YOKOGAWA CL320 User Manual

User’s Manual
CL320 Leakage Clamp-on Tester
IM CL320
Contents
Precautions for Safety Use of the Instrument
1. Instrument Layout
2. Measurement
2.1 Preparation for Measurement
2.2 AC Current Measurement
2.3 How to Use Frequency Selector Button
3. Other Functions
3.1 Auto-Power-Off Function
3.2 Data Hold Function
3.3 Optional Accessories
4. Battery Replacement
5. Specifications
6. Calibration and After-sales Service
Precautions for Safe Use of the Instrument
When handling the instrument, ALWAYS observe all of the cautionary notes on safety given below. Yokogawa M&C Corporation is not at all liable for damage resulting from misuse of this product by the user that is contrary to these cautionary notes. Various symbols are used on the instrument and in this manual to ensure the product is used safety and to protect operators and prop­erty from possible hazards or damage. The following safety symbols are used where appropriate. Read the explanations carefully and familiarize yourself with the symbols before reading the text.
The instrument and this manual use the following safety symbols:
Danger! Handle with Care.
This symbol indicates that the operator must refer to an ex­planation in the User’s Manual in order to avoid the risk of personal injury or death and/or damage to the instrument.
Double Insulation
This symbol indicates double insulation.
AC Voltage/Current
This symbol indicates AC voltage or current.
Ground
Indicates that there is a possibility of serious personal injury or loss of life if the operating procedure is not followed correctly and describes the precautions for avoiding such injury or loss of life.
Indicates that there is a possibility of serious personal injury of dam­age to the instrument if the operating procedure is not followed cor­rectly and describes the precautions for avoiding such injury or dam­age.
NOTE
Draws attention to information essential for understanding the opera­tion and features.
Never make measurement on a circuit above 300V AC.
Do not use the instrument in an atmosphere where any flammable
Do not attempt to make measurement in the presence of flamma-
Avoid using the instrument if it has been exposed to rain or mois-
Do not exceed the maximum allowabIe input of any measurement
This symbol indicates ground (earth)
WARNING
CAUTION
WARNING
or explosive gas is present.
ble gasses, fumes, vapor or dust. Otherwise, the use of the instru­ment may cause sparking, which can lead to an explosion.
ture or if your hands are wet.
range.
1st Edition: Apr. 2003 (MC)
IM CL320
Never open the battery compartment cover when making meas­urement.
Do not use the instrument if there is any damage to the casing or when the casing is removed.
Do not install substitute parts or make any modification to the in­strument. Return the instrument to Yokogawa M&C or your dis­tributor for repair or re-calibration.
Always switch off the instrument before opening the battery com­partment cover for battery replacement.
WARNING
To avoid damage to the instrument or electric shock! The restrictions on the maximum voltage level for which the CL320 testers can be used, depend on the over-voltage categories specified by the safety standards. These category specifications are formulated to protect operators against transient impulse voltage in power lines.
Function
Over-voltage category I (CAT.I):
Signal level, special equipment or parts of equipment, telecommunication,
electronic etc., with smaller transient over-voltages than CAT.II.
Over-voltage category II (CAT.II)
Local level, appliance, portable equipment etc., with smaller transient
over-voltages than CAT.III.
Over-voltage category III (CAT.III):
Distribution level, fixed installation, with smaller transient over-voltages than
CAT.IV.
A
Maximum Allowable Input
OVERVOLTAGE CATEGORY III
Measuring circuit voltage : 300Vrms AC
200Arms AC
CAUTION
Be sure to set the Range switch to the "OFF" position after use.
When the instrument will not be in use for a long period of time, Place it in storage after removing the battery.
Use a damp cloth and detergent for cleaning the instrument. Do not use abrasives or solvents.
NOTE
Radiation immunity affects the accuracy of CL320 testers under the conditions specified in EN 61000-4-3:1997.
If equipment generating strong electromagnetic interference is located nearly, the testers may malfunction.
1. Instrument Layout
Open/Close Lever
Transformer
LCD
Frequency response of 50/60Hz
Frequency response of WIDE
Low battery indicator
Data Hold Switch
Range Switch
Frequency Selector Switch
Data hold mode indicator
Unit of measurement quantity
Hand Strap
Display
2. Measurement
2.1 Preparation for Measurement
WARNING
Do not make measurement on a circuit above 300V AC. This may cause shock hazard or damage to the instrument or equipment under test.
CAUTION
The jaw section is a delicate, precision sensor. Do not subject the
jaw to unreasonably strong shock, vibration, or force when using it.
If dust gets into the tops of the jaws, remove it immediately. Do not
close the jaws when dust is trapped in its joints as the sensor may break.
Please check that the Range switch is set to the desired position
before measurement.
NOTE
During current measurement, keep the transformer jaws fully
closed. Otherwise, accurate measurement cannot be made. The maximum measurable conductor size is approx. 24mm in diameter.
When measuring large current, the transformer jaws may buzz.
This has no effect on the instrument’s performance or safety.
2.2 AC Current Measurement
(1) Set the Range switch to the desired position. Current to measure
should be within the selected measuring range.
(2) Normal measurement :
Press the jaw open/close lever to open the transformer jaws and close them over one conductor only. Measured current value is shown on the display. Earth leakage current or small current that flows through a grounded wire can also be measured by this method.
Correct Wrong
Load
(3) Measuring out of balance leakage current :
Clamp onto all conductors except a grounded wire. Measured current value is shown on the display.
Load
3-phase 3-wire
Note : In case of 3-phase 3-wire, clamp four wires for measurement.
Note : In case of 1-phase 3-wire, clamp three wires for measurement.
1-phase 2-wire
2.3 How to Use Frequency Selector Button
When high frequencies from such equipment as inverters are present in the circuit under test, the instrument measures AC current of not only 50Hz or 60Hz of fundamental frequency but also of these high frequencies and harmonics. To eliminate the effect of such high frequency noise and measure AC current of 50Hz or 60Hz fundamental frequency, a "high-cut" filter circuit in incorporated into the instrument which works when "50/60Hz" frequency response is selected with the Frequency Selec­tor button. Cut-off frequency of "high-cut" filter is about 100Hz with attenuation characteristic of approx. -24dB/octave.
NOTE
Characteristic of -24dB/octiave means that signal magnitude declines to about one sixteenth of that at the initial frequency when frequency doubles. The Frequency Selector button has the following two positions.
WIDE (40Hz or more) : Permits measurement of currents of fundamental frequencies as well as currents of high frequencies generated by such equipment as inverters.
50/60Hz (40 to approx. 100Hz) : Filters out high frequency currents and measures current of fun­damental frequency only.
When the left side of the display. When the frequency response is switched to WIDE with "WIDE" mark shown on the display.
Attenuation
(dB)
Recently there has been increased use of power through inverters, switching regulators, etc. When the high frequency noise from such appliances leaks or flows into the ground through capacitors not filtering completely, the earth leakage breaker may trip even though there is no "actual" leakage. In such a case, the instrument do not give leakage current reading if "50/60Hz" frequency response is se­lected. Take care readings with the 50/60Hz and WIDE frequency responses respectively to make effective use of the Frequency Selector button.
button is pressed, "50/60Hz" mark is shown on the
Frequency characteristics
button is pressed again,
All ranges WIDE
position
All ranges at 50/60Hz Position (-24dB/oct)
f (Hz)Frequency
Load
3. Other Functions
3.1 Auto-Power-Off Function
This is a function to prevent the instrument from being left powered on and conserve battery power. The instrument automatically turns off about 10 minutes after the last switch or button operation. To return to the normal mode, turn the Range switch to OFF, then to the desired position.
3.2 Data Hold Function
Load
This is a function to freeze the reading on the display. When the
button is pressed once, the current reading is held even though current under test varies. " corner of the display.
To exit the data hold mode, press the
NOTE
When the auto-power-off function works while the instrument is in the data hold mode, data hold is cancelled.
" mark is shown on the upper right
button again.
3.3 Optional Accessories
Clamp Adapter Model 99025 (For AC current measurement only)
Clamp Adapter Model 99025 is designed to increase the measuring capability of a clamp meter. With the use of the Clamp Adapter, you can not only extend current range over 2000A, but also clamp on a large bus-bar or conductor.
(1) Set the Range switch to the desired position. (2) As shown in the figure right, clamp Model CL320 onto the pickup
coil of Model 99025. (3) Clamp Model 99025 onto the bus-bar or conductor under test. (4) Take the reading on Model CL320 and multiply it by 10.
NOTE
The clamp adapter is not applicable to leakage current measurement. For detailed specification, refer to the Clamp Adapter User’s Manual.
4. Battery Replacement
WARNING
To avoid electric shock hazard, never try to replace batteries during measurement.
CAUTION
Do not mix new and old batteries.
Make sure to install battery in correct polarity as indicated in bat-
tery compartment.
Percentage
If the battery voltage becomes too low for the instrument to operate normally, " Note that when the battery is completely exhausted, the display blanks without "
(1) Set the Range switch to the "OFF" position. (2) Press in the hole on the battery compartment cover with the tip of
a pointed object, then slide open the cover. (3) Replace the battery observing correct polarity. Use two new
LR-44 or SR-44 batteries. (4) Slide the battery compartment cover back in place.
" is shown on the display. Then, replace the battery.
" shown.
5. Specifications
Instrument Specifications
Measuring Ranges and Accuracy (at 23 ±5°C, relative humidity up to 75%)
AC Current
Ranges
40mA 0 to 19.99mA
200mA 0 to 199.9mA
200A
General Specifications
Operating System : Dual integration
Measurement Function : AC current
Display : Liquid crystal display with maximum counts of 1999
Overrange Indication : "1" flashes on the highest digit
Response Time : Approx. 2 seconds.
Sample Rate : Approx. 2 times per seconds.
Temperature and Humidity for Guaranteed Accuracy : 23°C ±5°C,
relative humidity up to 75% without condensation
Operating Temperature and Humidity : 0 to 40°C, relative humidity up to 85% without condensation
Storage Temperature and Humidity : -10 to 50°C, relative humidity up to 75% without condensation
Effect of conductor position :
The difference between maximum and minimum values to a 10
mm-dia conductor, at every part inside the jaws; Within 5dgt for 0 to 50A Within 2% for 50 to 200A
Effect of external magnetic field : 10 mA or less in proximity to a
14.5 mm-dia conductor carrying 100 A
Effect of residual current : 10 mA or less in proximity to a 10 mm-dia conductor carrying 50 A
Power Source : Two LR-44 or SR-44 battery
Battery Life : Approx. 15 hours (continuous)
Current Consumption : Approx. 5mA
Auto-power-off function : Turns power off approx. 10 minutes after
the last switch operation
Withstanding Voltage : 3700V AC, 1 minute between electrical circuit and housing case or metal part of the jaws
Insulation Resistance : 10MΩ or greater at 1000V between elec- trical circuit and housing case or metal part of the jaws
Conductor Size : Approx. 24mm diameter max.
Dimensions : Approx. 60(W) x 149(H) x 26(D) mm
Weight : Approx. 120g
Safety Standard: EN 61010-1
EMC Standard : EN 61326
EN 55022
Accessories : LR44 batteries···························2
Optional Accessories : Clamp adapter Model 99025
Measuring
range
0 to 100.0A
100.1 to 199.9A
Carrying case Model 93033·······1 User’s Manual ···························1
WIDE position 50/60 position
±2.0% rdg ±4dgt (50/60Hz) ±5.0% rdg ±6dgt (40 to 400Hz)
±5.0% rdg ±4dgt (50/60Hz)
EN 61010-2-032 (300V AC CAT III, Pollution degree2, indoor use)
Accuracy
Frequency Selector Switch
±3.0% rdg ±5dgt (50/60Hz)
±5.0% rdg ±5dgt (50/60Hz)
6. Calibration and After-sales Service
Should any failure occur while you are using the tester, follow the instructions given below. If the tester still fails to operate correctly and needs repair, contact the vendor from whom you purchased the in­strument or the nearest Yokogawa M&C sales office.
Turn off the POWER switch once, then turn it back on again.
If the tester does not turn on, replace the battery with a new one.
Calibration It is recommended that the instrument be calibrated once every year.
YOKOGAWA M&C CORPORATION International Sales Dept.
2-9-32 Nakacho, Musashino-shi, Tokyo, 180-8750 Japan Phone: 81-422-52-5716 Facsimile: 81-422-55-8654
YOKOGAWA CORPORATION OF AMERICA (U.S.A.)
Phone: 1-770-253-7000 Facsimile: 1-770-251-2088
YOKOGAWA EUROPE B. V. (THE NETHERLANDS)
Phone: 31-334-64-1611 Facsimile: 31-334-64-16 10
YOKOGAWA AMERICA DO SUL S. A. (BRAZIL)
Phone: 55-11-5681-2400 Facsimile: 55-11-5681-1274
YOKOGAWA ENGINEERING INSTRUMENTS KOREA CORPORATION (KOREA)
Phone: 82-2-551-0660 to -0664 Facsimile: 82-2-551-0665
YOKOGAWA AUSTRALIA PTY. LTD. (AUSTRALIA)
Phone: 61-2-9805-0699 Facsimile: 61-2-9888-1844
YOKOGAWA BLUE STAR LTD. (INDIA)
Phone: 91-80-227-1513 Facsimile: 91-80-227-4270
LTD. YOKOGAWA ELECTRIC (RUSSIAN FEDERATION)
Phone: 7-095-737-7868 Facsimile: 7-095-737-7869
KIM3E-2003.2
Loading...