The “OutF” is displayed at f < 45, 65 < f (f: fundamental frequency)
Inrush Current
Function Range
Resolution
(Maximum reading)
Accuracy
ACA
100 A 99.99 A 2.5% + 20
600 A 600.0 A* 2.5% + 5
Maximum input current: approx. 600 Arms *600 A : Guaranteed accuracy (not maximum reading) 100A range: ACA1 ≥ 10 Arms (Sine wave, 50Hz/60Hz)
600A range: ACA ≥ 100 Arms (Sine wave, 50Hz/60Hz) Measurement time: approx. 100ms
Active Power
Function Range
Resolution
(Maximum reading)
Accuracy
ACW DCW
10 kW 9.999 kW*
ACW: 2.5% + 11** DCW: 2.2% + 22**
100 kW 99.99 kW
600 kW 600.0 kW**
* The measured value < 1.000kW: add 10digits to the accuracy. **Conditions of accuracy (combination of Voltage and Current
range) 10 kW range: 100 V and 100 A 100 kW range: 100 V and 600 A or 1000 V and 100 A 600 kW range: 1000V and 600 A Other combinations:
Accuracy: (Current accuracy×Voltage reading) + (Voltage
accuracy×Current reading)
**600 kW : Guaranteed accuracy (not maximum reading) Maximum input voltage and current: 1000 Vrms, 600 Arms ACW: ACV ≥ 10 Vrms and ACA ≥ 5 Arms (Sine wave, 50 ≤ f
60Hz, PF=1.00)
DCW: at DCV ≥ 10 V and DCA ≥ 5 A
Power Factor
Function Resolution (Measuring range) Accuracy
Power factor -1.00~0.00~1.00 ±(3°+2digits)
Maximum input voltage and current: 1000 Vrms, 600 Arms PF: ACV ≥ 10 Vrms and ACA ≥ 5 Arms (Sine wave, 50 ≤ f ≤ 60Hz)
Resistance/Continuity check
Function Range
Resolution
(Maximum reading)
Accuracy
Resistance
1000
999.9
1.0% + 5
10 k
9.999 k
1.0% + 3
100 k
99.99 k
Continuity check
1000
999.9
1.0% + 5
The buzzer turns on for resistances lower than approx. 30Ω. (Response time: approx. 100msec)
Maximum input voltage: 1000 Vrms Maximum test current: approx. 0.5mA Open circuit voltage: approx. 3V
Diode Test
Function Resolution (Measuring range) Accuracy
Diode Test 0.40~0.80 V ±0.1 V
Maximum test current: approx. 0.5mA Open circuit voltage: approx. 1.8V
General Specifi cations
Display count
:
9999 / 6000
Measuring rate
:
3 times / sec. Over range indicator: “OL” or “-OL” Auto Power Off
:
Approx. 15 minute. Low-battery indicator
:
(four steps)
Power supply
:
9V alkaline battery (6LR61) Battery life
:
When using alkaline battery, backlight off Approx. 20 hours Operating temperature and humidity: 0 ~ 50 °C (with no condensation)
80% RH (0 ~ 30 °C)
75% RH (30 ~ 40 °C)
45% RH (40 ~ 50 °C) Temperature coeffi cient: At 0 to 18 °C and 28 to 50 °C Add 23±5 °C accuracy x 0.2 / °C Storage temperature: -10 to 50 °C, 80% RH or less (remove the battery) Withstand voltage: AC 6880 Vrms 5 sec. (between the core and the case) AC 4300 Vrms 5 sec. (between the core and the voltage input terminals) AC 6880 Vrms 5 sec. (between the voltage input terminals and the case) Insulation resistance: 100MΩ or greater at 1000 VDC
(between the core and the case, the core and the voltage input terminals and the voltage input terminals and the case)
Compliant standards:
Safety standards: EN 61010-1, EN 61010-2-032 1000V CAT.III, 600V CAT.IV EN 61010-031 (the test leads) Pollution degree 2, Indoor use, Altitude 2000m or less EMC standards: EN 61326-1, EN 61326-2-1, EN 61326-2-2,
EN 55011 Dimensions: Approx 87.5 mm(W) x 242 mm(L) x 51 mm(D) Diameter of measurable conductors
: ϕ
37mm (Maximum)
Weight
:
Approx. 435g (including the battery)
Accessories
:
Test leads 1set (Red and Black) Carrying case 9V alkaline battery (6LR61) User’s Manual Accessories (Sold Separtely): Lead with Alligator Clip Model code 99014