Yokogawa AM100D, AM500D, AM400D, AM200D, AM300D User Manual

User's Manual
Models AM100D, AM200D, AM300D, AM400D, and AM500D Magnetic Flow Tube
IM 1E6D0-01E
IM 1E6D0-01E
17th Edition

CONTENTS

CONTENTS
1. INTRODUCTION..........................................................................................1-1
2. HANDLING PRECAUTIONS ....................................................................... 2-1
2.1 Checking Model and Specifications.................................................... 2-1
2.2 Accessories ......................................................................................... 2-1
2.3 Storage Precautions............................................................................ 2-1
2.4 Installation Location Precautions ........................................................ 2-1
2.5 Terminal Box Reorientation Precautions ............................................ 2-1
3. INSTALLATION ........................................................................................... 3-1
3.1 Piping Design Precautions.................................................................. 3-1
3.2 Handling Precautions .......................................................................... 3-3
3.2.1 General Precautions ..................................................................... 3-3
3.2.2 Flow Tube Piping ......................................................................... 3-4
3.3 Mounting.............................................................................................. 3-5
3.3.1 Nominal Diameter 2.5 mm (0.1˝) to 10 mm (0.4˝)
Union Joint Type .......................................................................... 3-5
3.3.2 Nominal Diameter 2.5mm (0.1˝) to 40mm (1.5˝) Wafer Type ..... 3-6
3.3.3 Nominal Diameter 50 mm(2˝) to 200 mm(8˝) Wafer Type .......... 3-9
3.3.4 Nominal Diameter 15 mm (0.5˝) to 400 mm (16˝)
Flange Type ............................................................................... 3-12
3.3.5 Mominal Diameter 500 mm (20˝) to 2600 (104˝)
Flange Type ............................................................................... 3-14
3.3.6 Mounting Procedure for Sanitary Type ...................................... 3-15
3.4 Wiring Precautions ............................................................................ 3-16
3.4.1 Protective Grounding .................................................................. 3-16
3.4.2 General Precautions ................................................................... 3-16
3.4.3 Cable Types ............................................................................... 3-16
3.4.4 Connnection to AM11Magnetic Flow Converter ........................ 3-17
3.4.5 Wiring Ports................................................................................ 3-18
4. MAINTENANCE...........................................................................................4-1
4.1 Regular Inspection Items .................................................................... 4-1
4.2 Trouble Shooting................................................................................. 4-1
5. OUTLINE......................................................................................................5-1
6. HAZARDOUS DUTY TYPE INSTRUMENT ................................................ 6-1
6.1 FM ....................................................................................................... 6-1
6.2 CSA ..................................................................................................... 6-2
6.3 CENELEC (KEMA).............................................................................. 6-2
6.4 JIS ....................................................................................................... 6-3
INSTALLATION AND OPERATING PRECAUTIONS FOR JIS FLAMEPROOF
EQUIPMENT ...................................................................................... EX-B03E
FD No. IM 1E6D0-01E 17th Edition: Nov. 2002 (YG) IM 1E7D0-01E
All Rights Reserved, Copyright © 1990, Yokogawa Electric Corporation
1. INTRODUCTION

1. INTRODUCTION

This instrument has been already adjusted at the factory before shipment.
To ensure correct use of the instrument, please read this manual thoroughly and fully understand how to operate the instrument before operating it.
Regarding This Manual
•This manual should be passed on to the end user.
• Before use, read this manual thoroughly to compre­hend its contents.
• The contents of this manual may be changed without prior notice.
• All rights reserved. No part of this manual may be reproduced in any form without Yokogawa’s written permission.
•Yokogawa makes no warranty of any kind with regard to this material, including, but not limited to, implied warranties of merchantability and suitability for a particular purpose.
• All reasonable effort has been made to ensure the accuracy of the contents of this manual. However, if any errors are found, please inform Yokogawa.
• Yokogawa assumes no responsibilities for this product except as stated in the warranty.
• If the customer or any third party is harmed by the use of this product, Yokogawa assumes no responsi­bility for any such harm owing to any defects in the product which were not predictable, or for any indirect damages.
Safety Precautions
• The following general safety precautions must be observed during all phases of operation, service, and repair of this instrument. Failure to comply with these precautions or with specific WARNINGS given elsewhere in this manual violates safety standards of design, manufacture, and intended use of the instrument. YOKOGAWA Electric Corpora­tion assumes no liability for the customer’s failure to comply with these requirements. If this instrument is used in a manner not specified in this manual, the protection provided by this instrument may be impaired.
The following safety symbol marks are used in
this manual and instrument;
WARNING
A WARNING sign denotes a hazard. It calls attention to procedure, practice, condition or the like, which, if not correctly performed or adhered to, could result in injury or death of personnel.
CAUTION
A CAUTION sign denotes a hazard. It calls attention to procedure, practice, condition or the like, which, if not correctly performed or adhered to, could result in damage to or destruction of part or all of the product.
IMPORTANT
A IMPORTANT sign denotes an attention to avoid leading to damage to instrument or system failure.
NOTE
A NOTE sign denotes a information for essential understanding of the operation and features.
Protective grounding terminal. Function grounding terminal. This terminal
should not be used as a “Protective grounding terminal”.
Alternating current. Direct current.
1-1
IM 1E6D0-01E
Warranty
• The guaranteed term of this instrument is described in the quotation. We repair the damages that occurred during the guaranteed term for free.
• Please contact with our sales office when this instrument is damaged.
• If the instrument has trouble, please inform us model code, serial number, and concrete substances or situations. It is preferable to be attached a outline or data.
• We decide after the examination if free repair is available or not.
• Please consent to the followings for causes of damages that are not available as free repair, even if it occured during the guaranteed term.
A:Unsuitable or insufficient maintenance by the
customer.
B: The handling, using, or storage that ignore the
design and specifications of the instrument.
C: Unsuitable location that ignore the description in
this manual.
D:Remaking or repair by a person except whom we
entrust.
E: Unsuitable removing after delivered. F: A natural disaster (ex. a fire, earthquake, storm and
flood, thunderbolt) and external causes.
1. INTRODUCTION
For the safety using;
WARNING
• The Magnetic Flow Tube is a heavy instrument. Please give attention to prevent that persons are injured by carrying or installing. It is prefer­able for carrying the instrument to use a cart and be done by two or more persons.
• In wiring, please confirm that the cables are not powered before connecting.
• When removing the instrument from hazardous processes, avoid contact with the fluid and the interior of the meter.
• In case of Hazardous duty type instrument, further requirements and differences are described in Chapter 6 “HAZARDOUS DUTY TYPE INSTRUMENT”. The description in Chapter 6 is prior to other description in this instruction manual.
1-2
IM 1E6D0-01E
2. HANDLING PRECAUTIONS

2. HANDLING PRECAUTIONS

This instrument has been already tested thoroughly at the factory. When the instrument is delivered, please check externals and make sure that no damage occurred during transportation.
In this chapter, handling precautions are described. Please read this chapter thoroughly at first. And please refer to the relative matter about other ones.
If you have any problems or questions, please make contact with Yokogawa sales office.

2.1 Checking Model and Specifications

The model and specifications are shown on the Data Plate. Please confirm the specifications between the instrument that was delivered and the purchase order (refer to the chapter 5. Outline).
Please let us know Model and Serial No. when making contact with Yokogawa sales office.
MAGNETIC FLOW DETECTOR
AM
L H
mm

2.3 Storage Precautions

In case the instrument is expected to be stored over a long term, please give attention to the followings;
• The instrument should be stored in its original packing condition.
• The storage location should be selected according to the following conditions:
1) The location where it is not exposed to rain or
water.
2) The location where there is few vibration or
shock.
3) Temperature and humidity should be:
Temperature: –30 to 60˚C (–22 to 140˚F) Humidity: 5 to 80% RH (no condensation) Preferable ambient temperature and humidity
are 25˚C(77˚F) and about 65% RH.
2.4 Installation Location
Precautions
Please select the installation location considering the following items to ensure long term stable operation of the flow tube.
Made in Japan
F0201.EPS
Figure 2.1 Data Plate

2.2 Accessories

When the instrument is delivered, please make sure that the following accessories are in the package.
• Centering device 1-set (for wafer type)
•Hexagonal wrench 1-piece (for hazardous duty type except JIS flameproof type)
•Hexagonal wrench 2-piece (only for JIS flameproof type)
• Ambient Temperature: Please avoid to install the instrument at the location where temperature changes continuously. If the location receives radiant heat from the plant, provide heat insulation or improve ventilation.
•Atmospheric Condition: Please avoid to install the instrument in an corrosive atmosphere. In case of installing in the corrosive atmosphere, please keep ventilating sufficiently and prevent rain from entering the conduit.
•Vibration or shock: Please avoid to install the instrument at the location where there is heavy vibration or shock.
2.5 Terminal Box Reori-
entation Precautions
Please do not change the terminal box orientation at the customer’s site. If the terminal box reorientation is required, please contact Yokogawa office or service center.
2-1
IM 1E6D0-01E
3. INSTALLATION

3. INSTALLATION

CAUTION
This instrument must be installed by expert engineer or skilled personnel. The procedures described in this chapter are not permitted for operators.
3.1 Piping Design Pre­cautions
IMPORTANT
Please design the correct piping referring to the followings to prevent damage for flow tube and to keep correct measuring.
(1) Location
Gate valve fully open
5 D or more 2 D or more 2 D or more
Tee
Figure 3.1.1 Minimum Length of Required Straight Run
Reducer pipe Expander pipe
Do not care to 0 D Do not care to 0 D
90° degrees bent
D: Nominal diameter of flow tube
10 D or more
Various types of valves
10 D or more5 D or more5 D or more Do not care to 0 D Do not care to 0 D
NOTE
1. Nothing must be inserted or installed in the metering pipe than may interfere with the magnetic field, induced signal voltages, and flow velocity distribution.
2. These straight runs may not be required on the downstream side flowmeter. However, if the downstream valve or other fittings cause channeling on the upstream side, provide a straight run of 2 D to 3 D on the downstream side.
2 D or more
F030101.EPS
IMPORTANT
Please install the flow tube to the location where it is not exposed to direct sunlight and ambient temperature is –10 to + 60°C (14 to 140°F).
(2) Noise Rejection
IMPORTANT
The instrument should be installed away from large electrical motors, transformers and other power sources in order to avoid interference with the measurement.
(3) Length of Straight Run
To keep accurate measuring, JIS B7554 “Electro Magnetic Flow Tubes” explains about upstream piping condition of Magnetic Flow Tubes.
We recommend to our customers about the piping conditions shown in Figure 3.1.1 based on JIS B7554 and our piping condition test data.
(4) Liquid Conductivity
IMPORTANT
Please avoid to install the flow tube at location where liquid conductivity is likely to be non­uniform. Because it is possible to have bad influences to the flow indication by non-uniform conductivity when a chemical liquid is injected from upstream side close to the flow tube. When this occurs, it is recommended that chemical application ports are installed on the downstream side of the flow tube. In case chemicals must be added upstream side, please keep the pipe length enough so that liquid is properly mixed.
(BAD)
Upstream side
Figure 3.1.2 Chemical Insertion
(GOOD)
Downstream side
F030102.EPS
3-1
IM 1E6D0-01E
3. INSTALLATION
(5) Liquid Sealing Compound
IMPORTANT
Please give attention in using Liquid Sealing Compound to the piping, because it brings bad influences to measurement by flowing out and cover the surfaces of electrode and earth-ring.
(6) Service Area
Please select the location where there is enough area to service installing, wiring, overhaul, etc.
(7) Bypass Line
It is recommended to install the Bypass Line to facilitate maintenance and zero adjustment.
Bypass valve
Block valve
Block valve
F030103.EPS
Please design the piping that a fluid is always filled in the pipes. The Vertical Mounting is effective for fluids that is easily separate or slurry settles within pipes.
In this case, please flow a fluid from bottom to up.
(GOOD)
h
h>0
Horizontal mounting Vertical mounting
(BAD)
(GOOD)
Figure 3.1.4 Filling the Pipe with Liquid
h>0
(BAD)
h
F030104.EPS
(10) No Air Bubbles
IMPORTANT
Please give attention to prevent bad influences or measuring errors from air bubbles that gath­ers inside measuring pipes.
In case the fluid includes air bubbles, please design the piping that prevent to gather air bubbles. In case valves are installed upstream of the flow tube, it is possible that a valve causes air bubbles, please install the flow tube upstream side of a valve.
Figure 3.1.3 Bypass Line
(8) Supporting the Flow Tube
CAUTION
Please avoid to support only the flow tube, but fix pipes at first and support the flow tube by pipes to protect the flow tube from forces caused by vibration, shock, expansion and contraction through piping. For small sized flow tubes, please provide a mounting base so thet the tubes are fixed in the piping. See the section 3.3 Mounting.
(9) Piping Condition
IMPORTANT
The piping should be designed so that a full pipe is maintained at all times to prevent loss of signal and erroneous readings.
(GOOD)
(BAD)
(GOOD)
Figure 3.1.5 Avoiding Air Bubbles
(11) Mounting Direction
IMPORTANT
When the electrodes are vertical to ground, the electrode is covered with air bubbles at upper side or slurry at downside, and it may cause the measuring errors. Please be sure to mount the terminal box upper side of piping to prevent water penetration into terminal box.
(Good)
(No good)
Electrodes
Electrodes
(No good)
Air Bubbles
Slurry
Figure 3.1.6 Mounting Direction
3-2
(BAD)
F030105.EPS
Water slowly percolates downward into terminal box.
F030106.EPS
IM 1E6D0-01E
3. INSTALLATION
(12) Grounding
IMPORTANT
Improper grounding can have an adverse affect on the flow measurement. Please ensure that the instrument is properly grounded.
The electromotive force of the magnetic flow tube is minute and it is easy to be affected by noise. And also that reference electric potential is the same as the measuring fluid potential. Therefore, the reference electric potential (terminal potential) of the Flow Tube and the Converter/Amplifier also need to be the same as the measuring fluid. And moreover, that the poten­tial must be the same with ground.
Please be sure to ground according to Figure 3.1.7.
600 V vinyl insulated electric cable
2
or larger)
(2 mm
3.2 Handling Precau­tions
WARNING
The Magnetic Flow tube is a heavy instrument. Please be careful to prevent persons from injuring when it is handled.

3.2.1 General Precautions

(1) Precaution for Carrying
The Magnetic Flow Tube is packed tightly. When it is unpacked, please give attention to prevent damages to the flow tube. And to prevent the accident during carry to the installing location, please carry it near the location keeping packed as it delivered.
CAUTION
Earth ring
Grounding resistance 100 or less (10 or less for JIS flameproof type)
In case earth rings are used.
Note; See "3.4.1 Protective Grounding" for information on protective grounding.
Figure 3.1.7 Grounding
In case earth rings are not used. (Available only for metal piping)
F030107.EPS
In case the Magnetic Flow Tube lifts up, please refer to Figure 3.2.1. Please never lift up by using a bar through the flow tube. It damages liner severely.
Horizontal Lifting
Figure 3.2.1 Lifting Flow Tubes
Vertical Lifting Sling Rigging Method
F030201.EPS
3-3
IM 1E6D0-01E
3. INSTALLATION
(2) Precaution for Shock
CAUTION
Care should be taken not to drop the flow tube or subject it to excessive shock. This may lead to liner damage which will cause inaccurate readings.
(3) Flange Protection Covers
IMPORTANT
Please keep the protection cover (ex. corrugated paper or anything possible to protect) attached with flange except when mounting to the pipe.
(4) Terminal Box Cover
IMPORTANT

3.2.2 Flow Tube Piping

CAUTION
Mis-aligned or slanted piping can lead to leakage and damage to flanges.
•Please correct mis-alignment or slanted piping and
improper distance between mounting flanges before install the flow tube. (Please refer to Figure 3.2.2)
• Inside a pipeline which is newly installed, some
foreign substances (such as welding scrap or wood chips) may exist. Please remove them by flushing piping before mounting the flow tube.
Slant
Mis-alignment
F030202.EPS
Please never leave the terminal box cover open until wiring to prevent insulation deterioration.
(5) Long-term Non-use
IMPORTANT
It is not preferable to leave the flow tube for long term non-use after installation. In case the flow tube is compelled to do that, please take care of the flow tube by the follow­ings.
• Confirmation of Sealing Condition for the Flow Tube
Please confirm the sealing conditions of the terminal
box screw and wiring ports.
In case of the Conduit Piping, please provide the drain plugs or waterproof glands to it to prevent that moisture or water penetrates into the flow tube through the conduit.
• Regular Inspections Please inspect the sealing condition (as above
mentioned) and inside of the terminal box. And when it is suspect that water penetration into the inside flow tube (ex. rain fall), please inspect when it happened.
Figure 3.2.2 Slant and Mis-alignment of Flow Tube Piping
3-4
IM 1E6D0-01E
3. INSTALLATION

3.3 Mounting

3.3.1 Nominal Diameter 2.5 mm (0.1˝)
to 10 mm (0.4˝) Union Joint Type
NOTE
Please ensure to use the attached connecting fittings.
Ceramic linings with a diameter of 2.5, 5 or 10 mm are connected using union joints.
Use the connecting fittings according to the table below. Depending on whether the fitting is to be welded to or screwed on to the piping.
Table 3.3.1 Fitting Dimensions
Screw joint (Code: U2, U3)
D
(1) Mounting Direction
Please mount the Magnetic Flow Tube matching the flow direction of the fluid to be measured with the direction of the arrow mark on the flow tube.
IMPORTANT
If it is impossible to match the direction, please never remodel by changing direction of the terminal box. In case the measuring fluid flows against the arrow direction, please refer to the section “Reversing Flow Direction” in the Instruc­tion Manual of AM11 Magnetic Flow Converter.
(2) Connecting Process Piping
Weld or screw the connecting fittings to the process piping.
IMPORTANT
ØA
(0.16")
Size
mm(inch)
2.5(0.1)
5(0.2)
10(0.4)
ØAØBØB
(0.16")
Size
mm(inch)
2.5(0.1) 5(0.2)
10(0.4)
0 –0.1
ØC
11.5(0.4")
4
30(1.2")
Code A B C D
ØC
R1/4(PT1/4)
R1/4(PT1/4)
R3/8(PT3/8)
0.3 0
ØD
18.5(0.73")
18.5(0.73")
22.5(0.89")
22(0.87")
U2
22(0.87")
U3
22(0.87")
U2
22(0.87")
U3
25(0.98")
U2
25(0.98")
U3
Weld joint (Code: U1)
4
Code A B C D
22(0.87")
U1
22(0.87")
U1
25(0.98")
U1
8(0.31") 8(0.31") 8(0.31")
8(0.31") 10(0.39") 10(0.39")
35(1.38")
8(0.31")
8(0.31") 10(0.39")
18.5(0.73")
18.5(0.73")
18.5(0.73")
18.5(0.73")
22.5(0.89")
22.5(0.89")
10(0.39")
14.3(0.56")
14.3(0.56")
17.8(0.70")
NPT1/4
NPT1/4
NPT3/8
0 –0.1
T030301.EPS
• Please be sure to pass the connecting fittings through the union joint nuts in advance. Then connect the connecting fitting to the piping by screwing or welding the connecting fitting to the piping (see Figure 3.3.1).
• In case of weld joint type, please pay attention the welding condition to avoid deforming piping or making the stagnant portion of the fluid; joint preparation, level defference in butt joint, welding current.
(3) Positioning the Flow Tube
Install the magnetic flow tube on a mounting base and position it so that the center axis of the flow tube is aligned with that of the piping. Then mount the flow tube to union joint nuts by screwing the nuts to the connecting ports of the flow tube.
CAUTION
The ceramic pipe will be damaged if they are tightened when they are not properly aligned.
3-5
IM 1E6D0-01E
3. INSTALLATION
(4) Tightening Nuts
CAUTION
Tighten the union joint nuts according to Torque Values in Table 3.3.1 using a torque wrench. As the gasket material is Fluorocarbon PTFE, it is possible that nuts may loose by it’s character as time passes. Please tighten the nuts regularly. The table below shows the tightening torque values. Be sure to use gasket : t=1.5 attached.
Gasket
Connecting fitting
Union joint nut
Piping*
Mounting base*
*: user's scope
Table 3.3.2
Size: mm(inch) Tightening Torque N-m {kgf-cm} [in-lbf]
2.5(0.1) 5(0.2)
10(0.4)
Max.12{122}[106] Max.12{122}[106] Max.18{183}[160]
T030302.EPS
3.3.2 Nominal Diameter 2.5mm (0.1˝) to 40mm (1.5˝) Wafer Type
IMPORTANT
Please use appropriate bolts and nuts according to process connection. In case stud type of through bolts are used, be sure outside diameter of a shank is smaller than a thread ridge’s one. Please use compressed non-asbestos fiber gasket, PTFE gasket or the gasket which has equal elasticity. In case of optional code/FRG, please use rubber gasket or others which has equal elasticity. Be sure the inner diameter of the gasket does not protrude to inner piping. (Refer to Table 3.3.8)
Horizontal Mounting
(1) Mounting Direction
Please mount the Magnetic Flow Tube matching the flow direction of the fluid to be measured with the direction of the arrow mark on the flow tube.
IMPORTANT
If it is impossible to match the direction, please never remodel by changing direction of the terminal box. In case the measuring fluid flows against the arrow direction, please refer to the section “Reversing Flow Direction” in the Instruc­tion Manual of AM11 Magnetic Flow Converter.
(2) Mounting Centering Devices
To keep concentricity of the Flow Tube with pipes, please mount centering devices on the Mini-Flanges of the Flow Tube.
Please give attention to the nominal diameter and flange ratings of the centering devices.
Vertical Munting
Figure 3.3.1 Mounting Procedure (Size: 2.5 mm(0.1") to
10 mm(0.4"))
F030301.EPS
3-6
IM 1E6D0-01E
3. INSTALLATION
(3) Positioning Flow Tube
Please pass two through-bolts to adjacent holes of both flanges and mount the Flow Tube, and pass other through-bolts to other holes. (Refer to Figure 3.3.2/
3.3.3) In case stud type of through-bolts are used, position them coming in contact centering devices with thread of bolts.
(4) Tightening Nuts
Please tighten the bolts according to Torque Values in Table 3.3.3. In case of PVC piping, please select optional code /FRG, use rubber gasket and tighten with the torque value in Table 3.3.4.
Through-bolts (four)
Nuts
Please use appropriate bolts and nuts according to process connection.
CAUTION
In case of PFA lining type, as the lining material is Fluorocarbon PFA, it is possible that nuts may loose by its character as time passes. Please tighten the nuts regularly. Please be sure to tighten the bolts following prescribed torque values. Please tighten the flange bolts diagonally with the same torque values, step by step up to the prescribed torque value.
Gasket (two)
Mini-flange
Centering devices (two)
Flange
Nuts (eight)
Horizontal Mounting Vertical Mounting
Figure 3.3.2 Mounting Procedure (Size: 2.5 mm(0.1") to 15 mm(0.5"))
Through-bolts (four)
Gasket (two)
Mini-flange
Nuts (eight)
Please use appropriate bolts and nuts according to process connection.
Centering devices (two)
F030302.EPS
Flange
Horizontal Mounting Vertical Mounting
Figure 3.3.3 Mounting Procedure (Size: 25 mm(1"), 40 mm(1.5"))
F030303.EPS
3-7
IM 1E6D0-01E
Table 3.3.3 Tightening Torque Values for Metal Piping
Tightening Torque Values for PFA lining / Polyurethane lining Type N-m {kgf-cm} [in-lbf]
Size mm(inch)
2.5(0.1), 5(0.2) 10(0.4), 15(0.5)
25(1)
40(1.5)
Flange Rating
6 to 9 {61 to 92} [53 to 80]
15 to 22 {153 to 224} [133 to 195]
21 to 32 {214 to 327} [186 to 283]
JIS ANSI DIN
10K
20K
6 to 9 {61 to 92} [53 to 80]
15 to 22 {153 to 224} [133 to 195]
21 to 32 {214 to 327} [186 to 283]
150
6 to 9 {61 to 92} [53 to 80]
12 to 18 {122 to 184} [106 to 159]
17 to 26 {173 to 265} [150 to 230]
300
6 to 9
{61 to 92}
[53 to 80]
15 to 22 {153 to 224} [133 to 195]
25 to 38 {255 to 388} [221 to 336]
{112 to 173}
{214 to 327} [186 to 283]
Maximum Tightening Torque Values for Ceramic lining Type N-m {kgf-cm} [in-lbf]
Size mm(inch)
15(0.5)
25(1)
40(1.5)
Flange Rating
{143}
[124]
{306}
[265]
{449}
[389]
10K
14
30
44
JIS
20K
14
{143}
[124]
30
{306}
[265]
44
{449}
[389]
150
14
{143}
[124]
22
{224}
[195]
33
{337}
[292]
ANSI
300
14
{143}
[124]
30
{306}
[265]
51
{520}
[451]
3. INSTALLATION
PN10/16
6 to 9 {61 to 92} [53 to 80]
11 to 17
[97 to 150]
21 to 32
DIN
PN10/16
14
{143}
[124]
25
{255}
[221]
50
{510}
[442]
*Please use compressed non-asbestos fiber gasket, PTFE gasket or the gasket which has equal elasticity.
T030303.EPS
Table 3.3.4 Tightening Torque Values for PVC Piping
Tightening Torque Values for PFA lining / Polyurethane lining Type N-m {kgf-cm} [in-lbf]
Size mm(inch)
2.5(0.1), 5(0.2)
10(0.4), 15(0.5)
25(1)
40(1.5)
Flange Rating
10K
2.0 {20} [18]
5.2 {53} [46]
7.4 {76} [65]
JIS
20K
150
2.1 {21} [19]
4.2 {43} [37]
6.0 {61} [53]
ANSI
300
DIN
PN10/16
2.0 {20} [18]
4.0 {41} [35]
7.4 {76} [65]
Maximum Tightening Torque Values for Ceramic Type N-m {kgf-cm} [in-lbf]
Size mm(inch)
15(0.5)
40(1.5)
25(1)
Flange Rating
10K
1.3 {13} [12]
3.5 {36} [31]
5.7 {58} [50]
JIS
20K
150
1.3 {13} [12]
2.8 {29} [25]
4.6 {47} [41]
ANSI
300
DIN
PN10/16
1.3 {13} [12]
2.7 {28} [24]
5.7 {58} [50]
*Please select optional code/FRG and use rubber gasket or others which has equal elasticity.
T030304.EPS
3-8
IM 1E6D0-01E
3. INSTALLATION
3.3.3 Nominal Diameter 50 mm(2˝) to 200 mm(8˝) Wafer Type
IMPORTANT
Please use appropriate bolts and nuts according to process connection. In case stud type of through bolts are used, be sure outside diameter of a shank is smaller than a thread ridge’s one. Please use compressed non-asbestos fiber gasket, PTFE gasket or the gasket which has equal elasticity. In case of optional code/FRG, please use rubber gasket or others which has equal elasticity. Be sure the inner diameter of the gasket does not protrude to inner piping. (Refer to Table 3.3.8)
(1) Mounting Direction
Please mount the Magnetic Flow Tube matching the flow direction of the fluid to be measured with the direction of the arrow mark on the flow tube.
IMPORTANT
NOTE
When installing a size 150mm with JIS F12 (JIS75M) flange, please displace in circumferen­tial direction slightly because the cover of electrode chamber will interfere against the bolts.
(4) Tightening Nuts
Please tighten the bolts according to Torque Values in Table 3.3.5. In case of PVC piping, please select optional code/FRG, use rubber gasket and tighten with the torque value in Table 3.3.6.
CAUTION
In case of PFA lining type as the lining material is Fluorocarbon PFA, it is possible that nuts loose by its character as time passes. Please tighten the nuts regularly. Please be sure to tighten the bolts following prescribed torque values. Please tighten the flange bolts diagonally with the same torque values, step by step up to the prescribed torque value.
If it is impossible to match the direction, please never remodel to change direction of the termi­nal box. In case the measuring fluid flows against the arrow direction, please refer to the section “Reversing Flow Direction” in the Instruc­tion Manual of AM11 Magnetic Flow Converter.
(2) Mounting Centering Devices
To keep concentricity between the Flow Tube and pipes, centering devices must be used. Pass two through-bolts through the four centering devices (two for each) and lower adjacent holes of both flanges. (Refer to Figure 3.3.4)
Please give attention to the nominal size and flange ratings of the centering devices. (Refer to Table 3.3.7)
(3) Positioning Flow Tube
Position the Flow Tube coming in contact four center­ing devices with Mini-Flanges. At this time, pay attention to avoid four centering devices come in contact with Housing. In case stud type of through­bolts are used, position them coming in contact four centering devices with thread of the bolts. (Refer to Figure 3.3.4) After positioning the Flow Tube, pass remaining through-bolts to remaining holes.
Nuts
Please use appropriate bolts and nuts according to Process connection.
Horizontal Mounting Vertical Mounting
Figure 3.3.4 Mounting Procedure
Through bolts
Gaskets (two)
Flanges
Housing
Mini-Flange
Centering devices (four)
F030304.EPS
3-9
IM 1E6D0-01E
Table 3.3.5 Tightening Torque Values for Metal Piping
Tightening Torque Values for PFA lining / Polyurethane lining Type N-m {kgf-cm} [in-lbf]
Size mm(inch)
Maximum Tightening Torque Values for Ceramic lining Type N-m {kgf-cm} [in-lbf]
Size mm(inch)
*Please use compressed non-asbestos fiber gasket, PTFE gasket or the gasket which has equal elasticity.
Flange Rating
Flange Rating
{286 to 429} [248 to 372]
{214 to 316} [186 to 274]
{357 to 520} [310 to 451]
{663 to 959} [575 to 832]
{582 to 857} [504 to 743]
50(2)
80(3)
100(4)
150(6)
200(8)
50(2)
80(3)
100(4)
150(6)
200(8)
JIS ANSI DIN
10K 20K 150 300 PN10
28 to 42
21 to 31
35 to 51
65 to 94
57 to 84
10K 20K
50 {510} [442]
36 {367} [319]
48 {490} [425]
79 {806} [699]
70 {714} [619]
{143 to 214} [124 to 186]
{265 to 398} [230 to 345]
{439 to 653} [381 to 566]
{439 to 694} [381 to 602]
{622 to 939} [540 to 814]
JIS
14 to 21
26 to 39
43 to 64
43 to 68
61 to 92
27 {276} [239]
44 {449} [389]
58 {592} [513]
55 {561} [487]
76 {776} [673]
28 to 42
{286 to 429}
[248 to 372]
41 to 61
{418 to 622}
[363 to 540]
35 to 51
{357 to 520}
[310 to 451]
63 to 89
{643 to 908}
[558 to 788]
93 to 120 {949 to 1224} [823 to 1062]
ANSI
150 300
50 {510} [442]
75 {765} [664]
49 {500} [434]
66 {673} [584]
102
{1041}
[903]
14 to 21 {143 to 214} [124 to 186]
25 to 37 {255 to 378} [221 to 327]
41 to 61 {418 to 622} [363 to 540]
41 to 60 {418 to 612} [363 to 531]
65 to 93 {663 to 949} [575 to 823]
27
{276}
[239]
44
{449}
[389]
56
{571}
[496]
43
{439}
[381]
76
{776}
[673]
{663 to 959} [575 to 832]
94 to 125 {959 to 1276} [832 to 1106]
65 to 94
DIN PN
PN10 PN16
103
{1051}
[911]
Table 3.3.6 Tightening Torque Values for PVC Piping
Tightening Torque Values for PFA lining / Polyurethane lining Type N-m {kgf-cm} [in-lbf]
Size mm(inch)
Maximum Tightening Torque Values for Ceramic lining Type N-m {kgf-cm} [in-lbf]
Size mm(inch)
*Please select optional code/FRG and use rubber or gasket or others which has equal elasticity.
Flange Rating
50(2)
80(3)
100(4)
150(6)
200(8)
Flange Rating
50(2)
80(3)
100(4)
150(6)
200(8)
JIS ANSI DIN
10K 20K 150 300 PN10
9.8
{100}
[87]
7.2 {73} [64]
12.2
{124} [108]
21.4
{218} [189]
19.3
{197} [171]
JIS
10K 20K
8.2 {84} [73]
6.2 {63} [55]
8.0 {82} [71]
19.8
{202} [175]
17.5
{179} [155]
——
——
——
——
————
——
——
——
——
9.8
{100}
[87]
14.4 {147} [127]
12.2 {124} [108]
20.5 {209} [181]
27.6 {282} [244]
ANSI
150 300
8.2 {84} [73]
12.4 {127} [110]
8.1 {83} [72]
18.9 {193} [167]
25.1 {256} [222]
21.4 {218} [189]
28.9 {295} [256]
PN10 PN16
19.8 {202} [175]
26.2 {267} [232]
DIN
PN16
28 to 42 {286 to 429} [248 to 372]
21 to 31 {214 to 316} [186 to 274]
35 to 52 {357 to 531} [310 to 460]
65 to 94 {663 to 959} [575 to 832]
58 to 84 {592 to 857} [513 to 743]
63
{643}
[558]
36
{367}
[319]
48
{490}
[425]
76
{776}
[673]
67
{684}
[593]
PN16
9.8
{100}
[87]
7.2
{73}
[64]
12.2 {124} [108]
21.4 {218} [189]
19.3 {197} [171]
8.2
{84}
[73]
6.2
{63}
[55]
8.0
{82}
[71]
19.8 {202} [175]
17.5 {179} [155]
JIS G3451
F12
41 to 62 {418 to 633} [363 to 549]
68 to 102
{694 to 1041}
[602 to 903]
68 to 100
{694 to 1020}
[602 to 885]
69 to 101
{704 to 1031}
[611 to 894]
JIS G3451
F12
80 {816} [708]
105
{1071}
[929]
84 {857} [743]
102
{1041}
[903]
T030305.EPS
JIS G3451
F12(75M)
14.4 {147} [127]
24.4 {249} [216]
23.4 {239} [207]
31.6 {322} [280]
JIS G3451
F12(75M)
12.3 {126} [109]
16.1 {164} [142]
21.6 {220} [191]
28.7 {293} [254]
T030306.EPS
3. INSTALLATION
3-10
IM 1E6D0-01E
Table 3.3.7 Centering Device Identification
Flange Rating
Lining mm(inch)
50(2)
PFA, polyure­thane
80(3) 100(4) 150(6) 200(8)
50(2)
80(3)
Ceramics
100(4) 150(6) 200(8)
JIS 10K
JIS 20K
B B B C C B B B B B
*Each Centering Devices is engraved a character as identifidation.
B F F D D B F F C C
JIS G3451
F12
H H D D
H H G C
ANSI 150 ANSI 300
B F C C D B F C B G
F C H E E
F C H D
J
DIN PN
10/16
F
G
F C C
F G
F B B
T030307.EPS
Table 3.3.8 Earth Ring inside diameter
Size
2.5(0.1) 5(0.2)
10(1.4) 15(0.5)
25(1)
40(1.5)
50(2)
80(3) 100(4) 150(6) 200(8)
250(10) 300(12) 350(14) 400(16)
Unit: mm(inch)
PFA/Polyurethane lining Ceramic lining
φ15(0.6) φ15(0.6) φ15(0.6) φ15(0.6) φ27(1.1) φ40(1.6) φ52(2.1) φ81(3.2)
φ98(3.9) φ140.7(5.6) φ188.9(7.5) φ239.1(9.5)
φ291.3(11.5) φ323.4(12.8) φ373.5(14.8)
— — —
φ15(0.6) φ27(1.1) φ40(1.6) φ52(2.1) φ81(3.2)
φ98(3.9) φ144(5.7) φ192(7.6)
— — — —
Size
500(20) 600(24) 700(28) 800(32)
900(36) 1000(40) 1100(44) 1200(48) 1350(54) 1500(60) 1600(64) 1800(72) 2000(80) 2200(88) 2400(96)
2600(104)
Polyurethane lining
φ468(18.4) [φ485(19.1)] φ563(22.2) [φ589(23.9)] φ665(26.2) [φ689(27.1)] φ765(30.1) [φ788(31.0)] φ855(33.7) [φ888(35.0)] φ942(37.1) [φ990(39.0)] φ1085(42.7) φ1185(46.7) φ1335(52.6) φ1485(58.5) φ1585(62.4) φ1785(70.3) φ1985(78.1) φ2185(86) φ2385(93.9) φ2585(101.8)
Unit: mm(inch)
*Please ensure that the I.D. of the gasket does not protrude into the I.D. of the Earth Ring.
(This dimension is also applied when no earth ring is used)
*[ ] ; for Process connection code G1
3. INSTALLATION
T030308.EPS
3-11
IM 1E6D0-01E
3. INSTALLATION
3.3.4 Nominal Diameter 15 mm (0.5˝) to 400 mm (16˝) Flange Type
IMPORTANT
Please use appropriate bolts and nuts according to process connection. Please use compressed non-asbestos fiber gasket, PTFE gasket or the gasket which has equal elasticity. In case of optional code/FRG, please use rubber gasket or others which has equal elasticity. Be sure the inner diameter of the gasket does not protrude to inner piping.(Refer to Table 3.3.8)
(1) Mounting Direction
Please mount the Magnetic Flow Tube matching the flow direction of the fluid to be measured with the direction of the arrow mark on the flow tube.
IMPORTANT
(2) Tightening Nuts
Please tighten the bolts according to Torque Values in Table 3.3.9. In case of PVC piping, please select optional code/FRG, use rubber gasket and tighten with the torque value in Table 3.3.10.
CAUTION
In case of PFA lining type as the lining material is Fluorocarbon PFA, it is possible that bolts loose by its character as time passes. Please tighten the nuts regularly. Please be sure to tighten the bolts following prescribed torque values. Please tighten the flange bolts diagonally with the same torque values, step by step up to the prescribed torque value.
If it is impossible to match the direction, please never remodel to change direction of the termi­nal box. In case the measuring fluid flows against the arrow direction, please refer to the section “Reversing Flow Direction” in the Instruc­tion Manual of AM11 Magnetic Flow Converter.
Gasket (two)
Flange (Flow tube)
Bolts
Please use appropriate bolts and nuts according to process conneciton.
Figure 3.3.5 Mounting Procedure (Size: 15 mm (0.5") to 400 mm (16"))
Nuts
Flange
(Piping side)
3-12
F030305.EPS
IM 1E6D0-01E
Table 3.3.9 Tightening Torque Values for Metal Piping in N-m{kgf-cm} [in-lbf]
15(0.5mm)
25(1mm)
40(1.5mm)
50(2mm)
80(3mm)
100(4mm)
150(6mm)
200(8mm)
250(10mm)
300(12mm)
350(14mm)
400(16mm)
Flange
Rating
{31 to 51} [27 to 44]
{82 to 133} [71 to 115]
{184 to 265} [159 to 230]
{224 to 316} [195 to 274]
{153 to 224} [133 to 195]
{214 to 357} [186 to 310]
{663 to 959} [575 to 832]
{582 to 857} [504 to 743]
142 to 174 {1449 to 1776} [1257 to 1540]
114 to 138 {1163 to 1408} [1009 to 1221]
158 to 183 {1612 to 1867} [1398 to 1619]
243 to 261 {2480 to 2663} [2150 to 2310]
Size mm(inch)
*Please use compressed non-asbestos fiber gasket, PTFE gasket or the gasket which has equal elasticity.
JIS ANSI DIN
10K 20K 150 300 PN10
3 to 5
8 to 13
18 to 26
22 to 31
15 to 22
21 to 35
65 to 94
57 to 84
3 to 5
{31 to 51}
[27 to 44]
8 to 13 {82 to 133} [71 to 115]
18 to 26 {184 to 265} [159 to 230]
11 to16
{112 to 163}
[97 to 142]
18 to 27 {184 to 276} [159 to 239]
25 to 44 {255 to 449} [221 to 389]
43 to 68 {439 to 694} [381 to 602]
61 to 92 {622 to 939} [540 to 814]
154 to 182
{1571 to 1857}
[1363 to 1611]
125 to 145
{1276 to 1480}
[1106 to 1283]
3 to 5 {31 to 51} [27 to 44]
6 to 10
{61 to 102}
[53 to 88]
15 to 21
{153 to 214}
[133 to 186]
23 to 31
{235 to 316}
[204 to 274]
35 to 43
{357 to 439}
[310 to 381]
22 to 35
{224 to 357}
[195 to 310]
63 to 89
{643 to 908}
[558 to 788]
93 to 120
{949 to 1224} [823 to 1062]
145 to 177 {1480 to 1806} [1283 to 1566]
164 to 187 {1673 to 1908} [1451 to 1655]
245 to 284 {2500 to 2898} [2168 to 2513]
253 to 275 {2582 to 2806} [2239 to 2434]
3 to 5
{31 to 51}
[27 to 44]
8 to 13 {82 to 133} [71 to 115]
21 to 31 {214 to 316} [186 to 274]
11 to 16 {112 to 163}
[97 to 142]
18 to 26 {184 to 265} [159 to 230]
25 to 42 {255 to 429} [221 to 372]
41 to 59 {418 to 602} [363 to 522]
65 to 93 {663 to 949} [575 to 823]
126 to 151
{1286 to 1541}
[1115 to 1336]
154 to 180
{1571 to 1837}
[1363 to 1593]
65 to 94
{663 to 959}
[575 to 832]
94 to 125 {959 to 1276} [832 to 1106]
136 to 164 {1388 to 1673} [1204 to 1451]
155 to 199 {1582 to 2031} [1372 to 1761]
152 to 192 {1551 to 1959} [1345 to 1699]
248 to 331 {2531 to 3378} [2195 to 2929]
PN16
3 to 5 {31 to 51} [27 to 44]
6 to 10
{61 to 102}
[53 to 88]
18 to 26 {184 to 265} [159 to 230]
23 to 31 {235 to 316} [204 to 274]
16 to 22 {163 to 224} [142 to 195]
21 to 35 {214 to 357} [186 to 310]
65 to 94 {663 to 959} [575 to 832]
58 to 84 {592 to 857} [513 to 743]
154 to 175 {1571 to 1786} [1363 to 1549]
175 to 213 {1786 to 2173} [1549 to 1885]
JIS G3451
F12(75M)
33 to 47 {337 to 480} [292 to 416]
47 to 75 {480 to 765} [416 to 664]
65 to 100
{663 to 1020}
[575 to 885]
69 to 101
{704 to 1031}
[611 to 894]
215 to 270 {2194 to 2755} [1903 to 2389]
190 to 249 {1939 to 2541} [1681 to 2204]
274 to 325 {2796 to 3316} [2425 to 2876]
313 to 395 {3194 to 4031} [2770 to 3496]
T030309.EPS
3. INSTALLATION
Table 3.3.10 Tightening Torque Values for PVC Piping in N-m{kgf-cm} [in-lbf]
Flange
mm(inch)
*Please select optional code/FRG and use rubber or gasket or others which has equal elasticity.
RatingSize
15(0.5)
25(1)
40(1.5)
50(2)
80(3)
100(4)
150(6)
200(8)
JIS
10K 20K
1.1
{11}
[10]
2.9
{30}
[26]
5.9
{60}
[52]
7.2
{73}
[64]
4.9
{50}
[43]
8.1
{83}
[72]
29.8 {304} [264]
26.3 {268} [233]
ANSI
150 300
1.1 {11} [10]
2.3 {23} [20]
4.7 {48} [42]
7.2 {73} [64]
9.9
{101}
[88]
8.2 {84} [73]
28.5
{291}
[252]
37.7
{385}
[334]
DIN
PN10 PN16
29.8
{304}
[264]
39.4 {4,2} [349]
1.1 {11} [10]
2.2 {22} [19]
5.9 {60} [52]
7.2 {73} [64]
4.9 {50} [43]
8.1 {83} [72]
29.8
{304} [264]
26.3
{268} [233]
JIS G3451
F12(75M)
9.9
{101}
[88]
16.3 {166} [144]
32.6
{33}
[288]
43.1 {440} [381]
T030310.EPS
3-13
IM 1E6D0-01E
3. INSTALLATION
3.3.5 Mominal Diameter 500 mm (20") to 2600 (104") Flange Type
(1) Mounting Direction
Please mount the Magnetic Flow Tube matching the flow direction of the fluid to be measured with the direction of the arrow mark on the flow tube.
IMPORTANT
If it is impossible to macth the direction, please never remodel to change direction of the termi­nal box. In case the measuring fluid flows against the arrow direction, please refer to the section “Reversing Flow Direction” in the Instruc­tion Manual of AM11 Magnetic Converter.
CAUTION
When lifting the flow tube, please use the lifting rings (eye bolts or shackle). To assure safety, please keep lifting angle less than 90 degrees as shown in Figure 3.3.6. Please do not shock the installation foundation bracket when installing the flowmeter as the bracket may be damaged.
(3) Installation Foundation Dimensions
Table 3.3.11 Installation Foundation Dimensions
[Nominal Dia. 500 mm (20") to 1000 mm (40")]
150* (5.9)
4-Anchor bolt
Size:
mm (inch)
500 (20) 600 (24) 700 (28) 800 (32) 900 (36)
1000 (40)
Table 3.3.12 Installation Foundation Dimensions
A
350 (13.8) 400 (15.7) 450 (17.7) 550 (21.7) 700 (27.6) 800 (31.5)
B
350 (13.8) 400 (15.7) 500 (19.7) 550 (21.7) 650 (25.6) 700 (27.6)
C
420 (16.5) 470 (18.5) 570 (22.4) 620 (24.4) 770 (30.3) 870 (34.3)
125 (4.9) 125 (4.9) 125 (4.9) 125 (4.9) 125 (4.9) 125 (4.9)
T030311.EPS
[Nominal Dia. 1100 mm (44") to 2600 mm (104")]
D
90° or less
F030306.EPS
Figure 3.3.6 Lifting Flow Tube
(2) Positioning Flow Tube
Please position the flow tube using a jack.
IMPORTANT
Please apply the jack to near the flow tube support and insert a steel liner between the bracket and flow tube support. Never use wooden liner.
F*
500 (19.7)
A
16-T
D
G
D
G
H
IKJC
H
Size:
mm (inch)
1,100 (44)
1,211 (47.7)
1,200 (48)
1,261 (49.6)
1,350 (54)
1,366 (53.8)
1,500 (60)
1,490 (58.7)
1,600 (64)
1,698 (66.9)
1,800 (72)
1,864 (73.4)
2,000 (80)
2,010 (79.1)
2,200 (88)
2,172 (85.5)
2,400 (96)
2,218 (87.3)
2,600 (104)
2,300 (90.6)
A
1,500 (59.1) 1,600 (63.0) 1,750 (68.9) 1,900 (74.8) 2,100 (82.7) 2,250 (88.6)
2,450 (96.5) 2,700 (106.3) 2,900 (114.2)
LL
C
D
600
(23.6)
700
(27.6)
(F)
200* (7.9)
250* (9.8)
Dimensions
G
450 (17.7) 500 (19.7)
400
550 (21.7)
(15.7)
600 (23.6) 650 (25.6) 700 (27.6)
500
700 (27.6)
(19.7)
730 (28.7) 770 (30.3)
H
I 520 (20.5) 540 (21.3) 640 (25.2) 700 (27.6) 700 (27.6) 750 (29.5)
1,070 (42.1) 1,200 (47.2) 1,330 (52.4)
J
1,100 (43.3)
720 (28.3)
1,200 (47.2)
780 (30.7)
1,350 (53.1)
880 (34.6)
1,500 (59.1)
980 (38.6)
1,650 (65.0)
1,080 (42.5)
1,800 (70.9)
1,180 (46.5)
2,000 (78.7)
1,300 (51.2)
2,200 (86.6)
1,430 (56.3)
2,400 (94.5)
1,560 (61.4)
2,600 (102.4)
1,700 (66.9)
T030312ilust.EPS
K
L
130
(5.1)
170
(6.7)
200
(7.9)
M16*
M20*
T030312.EPS
Note 1: See the external dimensions for the support dimensions. Note 2: The value marked as * is reference dimensions.
T
3-14
IM 1E6D0-01E
3. INSTALLATION
(4) Connecting to Pipe
Please pass bolts from pipe line side, not flow tube side, and tighten the bolts according to Torque Values in Table 3.3.9.
CAUTION
• Please be sure to tighten the bolts following prescribed torque values. Please tighten the flange bolts diagonally with the same torque values, step by step up to the prescribed torque value.
• Please completely cover the brackets and liners with mortar.
Figure 3.3.7 Mounting Flow Tube
Table 3.3.13 Tightening Torgue Values for Metal Piping
Flange
JIS G3451 F12/JIS7.5K
Rating
SIze: mm (inch)
500 (20) 600 (24) 700 (28) 800 (32)
900 (36) 1000 (40) 1100 (44) 1200 (48) 1350 (54) 1500 (60) 1600 (64) 1800 (72) 2000 (80) 2200 (88) 2400 (96) 2600 (104)
* Please use rubber gasket or the gasket which has equal elasticity.
N-m N-m N-mkgf-cm kgf-cm kgf-cmin-Ibf in-Ibf in-Ibf
121
1234
to 1530
1183
to 1479
1765
to 2193
1836
to 2285
1040
to 1295
2356
to 2938
3040
to 3794
3070
to 3835
4406
to 5498
4723
to 5896
4774
to 5967
4947
to 6171
6273
to 7834
6997
to 8752
7742
to 9670
10261
to 12821
1071
to 1327
1027
to 1283
1531
to 1903
1593
to 1982
903
to 1124
2044
to 2549
2637
to 3292
2664
to 3327
3823
to 4770
4097
to 5115
4142
to 5177
4292
to 5354
5442
to 6796
6071
to 7593
6717
to 8389
8903
to 11124
to 150
116
to 145
173
to 215
180
to 224
102
to 127
231
to 288
298
to 372
301
to 376
432
to 539
463
to 578
468
to 585
485
to 605
615
to 768
686
to 858
759
to 948
1006
to 1257
63 78 104 115 175 204
to 79 to 97 to 130 to 144 to 182 to 254
— — — — — — — — — —
JIS10K
643
to 806
796
to 989
1061
to 1326
1173
to 1469
1785
to 1856
2081 to 2591
— — — — — — — — — —
558
to 699
690
to 858
920
to 1150
1018
to 1274
1549
to 1611
1805
to 2248
— — — — — — — — —
59 to 73 67 to 84
— — — — — — — — — — — — — —
ANSI150
602 to 745 683 to 857
— — — — — — — — — — — — — —
522 to 646 593 to 743
— — — — — — — — — — — — — —
T030313.EPS
IMPORTANT
If it is impossible to macth the direction, please never remodel to change direction of the termi­nal box. In case the measuring fluid flows against the arrow direction, please refer to the section “Reversing Flow Direction” in the Instruc­tion Manual of AM11 Magnetic Converter.
(2) Welding of Mating Ferrule to Piping
IMPORTANT
Weld the attached ferrules to the piping. Please pay attention to the welding condition to avoid deforming piping or making the stagnant portion of the fluid; joint preparation, level difference in butt joint, welding current.
(3) Mounting Gasket
Mount the attached gasket so it fits into the groove on the ferrule.
(4) Positioning Flow Tube
Position the flow tube between the mating ferrule.
(5) Tightening Clamp
Mount the clamp so they cover the flow tube and mating ferrule tapered part.
Clamp
Ferrule
Pipe
3.3.6 Mounting Procedure for Sani­tary Type
The sanitary type is mounted using IDF clamps.
(1) Mounting Direction
Please mount the Magnetic Flow Tube matching the flow direction of the fluid to be measured with the direction of the arrow mark on the flow tube.
Figure 3.3.8 Mounting Procedure
3-15
Welding
F030308.EPS
IM 1E6D0-01E
3. INSTALLATION

3.4 Wiring Precautions

This section is described wiring only for flow tube side. Please see "Wiring" in AM11 Magnetic Flow Converter Instruction Manual for converter side.

3.4.1 Protective Grounding

CAUTION
Please be sure to connect protective grounding of ADMAG with cable of 2mm2 or larger cross section in order to avoid the electrical shock to the operators and maintenance engineers and prevent the influence of external noise. And further connect the grounding wire to the mark (100or less).

3.4.2 General Precautions

Please give attention to the followings in wiring.
• Please be sure to fully tighten the terminal box cover before the power is turned on.
• Please be sure to turn off the power before opening the terminal box cover.

3.4.3 Cable Types

(1) Dedicated Signal Cable(AM011)
The flow signal is transmitted via this dedicated cable. The cable is constructed with double shielding over the two conductors, and used heat-resistant vinyl as the outer jacket material.
Finished diameter: 10.5 mm (0.413”) Maximum length: 200 m (660 ft) Maximum temperature: 80°C (176°F)
CAUTION
• In case the ambient temperature exceeds 50°C (122°F), please use heat-resistant cable with maximum allowable temperature of 70°C (158°F) or above for JIS flameproof type.
• Please pay attention to avoid the cable is bended excessively.
• Please do not connect cables outdoors in case of rain to prevent damages from dew formation and to keep insulation inside the terminal box of the flow tube.
• Please do not splice the cable between a flow tube and a converter if it is too short. Please replace the short cable with the cable which is appropriate length wholly.
• The all cable ends are to be provided with round crimp-on terminal.
• The signal cables must be routed in separate steel conduit tubes or flexible tubes.
•Please keep conduit or flexible tube water-tight using sealing tape.
•Please ground each of a flow tube and a converter separately.
• Please cover each shield of the signal cable with PVC tube or PVC tape to avoid contacting between two shields; shield and case.
•When waterproof glands or union equipped waterproof glands are used, the glands must be properly tightened to keep the box watertight.
Figure 3.4.1 Dedicated Signal Cable AM011
IMPORTANT
If the cable is longer than required, cut off any extra length, rather coiling it up, and terminate the conductors as shown in Figure 3.4.2. Avoid using intermediate terminal boards to extend the cable length, or this will interrupt the shielding.
ACB
SA
On the converter
Figure 3.4.2 Treatment of Dedicated Signal Cable
30 (1.2)
(WHITE) (BLACK) (RED)
side
150
(5.9)
SB
70 (2.8)
8 (0.3) Max.
20 (0.8)
120 (4.7)
130 (5.1)
L (SPECIFIED LENGTH)
AM011*A
ACB
90 (3.5)
(WHITE) (BLACK) (RED)
8 (0.3) Max.
150
(5.9)
On the flow tube
ø10.5 (0.4)
30 (1.2)
90 (3.5)
side
F030402.EPS
3-16
IM 1E6D0-01E
3. INSTALLATION
CAUTION
Since A, B, SA, SB, and C all operate at differ­ent electrical potentials, securely insulate them from each other so they do not touch. The shields must not be allowed to touch each other or to touch the case. Cover each shield with vinyl tube or wrap in vinyl tape.
NOTE
Conductors A and B carry the signal from the electrodes, and C is at the potentials of the liquid it self (signal common) . Shields SA and SB are kept at the same potentials as the individual electrodes (these are actively driven shields). This is done to reduce the effect of the distrib­uted capacitance of the cable at long cable length. Note that, since the signals from the individual electrodes are impedance converted inside the converter, errors will result if they come in contact with any other component. Great care must be taken in the cable end treatment.

3.4.4 Connnection to AM11Magnetic Flow Converter

Connect the flow tube and converter in the following method.
EX1
EX2
Dedicated signal cable AM011-2
A
B
C
Flow tube
Figure 3.4.4 Connection
CSAAB
EX2
EX1
Note: Terminate those shielding wire terminal
SB
Converter
Terminal
SA
A B
SB
C EX1 EX2
using insulating tape.
AM11 converter
Flow tube
(See Note below)
A B
(See Note below)
C
EX1 EX2
F030404.EPS
(2) Excitation Cable
Please use Polyvinyl chloride insulated and sheathed control cables (JIS C3401) or Polyvinyl chloride insulated and sheathed portable power cables (JIS C3312) or equivalents.
Outer Diameter
• 6.5 to 12mm in diameter (7.5 to 12 mm for water­proof gland / ECG, /ECU, /ECW)
Nominal Cross Section
•Single wire; 0.5 to 2.5mm2 , Stranded wire; 0.5 to
2
2.5mm
EX2
EX1
85
(3.3)
On the converter side On the flow tube side
(3.3)
85
EX1
Unit: mm (inch)
EX2
Figure 3.4.3 End Treatment of Excitation Cable
F030403.EPS
3-17
IM 1E6D0-01E
3. INSTALLATION

3.4.5 Wiring Ports

Please select the most suitable standard of wiring procedure for the wiring ports by customer’s own.
A : Using the Waterproof Gland
IMPORTANT
To prevent water or condensate from entering the converter housing, waterproof glands are recommended. Do not over-tighten the glands or damage to the cables may result. Tightness of the gland can be checked by confirming that the cable is held firmly in place.
Waterproof gland Optional code : /ECG
Gasket
Tightening gland
Waterproof gland with union joint Optional code : /ECU
G1/2 female
Gasket
Tightening gland
G1/2 female
B : Insulation Check
After wiring is completed, check insulation of the following terminals together with the wiring under the condition of the converter side wiring terminals disconnected.
Between terminal EX1 and terminal A, B, C Between terminal C and terminal A, B Between terminal A and terminal B Between terminal EX1 and ground Between terminal EX2 and ground
All insulation measurements must be performed with a 500V megger. Insulation resistances must be 100M or more each.
IMPORTANT
Be sure to disconnect the cables at the terminal of the converter when checking insulation.
C : Conduit Wiring
In case of conduit wiring, please use the waterproof gland to prevent water flowing through the conduit pipe into the wiring connection.
Please slope the conduit pipe down, and install a drain valve at the low end of the vertical pipe.
Waterproof gland Optional code : /ECW
Gasket Tightening gland G3/4
Figure 3.4.6 Waterproof Gland
Please open the drain valve regularly.
G1/2 female
F030406.EPS
Drain valve
F030407.EPS
Figure 3.4.7 Conduit Wiring
3-18
IM 1E6D0-01E
4. MAINTENANCE

4. MAINTENANCE

WARNING
This instrument must be repaired or mainte­nance-serviced by expert engineer or skilled personnel. The procedures described in this chapter are not permitted for operators.
Regular maintenance and inspection should be carried out to fully utilize all functions and to obtain maximum performance from the magnetic flowmeter.

4.1 Regular Inspection Items

(1)Inspection of moisture-proofing inside the
terminal box: Once/year
(2)Refastening of piping joint screws: About
twice/year
(3)Inspection of electrodes and lining (in case
of adhesive and/or abrasive fluid, etc.)
Determine the period of regular inspection as necessary.
(2) Insulation Resistance Check
Check the insulation resistances in accordance with the tables below. If one of them falls below the value in the tables, replacement or repair of the flow tube is needed. In case of submersible type flowmeter, release wiring connection of converter side and measure resistance at cable terminations.
Coil Circuit
Checking is possible even if the pipe is filled with fluid.
Test T erminals
Between Terminals EX1 and C
Test V oltage Specification
500 V DC 1M or more
T0401.EPS
Signal Circuit
Be sure to empty and dry the pipe inside, and release wiring connection of converter side before checking.
Test T erminals
Between Terminals A and C Between Terminals B and C
Test V oltage
500 V DC 100M or more for each
Specification
T0402.EPS

4.2 Trouble Shooting

Since the ADMAG magnetic flowmeter has “self diagnostic functions”, if a failure occurs, it is displayed on the AM11 magnetic flow converter. Please refer to Instruction Manual of AM11 magnetic flow converter.
IMPORTANT
Be sure to disconnect the cables at the terminals of the flow tube when checking.
(1) Excitation Coil Check
Check that the resistance between terminals EX1 and EX2 in the terminal box is 150 or less with a multimeter. If it is not, coils may be broken down, and replacement or repair of the flow tube is needed.
4-1
IM 1E6D0-01E
5. OUTLINE
STANDARD SPECIFICATIONS
Protection:
General Purpose /Explosion proof /Sanitary Type:
IP67, NEMA4X, JIS C0920 water tight type.
Submersible Type: JIS C0920 submersible type, IP68.
(Test Condition: 50m below the surface of the water, equivalent to 0.5MPa pressure, for one month. If always under water or corrosion fluid, contact Yokogawa office.)
Size:
General Purpose type
Fluorocarbon
Lining
Size in
2.5(0.1), 5(0.2),
mm
10(0.4),15(0.5),
(inch)
25(1), 40(1.5), 50(2), 65(2.5), 80(3), 100(4), 125(5), 150(6), 200(8),250(10), 300(12),350(14), 400(16)
Submersible type
PFA
Lining
25(1),
Size in
40(1.5),
mm
50(2),
(inch)
80(3), 100(4), 150(6), 200(8), 250(10), 300(12), 350(14), 400(16)
PFA
25(1), 40(1.5), 50(2),
80(3), 100(4), 150(6), 200(8), 250(10), 300(12), 350(14), 400(16),500(20), 600(24), 700(28), 800(32),900(36), 1000(40),1100(44), 1200(48), 1350(54), 1500(60),1600(64), 1800(72),2000(80), 2200(88),2400(96), 2600(104)
Ceramic
2.5(0.1), 5(0.2), 10(0.4), 15(0.5), 25(1), 40(1.5), 50(2), 80(3), 100(4), 150(6), 200(8)
Polyurethane
25(1), 40(1.5), 50(2), 80(3), 100(4), 150(6), 200(8), 250(10), 300(12), 350(14), 400(16), 500(20), 600(24), 700(28), 800(32), 900(36), 1000(40),1100(44),1200(48), 1350(54), 1500(60), 1600(64), 1800(72),2000(80), 2200(88 ), 2400(96), 2600(104)
Explosion proof type
Lining Size in
mm
(inch)
Sanitary type*1
Lining Size in
mm
(inch)
*1: 15, 125mm for Sanitary type flow tubes are available on request.
Coating:
General Purpose /Explosion Proof /Sanitary Type:
Body: Size 2.5 to 100 mm (0.1 to 4in.); No
coating (Stainless steel surface)
Size 125mm (5in.) or more; Polyure-
thane corrosion-resistant coating Frosty-white (Munsell 2.5Y8.4/1.2)
Terminal box : Polyurethane corrosion-resistant
coating Case; Frosty white (Munsell 2.5Y8.4/1.2) Cover; Deep sea moss green (Munsell
0.6GY3.1/2.0)
Submersible type: Non-tar epoxy coating(Black)
Flow Tube Material:
Size 2.5 to 15 mm (0.1 to 0.5in.)
Housing: Stainless steel(SCS11) Flange (15mm(0.5 in.)only) : Stainless
steel.(SUS304)
Pipe: Stainless steel (SCS13)*or Alumina
ceramic (99.9%)
Terminal box : Aluminum alloy.
Size 25 to 100 mm (1 to 4in.)
Housing: Stainless steel(SUS304) Flange : Stainless steel (SUS304) Pipe: Stainless steel (SUS304)*or Alumina
ceramic (99.9%)
Terminal box : Aluminum alloy.
hydraulic
Polyurethane
PFA/Ceramic
2.5(0.1), 5(0.2), 10(0.4), 15(0.5),25(1), 40(1.5), 50(2), 80(3), 100(4), 150(6), 200(8)
PFA
25(1), 40(1.5), 50(2), 65(2.5), 80(3), 100(4),
T01.EPS

5. OUTLINE

Size 125 to 400 mm (5 to 16in.)
Housing: Carbon steel Flange Carbon steel Pipe: Stainless steel (SUS304)*or Alumina
ceramic (99.9%, only for size 150mm
and 200mm (6 and 8in.) Terminal box : Aluminum alloy. * For PFA or Polyurethane lining
Size 500 to 2600 mm (20 to 104in.)
Housing: Carbon steel Flange Carbon steel Pipe: Stainless steel (SUS304)
Terminal box:cover; Aluminum alloy
case; Stainless steel (SUS304)
Wetted Part Material:
Lining: Fluorocarbon PFA, Alumina ceramic,
Polyurethane
Electrode: Stainless steel (SUS316L), Hastelloy C
(equivalent to Hastelloy C-276), Titanium, Tantalum, Platinum-Iridium, Platinum­alumina cermet only for ceramic lining. *For size over 500mm and sanitary type, SUS316L only
Earth Ring/Earth Electrode:Stainless steel (SUS316),
Hastelloy C (equivalent to Hastelloy C-
276), Titanium,SUS304,(Size 500 to 1000mm (20 to 40in.), SS400 lined with SUS316 (Size 1100 to 2600mm (40 to 104in.) ), PFA lining+Earth electrodes (Tantalum, Platinum-Iridium).
Note: Hastelloy is a registered trademark of
Ha ynes International Inc.
Gasket: • VALQUA#7020;Fluoro resin with filler
(between flow tube body and earth ring; for ceramic lining)
• VALQUA#4010;Fluoro rubber, viton (between flow tube body and earth ring; for optional code /FRG)
• Non-asbestos joint sheet sheathed with fluoro resin (between earth ring and process flange; for optional code /BCF or /BSC)
• Chloroprene rubber (between earth ring and process flange; for optional code /BCC or /BSC)
• EPDM, ethylene propylene rubber (for sanitary type)
* Other gaskets between flow tube body and earth ring;
• VALQUA#7026;corrosion resistance gasket (Fluoro resin with carbon)
• VALQUA#4010(Mixing#RCD970);Alkali resistance gasket for PVC piping (Fluoro rubber)
• VALQUA#4010(Mixing#RCD470);Acid resistance gasket for PVC piping (Fluoro rubber)
Contact Yokogawa office. (Refer to TI 1E6A0-06E)
Union Joint:Stainless steel (SUS316L), for ceramic
lining size 10mm (0.4in.) or less*
*Contact Yokogwa office if PVC union joints are required.
Ferrule(for sanitary type):SCS13
5-1
IM 1E6D0-01E
5. OUTLINE
Electrode Construction:
• General Purpose/Ex-proof/Submersible type
PFA, Polyurethane Linings: External Insertion type. Ceramic Lining: Integral type.
• Sanitary type
Internal Insertion type. * Only PFA lining is available for sanitary type
Electrical Connection:
JIS G1/2(PF1/2)female, ANSI 1/2NPT female, DIN Pg13.5 female, ISO M20X1.5 female
Terminal Connection:
M4 size screw terminal.
Grounding:
100 or less * In case of JIS Flameproof type, JIS Class C(10Ω or
less) or JIS Class A(10or less)
HAZARDOUS AREA CLASSIFICATION
AM100 / 200DN
FM:
• Explosion proof for Class I, Division 1, Groups A, B, C & D. Dust-ignitionproof for Class II/III, Division 1, Groups E, F &G. Intrinsically safe (electrode) for Class I, Division 1, Groups A, B, C & D. Electrode Circuit Vmax: 250V ac/dc Temp. Class. T6 Enclosure: NEMA 4X
• Nonincendive for Class I, Division 2, Groups A, B, C & D; Suitable for Class II, Division 2, Groups F &G; Class III, Division 1 and 2. Intrinsically safe (elec­trode) for Class I, Division 1, Groups A, B, C & D.
Electrode Circuit Vmax: 250V ac/dc Excitation Circuit: 130Vp 72/75 Hz Temp. Class. T5 Enclosure: NEMA 4X
* Installation shall be in accordance with the
manufacturer’s instructions and the National Electric Code, ANSI/NFPA-70.
CENELEC
KEMA No. Ex-94.C.8524
EEx dm[ia]IIC T6...T4 Electrode Circuit Vmax: 250V ac/dc Excitation Circuit: 130Vp 72/75 Hz Temp. Class T6 T5 T4 T3 Process Temp. 70 85 120 150˚C
CSA :
• Nonincendive for Class I, Division 2, Groups A, B, C & D; Suitable for Class II, Division 2, Groups F &G; Class III, Division 2. Intrinsically safe (electrode) for Class I, Division 1, Groups A, B, C & D. Electrode Circuit Vmax: 250V ac/dc Excitation Circuit: 130Vp 72/75 Hz, 11 VAmax Temp. Class T5 T4 T3 Process Temp. 85 120 150˚C Enclosure: Type 4
JIS:
• Exde[ia]II C T4X Converter, Terminal box ; Explosion proof Flow Tube ; Increased Safety Signal Circuit ; Intrinsically Safety(ia) Ambient Temperature : -10˚C to 60 ˚C* Fluid Temperature : 120˚Cmax. Electrode Circuit : 250V AC/DC Grounding : JIS Class C(10 or less) or JIS Class A(10Ω or less)
* In case the ambient temperature exceeds 50˚C,
use heat-resistant cables with maximum allowable temperature of 70˚C or above.
STANDARD PERFORMANCE
Accuracy:
PFA and Ceramic Lining
Vs: Span setting value (m/s)
Size in
mm (inch)
2.5 to 15
(0.1 to 0.5)
25 to 400
(1 to 16)
Polyurethane Lining
Size in
mm (inch)
25 to 400
(1 to 16)
500 to 1000
(20 to 40)
1100 to 2000
(44 to 80)
2200 to 2600
(88 to 104)
Repeatability:
0.1% of flowrate (1mm/s Minimum )
Maximum Power Consumption:
28W (for combination with AM11 converter).
Insulation Resistance:
• 100M between excitation terminal and each signal terminal at 500V DC.
• 100M among signal terminals at 500V DC.
Withstand Voltage (Except for ex-proof type):
• 1000V AC or 1400 V DC between excitation terminal and ground terminal for 1minute.
(Ex-proof type):
• 1500V AC between excitation terminal and ground terminal for 1 minute.
• 500V AC between each signal terminal and ground terminal for 1 minute.
• 1760V AC between each signal terminal and each excitation terminal for 1 minute.
Span in m/s
(ft/s)
0.1 to 0.3(0.3 to 1)
0.3 to 1(1 to 3)
1 to 3 (3 to 33) (both included)
0.1 to 0.3(0.3 to 1)
0.3 to 1 (1 to 3)
1 to 10(3 to 33) (both included)
Span in m/s
(ft/s)
0.1 to 0.3(0.3 to 1)
0.3 to 1(1 to 3)
1 to 10 (3 to 33)
0.1 to 0.3(0.3 to 1)
0.3 to 1(1 to 3)
1 to 10 (3 to 33)
0.3 to 1(1 to 3)
1 to 10(3 to 33)
0.3 to 1(1 to 3)
1 to 10(3 to 33)
Accuracy
0.15/Vs % of span
0.5% of span
0.25% of span (at indications below 50%)
0.5% of flowrate indication (at indications 50% of span or more)
0.075/Vs % of span
0.25% of span (at indications below 50% of span)
0.5% of flowrate indication (at indications 50% of span or more)
0.1% of span (at indications below 20% of span)
0.5% of flowrate indication (at indications 20% of span or more)
Vs: Span setting value (m/s)
Accuracy
0.15/Vs % of span
0.5% of span
0.25% of span (at indications below 50% of span)
0.5% of flowrate indication (at indications 50% of span or more)
0.225/Vs % of span
0.75 % of span
0.5% of span
0.75 % of span
0.5% of span 1/Vs % of span 1% of span
T02.EPS
T03.EPS
5-2
IM 1E6D0-01E
5. OUTLINE
CAUTION
When performing the Voltage Breakdown Test, Insulation Resistance Test or any unpowered electrical test, wait 10 seconds after the power supply is tumed off before removing the housing cover. Be sure to remove the Short Bar at termi­nal “G”. After testing, return the Short Bar to its correct position. Screw tightening torque should be 12kg-cm(0.88ft-lb) or more, becase the G­terminal is thought as a protective grounding and should conform to the Safety Requirements.
NORMAL OPERATING CONDITION
Ambient Temperature:
-10 to 60˚C (14 to 140˚F)
Ambient Humidity:
5 to 95%RH (No condensation)
Power Suppply:
Supplyed from magnetic flow converter
Measurable Flowrate
3
English Units (Size : inch, Flowrate : GPM)
Max. Flowrate
@10m/s
0.1767
0.7068
2.8274
6.361
17.671
45.23
70.68
119.45
180.95
282.74
441.7
636.1 1,130.9 1,767.1 2,544.6
3,463 4,523
7,068 10,178 13,854 18,095 22,902 28,274
Max. Flowrate
@10m/s
34,211 40,715 51,529 63,617 72,382 91,608
113,097 136,847 162,860 191,134
/h)
0.0081
0.0322
0.1286
0.2008
0.8032
1.8071
3.213
5.020
7.229
12.851
20.079
28.914
51.41
80.32
115.66
157.42
205.61
321.3
462.7
629.7
822.5
1040.9
1285.1
4,665 5,552 7,026 8,674
9,870 12,491 15,421 18,659 22,206 26,061
Max. Flowrate
@33ft/s
0.8031
3.212
12.850
20.078
80.31
180.70
321.2
501.9
722.8
1,285.0
2007.8
2,891.3
5,140
8,031 11,565 15,741 20,560 32,125 46,261 62,966 82,242
104,087 128,503
Max. Flowrate
@33ft/s
155,489 185,045 234,197 289,133 328,969 416,351 514,014 621,957 740,181 868,684
T04.EPS
Size
0.1
0.2
0.4
0.5
1.5
2.5
10 12 14 16 20 24 28 32 36 40
Size
44 48 54 60 64 72 80 88 96
104
Min. Flowrate
@0.33ft/s
1
2
3 4 5 6 8
Min. Flowrate
@1.0ft/s
SI Units (Size : mm, Flowrate : m
Min. Flowrate
@0.1m/s
Size
2.5
0.0018
5
0.0071
10
0.0283
15
0.0637
25
0.1768
40
0.4524
50
0.7069
65
1.1946
80
1.8096
100
2.8275 125 150 200 250 300 350 400 500 600 700 800 900
1000
Size
1100 1200 1350 1500 1600 1800 2000 2200 2400 2600
* Measurable flow velocity is from 0m/s(ft/s).
4.418
6.362
11.310
17.672
25.447
34.64
45.24
70.69
101.79
138.55
180.96
229.03
282.75
Min. Flowrate
@0.3m/s
1,026.4 1,221.5 1,545.9 1,908.6 2,171.5 2,748.3
3,393 4,106 4,886 5,735
Distance between Flow Tube and Converter:
Size 15 mm(0.5in.) to 400mm(16in.)
m(ft)
200(660)
Cable
length
100(330)
As shown in accuracy description
50(170)
0
520 µS/cm
Liquid conductivity
PFA, Size 2.5 to 10mm (0.1 to 0.4in.)
Cable
length
m(ft)
100(330)
50(170)
15(50)
3(10)
0
Add 0.5% to the accuracy shown in accuracy description.
As shown in accuracy description
20 50 200 µS/cm
Liquid conductivity
Ceramics, Size 2.5 to 10mm (0.1 to 0.4in.)
Cable
length
m(ft)
100(330)
50(170)
15(50)
3(10)
0
Add 0.5% to the accuracy shown in accuracy description.
As shown in accuracy description
203050 200 µS/cm
Liquid conductivity
F01 .EPS
* In case of size 500mm(20in.)or larger, the maximum
cable length is 200m(660ft) and the minimum conductivity is 50␮S/cm.
Fluid Temperature and Pressure:
PFA Lining
Pressure
MPa(kg/cm2){psi}
2(20){285}
1.5(15){214} 1(10){142}
-0.1(-1){14.2}
Ceramics Lining
Pressure
MPa(kg/cm2){psi}
4
(40){570}
2(20){285}
-0.1(-1){14.2}
Polyurethane Lining
Pressure
MPa(kg/cm2){psi}
2(20){285} 1(10){142}
0.75(7.5){107}
-0.1(-1){14.2}
-10
(14)0(32)40(104)80(175)
-10 (14)0(32)
-10
(14)0(32)40(104)
Temperature
General/Sanitary
Explosion Proof
120
100
(248)
(210)
2.5 to 50 mm (General purpose) 80 to 200 mm (General purpose)
2.5 to 50 mm (Explosion proof) 80 to 200 mm (Explosion proof)
120
80
100
(248)
(175)
(210)
25 to 400 mm 500 to 1000 mm 1100 to 2600 mm
deg
C (
deg
F)
160
(320)
180
(356)
F02.EPS
5-3
IM 1E6D0-01E
5. OUTLINE
Reasonable Figures for Thermal Shock of Ceramic Lining:
Size 2.5 to 25 mm(0.1 to 1 in.)
T°C(°F) 120(248)
100(212)
70(158)
60(140)
1(3) 5(15) 10(30)
Size 40 and 50 mm(1.5 and 2 in.)
T°C(°F)
100(212)
90(194)
50(122)
30(86)
1(3) 5(15) 10(30)
Size 80 to 200 mm(3 to 8 in.)
T°C(°F)
70(158)
50(122)
30(86)
1(3) 5(15) 10(30)
Flow Velocity m/s(ft/s)
Flow Velocity m/s(ft/s)
Flow Velocity m/s(ft/s)
Increase
Decrease
Increase
Decrease
Increase
Decrease
F03.EPS
ACCESSORIES
Centering device (Wafer type) 1set Hexagonal Wrench (JIS Flameproof type) 2sets Hexagonal Wrench (Ex-proof type except JIS) 1set
TERMINAL CONNECTION
Terminal symbols Description
A B
C EX1 EX2
Flow signal output
Exciting current input
Protective grounding (outside of the terminal box)
T06.EPS
GASKET
Please use compressed non-asbestos fiber gasket, PTFE gasket or the gasket which has equal elasticity. In case of optional code/FRG, please use rubber gasket or others which has equal elasticity.
SIZING DATA
10.0
5.0
Flow velocity (m/s)
1.0
0.5
0.3
0.1
0.001
33
Flow velocity (ft/s)
10
5.0
2.0
1.0
0.01
SI Units
Size: mm
2.5
0.1
English Units
0.1
0.2
5
1
Flowrate (m /h)
Size: inch
0.4
1,350
2,000
1,600
25
15
10
10
3
1
0.5
1.5
65
40
2
80
50
100
3
4
2.5
100
5
200
250
150
125
1,000
6
8
12
10
500
700
400
10,000
20
800
900
600
1,000
1,200
1,100
1,500
100,000
60
40
24
28
54
32
48
44
36
64
350
300
16
14
2,400
2,200
2,600
1,800
72
04
88
80
96
1
0.33
0.01
0.1
1.0
10
Flowrate (GPM)
100
1,000
10,000
100,000
1,000,000
F04.EPS
* Measurable flow velocity is from 0 m/s.
5-4
IM 1E6D0-01E
MODEL AND SUFFIX CODE
General purpose/Explosion proof/Submersible Type AM100D, 200D
Application
N
Lining material
AC
CUA
C
A
C
Model Suffix code Description
AM102D AM105D AM110D AM115D AM202D AM204D AM205D AM206D AM208D AM210D AM212D AM215D AM220D
Use G
Lining
Process connection Note 3
Electrode material
Earth ring Earth electrode material
Electrical connection
Style code Optional specification
Note 1: Process connection for size 2.5 to 10mm(0.1 to 0.4in.), wafer type is equal to one for 15mm(0.5in.). Note 2: Select PN16 when requirement of PN10 for size 100mm(4in.)or less because of same mating dimensions.
Note 3: Flange type is available for size 15mm or larger, PFA or Polyurethane lining. Note 4: Select ANSI 1/2NPT female electrical connection(code A) in case of requirement of FM/CSA explosion proof type.
Note 5: Select JIS G1/2 female electrical connection (code J) and optional code /JF3 with /G12 in case of requirement Note 6: Platinum-iridium and Tantalum earth electrodes are not available with 65, 125mm and ceramics 150, 200mm.
. . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . .
W
. . . . . . . . . . . . . . . . . . .
N
. . . . . . . . . . . . . . . . . . .
C
. . . . . . . . . . . . . . . . .
-A
. . . . . . . . . . . . . . . . .
-U
. . . . . . . . . . . . . . . . .
-C
. . . . . . . . . . . . . .
K1
. . . . . . . . . . . . . .
K2
. . . . . . . . . . . . . .
B1
. . . . . . . . . . . . . .
B2
. . . . . . . . . . . . . .
E2
. . . . . . . . . . . . . .
H1
. . . . . . . . . . . . . .
J1
. . . . . . . . . . . . . .
J2
. . . . . . . . . . . . . .
A1
. . . . . . . . . . . . . .
A2
. . . . . . . . . . . . . .
D1
. . . . . . . . . . . . . .
D2
. . . . . . . . . . . . . .
G1
. . . . . . . . . . . . . .
U1
. . . . . . . . . . . . . .
U2
. . . . . . . . . . . . . .
U3
. . . . . . . . . . .
-L
. . . . . . . . . . .
-P
. . . . . . . . . . .
-E
. . . . . . . . . . .
-H
. . . . . . . . . . .
-T
. . . . . . . . . . .
-V
. . . . . . . . .
S
. . . . . . . . .
P
. . . . . . . . .
N
. . . . . . . . .
H
. . . . . . . . .
T
. . . . . . . . .
V
Provide 15mm process flanges for these flow tubes.
For CENELEC explosion proof type, select ANSI 1/2NPT (code A), DIN Pg13.5(code D) or ISO M201.5(code M) electrical connection.
of JIS Flameproof type.
Size 2.5 mm (0.1in.) Size 5 mm (0.2in.) Size 10 mm (0.4in.) Size 15 mm (0.5in.) Size 25 mm (1in.) Size 40 mm (1.5in.) Size 50 mm (2in.) Size 65 mm (2.5in.) Size 80 mm (3in.) Size 100 mm (4in.) Size 125 mm (5in.) Size 150 mm (6in.) Size 200 mm (8in.)
General purpose Submersible CENELEC, FM, CSA Ex.proof JIS Flameproof
Fluorocarbon PFA Polyurethane Ceramic
JIS 10K wafer JIS 20K wafer ANSI 150 wafer ANSI 300 wafer DIN PN10/16 wafer JIS F12 (JIS75M) wafer JIS 10K flange JIS 20K flange ANSI 150 flange ANSI 300 flange DIN PN10 flange DIN PN16 flange JIS F12 (JIS75M) flange Union joint (weld joint) Union joint (R1/4 or R3/8) Union joint (1/4NPT or 3/8NPT)
SUS316L Platinum-iridium Platinum-alumina cermet Hastelloy C 276 equivalent Tantalum Titanium
SUS316 Platinum-iridium electrode None Hastelloy C276 equivalent Tantalum Titanium
. . . . . .
J
JIS G1/2 (PF1/2)female
. . . . . .
A
ANSI 1/2NPT female
. . . . . .
D
DIN Pg13.5 female
. . . . . .
M
ISO M20 X 1.5 female
Style A
*A
Refer to optional specification code
G
ANAAAAAN ANAAAAAN ANAAAAAN ANAAAAAN AAAAAAAA AAAAAAAA AAAAAAAA ANNNNNNN AAAAAAAA AAAAAAAA ANNNNNNN AAAAAAAA AAAAAAAA
AAANNNNN NNNNNNNA NNNNNAAN NNNAANNN
ANNANANA NANNNNNN NNANANAN
AAAAAAAA AAAAAAAA AAAAAAAA AAAAAAAA AAAAAAAA AAAAAAAA AANANANA AANANANA AANANANA AANANANA AANANANA AANANANA AANANANA NNANANAN NNANANAN NNANANAN
AANANANA ANNANANN NNANANAN ANNANANN ANNANANN ANNANANN
AAAAAAAA ANAAAAAN NNANANAN ANAAAAAN ANAAAAAN ANAAAAAN
AAAAANNA AAANNAAN AAANNAAN AAANNAAN
W
A: Available N: Not Available
U
A
Note 1
N
Note 1
N
Note 1
N
Note 1
N A A A N A A N A A
N A
Note 4
N
Note 5
N
N A N
A A
Not available with 65/125mm
A A
Not available with 65/125mm
A A
Size 80mm or larger
A A
Not available
A
with 65/125mm
A A
Size 150/200mm only
A
Note 2
A
Size 80/100/150/200mm only
N
Ceramic lining,
N
size 2.5/5/10mm only
N
A N N
Not available
N
with 65/125mm
N N
A N
Note 6 Ceramic size 2.5/5/10mm only
N
Not available with 65/125mm
N
Note 6
N
Not available with 65/125mm
N A
N N N
Not available with 65, 125mm.
5. OUTLINE
T07.EPS
5-5
IM 1E6D0-01E
General purpose/Submersible Type AM300D
Application
Model
AM325D AM330D AM335D AM340D
Use G
W
Lining
Process
Electrode material
Earthring
Electrical connection
Style code
Optional specification
Suffix code
. . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . .
-A
. . . . . . . . . . . . . . . . .
-U
. . . . . . . . . . . . . .
J1
. . . . . . . . . . . . . .
J2
. . . . . . . . . . . . . .
A1
. . . . . . . . . . . . . .
A2
. . . . . . . . . . . . . .
D1
. . . . . . . . . . . . . .
D2
. . . . . . . . . . . . . .
G1
. . . . . . . . . . .
-L
. . . . . . . . . . .
-P
. . . . . . . . . . .
-H
. . . . . . . . . . .
-T
. . . . . . . . . . .
-V
. . . . . . . . .
S
. . . . . . . . .
H
. . . . . . . . .
V
. . . . . .
J
. . . . . .
A
. . . . . .
D
. . . . . .
M
-000
Description
Size 250 mm (10in.) Size 300 mm (12in.) Size 350 mm (14in.) Size 400 mm (16in.)
General purpose Submersible
Fluorocarbon PFA Polyurethane
JIS 10K flange JIS 20K flange ANSI 150 flange ANSI 300 flange DIN PN10 flange DIN PN16 flange JIS G3451 F12 flange
SUS316L Platinum-iridium Hastelloy C 276 equivalent Tantalum Titanium SUS316 Hastelloy C 276 equivalent Titanium JIS G1/2(PF1/2)female ANSI 1/2NPT female DIN Pg13.5 female ISO M20X1.5 female
Always-000 Style A
*A
Refer to optional specification table
/
GW
Lining material
AAA AAA AAA AAA
AAN NNA
ANN NAA
AAA AAA AAA AAA AAA AAA AAA
AAA ANN ANN ANN ANN AAA ANN ANN AAA AAA AAA AAA
•General purpose/Submersible Type AM400D/AM500D
Model Suffix code Description
AM405D AM406D AM407D AM408D AM409D AM410D AM511D AM512D AM513D AM515D AM516D AM518D AM520D AM522D AM524D AM526D
G
Use
W
Lining
Process connection
Electrode material
Earth ring material
Wiring port
Style code
Optional specification /
*1 Size 500 to 1000mm(20 to 40in.) *2 Size 500/600mm(20/24in.) *3 Size 500 to 1500mm(20 to 60in.) *4 Size 1600mm(64in.) or larger *5 Size 1100mm(44in.) or larger
U
J1 A1 G1 W1
*1 *2 *3 *4
L
S
J A
Size: 500 mm (20in.) Size: 600 mm (24in.) Size: 700 mm (28in.) Size: 800 mm (32in.) Size: 900 mm (36in.) Size: 1000 mm (40in.) Size: 1100 mm (44in.) Size: 1200 mm (48in.) Size: 1350 mm (54in.) Size: 1500 mm (60in.) Size: 1600 mm (64in.) Size: 1800 mm (72in.) Size: 2000 mm (80in.) Size: 2200 mm (88in.) Size: 2400 mm (96in.) Size: 2600 mm (104in.)
General purpose Submersible
Polyurethane
JIS 10K Flange ANSI Class 150 Flange JIS G3451 F12 Flange JIS 7.5K Flange
SUS316L SUS304(for AM400)
SS400 lined with SUS316
JIS G1/2(PF1/2) female
*1
ANSI 1/2NPT female
-000
Always -000
Style A
*A
*5
Style C
*C
Refer to optional specification table
A: Available N: Not Available
UUA
Only for size 250 or 300 mm(10 or 12in.) Only for size 250 or 300 mm(10 or 12in.) Only for size 250 or 300 mm(10 or 12in.)
(for AM500)
T09.EPS
5. OUTLINE
T08.EPS
5-6
IM 1E6D0-01E
Sanitary Type
5. OUTLINE
Model
AM202DH AM204DH AM205DH AM206DH AM208DH
AM210DH Lining Process connection
Electrode material
Earthring
Wiring port
Style code
Optional specification
Suffix code
. . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . .
-A
. . . . . . . . . . . . . .
C1
. . . . . . . . . . .
-L
. . . . . . . . .
N
. . . . . .
J
. . . . . .
A
. . . . . .
D
. . . . . .
M
*A
/
Description
Size 25 mm (1in.) Size 40 mm (1.5in.) Size 50 mm (2in.) Size 65 mm (2.5in.) Size 80 mm (3in.) Size 100 mm (4in.)
Fluorocarbon PFA IDF clamp SUS316L
None JIS G1/2(PF1/2)female ANSI 1/2NPT female DIN Pg13.5 female ISO M20X1.5 female
Style A Refer to optional specification code
T10.EPS
Optional Specifications
Item
Stainless steel tag plate
Waterproof Gland
Waterproof Gland with Union Joint
Gasket for PVC Piping DHC use (for size 100 to
400mm)
Epoxy Coating High Anti-corrosion
Coating Material Certificate
(Note 2)
Bolt & Nut Assembly (Note 3)
FM Approval CSA Certification (Note 4)
CENELEC Certification (KEMA Approval)(Note 4)
JIS Flameproof (Note 4)(Note 5)
Flameproof Packing Adapter for JIS Flameproof(Note 5)
Silicon Rubber Gasket for sanitary type GOST Certification
C-Tick mark
Mirror Finished Ceramics
Oil-prohibited Use Oil-prohibited Use with
Dehydrating T reatment Hydrostatics Test
Certificate Calibration Cretificate
Note1 No need to select because waterproof glands(union joint)are attached for submersible type as standard. Note2 In case of requirement of EN10204 3.1B for Material Certificate, contact Yokogawa office. Note3 It is available only for JIS 10K wafer, JIS 20K wafer or ANSI 150 wafer type, not available with 65, 125mm. Note4 It is available only for size 2.5 to 200mm(0.1 to 8in.). Note5 Select optional code /JF3 with /G12 in case of requirement of JIS Flameproof type.
Stainless steel (SUS304) tag plate is fixed with screws.
Waterproof glands are attached to all wiring ports. For JIS G1/2 only.
Waterproof glands (union joint) are attached to all wiring ports. For JIS G1/2 only.
Gasket are attached between earth ring and flow tube. For 200mm or smaller size. (except 65,125mm)
and Cooling use. Terminal box; urethane resin potting. Wired 30m signal cable at factory.
Coating is changed to epoxy coating. Coating is changed to three-layer coating (Urethane
coating on two-layer Epoxy coating) Reproduced material certificate for pipe, electrode,
earth ring, mini-flange and flange (depends on spec.). Carbon steel bolts/nuts and chloroprene gaskets
assembly for wafer type Carbon steel bolts/nuts and non-asbestos PTFE-
wrapped gaskets assembly for wafer type Stainless steel bolts/nuts and chloroprene gaskets
assembly for wafer type Stainless steel bolts/nuts and non-asbestos PTFE-
wrapped gaskets assembly for wafer type FM Explosion proof/Nonincendive, CSA Nonincendive For 200mm or smaller size.
CENELEC Explosion proof For 200mm or smaller size.
JIS Flameproof type For 200mm or smaller size.
Two Flameproof Packing Adapters are attached.
In case of fluid temp. over 120 degC(248 degF); 160 degC (320 degF) max. (Not available with 65mm)
Calibration Certificate for GOST (only for products produced at YMF)
AS/NZS2064 compliance Only for Australia or New Zealand
Mirror finishing on the inside of ceramic tube(Rmax.<= 1micro-meter) Degreased cleansing treatment
Degreased cleansing treatment; Packaging with desiccant
Test pressure depends on process connection (Test duration 10minutes) Test result is full in NOTE of QIC.
Level2:Declaration and Calibration Equipment List Level3:Declaration and Primary Standard List Level4:Declaration and YOKOGAWA Measuring
Instruments Control System
Specification
Condensation proof for District Heating
General AM***DG
A A
A
A A
A A
A A
A A
A
N
N
N N
N
A A
A A A A A A A
Ex-proof
AM***DC
A N
N
A N
A A
A A
A A
A
N
N
(Note 5)
(Note 5)
N
N N
A A A A A A A
Applicable Model
AM***DN
A N
N
A N
A A
A A
A A
A
A
A
N N
N
A N
A A A A A A A
A : Available N : Not available
Submersible
AM***DW
N N
Standard (Note 1)
A N
N N
N N
N N
N
N
N
N N
N
A A
N N N A A A A
Sanitary
AM***DH
Code
/SCT
A A
/ECG
/ECU
A
N
/FRG
N
/DHC
A
/EPF
/X2
N
N
/M01
N
/BCC
N
/BCF
N
/BSC
N
/BSF
N
/ND
N
/CE
N
/JF3
N
/G12
/SRG
A
/GOS
A
/CTK
A
/MRR
N
/K1
N
/K5
N N
/T01
A
/L2
A
/L3
A
/L4
T11.EPS
5-7
IM 1E6D0-01E
EXTERNAL DIMENSIONS
Ground Terminal
(M4)
H**
ø86(3.4)
48
(1.9)
L*
Shroud(for ex-proof)
36 (1.4)
H2**
H1
58
(2.3)
5. OUTLINE
Unit : mm (Approx. inch)
102
G
K
105
AM D
C-A
B
109
(4.3)
110 115
N
E
Type Size code Size Lining code Face-to-face Outer dia. Width Height Height
D
ø
W
Height Weight kg(lb)
Lining code A : PFA lining C : Ceramics pipe
4-ø5.8(0.2)
* The face-to-face length is longer by approx.22mm (0.89")
** The height is shorter by 3mm (0.11") for ex-proof type.
øD
W
H H1 H2
for earth ring P,T. The face-to-face length is longer by approx.2mm (0.08")for PFA lining with optional code/FRG.
G
K
115
AM D
C-C
B
N
E
General (G), Ex-proof(C,N)
102 105 110 115
2.5(0.1)
5(0.2) 10(0.4)
A
L
85(3.3)*
44(1.7) 72(2.8)
214(8.4)**
66(2.6)
128(5.0)**
2.4(5.3)
15(0.5)
A.C
SD1.eps
Ground Terminal
(M4)
H*
102
G
105
AM D
C-C
U
110
N
Process Connection
Size code
U1 U2 U3
Type Size code Size Lining code Process connection Face-to-face Width Height Height Height Weight kg(lb)
Lining code C : Ceramics pipe *The height is shorter by 3mm(0.12") for ex-proof type.
102
L W H
H1 H2
105 110
Weld joint
R1/4
1/4NPT
General (G), Ex-proof(C,N)
102
2.5(0.1)
U1
140(5.5)
105
5(0.2)
C U2, U3 130(5.1)U1140(5.5)
72(2.8)
202(8.0)*
60(2.4)
116(4.6)*
2.4(5.3)
R3/8
3/8NPT
U2, U3 130(5.1)
110
10(0.4)
U1
140(5.5)
SD2c.eps
ø86(3.4)
48
(1.9)
L
U2, U3 130(5.1)
øA
4
(0.16)
Size
2.5
(0.1)
5
(0.2)
10
(0.4)
36 (1.4)
H2*
H1
11.5(0.45)
A 22(0.87) 22(0.87) 22(0.87) 22(0.87) 25(0.98) 25(0.98)
Shroud (for ex-proof)
30(1.2)
B 8(0.31) 8(0.31) 8(0.31) 8(0.31)
10(0.39) 10(0.39)
C
18.5(0.73)
18.5(0.73)
18.5(0.73)
18.5(0.73)
22.5(0.89)
22.5(0.89)
58
(2.3)
NPT1/4
NPT1/4
NPT3/8
øB
D
R1/4
R1/4
R3/8
109
(4.3)
W
4-ø5.8(0.2)
D
øD
10
(0.39)
C
øC
D
18.5(0.73)
18.5(0.73)
22.5(0.89)
SD2.eps
øC
øB
øA
(0.16)
2.5(0.1)
4
Size
5(0.2)
10(0.4)
A 22(0.87) 22(0.87) 25(0.98)
35
(1.38)
B 8(0.31) 8(0.31)
10(0.39)
14.3(0.56)
14.3(0.56)
17.8(0.70)
5-8
IM 1E6D0-01E
5. OUTLINE
Ground Terminal (M4)
H
202 204 205
AM D
206 208 210
Type Size code Size Lining code Face-to-face Outer dia Height Height Weight kg(lb)
Lining code A : PFA lining
* The face-to-face length is longer by approx.22mm(0.89")for earth ring P,T.
The face-to-face length is longer by approx.2mm(0.08")for PFA or Polyuretane lining with optional code/FRG.
** Submersible flowtubes are provided with 30m(98ft) of signal and excitation cables, potted terminal box, and waterproof gland fittings.
Please add 9.5kg(20.9lb) for submersible type.
o86(3.4)
48
(1.9)
L*
K
G
AB
W
-
UE
C
CH
N
204
202
25(1)
40(1.5)
A.U.C
93(3.7)*
68(2.7) 197(7.8) 111(4.4)
2.3(5.5)
106(4.2)*
86(3.4) 217(8.5) 131(5.2)
3.2(7.1)
L* D H
H1
U : Polyurethane rubber lining C : Ceramics pipe
Water-proof gland (for submersible type**)
36 (1.4)
H1
General(G), Submersible(W)
205
50(2)
120(4.7)*
120(4.7)
99(3.9)
117(4.6)
230(9.1)
248(9.8)
144(5.7)
162(6.4)
4.2(9.3)
5.2(11.5)
206
65(2.5)
Shroud (for ex-proof)
208
210
80(3)
100(4)
A.U C A.C AA C
160(6.3)*
180(7.1)*
129(5.1)
155(6.1)
270(10.6)
184(7.2)
7.3(16.1)
296(11.7)
210(8.3)
10.2(22.5)
260(10.2)
208 80(3)
160(6.3)* 129(5.1)
174(6.9)
6.9(15.2)
109(4.3)
210
100(4)
180(7.1)*
155(6.1)
296(11.7)
210(8.3) 10(22.1)
oD
202 25(1)
93(3.7)*
68(2.7) 195(7.7) 109(4.3)
2.3(5.5)
EX-proof(C,N)
204
40(1.5)
106(4.2)*
86(3.4) 214(8.4) 128(5.0)
3.2(7.1)
205
50(2)
120(4.7)*
99(3.9) 228(9.0) 142(5.6)
4.2(9.3)
208 80(3)
160(6.3)*
129(5.1)
268(10.6)
182(7.2)
7.3(16.1)
210
100(4)
180(7.1)*
155(6.1)
296(11.7)
208(8.2)
10.2(22.5)
208 80(3)
160(6.3)*
129(5.1)
258(10.2)
172(6.8)
6.9(15.2)
210
100(4)
180(7.1)* 155(6.1)
294(11.6)
208(8.2) 10(22.1)
Ground Terminal (M4)
36 (1.4)
H1
212
G
215
AM
D
W
220
N
C Type Size code Size Lining code Face-to-face Outer dia. Height Height Width Weight kg(lb)**
Lining code A : PFA lining U : Polyurethane rubber lining
36 (1.4)
H1
-
AB
UE
K
H
L D
H H1 W
ø86(3.4)
15.7(34.6)
48
(1.9)
o86(3.4)
48
(1.9)
L*
General(G), Submersible(W)
215
212
150(6)
125(5)
A
230(9.1)*
230(9.1)
200(7.9)
175(6.9)
339(13.3)
313(12.3)
253(9.9)
227(8.9)
256(10.1)
230(9.1)
17.9(39.4)
Water-proof gland (for submersible type**)
H
220
200(8)
150(6)
A, U
300(11.8)*
230(9.1)*
250(9.8)
200(7.9)
389(15.3)
336(13.2)
303(11.9)
250(10.1)
307(12.1)
256(10.1)
28.4(62.6)
20.9(46.1)
Shroud(for ex-proof)
Ground Terminal (M4)
H
Shroud(for ex-proof)
oD
Ex-proof(C, N)
215
220
200(8)
300(11.8)*
250(9.8) 386(15.2) 300(11.8) 307(12.1)
33.4(73.6)
109(4.3)
109(4.3)
W
* The face-to-face length is longer by approx.30mm(1.2")for earth ring P,T. The face-to-face length is longer by approx.2mm(0.08")for optional code/FRG. **Submersible flowtubes are provided with 30m (98ft) of signal and excitation calbles, potted terminal box, and waterproof gland fittings. Please add 9.5kg(20.9lb) for submersible type.
SD4.eps
K
215
G
B
-
DCAM
220
N
E
C
Type Size code Size
øD
Lining code Face-to-face Outer dia Height Height Weight kg(lb)
Lining code C : Ceramics pipe
H
General(G) Ex-proof(C, N)
215
220
200(8)
302(11.9) 264(10.4)
402.5(15.8)
316.5(12.5)
33.6(74.1)
L
øD
H
H1
150(6)
232(9.2) 214(8.5)
352.5(13.9)
266.5(10.5)
21.6(47.7)
C
350(13.8) 264(10.4)
24.6(54.2)
215
150(6)
232(9.1) 214(8.4)
220
200(8)
302(11.9) 264(10.4) 400(15.7) 314(12.4)
38.6(85.1)
SD7.eps
L
5-9
IM 1E6D0-01E
5. OUTLINE
Shroud (for ex-proof)
t*
214**
(8.43)
Ground Terminal
(M4)
36(1.42)
128**
(5.04)
66
(2.6)
ø86(3.4)
48(1.9)
L*=200(7.9)
58
(2.3)
Shroud (for ex-proof)
Water-proof gland (for submersible type***)
H**
204
40(1.5)
A, U
J1
J2
A1
244(9.6)**
237(9.3)**
158(6.2)**
151(5.9)**
87.5(3.4)**
140(5.5)
127(5.0)
23(0.9)
25(1)
25(1)
~30(1.2)*
~31(1.2)*
105(4.13)
99(3.90)
45
45
45
19(0.75)
16(0.63)
4
4
4
7.7(16.9)
7.0(15.4)
Water-proof gland (for submersible type***)
H H1 H2 øD
t
øC
␪⬚
øh
N
t*
J1 226(8.9)** 140(5.5)**
125(4.9)
21(0.8) ~26(1)*
90(3.54)
45 19(0.75)
4
5.2(11.4)
ø86(3.4)
48
(1.9)
*L=200(7.9)
J2
226(8.9)**
217(8.5)**
140(5.5)**
131(5.2)**
77(3.0)**
125(4.9)
108(4.3)
23(0.9)
~28(1.1)*
~28(1.1)*
79(3.11)
90(3.54)
45
16(0.63)
19(0.75)
4
5.5(12.1)
202 25(1) A, U
A1
21(0.8)
45
4
4.6(10.1)
ø86(3.4)
48
(1.9)
36 (1.4)
(H2)**
H1**
General(G), Submersible(W), Ex-proof(C,N)
A2
D2
225(8.9)**
221(8.7)**
244(9.6)**
139(5.5)**
135(5.3)**
158(6.2)**
124(4.9)
115(4.5)
140(5.5)
25(1)
22(0.9)
~31(1.2)*
~28(1.1)*
~28(1.1)* 105(4.13)
89(3.50)
85(3.35)
45
45
19(0.75)
19(0.75)
14(0.55)
4
4
5.6(12.3)
5.1(11.2)
7.4(16.3)
Ground Terminal (M4)
G
J
202
W
A
-
A
204
AM D
C
U
D
205
N
Type
Size code
Size
Lining code
Process Connection
Height Height Height
Outer dia.
Thickness
Pitch circle dia.
Bolt hole pitch
Hole dia.
Number of holes
Weight kg(lb)***
Process connection : J1 ; JIS10K J2 ; JIS20K A1 ; ANSI 150 A2 ; ANSI 300 D2 ; DIN PN16
Lining code A : PFA Lining
U : Polyurethane lining
Ground Terminal (M4)
109(4.3)
A2 251(9.9)** 165(6.5)**
155(6.1)
28(1.1)
~34(1.3)* 114(4.49)
45 22(0.87)
4
9.2(20.2)
72(2.8)
D2 249(9.8)** 163(6.4)**
150(5.9)
22(0.9)
~28(1.1)* 110(4.33)
45
18(0.71)
4
8.0(18.5)
Shroud (for ex-proof)
G
J
C
115 -
A
A
N
D
General(G) Ex-proof(C,N)
115
15(0.5)
A
A1
J2
øD
øC
øh
t
J1
95(3.7)
19(0.7)~
24(0.9)*
70(2.8) 15(0.6)
4.0(8.8)
95(3.7) 21(0.8)~ 26(1.0)*
70(2.8)
15(0.6)
4.2(9.3)
89(3.5)
18(0.7)~
25(1.0)*
61(2.4) 16(0.6)
3.8(8.4)
95(3.7) 21(0.8)~ 28(1.1)*
67(2.6)
16(0.6)
4.2(9.3)
AM D
Type Size code Size Lining code Process Connection Outer dia.
h
4
D
Thickness
ø
Pitch circle dia.
øC
Hole dia. Weight kg(lb)
Process connection : J1 ; JIS10K J2 ; JIS20K A1 ; ANSI 150 A2 ; ANSI 300 D2 ; DIN PN16 Lining code A : PFA lining
)
.23
.8(0
5
* The face-to-face length is longer by approx.22mm (0.89") for earth ring P,T.
4
The thickness(t) is longer by approx.11mm (0.43")for earth ring P,T. The face-to-face length is longer by approx.2mm (0.08") for optional code/FRG. The thickness(t) is longer by approx.1mm (0.04") for optional code/FRG. ** The height is shorter by 3mm (0.12") for ex-proof type.
109(4.3)
h
N
øD
ø
C
␪⬚
* The face-to-face length is longer
by approx.22mm (0.89") for earth ring P,T.
The thickness(t) is longer
by approx.11mm (0.43") for earth ring P,T.
The face-to-face length is longer
D2
by approx.2mm (0.08") for optional code/FRG.
The thickness(t) is longer by approx.1mm (0.04")
263(10.4)**
for optional code/FRG.
177(7.0)**
** The height is shorter by 2.5mm (0.1") for ex-proof type. *** Submersible meters are provided with 30m (98ft) of
165(6.5)
signal and excitation cable, potted terminal box, and
24(0.9)
waterproof fitlings. Please add 9.5kg (20.9lbs) in
~30(1.2)*
weight for submersible type.
125(4.92)
45
18(0.71)
4
10.2(22.5)
SD12.eps
J1 258(10.2)** 172(6.8)**
155(6.1)
23(0.9)
~29(1.1)* 120(4.72)
45 19(0.75)
4
9.0(19.8)
J2 258(10.2)** 172(6.8)**
94.5(3.7)**
155(6.1)
25(1)
~31(1.2)* 120(4.72)
22.5
19(0.75)
8
9.1(20)
205
50(2)
A, U
A1
257(10.1)**
171(6.7)**
152(6.0)
26(1)
~33(1.3)* 121(4.76)
45
19(0.75)
4
9.4(20.7)
A2
263(10.4)**
177(7.0)**
165(6.5)
30(1.2)
~37(1.5)* 127(5.00)
22.5
19(0.75)
8
10.8(23.8)
109(4.3)
D2
A2
95(3.7)
20(0.8)~
26(1.0)*
65(2.6) 14(0.6)
4.2(9.3)
SD11.eps
(H2)**
36 (1.4)
H**
t*
H1**
G
J
W
A
A
208
-
AM D
C
U
D
210
N
G
Type
Size code
Size
Lining code
Process Connection
Height Height Height
Outer dia.
Thickness
Pitch circle dia.
Bolt hole pitch
Hole dia.
Number of holes
Face-to-face
Weight kg(lb)***
Process connection : J1 ; JIS10K J2 ; JIS20K A1 ; ANSI 150 A2 ; ANSI 300 D2 ; DIN PN16 G1 ; JIS F12
Lining code A : PFA Lining
J1
H
288(11.3)**
H1
202(8.0)** H2 øD
185(7.2)
25(1)
t
~31(1.2)*
øC
150(5.1)
␪⬚
22.5
øh
19(0.7)
8
N L
13(28.6)
U : Polyurethane lining
J2
296(11.7)**
210(8.3)**
200(7.9)
29(1.1)
~35(1.4)*
160(6.3)
22.5
23(0.8)
8
15(33.0)
*L
General(G), Submersible(W), Ex-proof(C,N)
208 80(3) A, U
A1
A2
D2
8
296(11.7)**
210(8.3)**
200(7.9)
26(1)
~32(1.3)* 160(6.3)
22.5
18(0.7)
8
15(33.1)
G1
301(11.9)**
215(8.5)**
211(8.3)
25(1)
~32(1.3)* 168(6.6)
45
19(0.7)
4
15.5(34.2)
291(11.4)*
205(8.1)*
109.5(4.3)**
191(7.5)
31(1.2)
~38(1.5)* 152(6.0)
45
19(0.7)
4 200(7.9)*
15.3(33.7)
300(11.8)**
214(8.4)*
210(8.3)
36(1.4)
~43(1.7)* 168(6.6)
22.5
22(0.8)
18.3(40.3)
J1
324(12.8)**
238(9.4)**
210(8.3)
25(1)
~31(1.2)* 175(6.9)
22.5
19(0.7)
8
21.0(46.3)
J2 331(13.0)** 245(9.6)**
225(8.9)
31(1.2)
~37(1.5)* 185(7.3)
22.5
23(0.9)
8
24.2(53.4)
210
100(4)
A, U
A1
333(13.1)*
247(9.7)*
132.5(5.2)**
229(9.1)
31(1.2)
~38(1.5)* 191(7.5)
22.5
19(0.7)
8 250(9.8)*
25.0(55.1)
346(13.6)**
260(10.2)*
254(10)
~46(1.8)*
200(7.9)
32.4(71.4)
A2
39(1.5)
22.5
22(0.9)
8
D2
329(13.0)**
243(9.6)**
220(8.7)
26(1)
~32(1.3)*
180(7.1)
22.5
18(0.7)
8
22.7(50.1)
-øh
N
D
ø
ø
C
␪⬚
* The face-to-face length is longer
by approx.22mm (0.89") for earth ring P,T.
The thickness(t) is longer by approx.11mm (0.43")
for earth ring P,T.
The face-to-face length is longer
G1
by approx.2mm (0.08") for optional code/FRG.
The thickness(t) is longer by approx.1mm (0.04")
338(13.3)**
for optional code/FRG.
252(9.9)**
** The height is shorter by 2.5mm (0.1") for ex-proof type. *** Submersible meters are provided with 30m (98ft) of
238(9.4)
signal and excitation cable, potted terminal box, and
25(1)
waterproof fitlings. Please add 9.5kg (20.9lbs) in weight
~32(1.3)*
for submersible type.
195(7.7)
19
22.5(0.8) 4
24.1(53.1)
SD13.eps
5-10
IM 1E6D0-01E
5. OUTLINE
ø86(3.4)
48(1.9)
36
(1.4)
Ground Terminal (M4)
H2**
H3
J
G
215
A
A
-
W
AM D
220
D
U
C
G
N
Type General(G), Submersible(W), Ex-proof(C, N)
Size code 215
Size
Lining code Process connection Face-to-face
Outer dia.
Height
Height
Pitch circle dia. Bolt hole pitch
Number of holes
Hole dia.
Thickness(A)
Thickness(U) Weight(General) kg(lb) Weight(Submersible) kg(lb) Weight(Ex-proof) kg(lb)
J1 G1 A1 J2 A2 D1 D2 J1 G1 A1 J2 A2 D1 D2
L
280(11)
øD
387(15.2)*
382(15)*
H
317(12.5)
H1 H2
143(5.6)
H3
240(9.4)
øC
22.5
␪⬚
8
N
23(0.9)
øh
30(1.2)*
t
31(1.2)*
t
29(63.9)
40.5(89.3)
38.5(84.9) 32(70.6)
290(11.4)
327(12.9)
148(5.8) 247(9.7)
19(0.7) 30(1.2)* 31(1.2)* 31(68.3)
34(75.0)
150(6) 200(8)
270(10.6)* 340(13.4)*
318(12.5)
305(12)
30 6
279(11.0)
381(15.0)*
316(12.4)
143(5.6) 241(9.5)
22.5
23(0.9)
33.4(1.3)*
34.4(1.4)* 31(68.3)
40.5(89.3) 34(75.0)
8
394(15.5)*
342(13.4)
152.5(6.0) 156(6.1)
260(10.2)
15 12
25(1) 36(1.4)* 37(1.5)* 37(81.6)
46.5(102.5) 40(88.2)
401(15.8)* 354(13.9)
162(6.4)
270(10.6)
22(0.9)
44.5(1.8)*
45.5(1.8)* 48(105.8)
57.5(126.8) 51(112.5)
15
12
285(11.2)
384(15.1)*
322(12.7)
146(5.7) 240(9.4)
22.5 8
22(0.9) 30(1.2)* 31(1.2)* 30(66.1)
39.5(87.1) 33(72.8)
L*
285(11.2)
384(15.1)*
322(12.7)
146(5.7) 240(9.4)
22.5 8
22(0.9) 30(1.2)* 31(1.2)* 31(68.3)
40.5(89.3) 34(75.0)
A, U
330(13) 432(17.0)* 367(14.4)
168(6.6) 290(11.4)
12 23(0.9) 30(1.2)* 31(1.2)* 41(90.2)
50.5(111.4) 46(101.4)
15
t*
342(13.5)
438(17.2)*
379(14.9)
174(6.9)
299(11.8)
22.5 8
19(0.9) 32(1.3)* 33(1.3)*
46(101.2)
55.5(122.4) 51(112.5)
Shroud(for ex-proof)
Water proof gland (for submersible type***)
H**
H1
220
343(13.5)
350(13.8)
177.5(7.0)
8
442(17.4)* 387(15.2)
178(7.0) 305(12)
15
12 25(1.0) 38(1.5)* 39(1.5)*
52(114.4)
61.5(135.6) 57(125.7)
381(15.0) 457(18.0)* 418(16.4)
194(7.6)
330(10.6)
12
25(1.0)
49.1(1.9)*
50.1(2.0)* 73(160.6)
82.5(181.9) 78(172.0)
438(17.3)*
379(14.9)
175(6.9)
298(11.7)
22.5
23(0.9)
36.4(1.4)*
37.4(1.5)* 49(107.8)
58.5(129.0) 54(119.1)
15
340(13.4)
437(17.2)*
377(14.8)
173(6.8)
295(11.6)
22.5 8
22(0.9) 32(1.3)* 33(1.3)* 45(99.2)
54.5(120.2) 50(110.3)
109(4.3)
N-øh
øD
øC
␪⬚
* The face-to-face length is longer by approx.28mm (1.1") for earth ring P,T. The thickness(t) is longer by approx.14mm (0.55") for earth ring P,T. The face-to-face length is longer by approx.2mm (0.08") for optional code/FRG. The thickness(t) is longer by approx.1mm (0.04") for optional code/FRG. ** The height is shorter by 2.5mm (0.1") for ex-proof type. *** Submersible meters are provided with 30m (98ft) of signal and excitation cable, potted terminal box, and waterproof gland fittings.
340(13.4)
437(17.2)*
377(14.8)
173(6.8)
295(11.6)
15
12
22(0.9) 32(1.3)* 33(1.3)*
Process connection : J1 ; JIS10K J2 ; JIS20K A1 ; ANSI 150 A2 ; ANSI 300
46(101.2)
Lining code A : PFA Lining
55.5(122.4) 51(112.5)
SD14.eps
D1 ; DIN PN10 D2 ; DIN PN16 G ; JIS F12
U : Polyurethane lining
JIS Flameproof Packing Adapter /G12
18(0.71)
F
G
*Packing (Choose from the table below depend on cable outside diameter)
Dimension
T1 T2 C D
G 1/2 G 1/2
(1.38)
35
L
39
(1.54)
T2
T1
16.5(0.65)
Cable outer diameter
L
8.0 to 10.0 (0.31 to 0.39)
94.5
(3.72)
10.0 to 12.0 (0.39 to 0.47)
Adapter body(M. Screw) O-Ring Packing case Hexagon socket set screw
Packing *
Hexagon socket set screw
O-Ring
O-Ring Washer Union nut Packing gland
Clamp ring Clamp nut O-Ring B.coupling
Cable(user's scope)
Packing diameter
F
10.0(0.39)12.0(0.47)
G 20.0 (0.79)
Unit : mm (Approx. inch)
C
Identification
mark
16 8-10 16 10-12
D
Weight
kg
(lb)
0.26
(0.57)
5-11
IM 1E6D0-01E
5. OUTLINE
ø86
Eye bolt
(3.4)
48
(1.9)
50 (2.0)
H
2
L
325
-
G
J
A
330
AM D
W
G
U
335 340
Type
Size code
Size
Lining code
Face-to-face
Eye bolt hole dia.
Height
Outer dia.
JIS 10K
JIS 20K
JIS F12
Lining code A : PFA lining U : Polyuretane lining ** Submersible meters are provided with 30m (98ft) of signal and excitation cable, potted terminal box, and waterproof fitlings. Please add 9.5kg (20.9lbs) in weight for submersible type.
Pitch circle dia.
Number of holes
Bolt hole pitch
Hole dia. Thickness(A) Thickness(U)
Weight kg(lb)**
Height
Outer dia.
Pitch circle dia.
Number of holes
Bolt hole pitch
Hole dia. Thickness(A) Thickness(U)
Weight kg(lb)**
Height
Outer dia.
Pitch circle dia.
Number of holes
Bolt hole pitch
Hole dia. Thickness(A) Thickness(U)
Weight kg(lb)**
øD øC
øD øC
øD øC
L e
H H1 H2
N
␪⬚
øh
t t
H H1 H2
N
␪⬚
øh
t t
H H1 H2
N
␪⬚
øh
t t
General(G), Submersible(W)
325
330
250
300
500(19.7)
430(16.9) 497(19.6)
454(17.9) 400(15.8)
355(14.0)
64(141.1) 512(20.2) 484(19.1)
430(16.9) 380(15.0)
67(147.7) 502(19.8) 464(18.3)
410(16.1) 360(14.2)
64(141.1)
30(1.2)
203(7.9)
12
15 25(1.0) 32(1.3) 33(1.3)
218(8.6)
12
15 27(1.1) 42(1.7) 43(1.7)
208(8.2)
8
22.5 23(0.9) 32(1.3) 33(1.3)
30(1.2) 544(21.4) 499(19.7)
226(9.0) 445(17.5) 400(15.8)
11.25 25(1.0) 34(1.3) 35(1.4)
81(178.6) 561(22.1) 534(21.0)
243(9.6) 480(18.9) 430(16.9)
11.25 27(1.1) 44(1.7) 45(1.8)
85(187.4) 553(21.8) 518(20.4)
235(9.3) 464(18.3) 414(16.3)
23(0.9) 34(1.3) 35(1.4)
81(178.6)
335 350
A , U
16
16
10 18
550(21.7)
35(1.4) 587(23.1) 553(21.8)
248(9.8) 490(19.3) 445(17.5)
16
11.25 25(1.0) 36(1.4) 37(1.4)
94(207.2)
– – – – – – – – – – –
607(23.9) 593(23.4) 268(10.6) 530(20.9) 472(18.6)
10
18 25(1.0) 36(1.4) 37(1.5)
94(207.2)
600(23.6)
35(1.4) 650(25.6) 623(24.5) 283(11.1) 560(22.0) 510(20.1)
27(1.1)
38(1.5)
39(1.5)
122(269.0)
661(26.0) 645(25.4) 294(11.6) 582(22.9) 524(20.6)
25(1.0)
36(1.4)
37(1.5)
122(269.0)
t
340 400
16
11.25
– – – – – – – – – – –
12 15
Ground T erminal (M4)
109(4.3)
Water-proof gland (for submersible type**)
N-øh
H
H
1
øD
␪⬚
325
-
G
A
A
330
AM D
W
D
U
335 340
ANSI
150
Number of holes
ANSI
300
DIN
PN10
DIN
PN16
Lining code A : PFA lining U : Polyuretane lining ** Submersible meters are provided with 30m (98ft) of signal and excitation cable, potted terminal box, and waterproof fitlings. Please add 9.5kg (20.9lbs) in weight for submersible type.
for AM330, AM335, AM340
Type
Size code
Size
Lining code
Face-to-face
Eye bolt hole dia.
Height
Outer dia.
Pitch circle dia.
Bolt hole pitch
Number of holes
Hole dia. Thickness(A) Thickness(U)
Weight kg(lb)**
Height
Outer dia.
Pitch circle dia.
Bolt hole pitch
Hole dia.
Thickness(A) Thickness(U)
Weight kg(lb)**
Height
Outer dia.
Pitch circle dia.
Number of holes
Bolt hole pitch
Hole dia. Thickness(A) Thickness(U)
Weight kg(lb)**
Height
Outer dia.
Pitch circle dia.
Number of holes
Bolt hole pitch
Hole dia. Thickness(A) Thickness(U)
Weight kg(lb)**
H1 H2 øD øC
øh
H1 H2 øD øC
H1 H2 øD øC
H1 H2 øD øC
H
␪⬚
N
H
N
␪⬚
øh
H
N
␪⬚
øh
H
N
␪⬚
øh
L e
t t
t t
t t
t t
General(G), Submersible(W)
325
330
250
300
500(19.7)
430(16.9) 500(19.7)
461(18.1)
206(8.1) 406(16.0) 362(14.3)
70(154.3) 519(20.4) 499(19.7)
225(8.9) 445(17.5) 387(15.2)
75(165.4) 495(19.5) 449(17.7)
201(7.9) 395(15.6) 350(13.8)
64(141.1) 500(19.7) 459(18.1)
206(8.1) 405(15.9) 355(14.0)
65(143.3)
30(1.2)
15
12 26(1.0) 38(1.5) 39(1.5)
16
11.25 29(1.1) 56(2.3) 57(2.2)
12
15 22(0.9) 34(1.3) 35(1.4)
12
15
22(0.9) 34(1.3) 35(1.4)
30(1.2) 563(22.2) 537(21.1)
245(9.7) 483(19.0) 432(17.0)
26(1.0) 40(1.6) 41(1.6)
90(198.4)
582(22.9) 575(22.6) 264(10.4) 521(20.5) 451(17.8)
11.25
32(12.6)
59(2.3)
60(2.4)
98(216.1)
544(21.4) 499(19.7)
226(9.0) 445(17.5) 400(15.8)
22(0.9) 34(1.3)
35(1.4) 81(178.6) 551(21.7) 514(20.2)
233(9.2) 460(18.1) 410(16.1)
22(0.9) 36(1.4) 37(1.5)
82(180.8)
15 12
16
12 15
12 15
335 350
A , U
550(21.7)
35(1.4) 609(24.0) 597(23.5) 270(10.6) 533(21.0) 476(18.7)
29(1.1)
45(1.8)
46(1.8)
110(242.5)
595(23.4) 568(22.4) 256(10.0) 505(20.0) 460(18.1)
11.25 22(0.9) 36(1.4) 37(1.5)
94(207.2)
øC
15 12
– – – – – – – – – – –
16
– – – – – – – – – – –
340 400
600(23.6)
35(1.4) 668(26.3) 660(26.0) 302(11.9) 597(23.5) 540(21.3)
11.25 16
29(1.1) 47(1.9) 48(1.9)
145(319.7)
– – – – – – – – – – –
652(25.7) 628(24.7) 286(11.3) 565(22.2) 515(20.3)
16
11.25
26(1.0) 36(1.4) 37(1.5)
122(269.0)
– – – – – – – – – – –
SD16.eps
5-12
AAM511/512/513MMM
IM 1E6D0-01E
5. OUTLINE
AM405/406/407/408/409/410
L
48(1.9)
N-øh
70(2.8)
40(1.6)
H
2
ø
D
C
ø
H
H
1
125(4.9)
L
1
(1.4)
35
L
4-ø24(0.9)
2
35
(1.4)
Model Size Face-to-face Height Height Height Outer dia.
JIS10K
Pitch circle dia. Number of holes Hole dia. Thickness Weight kg(lb)* Height Height Outer dia.
ANSI
Pitch circle dia.
150
Number of holes Hole dia. Thickness Weight kg(lb)* Height Height Outer dia.
JIS
Pitch circle dia.
F12
Number of holes Hole dia. Thickness Weight kg(lb)* Support interval Mounting bolt interval
* : The weight is added 9.5kg(20.9lb) for submersible type.
Cables are wired with water-proof glands for submersible type at the factory.
AM405
AM406
AM407
AM408
AM409
500(20)
600(24)
700(28)
750(29.5)
800(31.5)
L
450(17.7)
500(19.7)
H
1
840(33.1)
939(37.0)
H
334(13.1)
383(15.1)
H
2
675(26.6)
795(31.3)
øD
620(24.4)
730(28.7)
øC
20 27(1.1) 30(1.2)
260(573) 840(33.1) 334(13.1) 700(27.6) 635(25.0)
20 32(1.3) 43(1.7)
360(794) 849(33.4) 343(13.5) 706(27.8) 639(25.2)
12 27(1.1) 30(1.2)
245(540) 350(13.8) 350(13.8)
24 33(1.3) 32(1.3)
400(882) 939(37.0) 383(15.1) 815(32.1) 750(29.5)
20 35(1.4) 48(1.9)
450(992) 951(37.4) 395(15.6) 810(31.9) 743(29.3)
16 27(1.1) 33(1.3)
300(662) 400(15.8) 400(15.8)
N
øh
t
H
H
2
øD øC
N
øh
t
H
H
2
øD øC
N
øh
t
L
1
L
2
900(35.4) 550(21.7)
1043(41.1)
437(17.2) 905(35.6) 840(33.1)
24 33(1.3) 34(1.4)
510(1125)
– – – – – – – –
1050(41.3)
444(17.5) 928(36.5) 854(33.6)
16
33 (1.3)
35(1.4)
450(992) 450(17.7) 500(19.7)
800(32)
1050(41.3)
600(23.6)
1148(45.2)
492(19.4)
1020(40.2)
950(37.4)
28 33(1.3) 36(1.4)
680(1500)
– – – – – – – –
1153(45.4)
497(19.6)
1034(40.7)
960(37.8)
20 33(1.3) 37(1.5)
620(1367) 550(21.7) 550(21.7)
900(36) 1200(47.2) 650(25.6) 1247(49.1) 541(21.3) 1120(44.1) 1050(41.3)
28 33(1.3) 38(1.5)
870(1919)
– – – – – – –
– 1259(49.6) 553(21.8) 1156(45.5) 1073(42.2)
20 33(1.3) 39(1.5)
770(1698) 700(27.6) 650(25.6)
AM410
1000(40)
1300(51.2)
700(27.6)
1346(53.0)
590(23.2) 1235(48.6) 1160(45.7)
28 39(1.5) 40(1.6)
1200(2646)
– – – – – – – –
1361(53.6)
605(23.8) 1262(49.7) 1179(46.4)
24 33(1.3) 41(1.6)
980(2161) 800(31.5) 700(27.6)
AM511/512/513
ShackleSB30
A
T
16- R
S S
L
1
L
1860(73.2)
N- h
Model Size Face-to-face Height Height
D
C
H
H1
T
P Q Y
Interval
Shackle
Size Width
Support
Length Interval
Interval
Mounting Bolt
Hole dia. Outer dia. Pitch circle dia. Bolt hole pitch Number of holes
JIS F12
Hole dia. Thickness Weight*kg(lb)
*Submersible flowtubes are provided with 30m (98ft) of signal and excitation cables, potted terminal box, and waterproof gland fittings. Please add 9.5kg(20.9lb) for submersible type.
N-øh
5.6°
AM515
L
H1
H A B S Y
L1
P Q T R D C
N
h
t
AM511D 1100(44) 1650(65)
950(37.4) 1698(66.9) 1325(52.2)
SB24
200(7.9) 1280(50.4) 1211(47.7)
720(28.3)
1100(43.3)
130(5.1)
19(0.75) 1366(53.8) 1283(50.5)
7.5 24
33(1.3) 78(3.4)
1650(3638)
AM512D
1200(48) 1800(70.9) 1000(39.4) 1803(71.0) 1470(57.9)
SB24
200(7.9) 1380(54.3) 1261(49.6)
780(30.7)
1200(47.2)
130(5.1)
19(0.75) 1470(57.9) 1387(54.6)
6.4 28
33(1.3) 80(3.5)
1910(4212)
AM513D
1350(54) 2025(79.7) 1100(43.3) 1978(77.9) 1640(64.6)
SB30
200(7.9) 1540(60.6) 1366(53.8)
880(34.6)
1350(53.2)
130(5.1)
19(0.75) 1642(64.7) 1552(61.1)
6.4 28
39(1.5) 82(3.6)
2420(5336)
16- ø19
(0.7)
200(7.9)
1490(58.7) *2250(88.6)
200(7.9)
D C N
h t
AM515
1500(60) 1800(70.9) 1710(67.3)
32 39(1.5) 85(3.3)
3150(6946)
Model Size Outer dia.
) .0
5 (8
8
5
1
)
2
.2
7 (4
0
0
2
1
C
D
t
Pitch circle dia. Number of holes Hole dia.
JIS F12
Thickness Weight*kg(lb)
*Submersible flowtubes are provided with 30m (98ft) signal and excitation cables, potted termianl box, and
980(38.6)
1500(59.1) 1700(66.9)
5-13
waterproof gland fittings. Please add 9.5kg(20.9lb) for submersible type.
IM 1E6D0-01E
5. OUTLINE
A1
16-R
T
S
L1 L
T
S
N- h
H
H1
A2
C
P Q
Y
AM516/518/520/522/524/526
Model Size Face-to-face Height Height
Interval1 Interval2
Eye nut
Size Width
Support
Length Interval
Interval
Mounting bolt
Hole dia. Outer dia. Pitch circle dia. Bolt hole pitch Number of holes Hole dia.
JIS G5527
7.5K Flange
Thickness Weigjt* kg(lb)
*Submersible flowtubes are provided with 30m (98ft) of signal and excitation cables, potted terminal box, and waterproof gland fittings. Please add 9.5kg(20.9lb) for submersible type.
1600(64)
2400(94.5)
L
1280(50.4)
H1
2971(117.0)
H
1834(72.2)
A1
1872(73.7)
A2
B S
1850(72.8)
Y
1698(66.9)
L1
1080(42.5)
P
1650(65.0)
Q T R
1915(75.4)
D
1820(71.7)
C
N h
t
3650(8048)
AM516
M48
250(9.8)
170(6.7) 22(0.87)
5
36 39(1.5) 88(3.5)
AM518
1800(72)
2610(102.8)
1350(53.2)
3143(123.7)
2022(79.6) 2078(81.8)
M48
250(9.8) 2000(78.7) 1864(73.4) 1180(46.5) 1800(70.9)
170(6.7)
22(0.87) 2115(83.3) 2020(79.5)
4.1 44
39(1.5) 90(3.5)
5270(11620)
AM520
2000(80)
2800(110.2)
1450(57.1)
3346(131.7)
2191(85.7) 2300(90.6)
M48
250(9.8) 2220(87.4) 2010(79.1) 1300(51.2) 2000(78.7)
170(6.7)
22(0.87) 2325(91.5) 2230(87.8)
3.75 48
46(1.8) 92(3.6)
6500(14333)
AM522
2200(88)
2970(117.0)
1550(61.0)
3553(139.9)
2325(86.3) 2520(99.2)
M48
300(11.8) 2420(95.3) 2172(85.5) 1430(56.3) 2200(86.6)
200(7.9) 22(0.87)
2550(100.4)
2440(96.1)
3.5
52 46(1.8) 95(3.7)
8400(18522)
AM524
2400(96)
3120(122.8)
1700(66.9)
3811(150.0)
2421(95.3)
2724(107.2)
M64
300(11.8)
2620(103.2)
2218(87.3) 1560(61.4) 2400(94.5)
200(7.9)
22(0.87) 2760(108.7) 2650(104.3)
3.2 56
46(1.8) 97(3.8)
10000(22050)
3300(129.9)
3923(154.4) 2550(100.4) 2946(116.0)
2820(111.0)
2600(102.4)
2960(116.5) 2850(112.2)
14500(31973)
D
AM526
2600(104)
1700(66.9)
M64
300(11.8)
2300(90.6) 1700(66.9)
200(7.9) 22(0.87)
3.2 56
52(2.1)
101(4.0)
o86(3.4)
48
(1.9)
oD
1
L
2
1.7
(0.07)
1.7
(0.07)
L
L
2
Ground Terminal
(M4)
36
(1.4)
H
2
109
(4.3)
H
H
1
oD
2
D
o
202 204 205
AM DH
206 208 210
5-14
SD21.EPS
IM 1E6D0-01E

6. HAZARDOUS DUTY TYPE INSTRUMENT

6. HAZARDOUS DUTY TYPE INSTRUMENT
In this section, further requirements and differences for explosion proof type instrument are described. For explosion proof type instrument, the description in this chapter is prior to other description in this Instruction Manual.
NOTE
The terminal box cover is locked by special screw. In case of opening the terminal box cover, please use the Hexagonal Wrench attached.
CAUTION
Be sure to lock the cover with the special screw using the Hexagonal Wrench attached after tightening the cover.

6.1 FM

(2) Installation
WARNING
• All wiring shall comply with national electrical code ANSI/NFPA 70 and local electrical code.
• In hazardous locations, wiring to be in conduit as shown in the figure.
(3) Operation
WARNING
• Open circuit before opening the covers and seal all conduits with in 18 inches in hazardous locations.
• Take care not to generate mechanical spark when access to the instrument and peripheral devices in hazardous locations.
(4) Maintenance and Repair
(1) Technical Data
• Explosionproof for Class I Division 1 Groups A, B, C & D. Dust-ignitionproof for Class II/III Division 1 Groups E, F & G. Intrinsically safe (electrode) for Class I Division 1 Groups A, B, C & D
Electrode circuit Vmax : 250V ac/dc Temp. Class. T6 Enclosure : NEMA 4X
•Nonincendive for Class I, Division 2, Groups A, B, C & D ; Suitable for Class II, Division 2, Groups F & G ; Class III, Division 1 and 2
Intrinsically safe (electrode) for Class I Division 1
Groups A, B, C & D
Electrode Circuit Vmax : 250V ac/dc Excitation Circuit : 130Vp 72/75Hz Temp. Code : T5 Enclosure : NEMA 4X
WARNING
The instrument modification or parts replacement by other than authorized representative of Yokogawa Electric Corporation is prohibited and will void the approval of Factory Mutual Re­search Corporation.
HAZARDOUS LOCATIONS
Magnetic Flow Converter
Conduit
18" (457 mm) Max.
Sealing Fitting
F0601.EPS
6-1
IM 1E6D0-01E
6. HAZARDOUS DUTY TYPE INSTRUMENT

6.2 CSA

(1) Technical Data
• Nonincendive for Class I, Division 2, Groups A, B, C & D ; Suitable for Class II, Division 2, Groups E, F and G ; Class III, Division 2
Intrinsically safe (electrode) for Class I Division 1
Groups A, B, C & D
Electrode Circuit Vmax: 250V ac/dc Excitation Circuit: 130Vp 72/75Hz, 11VAmax Temp. Code T5 T4 T3 Process Temp 85 120 150°C Enclosure: Type 4
(2) Installation
WARNING
All wiring shall comply with Canadian Electrical
Code Part I and Local Electrical Codes.
(3) Operation
WARNING

6.3 CENELEC (KEMA)

WARNING
Only trained persons use this instrument in industrial locations.
(1) Technical Data
• CENELEC (KEMA) : KEMA No. Ex-94. C. 8524 EEx dm[ia]IIC T6...T3 Electrode circuit Vmax : 250V ac/dc Excitation Circuit : 130Vp 72/75Hz Temp. Class T6 T5 T4 T3 Process Temp 70 85 120 150°C
(2) Installation
WARNING
•All wiring shall comply with local installation requirements and local electrical code.
• In hazadous locations, the cable entry devices shall be of a certified flameproof type, suitable for the conditions of use and correctly installed.
CAUTION : OPEN CIRCUIT BEFORE REMOV-
ING COVER. OUVRIR LE CIRCUIT AVANT
D’ENLEVER LE COUVERCLE. Take care not to generate mechanical spark when access to the instrument and peripheral devices in hazardous location.
(4) Maintenance and Repair
WARNING
The instrument modification or parts replacement by other than authorized representative of YOKOGAWA Electric Corporation or YOKOGAWA Corporation of AMERICA is prohibited and will void Canadian Standards Explosionproof Certification.
(3) Operation
WARNING
• Open circuit before opening the covers.
• Take care not to generate mechanical spark when access to the instrument and peripheral devices in hazardous locations.
(4) Maintenance and Repair
WARNING
The instrument modification or parts replacement by other than authorized representative of Yokogawa Electric Corporation is prohibited and will void the certification.
6-2
IM 1E6D0-01E

6.4 JIS

WARNING
Care should be taken to install, wiring, piping to keep safety. This instrument is restricted to maintenance and repair. Please read "INSTAL­LATION AND OPERATING PRECAUTIONS FOR JIS FLAMEPROOF EQUIPMENT" in the end of this manual.
(1) Technical Data
• Construction : Exde [ia] II CT4X : Terminal box ; Explosion proof
Flow Tube ; Increased Safety Signal Circuit ; Intrinsically Safety (ia) Um=250 V AC 50/60 Hz, 250 V DC, Uo=250 V*, Io=3.37 mA*, Po=0.211 W
* Uo and Io are rms value.
6. HAZARDOUS DUTY TYPE INSTRUMENT
:Ignition and Explosion Class of gas or
vapour ; II CT4X
• Ambient Temperature : –10 to 60°C
• Fluid Temperature : 120°C or less
• Current Signal Circuit Allowable Voltage :
250V AC/DC
• Grounding : 10 or less
WARNING
In case the ambient temperature exceeeds 50°C, use heat-resistant cables with maximum allow­able temperature of 70°C or above.
(2) Wiring
Flameproof packing adapter is attached to electrical connection.
WARNING
Please use G12 (option) flameproof packing adapter attached.
6-3
IM 1E6D0-01E
6. HAZARDOUS DUTY TYPE INSTRUMENT
18(0.71)
F
G
*Packing (Choose from the table below depend on cable outside diameter)
L
T2
Dimension
T1 T2 C D
G 1/2 G 1/2
35
(1.38)
39
(1.54)
Figure 6.4.1 Flame Proof Packing Adapter
T1
16.5(0.65)
L
94.5
(3.72)
O-Ring Packing case
Hexagon socket set screw
Packing *
Hexagon socket set screw
O-Ring
O-Ring Washer
Cable outer diameter
8.0 to 10.0 (0.31 to 0.39)
10.0 to 12.0 (0.39 to 0.47)
Adapter body(M. Screw)
Union nut Packing gland
Clamp ring
Clamp nut O-Ring
B.coupling Cable(user's scope)
Packing diameter
F
10.0(0.39)12.0(0.47)
20.0
(0.79)
Unit : mm (Approx. inch)
C
D
F0603.EPS
Identification
G
mark
16 8-10 16 10-12
Weight
kg
(lb)
0.26
(0.57)
T0601.EPS
Follow the procedure for flame proof packing adapter setting.
CAUTION
Before tightening, confirm cable length from terminals to flame proof packing adapter when setting. Once it is tightened, loosening and re-tightening may damage its sealing performance.
(a) Measure the bi-direction of the cable outside diameter to one decimal place in mm. (b) Calculate the average of these value, and choose the suitable packing from attached two. [Refer to the figure.
6.4.1] (c) Screw the M.screw into the electrical connection. (Ensure O-ring) (d) Set union nut, B.coupling, clamp nut, clamp ring, packing gland, packing case with inserted packing and washer
in that order around the cable, and tighten packing gland. And then tighten clamp nut. Confirm packing is
compressed and cable is fixed. (e) Insert packing gland into M.screw. (f) Connect each wire of cable to terminal. (g) Tighten and fix union nut. (h) Tighten and fix hexagon socket set screw of M.screw and union nut.
6-4
IM 1E6D0-01E

INSTALLATION AND OPERATING PRECAUTIONS FOR JIS FLAMEPROOF EQUIPMENT

INSTALLATION AND OPERATING PRECAUTIONS FOR JIS FLAMEPROOF EQUIPMENT
Apparatus Certified Under Technical Criteria (IEC-compatible Standards)
1.General
The following describes precautions on electrical apparatus of flameproof construction (hereinafter referred to as flameproof apparatus) in explosion-protected apparatus.
Following the Labour Safety and Health Laws of Japan, flameproof apparatus is subjected to type tests to meet either the technical criteria for explosionproof electrical machinery and equipment (standards notification no. 556 from the Japanese Ministry of Labour) (hereinafter referred to as technical criteria), in conformity with the IEC Standards, or the “Recommended Practice for Explosion-Protected Electrical Installations in General Industries,” published in
1979. These certified apparatus can be used in hazardous locations where explosive or inflammable gases or vapours may be present.
Certified apparatus includes a certification label and an equipment nameplate with the specifications necessary for explosion requirements as well as precautions on explosion protection. Please confirm these precautionary items and use them to meet specification requirements.
For electrical wiring and maintenance servicing, please refer to “Internal Wiring Rules” in the Electrical Installation Technical Standards as well as “USER’S GUIDELINES for Electrical Installations for Explosive Gas Atmospheres in General Industry,” published in 1994.
construction is of completely enclosed type and its enclosure shall endure explosive pressures in cases where explosive gases or vapours entering the enclosure cause explosion. In addition, the enclosure construction shall be such that flame caused by explosion does not ignite gases or vapours outside the enclosure.
In this manual, the word "flameproof" is applied to the flameproof equipment combined with the types of protection "e", "o", "i", and "d" as well as flameproof equipment.
3.Terminology
(1) Enclosure
An outer shell of an electrical apparatus, which encloses live parts and thus is needed to configure explosion-protected construction.
(2) Shroud
A component part which is so designed that the fastening of joint surfaces cannot be loosened unless a special tool is used.
(3) Enclosure internal volume
This is indicated by:— the total internal volume of the flameproof enclosure minus the volume of the internal components essential to equipment functions.
To meet flameproof requirements, equipment that can be termed “flameproof” must:
(1) Be certified by a Japanese public authority in accordance
with the Labour Safety and Health Laws of Japan and have a certification label in an appropriate location on its case, and
(2) Be used in compliance with the specifications marked on
its certification label, equipment nameplate and precautionary information furnished.
2.Electrical Apparatus of Flame-
proof Type of Explosion-Pro­tected Construction
Electrical apparatus which is of flameproof construction is subjected to a type test and certified by the Japanese Ministry of Labour aiming at preventing explosion caused by electrical apparatus in a factory or any location where inflammable gases or vapours may be present. The flameproof
(4) Path length of joint surface
On a joint surface, the length of the shortest path through which flame flows from the inside to outside of the flameproof enclosure. This definition cannot be applied to threaded joints.
(5) Gaps between joint surfaces
The physical distance between two mating surfaces, or differences in diameters if the mating surfaces are cylindrical.
Note: The permissible sizes of gaps between joint surfaces, the path
length of a joint surface and the number of joint threads are determined by such factors as the enclosure’s internal volume, joint and mating surface construction, and the explosion classification of the specified gases and vapours.
1
EX-B03E
INSTALLATION AND OPERATING PRECAUTIONS FOR JIS FLAMEPROOF EQUIPMENT
4.Installation of Flameproof Ap-
paratus
(1) Installation Area
Flameproof apparatus may be installed, in accordance with applicable gases, in a hazardous area in Zone 1 or 2, where the specified gases are present. Those apparatus shall not be installed in a hazardous area in Zone 0.
Note: Hazardous areas are classified in zones based upon the
frequency of the appearance and the duration of an explosive gas atmosphere as follows: Zone 0: An area in which an explosive gas atmosphere is
present continuously or is present for long periods.
Zone 1: An area in which an explosive gas atmosphere is
likely to occur in normal operation.
Zone 2: An area in which an explosive gas atmosphere is not
likely to occur in normal operation and if it does occur it will exist for a short period only.
(2) Environmental Conditions
The standard environmental condition for the installation of flameproof apparatus is limited to an ambient temperature range from –20°C to +40°C (for products certified under Technical Criteria). However, some field-mounted instruments may be certified at an ambient temperature up to +60°C as indicated on the instrument nameplates. If the flameproof apparatus are exposed to direct sunshine or radiant heat from plant facilities, appropriate thermal protection measures shall be taken.
5.External Wiring for Flameproof
Apparatus
Flameproof apparatus require cable wiring or flameproof metal conduits for their electrical connections. For cable wiring, cable glands (cable entry devices for flameproof type) to wiring connections shall be attached. For metal conduits, attach sealing fittings as close to wiring connections as possible and completely seal the apparatus. All non-live metal parts such as the enclosure shall be securely grounded. For details, see the “USER’S GUIDELINES for Electrical Installations for Explosive Gas Atmospheres in General Industry,” published in 1994.
(1) Cable Wiring
• For cable wiring, cable glands (cable entry devices for flameproof type) specified or supplied with the apparatus shall be directly attached to the wiring connections to complete sealing of the apparatus.
• Screws that connect cable glands to the apparatus are those for G-type parallel pipe threads (JIS B 0202) with no sealing property. To protect the apparatus from corrosive gases or moisture, apply nonhardening sealant such as liquid gaskets to those threads for waterproofing.
•Specific cables shall be used as recommended by the “USER’S GUIDELINES for Electrical Installations for Explosive Gas Atmospheres in General Industry,” published in 1994.
•In necessary, appropriate protective pipes (conduit or flexible pipes), ducts or trays shall be used for preventing the cable run (outside the cable glands) from damage.
• To prevent explosive atmosphere from being propagated form Zone 1 or 2 hazardous location to any different location or non-hazardous location through the protective pipe or duct, apply sealing of the protective pipes in the vicinity of individual boundaries, or fill the ducts with sand appropriately.
•When branch connections of cables, or cable connections with insulated cables inside the conduit pipes are made, a flameproof or increased-safety connection box shall be used. In this case, flameproof or increased-safety cable glands meeting the type of connection box must be used for cable connections to the box.
(2) Flameproof Metal Conduit Wiring
• For the flameproof metal conduit wiring or insulated wires shall be used as recommended by the USER’S GUIDELINES for Electrical Installations for Explosive Gas Atmospheres in General Industry, published in
1994.
• For conduit pipes, heavy-gauge steel conduits conforming to JIS C 8305 Standard shall be used.
•Flameproof sealing fittings shall be used in the vicinity of the wiring connections, and those fittings shall be filled with sealing compounds to complete sealing of the apparatus. In addition, to prevent explosive gases, moisture, or flame caused by explosion form being propagated through the conduit, always provide sealing fittings to complete sealing of the conduit in the following locations:
(a) In the boundaries between the hazardous and non-
hazardous locations.
(b) In the boundaries where there is a different
classification of hazardous location.
• For the connections of the apparatus with a conduit pipe or its associated accessories, G-type parallel pipe threads (JIS B 0202) shall be used to provide a minimum of five-thread engagement to complete tightness. In addition, since these parallel threads do not have sealing property, nonhardening sealant such as liquid gaskets shall thus be applied to those threads for ensuring waterproofness.
• If metal conduits need flexibility, use flameproof flexible fittings.
2
EX-B03E
INSTALLATION AND OPERATING PRECAUTIONS FOR JIS FLAMEPROOF EQUIPMENT
6.Maintenance of Flameproof Apparatus
To maintain the flameproof apparatus, do the following. (For details, see Chapter 10 “MAINTENANCE OF EXPLOSION­PROTECTED ELECTRICAL INSTALLATION” in the USER’S GUIDELINES for Electrical Installations for Explosive Gas Atmospheres in General Industry.)
(1) Maintenance servicing with the power on.
Flameproof apparatus shall not be maintenance-serviced with its power turned on. However, in cases where maintenance servicing is to be conducted with the power turned on, with the equipment cover removed, always use a gas detector to check that there is no explosive gas in that location. If it cannot be checked whether an explosive gas is present or not, maintenance servicing shall be limited to the following two items:
(a) Visual inspection
Visually inspect the flameproof apparatus, metal conduits, and cables for damage or corrosion, and other mechanical and structural defects.
(b) Zero and span adjustments
These adjustments should be made only to the extent that they can be conducted from the outside without opening the equipment cover. In doing this, great care must be taken not to cause mechanical sparks with tools.
(2) Repair
If the flameproof apparatus requires repair, turn off the power and transport it to a safety (non-hazardous) location. Observe the following points before attempting to repair the apparatus.
(a) Make only such electrical and mechanical repairs as will
restore the apparatus to its original condition. For the flameproof apparatus, the gaps and path lengths of joints and mating surfaces, and mechanical strength of enclosures are critical factors in explosion protection. Exercise great care not to damage the joints or shock the enclosure.
(b) If any damage occurs in threads, joints or mating
surfaces, inspection windows, connections between the transmitter and terminal box, shrouds or clamps, or external wiring connections which are essential in flameproofness, contact Yokogawa Electric Corporation.
requirements for flameproof apparatus (however, bear in mind that the apparatus must always be restored to its original condition). If you attempt to repair the flameproof apparatus, company-specified components shall be used.
(d) Before starting to service the apparatus, be sure to check
all parts necessary for retaining the requirements for flameproof apparatus. For this, check that all screws, bolts, nuts, and threaded connections have properly been tightened.
(3) Prohibition of specification changes and
modifications
Do not attempt to change specifications or make modifications involving addition of or changes in external wiring connections.
7.Selection of Cable Entry De­vices for Flameproof Type
IMPORTANT
The cable glands (cable entry devices for flameproof type) conforming to IEC Standards are certified in combination with the flameproof apparatus. So, Yokogawa-specified cable entry devices for flameproof type shall be used to meet this demand.
References:
(1) Type Certificate Guide for Explosion-Protected Con-
struction Electrical Machinery and Equipment (relating to Technical Standards Conforming to International Standards), issued by the Technical Institution of Industrial Safety, Japan
(2) USER’S GUIDELINES for Electrical Installations for
Explosive Gas Atmospheres in General Industry (1994), issued by the Japanese Ministry of Labour, the Research Institute of Industrial Safet
CAUTION
Do not attempt to re-process threaded connections or refinish joints or mating surfaces.
(c) Unless otherwise specified, the electrical circuitry and
internal mechanisms may be repaired by component replacement, as this will not directly affect the
3