Yokogawa ADMAG AXW User Manual

User’s Manual
AXW Magnetic Flowmeter Remote Flowtube
IM 01E25D11-01EN
IM 01E25D11-01EN
2nd Edition
AXW Magnetic Flowmeter Remote Flowtube
IM 01E25D11-01EN 2nd Edition
Contents
1. INTRODUCTION ........................................................................................ 1-1
1.1 Using the Magnetic Flowmeter Safely ............................................................ 1-2
1.2 Warranty .............................................................................................................1-3
1.3 Combination Remote Converters ...................................................................1-3
2. HANDLING PRECAUTIONS ..................................................................... 2-1
2.1 Checking Model and Specications ...............................................................2-1
2.2 Storage Precautions .........................................................................................2-1
2.3 Installation Location Precautions ...................................................................2-1
3. INSTALLATION ......................................................................................... 3-1
3.1 Piping Design Precautions ..............................................................................3-1
3.2 Handling Precautions .......................................................................................3-3
3.2.1 General Precautions ..........................................................................3-3
3.2.2 Flowmeter Piping ...............................................................................3-4
3.3 Mounting Procedures .......................................................................................3-4
4. WIRING ...................................................................................................... 4-1
4.1 Wiring the Remote Flowtube ...........................................................................4-1
4.1.1 Wiring Precautions ............................................................................. 4-1
4.1.2 Cables ................................................................................................ 4-2
4.1.3 Wiring Ports .......................................................................................4-3
4.1.4 Wiring Connections ............................................................................4-4
5. MAINTENANCE ......................................................................................... 5-1
5.1 Changing Direction of Electrical Connection ................................................5-1
5.2 Regular Inspection Items ................................................................................. 5-2
5.3 Excitation Coil and Insulation Resistance Check ........................................5-2
5.4 Troubleshooting ................................................................................................5-3
5.4.1 No Indication ......................................................................................5-3
5.4.2 Unstable Zero .................................................................................... 5-4
5.4.3 Disagreement Between Indication and Actual Flow .......................... 5-5
6. OUTLINE .................................................................................................... 6-1
n STANDARD SPECIFICATIONS ........................................................................ 6-1
n STANDARD PERFORMANCE .......................................................................... 6-1
n NORMAL OPERATING CONDITIONS .............................................................. 6-2
n MODEL AND SUFFIX CODE .............................................................................6-3
2nd Edition: Sep. 2013 (KP) All Rights Reserved, Copyright © 2012, Yokogawa Electric Corporation
IM 01E25D11-01EN
n OPTIONAL SPECIFICATIONS .........................................................................6-5
n OPTIONAL SPECIFICATIONS (continued) .....................................................6-6
n DIMENSIONAL DRAWINGS .............................................................................6-7
n SIZING DATA ....................................................................................................6-19
Revision Information ...............................................................................................i
ii
IM 01E25D11-01EN
<1. INTRODUCTION>

1. INTRODUCTION

1-1
This instrument has been adjusted at the factory before shipment. To ensure correct use of the instrument, please read this manual thoroughly and fully understand how to operate the instrument before operating it.
NOTE
The ADMAG AXW remote owtube is used in combination with the AXFA11 remote converter. This manual describes the hardware conguration of the ADMAG AXW remote owtube. For details of the AXFA11 remote converter, see IM 01E20C01-01E instruction manual. When setting the parameter “C30” in the remote converter, select “ADMAG AXF” for ADMAG AXW remote owtube.
n Regarding This User’s Manual
• This manual should be provided to the end user.
• Before use, read this manual thoroughly to comprehend its contents.
• The contents of this manual may be changed without prior notice.
• All rights are reserved. No part of this manual may be reproduced in any form without Yokogawa’s written permission.
• Yokogawa makes no warranty of any kind with regard to this material, including, but not limited to, implied warranties of merchantability and suitability for a particular purpose.
• All reasonable effort has been made to ensure the accuracy of the contents of this manual. However, if any errors or omissions are found, please inform Yokogawa.
• Yokogawa assumes no responsibilities for this product except as stated in the warranty.
• Please note that this user’s manual may not be revised for any specication changes, construction changes or operating part changes that are not considered to affect function or performance.
• If the customer or any third party is harmed by the use of this product, Yokogawa assumes no responsibility for any such harm owing to any defects in the product which were not predictable, or for any indirect damages.
n Safety and Modication Precautions
• The following general safety precautions must be observed during all phases of operation, service, and repair of this instrument. Failure to comply with these precautions or with specic WARNINGS given elsewhere in this manual violates safety standards of design, manufacture, and intended use of the instrument. Yokogawa assumes no liability for the customer’s failure to comply with these requirements. If this instrument is used in a manner not specied in this manual, the protection provided by this instrument may be impaired.
• Yokogawa will not be liable for malfunctions or damage resulting from any modication made to this instrument by the customer.
• The following safety symbol marks are used in this user’s manual and instrument.
WARNING
A WARNING sign denotes a hazard. It calls attention to procedure, practice, condition or the like, which, if not correctly performed or adhered to, could result in injury or death of personnel.
CAUTION
A CAUTION sign denotes a hazard. It calls attention to procedure, practice, condition or the like, which, if not correctly performed or adhered to, could result in damage to or destruction of part or all of the product.
IMPORTANT
An IMPORTANT sign denotes that attention is required to avoid damage to the instrument or system failure.
NOTE
A NOTE sign denotes information necessary for essential understanding of operation and features.
IM 01E25D11-01EN
<1. INTRODUCTION>
1-2
Protective grounding terminal
Functional grounding terminal
(This terminal should not be used as a protective grounding terminal.)
Alternating current
Direct current

1.1 Using the Magnetic Flowmeter Safely

(1) Installation
WARNING
• Installation of the magnetic owmeter must be performed by expert engineer or skilled personnel. No operator shall be permitted to perform procedures relating to installation.
• The magnetic owmeter must be installed within the specication conditions.
• The magnetic owmeter is a heavy instrument. Be careful that no damage is caused to personnel through accidentally dropping it, or by exerting excessive force on the magnetic owmeter. When moving the magnetic owmeter, always use a trolley, forklift, or crane and have at least two people carry it.
• When the magnetic owmeter is processing hot uids, the instrument itself may become extremely hot. Take sufcient care not to get burnt.
• Where the uid being processed is a toxic substance, avoid contact with the uid and avoid inhaling any residual gas, even after the instrument has been taken off the piping line for maintenance and so forth.
• Do not apply excessive weight, for example, a person stepping on the magnetic owmeter.
• All procedures relating to installation must comply with the electrical code of the country where it is used.
(2) Wiring
WARNING
• The wiring of the magnetic owmeter must be performed by expert engineer or skilled personnel. No operator shall be permitted to perform procedures relating to wiring.
• When connecting the wiring, check that the supply voltage to the converter is within the range of the voltage specied for this instrument before connecting the power cable. In addition, check that no voltage is applied to the power cable before connecting the wiring.
• The protective grounding must be connected securely at the terminal with the mark to avoid danger to personnel.
(3) Operation
WARNING
• When opening the cover, wait for more than 10 minutes after turning off the power. Only expert engineer or skilled personnel are permitted to open the cover.
• Do not open the cover in wet weather or humid environment. When the cover is open, stated enclosure protection is not applicable.
• Be sure to set parameters as “Protect” on the write protect function after nish of parameter setting work.
Under extremely rare case, the infra-red
switches may respond unexpectedly in such conditions as sticking ball of water or extraneous substances on the surface of display panel glass according to the principle of infra-red switch operation.
Its probability rises in such cases as sticking
rain water by storm or other similar situation and washing up work near owmeter installation place.
Either to illuminate or stop illuminating the infra-
red switches by the ashlight may cause the mis-reaction.
Refer to the manual for converter on how to
use the write protect function in detail.
IM 01E25D11-01EN
<1. INTRODUCTION>
1-3
(4) Maintenance
WARNING
• Maintenance of the magnetic owmeter should be performed by the trained personnel having knowledge of safety standard. No operator shall be permitted to perform any operations relating to maintenance.
• When opening the cover, wait for more than 10 minutes after turning off the power.
• Do not open the cover in wet weather or humid environment. When the cover is open, stated enclosure protection is not applicable.
• Always conform to maintenance procedures outlined in this manual. If necessary, contact Yokogawa.
• Care should be taken to prevent the build up of dirt, dust or other substances on the display panel glass or data plate. If these surfaces do get dirty, wipe them clean with a soft dry cloth.

1.2 Warranty

• The terms of this instrument that are guaranteed are described in the quotation. We will make any repairs that may become necessary during the guaranteed term free of charge.
• Please contact our sales ofce if this instrument requires repair.
• If the instrument is faulty, contact us with concrete details about the problem and the length of time it has been faulty, and state the model and serial number. We would appreciate the inclusion of drawings or additional information.
• The results of our examination will determine whether the meter will be repaired free of charge or on an at-cost basis.
n The guarantee will not apply in the
following cases:
• Damage due to negligence or insufcient maintenance on the part of the customer.
• Problems or damage resulting from handling, operation or storage that violates the intended use and specications.
• Problems that result from using or performing maintenance on the instrument in a location that does not comply with the installation location specied by Yokogawa.
• Problems or damage resulting from repairs or modications not performed by Yokogawa or someone authorized by Yokogawa.
• Problems or damage resulting from inappropriate reinstallation after delivery.
• Problems or damage resulting from disasters such as res, earthquakes, storms, oods, or lightning strikes and external causes.
n Trademarks:
ADMAG and AXW are registered trademarks of
Yokogawa Electric Corporation.
Company names and product names used
in this material are registered trademarks or trademarks of their respective owners.

1.3 Combination Remote Converters

IMPORTANT
• The AXW remote owtube (size 500 (20 in.) to 1800 mm (72 in.)) should be used in combination with AXFA11 remote converter.
Contact Yokogawa before using it in
combination with converters other than AXFA11.
IM 01E25D11-01EN
Blank Page
<2. HANDLING PRECAUTIONS>

2. HANDLING PRECAUTIONS

2-1
This instrument has been inspected carefully at the factory before shipment. When the instrument is delivered, visually check that no damage has occurred during transportation. Read this section carefully as it contains important information on handling this instrument. Refer to the relevant sections for information not contained in this section. If you have any problems or questions, please contact Yokogawa sales ofce.
2.1 Checking Model and Specications
The model code and specications are found on the data plate located on the outside of the case. Check that the model code and specications match what you have ordered. Be sure you have your model number and serial number available when contacting Yokogawa.
KCC­REM­YHQ­EEN 165

2.2 Storage Precautions

If the instrument is to be stored for a long period of time after delivery, observe the following points.
The instrument should be stored in its original
packing condition in the storage location.
Select a storage location that fulls the following
conditions:
• A place where it will not be exposed to rain or water
• A place subject to minimal vibrations or shocks
• Temperature and humidity levels should be as follows:
Temperature: -10 to 70°C Humidity: 5 to 80% RH (no condensation)
The preferred ambient temperature
and humidity levels are 25°C and approximately 65% RH.
If the magnetic owmeter is transferred to
the installation site and stored without being installed, its performance may be impaired due to the inltration of rainwater and so forth. Be sure to install and wire the magnetic owmeter as soon as possible after transferring it to the installation location.
Figure 2.1.1 Data Plate
F0201.ai

2.3 Installation Location Precautions

Select the installation location with consideration to the following items to ensure long-term stable operation of the instrument.
n Ambient Temperature:
Avoid installing the instrument in locations
with constantly uctuating temperatures. If the location is subject to radiant heat from the plant, provide heat insulation or improve ventilation.
n Atmospheric Condition:
Avoid installing the instrument in a corrosive
atmosphere. In situations where this is unavoidable, consider ways to improve ventilation and to prevent rainwater from entering and being retained in the conduit pipes.
n Vibrations or Shocks:
Avoid installing the instrument in a place subject
to shocks or vibrations.
IM 01E25D11-01EN
Blank Page
<3. INSTALLATION>
(Incorrect)
(Correct)

3. INSTALLATION

gures.
WARNING
Installation of the magnetic owmeter must be performed by expert engineer or skilled personnel. No operator shall be permitted to perform procedures relating to installation.
When installing two or more magnetic owmeters on a single pipe, provide a run of at least 10D between them.
Gate valve fully open
Reducer pipe
Expander pipe
3-1
D: Flowtube Size

3.1 Piping Design Precautions

IMPORTANT
Design piping correctly, referring to the following to prevent damage to owtubes and to assure accurate measuring.
(1) Location
IMPORTANT
Install the owmeter in a location where it is not exposed to direct sunlight. The minimum ambient temperature is limited by the minimum uid temperature of the owtube (the lining). For more information, refer to Chapter 6 “OUTLINE”. The owmeter may be used in an ambient humidity where the relative humidity ranges from 0 to 100%. However, avoid long-term continuous operation at relative humidity above 95%.
5D or more2Dor more
Tee
0 is allowable.5D or more 0 is allowable.5D or more
Figure 3.1.1 Required Lengths of Straight Runs
0 is allowable. 0 is allowable.
90-degree bent
10D or more
Various valves
10D or more
or more
or more
*1: Do not install anything in the vicinity that may
interfere with the magnetic eld, induced signal voltages, or ow velocity distributions of the owmeter.
*2: A straight run may not be required on the
downstream side of the owmeter. However, if a downstream valve or other tting causes irregularity or deviation in ows, provide a straight run of 2D to 3D on the downstream side.
*3: The valves shall be mounted on the
downstream side so that deviated ows do not occur in the owtube and to avoid startup from an empty condition.
(4) Maintaining Stable Fluid Conductivity
2D
2D
F0301.ai
(2) Noise Avoidance
IMPORTANT
The owmeter should be installed away from electrical motors, transformers, and other power sources in order to avoid interference with measurement.
(3) Required Lengths of Straight Runss
To maintain accurate measurement, see JIS B7554 “Electro Magnetic Flowmeters” which explains the requirements for upstream piping conditions of magnetic owmeters. Based on JIS B7554 “Electro Magnetic Flowmeters” and our piping condition test data, we recommend the piping conditions as shown in the following
IMPORTANT
Do not install the owmeter where uid conductivity tends to become uneven. If chemicals are fed near the upstream side of a magnetic owmeter, they may affect the ow rate’s indications. To avoid this situation, it is recommended that the chemical feed ports be located on the downstream side of the owmeter. If it is unavoidable that chemicals must be fed on the upstream side, provide a sufcient length of straight run (approximately 50D) to ensure the proper mixture of uids.
Upstream side
Figure 3.1.2 Chemical Injection
Downstream side
F0302.ai
IM 01E25D11-01EN
<3. INSTALLATION>
Bypass valve
3-2
(5) Precautions for Use of Liquid Sealing
Compounds
IMPORTANT
Care must be taken in using liquid sealing compounds on the piping, as it may have a negative inuence on the ow indications by owing out and covering the surfaces of an electrode or grounding ring. In particular, care must be taken if a liquid sealing compound is used in the case of vertical piping.
(6) Service Area
Select locations where there is adequate space to service installing, wiring, overhauling, etc
(7) Bypass Line
It is recommended to install a bypass line to facilitate maintenance and zero adjustment.
Block valve
(9) Mounting Positions
• Pipes must be fully lled with liquids.
IMPORTANT
It is essential that pipes remain fully lled at all times, otherwise ow rate indications may be affected and measurement errors may be caused.
Piping shall be designed so as to maintain the interior of the owtube lled with uids.
Vertical mounting is effective in such cases as when uids tend to separate or solid matter may be precipitated. When employing vertical mounting, direct the uids from the bottom to the top to ensure that the pipes remain fully lled.
(Correct)
Figure 3.1.4 Mounting Positions
(Incorrect)
h
h>0
(Correct)
h>0
(Incorrect)
h
F0304.ai
Block valve
Figure 3.1.3 Bypass Line
F0303.ai
(8) Supporting the Flowmeter
CAUTION
Do not secure the owmeter separately to prevent the vibrations, shocks, and expansion and contraction forces of the piping from affecting it. Fix the pipeline or its anges rst, then let them support the owmeter. For vertical, mounting, make sure that the weight of piping does not weigh on the owmeter. To release the load from tightening the owmeter to the pipeline, set a expansive pipe in the downstream side.
• Avoid air bubbles.
IMPORTANT
If air bubbles enter a measurement pipe, ow rate indications may be affected and measurement errors may be caused.
In cases where uids contain air bubbles, piping must be designed to prevent them from accumulating in the measurement pipe of a owtube.
If a valve exists near the owmeter, try to mount the owmeter on the valve’s upstream side in order to prevent a possible reduction of pressure inside the pipe, thereby avoiding the possibility of air bubbles.
(Correct)
(Incorrect)
Figure 3.1.5 Avoiding Air Bubbles
(Correct)
(Incorrect)
Valve
F0305.ai
IM 01E25D11-01EN
<3. INSTALLATION>
Correct
• Mounting orientation
3-3
IMPORTANT
If electrodes are perpendicular to the ground, air bubbles near the top or precipitates at the bottom may cause measurement errors. Ensure that the terminal box of a remote owtube is mounted above the piping to prevent water from entering them.
Incorrect
Air bubble
Electrode
Figure 3.1.6 Mounting Orientation
Electrode
Precipitate
Incorrect
Water can seep into the terminal box.

3.2 Handling Precautions

F0306.ai
90 degrees or less
Eye bolt Eye plate
Figure 3.2.1 Lifting Flowtube
90 degrees or less
F0307.ai
(2) Avoiding Shocks from Impact
CAUTION
Care should be taken not to drop the owmeter or expose it to excessive shock. In particular, be careful not to subject the ange surface to shock. This may lead to liner damage which will result in inaccurate readings.
WARNING
The magnetic owmeter is a heavy instrument. Be careful that no damage is caused to personnel through accidentally dropping it, or by exerting excessive force on the magnetic owmeter. When moving the magnetic owmeter, always use a trolley, forklift, or crane and have at least two people carry it.

3.2.1 General Precautions

(1) Precaution during Transportation
The magnetic owmeter is packed tightly. When it is unpacked, pay attention to prevent damaging the owmeter. To prevent accidents while it is being transported to the installing location, transport it to the site in its original packing.
CAUTION
When lifting the owtube, use the lifting rings (eye bolts or eye plates) as in Figure 3.2.1. Never lift it using a bar passed through the owtube as this damages the liner severely.
(3) Flange Protection Covers
IMPORTANT
Keep the protective covering (i.e. the corrugated cardboard or other cushioning material) in place over the ange except when mounting the owmeter to the pipe.
(4) Terminal Box Cover
IMPORTANT
As it is possible that the insulation will deteriorate, do not remove the wrapping of the terminal box nor open the terminal box cover until it is time to wire it.
(5) Long-term Non-use
IMPORTANT
It is not desirable to leave the owmeter unused for a long term after installation. If this situation is unavoidable, take care of the owmeter by observing the following.
IM 01E25D11-01EN
<3.INSTALLATION>
3-4
• Conrmationofsealingconditionsforthe owmeter
Conrm that the terminal box screw and wiring ports are well sealed. Equip the conduit piping with drain plugs or waterproof glands to prevent moisture or water from penetrating into the owmeter through the conduit.
• Regularinspections
Inspect the sealing conditions as mentioned above, and the inside of the terminal box at least once a year. Also, due to rain, etc. when it is suspected that water may have penetrated into the inside owmeter perform supplementary inspections.
3.2.2 FlowmeterPiping
CAUTION
Misaligned or slanted piping can lead to leakage and damage to the anges.
(1) Correct any misaligned or slanted piping, and
any gaps that may exist between mounting anges before installing the owmeter (refer to Figure 3.2.2).
3.3 MountingProcedures
CAUTION
When attaching optional grounding rings to the owtube with lining material natural hard rubber or uorocarbon PTFE, gaskets must be placed between each grounding ring and the owtube. Fluid leakage will happen without these gaskets. These gaskets are to be supplied by customer. Do not forget those gaskets also when ordering and attaching the grounding rings later additionally.
NOTE
The tightening torque value varies depending on the type of lining and gasket as shown in the tables in this section.
IMPORTANT
Use bolts and nuts in compliance with the ange ratings. When choosing the gaskets, be sure to choose sheet gaskets designed to t for ange standard.
Slanted
Figure3.2.2 SlantedandMisalignedFlowmeter
Piping
(2) Inside a newly installed pipeline, there may
be some foreign substances such as residue from welding or wood chips. Remove them by ushing the piping before mounting the owmeter. This prevents the lining from being damaged, as well as the occurrence of erroneous measured signals resulting from foreign substances passing through the owtube during measurement.
Misaligned
F0308.ai
(1) MountingDirection
Mount the owmeter so that the ow direction of the uid to be measured is in line with the direction of the arrow mark on the owmeter. It may be especially difcult to move large size owtubes after bringing them into the pit. Check directions before bringing.
IMPORTANT
If it is impossible to match the direction of the arrow mark, the direction of the electrical connection can be changed. Refer to Section 5.1 to do this properly. In case the uid being measured ows against the arrow direction, refer to the parameter J20: FlowDirection in the user’s manual of the AXFA11 Magnetic Flowmeter Remote Converter (IM 01E20C01-01E).
IM 01E25D11-01EN
<3. INSTALLATION>
A
A
3-5
(2) Carrying Flowtube
90 degrees or less
Eye bolt
Figure 3.3.1 Carrying Flowtube
90 degrees or less
Eye plate
CAUTION
• When carrying the owtube, use the lifting rings (eye bolts or eye plates).
• To assure safety, keep lifting angle less than 90 degrees as shown in Figure 3.3.1
(3) Positioning Flowtube
F0309.ai
1. Standard (no grounding rings)
Customer
pipe
A A
Gaskets A supplied by customer
Figure 3.3.2 Installation without Grounding
Rings
Customer
pipe
F0310.ai
When using the GF type-1 gaskets, the gasket groove is required as mentioned above.
2. With optional grounding rings (code GR1)
Optional grounding rings
Customer
pipe
B
Gaskets A and B supplied by customer
B
Figure 3.3.3 Installation with Grounding Rings
GR1
Customer
pipe
F0311.ai
Bring in the owtube, place it and use a jack to adjust its position.
IMPORTANT
Apply the jack to the anges of the owtube. In addition, adjust any misalignment when the owtube is brought in, as the jack can adjust vertical position, but not horizontal one.
(4) Applying Gasket and optional Grounding
Rings
Gasket:
Necessary gaskets for piping connection are as below depending on the choice of grounding rings. Use sheet gaskets designed to t for ange standard. The GF type-1 gaskets by JIS G 3443-2 should be used for the JIS F12 ange models in sizes 1100 mm (44 in.) and above. In this case, the gasket groove is required on the customer pipe anges. The thickness of gasket should be 2mm (0.08in.) to 5mm (0.2in.) for sizes up to 1000 mm (40 in.), and 5 mm (0.2 in.) or more for larger sizes. The type of gasket should be a kind of soft rubber, or its equivalent in hardness.
It is recommended to use the same gasket for A and B. Both gaskets A and B are to be supplied by customer. When polyurethane or natural soft rubber lining, the gaskets B are not necessary.
3. With optional grounding rings (code GR2)
Optional grounding rings
with integrated gaskets B included
B
Customer
pipe
A A
Gaskets A supplied by customer
B
Customer
pipe
F0312.ai
Figure 3.3.4 Installation with Grounding Rings
GR2
This is available for the models with process connection JIS F12 (JIS 75M) in sizes 1100 mm (44 in.) and above. Only gaskets A are to be supplied by customer. The grounding rings are installed and locked onto the owtube with gaskets B when shipped from factory.
Mounting Procedure (no Grounding Rings):
Connect the owtube’s ange and the customer’s pipe which contact process uid by some wire supplied by customer.
IM 01E25D11-01EN
<3. INSTALLATION>
3-6
Mounting Procedure (with optional Grounding Rings GR1 for sizes up to 1000 mm (40 in.)):
1. Handles of the grounding ring have some holes which correspond to outer diameter of each ange type. There are printings near each hole. The printings show types of ange. See the table below.
Printing
Process
Connection Code
ASME -CA1
AWWA -CB1
PN10 -CE1 EN1092-1 PN10 PN16 -CE2 EN1092-1 PN16 10K -CJ1 JIS B2220 10K
AS -CS1, -CS2, -CT1
F12 -CG1 JIS F12 (JIS 75M)
Flange Standard
ASME B16.5 Class 150, ASME B16.47 Class 150
AWWA C207 Class D
AS2129 table D, E AS4087 PN16
2. Conrm the centering pin is xed to the hole corresponding to ange or x the centering pin to the correct hole.
3. Hang the grounding rings with their ange type printings outer side of the owtube. Set the angle of both handles symmetrically to be 45 degree from top. If there are any bolt-holes under the handles, turn the grounding rings clockwise in order to locate handles between bolt-holes. Center the grounding ring to the center of the owtube.
4. Connect the wire from the grounding ring to the screw of the owtube’s ange and x the wire by the nut. This procedure (item 1 to 4) must be done for the both sides of the owtube.
5. Install the owtube into the customer’s pipe with the gaskets A.
Centering Pin
Flowtube
Note : Gasket A and B are also placed concentrically with
Figure 3.3.5 Mounting Procedure with Grounding
Screw & Nut : Connect the wire from the
grounding ring or the customer’s pipe
Centering Pin
Gasket B
Grounding Ring
the owtube.
Handle
Clockwise
Rings GR1 for sizes up to 1000 mm (40 in.)
Printing of Flange Type
F12
10K
Handle
Mounting Procedure (with optional Grounding Rings GR1 for sizes 1100mm (44 in.)) and above :
1. The grounding ring is temporarily xed onto the owtube by four bolts. Hang the grounding ring up using a crane or a hoist so that it would not fall down from the owtube while setting the gasket B.
2. Unfasten the bolts and remove the grounding ring off from the owtube.
3. Place the gasket B to the owtube. Cut out holes on the gasket B if necessary, so that the bolts can go through. Fix the grounding ring to the owtube by the four bolts again.
4. Connect the wire from the grounding ring to the screw at the owtube ange and x the wire by the nut. This procedure (item 1 to 4) must be done for the both sides of the owtube.
Hole
Printed Surface
F0313.ai
IM 01E25D11-01EN
<3. INSTALLATION>
5. Install the owtube into the customer’s pipe with the gaskets A.
Screw & Nut : Connect the wire from the
grounding ring or the customer’s pipe.
Flowtube
Hang the grounding ring up with this point.
Unfasten the bolts and remove the grounding rings. Cut out some holes on the gasket B when necessary.
Wire
3-7
Grounding Ring
F0314.ai
Note : Gasket A and B should be placed concentrically with
the owtube.
Figure 3.3.6 Mounting Procedure with Grounding
Rings GR1 for sizes 1100 mm (44 in.) and above
Mounting Procedure (with optional Grounding Rings GR2):
The grounding rings are installed and locked onto the owtube with gaskets B when shipped from factory. Install the owtube into the customer’s pipe with gaskets A supplied by customer.
(5) Tightening Nuts
Pass the bolts from pipe line side, not owtube side, and tighten the bolts according to the torque values for the metal piping in Table 3.3.1 or 3.3.2
CAUTION
• Be sure to tighten the nuts according to the prescribed toeque values. Tighten them diagonally with the same torque values, step by up to the prescribed torque value.
IM 01E25D11-01EN
<3. INSTALLATION>
Table 3.3.1 Tightening Torque Values for Metal Piping (N-m)
Lining type
Gasket type Soft rubber gasket, or the equivalent in hardness (supplied by customer)
Process
connection Size mm (inch)
500 (20) 99 to 166 85 to 140 143 to 238 151 to 233
600 (24) 144 to 240 108 to 175 218 to 363 239 to 331
700 (28) 168 to 281 176 to 266 180 to 300 176 to 293 240 to 333
800 (32) 259 to 432 212 to 302 236 to 393 246 to 410 400 to 612
900 (36) 274 to 457 206 to 338 224 to 373 258 to 430 399 to 604
1000 (40) 274 to 457 277 to 422 307 to 512 286 to 477 422 to 587
Lining type Polyurethane rubber
Gasket type Soft rubber gasket, or the equivalent in hardness (supplied by customer)
Process
connection
Size mm (inch)
500 (20) 71 to 118 60 to 99 74 to 123 76 to 123 131 to 218
600 (24) 97 to 162 82 to 126 101 to 168 118 to 171 124 to 206
700 (28) 125 to 208 135 to 202 146 to 244 120 to 200 167 to 242 202 to 337
800 (32) 176 to 294 160 to 229 190 to 316 169 to 281 218 to 348 197 to 328
900 (36) 170 to 283 151 to 251 178 to 296 161 to 268 200 to 317 221 to 369
1000 (40) 175 to 291 206 to 314 220 to 367 165 to 275 253 to 370 218 to 363
B16.5 (500, 600)
B16.47 (700-1000)
ASME
B16.5 (500, 600)
B16.47 (700-1000)
Class 150
ASME
EN1092-1 PN10
JIS B2220 10K
Class 150
PTFE / Natural hard rubber / Natural soft rubber
EN1092-1 PN10
JIS B2220 10K
EN 1092-1
EN 1092-1 PN16
PN16
AWWA C207
Class D
AWWA C207
Class D
AS2129 Table
D, E
AS4087 PN16
AS2129 Table D, E
AS4087 PN16
(JIS 75M)
3-8
Unit: N-m
Unit: N-m
JIS F12
Lining type Natural hard rubber
Gasket type Soft rubber gasket, or the equivalent in hardness (supplied by customer)
Process
connection Size mm (inch)
1100 (44) 285 to 476
1200 (48) 180 to 300 327 to 546 298 to 497 400 to 582 281 to 468
1350 (54) 397 to 662
1400 (56) 233 to 388 379 to 632
1500 (60) 421 to 702
1600 (64) 238 to 397 532 to 886 532 to 887
1800 (72) 291 to 485 552 to 919 468 to 779
EN1092-1 PN6 EN1092-1 PN10
AWWA C207
Class D
AS2129 Table D, E
AS4087 PN16
Polyurethane
Unit: N-m
rubber
JIS F12
(JIS 75M)
IM 01E25D11-01EN
<3. INSTALLATION>
Table 3.3.2 Tightening Torque Values for Metal Piping (lbf-in)
Lining type
Gasket type Soft rubber gasket, or the equivalent in hardness (supplied by customer)
Process
connection Size mm (inch)
500 (20) 880 to 1467 748 to 1239 1266 to 2110 1332 to 2062
600 (24) 1275 to 2125 955 to 1546 1928 to 3214 2113 to 2932
700 (28) 1490 to 2483 1561 to 2357 1594 to 2657 1558 to 2596 2123 to 2943
800 (32) 2292 to 3820 1880 to 2671 2085 to 3475 2176 to 3627 3538 to 5413
900 (36) 2426 to 4043 1821 to 2991 1980 to 3301 2285 to 3809 3535 to 5346
1000 (40) 2426 to 4043 2450 to 3739 2717 to 4528 2534 to 4224 3734 to 5265
Lining type Polyurethane rubber
Gasket type Soft rubber gasket, or the equivalent in hardness (supplied by customer)
Process
connection
Size mm (inch)
500 (20) 626 to 1044 527 to 876 652 to 1087 674 to 1089 1159 to 1931
600 (24) 862 to 1436 727 to 1113 894 to 1490 1043 to 1512 1095 to 1825
700 (28) 1106 to 1843 1193 to 1791 1295 to 2159 1061 to 1769 1478 to 2142 1788 to 2980
800 (32) 1562 to 2603 1420 to 2024 1680 to 2800 1494 to 2491 1926 to 3076 1739 to 2899
900 (36) 1505 to 2508 1340 to 2218 1571 to 2619 1422 to 2370 1773 to 2808 1958 to 3263
1000 (40) 1546 to 2577 1824 to 2781 1951 to 3251 1459 to 2432 2239 to 3274 1928 to 3213
B16.5 (500, 600)
B16.47 (700-1000)
ASME
B16.5 (500, 600)
B16.47 (700-1000)
Class 150
ASME
EN1092-1 PN10
JIS B2220 10K
Class 150
PTFE / Natural hard rubber / Natural soft rubber
EN1092-1 PN10
JIS B2220 10K
EN 1092-1
EN 1092-1 PN16
PN16
AWWA C207
Class D
AWWA C207
Class D
AS2129 Table
D, E
AS4087 PN16
AS2129 Table D, E
AS4087 PN16
JIS F12
(JIS 75M)
3-9
Unit: lbf-in
Unit: lbf-in
Lining type Natural hard rubber
Gasket type Soft rubber gasket, or the equivalent in hardness (supplied by customer)
Process
connection Size mm (inch)
1100 (44) 2527 to 4211
1200 (48) 1594 to 2657 2898 to 4830 2639 to 4398 3539 to 5149 2484 to 4139
1350 (54) 3517 to 5862
1400 (56) 2060 to 3434 3358 to 5597
1500 (60) 3729 to 6215
1600 (64) 2109 to 3515 4705 to 7842 4713 to 7854
1800 (72) 2576 to 4293 4883 to 8138 4138 to 6897
EN1092-1 PN6 EN1092-1 PN10
AWWA C207
Class D
AS2129 Table D, E
AS4087 PN16
Polyurethane
(JIS 75M)
Unit: lbf-in
rubber
JIS F12
IM 01E25D11-01EN
Blank Page
<4. WIRING>

4. WIRING

4-1

4.1 Wiring the Remote Flowtube

This section describes the wiring of the remote owtube only. For information relating to the wiring of the converter, refer to the user’s manual of the AXFA11 Magnetic Flowmeter Remote Converter (IM 01E20C01-01E).
WARNING
The wiring of the magnetic owmeter must be performed by expert engineer or skilled personnel. No operator shall be permitted to perform procedures relating to wiring.
CAUTION
Once all wiring is complete, check the connections before applying power to the instrument. Improper arrangements or wiring may cause a unit malfunction or damage.

4.1.1 Wiring Precautions

Be sure to observe the following precautions when wiring:
CAUTION
In cases where the ambient temperature
exceeds 50°C (122°F), use external heat­resistant wiring with a maximum allowable temperature of 70°C (158°F) or above.
Do not connect cables outdoors in wet
weather in order to prevent damage from condensation and to protect the insulation, e.g. inside the terminal box of the owtube.
Do not splice the cable between the owtube
terminal and the converter if it is too short. Replace the short cable with a cable that is the appropriate length.
All the cable ends must be provided with
round crimp-on terminals and be securely wired.
The signal cables must be routed in separate
steel conduit tubes 16 (JIS C 8305) or exible conduit tubes 15 (JIS C 8309).
Keep conduits or exible tubes watertight
using sealing tape.
Ground the remote owtube and the converter
separately.
Cover each shield of the signal cable with vinyl
tube or vinyl tape to avoid contact between two shields or between a shield and a case.
When waterproof glands or union equipped
waterproof glands are used, avoid tightening the glands with an excessive torque.
Be sure to turn the power off before opening
the terminal box cover.
Before turning the power on, tighten the
terminal box cover securely.
When opening the terminal box cover, use a
hexagonal wrench (nominal size 3 mm). For handling the locking screw, refer to Figure
4.1.7.
Be sure to lock the cover using a hexagonal
wrench (nominal size 3 mm) after installing the cover. For handling the locking screw, refer to Figure 4.1.11.
• When submersible type or optional code DHC is selected, waterproof glands, signal and excitation cables are attached.
In order to preserve the effectiveness of
waterproof features, the terminal box cover and waterproof glands must not be detached from owmeter.
IMPORTANT
Prepare the signal cable and the excitation cable almost the same length. It is recommended to lay them together closely.
IM 01E25D11-01EN
<4. WIRING>

4.1.2 Cables

CAUTION
(1) Dedicated Signal Cable (AXFC)
Conductors (A and B)
Shields (SA and SB)
Tape
Outer jacket
Shield (C)
Insulation
Insulation
10.5 (0.413")
F0401.ai
Figure 4.1.1 Dedicated Signal Cable AXFC
The ow signal is transmitted via this dedicated cable. The cable is constructed with double shielding over the two conductors, and heat­resistant vinyl is used for the outer jacket material. Finished diameter: 10.5 mm (0.413”) Maximum length:
Combination with the AXFA11 converter: 200 m (660 ft)
Maximum temperature: 80°C (176°F)
As crimp terminals A, B, SA, SB and C have their own electrical potentials, securely insulate them so as not to come in contact with one another.
To prevent a shield from coming in contact with another shield or the case, cover each shield with a vinyl tube or wrap it in vinyl tape.
NOTE
Conductors A and B carry the signal from the electrodes, and C is at the potential of the liquid (signal common). Shields SA and SB are kept at the same potentials as the individual electrodes (these are actively driven shields.) This is done to reduce the effect of the distributed capacitance of the cable at long cable length. Note that, since the signals from the individual electrodes are impedance converted inside the converter, errors will result if they come in contact with any other component. Great care must be taken in the cable nish treatment.
4-2
IMPORTANT
If the cable is longer than required, cut off any extra length rather than coiling it up, and terminate the conductors as shown in Figure
4.1.2. Avoid using junction terminal boards to extend the cable length, as this will interrupt the shielding.
Unit : mm
(approx. inch)
ACB
SA
On the converter side
25 (0.98)
White Black
±5
150
8(0.3) max.
(5.9)
SB
50 (1.97)
20 (0.8)
70 (2.76)
Red
L (Specified Dimensions)
AXFC
60 (2.36)
Figure 4.1.2 Treatment of Dedicated Signal Cables
ACB
55 (2.17)
90 (3.54)
White Black Red
8 (0.3) max.
±5
(5.9)
150
On the flowtube side
ø10.5 (0.4)
F0402.ai
90 (3.54)
(2) Excitation Cable
JIS C 3401 control cable equivalent JIS C 3312 power cable equivalent 14 AWG Belden 8720 equivalent
Outer Diameter: 6.5 to 12 mm (0.26 to 0.47 in.)
10.5 or 11.5 mm (0.41 to 0.45 in.) for optional
code EG, EU and EW. Nominal Cross Section: Single wire: 0.5 to 2.5 mm Stranded wire: 0.5 to 1.5 mm
2
2
IM 01E25D11-01EN
<4. WIRING>
4-3
Unit : mm
(approx. inch)
Crimp terminal
EX2
EX1
85 (3.35)
On the converter side
Figure 4.1.3 Finish Treatment of Excitation Cable
85 (3.35)
On the flowtube side
EX1
EX2
F0403.ai
NOTE
• For excitation cables, always use a crimp terminal with an insulation cover.
• Use crimp tools from the manufacturer of the crimp terminal you want to use to connect the crimp terminal and cable.
• Use crimp tools that are appropriate for the diameter of the cable to be connected.

4.1.3 Wiring Ports

This instrument is of watertight construction as stipulated in JIS C0920. It is shipped with a wiring bracket (waterproof gland or waterproof gland with union), only in cases where an optional specication is selected for the wiring port. When submersible type or option code DHC is selected, waterproof glands and a 30-meter (or customer designated) length cable are attached with resin lled in the terminal box. In this case, wiring at this terminal box is not necessary and do not open it.
IMPORTANT
The wiring port is sealed with a cap (not water­proof). Do not remove the cap from the wiring port until wiring a cable. If waterproof property is necessary, please use waterproof glands.
(1) When waterproof property is unnecessary
(When there are no particular optional specications)
The wiring port is sealed with a cap (not water­proof) that must be removed before wiring. When wiring, handle the wiring with proper procedures for necessary protection.
(2) When waterproof property is necessary (Wiring using waterproof glands)
IMPORTANT
To prevent water or condensation from entering the terminal box, waterproof glands are recommended. Do not over-tighten the glands or damage to the cables may result. Tightness of the gland can be checked by conrming that the cable is held rmly in place.
For working on the electric wire tubes or the exible tubes (G1/2), remove the waterproof gland and attach them directly to the wiring port. Be sure to use the washers and gaskets as shown in the drawings. Check and see that the cable is rmly xed realizing waterproofness.
IM 01E25D11-01EN
<4. WIRING>

4.1.4 Wiring Connections

4-4
Washer
Gasket
Waterproof gland
Cable
F0404.ai
Figure 4.1.4 Waterproof Gland (Optional code EG)
Gasket
PF1/2
Washer
Tightening gland
Cable
When working on conduit pipes or flexible pipes (G1/2 only)
Figure 4.1.5 Waterproof Gland with Union Joint (Optional code EU)
F0405.ai
WARNING
Before wiring, be sure that the power supply for AXFA11 converter has been turned off to prevent an electrical shock.
(1) Removing Cover
Loosen the cover locking screw clockwise using a hexagonal wrench (nominal size 3 mm) to unlock the cover. (Upon shipment from the manufacturing plant, the cover is unlocked.) Remove the cover by turning it in the direction of the arrow as shown below.
(3) Conduit Wiring
When wiring the conduits, pass the conduit through the wiring connection port, and utilize the waterproof gland to prevent water from flowing in. Place the conduit pipe on an angle as shown in Figure 4.1.6. Install a drain valve at the low end of the vertical pipe, and open the valve regularly.
Drain valve
F0406.ai
Figure 4.1.6 Conduit Wiring
F0407.ai
Figure 4.1.7 Removing the Terminal Box Cover
(2) Terminal Conguration
When the cover is removed, the connection terminals will be visible.
Terminal Symbols
A B
C EX1 EX2
Figure 4.1.8 Terminal Conguration
Description
Flow signal output
Excitation current input
Protective grounding (Outside of the terminal)
F0408.ai
IM 01E25D11-01EN
<4.WIRING>
4-5
(3) WiringtheRemoteFlowtubewithAXFA11
Converters
Connect wiring as shown in the gure below.
SO1+ COMSO2+
FUSE
2.5A 250V
Shortbar
I+
CURRENT OUT
4-20mA out
N/– L/+
POWER SUPPLY
I–
AL+ AL– C SA A B SB
STATUS OUT
ALARM OUT
EX2EX1
P– SI1+ SI2+ COMP+
EXCIT ATION
PULSE OUT STATUS IN
SIGNAL
AXFA11 converter
AXFC dedicated
Excitation cable
A
EX2
B
EX1
C
Remote flowtube
signal cable
Converter
SA
A B
SB
C EX1 EX2
* Individually tape and insulate
the shields corresponding to SA and SB on the remote flowtube side.
Remote
flowtube
Taping*
A B
Taping*
C EX1 EX2
F0409.ai
Figure4.1.9 WiringDiagram
(4) Grounding
600 V vinyl insulated electric cable (2 mm2 or larger)
• Class D requirements (ground resistance.
100 Ω or less).
CAUTION
Be sure to connect the protective grounding of the remote owtube with a cable of 2 mm2 or larger cross section in order to avoid electrical shock to the operators and maintenance engineers and to prevent the inuence of external noise. Connect the grounding wire to the mark. The grounding should satisfy Class D requirements (ground resistance, 100 Ω or less).
IMPORTANT
Improper grounding can have an adverse affect on the ow measurement. Ensure that the instrument is properly grounded.
The electromotive force of the magnetic owmeter is minute and it is easy to be affected by noise. And also that reference electric potential is the same as the measuring uid potential. Therefore, the reference electric potential (terminal potential) of the owtube and the converter also need to be the same as the measuring uid. Moreover, that the potential must be the same with ground. Be sure to ground according to Figure 4.1.10. Refer to Figure 3.3.5 or 3.3.6 for wiring to the anges of remote owtube when optional grounding rings are not used.
Without optional grounding rings.
(Available only for metal piping)
With optional grounding rings.
F0410.ai
Figure4.1.10ProtectiveGroundingTerminalLocation
(5)InstallingtheCover
Install the cover to the owtube by turning it in the direction of the arrow as shown below. Tighten the cover locking screw counterclockwise using a hexagonal wrench (nominal size 3 mm) to lock the cover.
F0411.ai
Figure4.1.11 InstallingtheTerminalBoxCover
IM 01E25D11-01EN
Blank Page
<5. MAINTENANCE>

5. MAINTENANCE

5-1
WARNING
• Maintenance work must be carried out by the trained personnel having knowledge of safety standard and not by operators.
• When opening the cover, wait for more than 10 minutes after turning off the power. Furthermore, opening of the cover must also be carried out by the trained personnel having knowledge of safety standard.
CAUTION
• When opening the cover, use a hexagonal wrench (nominal size 3 mm).
• Be sure to lock the cover using a hexagonal wrench (nominal size 3 mm) after installing the cover.
5.1 Changing Direction of
F0501.ai
(4) Using the hexagonal wrench, loosen the screw
in the neck.
(5) Turn the terminal box in the desired direction.
NOTE
The terminal box can be turned –140 degree to +180 degree from the arrow mark indicating the ow direction. Do not exceed these angle.
(6) Using the hexagonal wrench, retighten the neck
screw.
+180º-140º
Electrical Connection
IMPORTANT
The following types can not be changed direction of electrical connection after delivery.
• Submersible Type.
• Optional code DHC (for district heating and cooling or condensation-proof).
(1) The following tools are required to change the
direction of the electrical connection:
• Hexagonal wrench (nominal size 1.5 mm)
• Wrench
(2) Turn off the power to the owmeter. (3) Using the wrench, loosen the hexagonal nut at
the neck of the instrument.
F0502.ai
(7) Using the wrench, retighten the hexagonal nut
at the neck. After that, check that the terminal box is xed.
IM 01E25D11-01EN
<5. MAINTENANCE>
5-2

5.2 Regular Inspection Items

(1) Inspection of moisture-proong inside the
terminal box: Once/year
(2) Retightening of piping joint screws: About
twice/year
(3) Inspection of electrodes and lining (in case
of adhesive and/or abrasive uids, etc.)
Determine the period of regular inspection as
necessary.

5.3 Excitation Coil and Insulation Resistance Check

WARNING
• Before checking of the excitation coil and the insulation resistance, be sure that the power supply for AXFA11 converter has been turned off.
• Before checking, be sure to disconnect the cables from the terminals of the remote owtube.
Coil Circuit
Checking is possible even if the pipe is lled with uid.
Test Terminals Test Voltage Specication
Between terminals EX1 and C
500 V DC (Use an insulation tester or the equivalent.)
1 MΩ or more
Signal Circuit
Before testing, be sure to empty and dry the interior of the pipe, checking that there is no adhesive material. Also undo the wiring connection on the converter side before testing.
Test Terminals Test Voltage Specication
Between terminals A and C Between terminals B and C
500 V DC (Use an insulation tester or the equivalent.)
100 MΩ or more for each
(1) Excitation Coil Check
Check that there is continuity between terminals EX1 and EX2 in the terminal box. If there is no continuity, the coils may be broken and replacement or repair of the owtube is necessary. The coil resistance is designed to be 150 Ω or less. If it is not, this may be an abnormal condition. Consult Yokogawa’s sales or service ofces.
(2) Insulation Resistance Check
Check the insulation resistances in the terminal box in accordance with the tables below. If any of them falls below the values listed in the tables, consult Yokogawa’s sales or service ofces for investigation. If the insulation resistance cannot be restored, replacement or repair of the owtube is needed. In case of submersible type owmeters, undo the wiring connection on the converter side and measure resistance at the cable terminals.
IM 01E25D11-01EN
<5. MAINTENANCE>

5.4 Troubleshooting

Although magnetic owmeters rarely require maintenance, failures may occur when the instrument is not operated correctly. This section describes troubleshooting procedures where the cause of the breakdown is identied through receiver indication.

5.4.1 No Indication

START
Is an error being displayed? Check the converter display.
5-3
Is an error being
displayed?
NO
Is anything else
being displayed?
YES
Does the
arrow on the tube match the
flow direction?
YES
Check whether the flowtube is filled with fluid.
Is the flowtube
full of fluid?
YES
Check the resistance between the flowtube’s A, B, and C terminals using a circuit tester.
YES
NO
NO
NO
Refer to the “Alarm Functions” in the AXFA11.
Perform either of the following: a. Reinstall the flowtube in
order to make the arrow and flow direction match.
b. Reverse the setting for the
flow direction.
Change the piping or the mounting condition so that the tube fills with the fluid.
resistance between A-C or B-C
Remove the tube and inspect the inside of the pipe.
Remove the foreign matter.
Is the
100 MΩ or more?
YES
Is foreign
matter adhering to
the walls?
YES
NO
NO
Contact a service center.
F0503.ai
IM 01E25D11-01EN
<5. MAINTENANCE>

5.4.2 Unstable Zero

START
Investigate whether or not the flowtube is filled with fluid and that it is free of bubbles.
*1
Is the flowtube
completely full of fluid?
YES
NO
*1: When checking for bubbles, it is
convenient if there is a gas vent hole on the flowtube’s downstream side.
Particular care must be taken in the case of horizontal mounting. In order to ensure complete filling of the tube, either adjust the mounting position or switch to vertical mounting.
5-4
Are there bubbles
in the fluid?
NO
Check for the presence of valve leakage.
Are valves leaking?
NO
Confirm the flowmeter grounding.
Confirm whether or not the
grounding wire is disconnected from the earth flange.
Is the flowmeter properly
grounded?
YES
Recheck the fluid to be measured.
● Does the fluid’s
conductivity vary?
● Is the fluid conductivity
within the limits?
NO
Is the fluid likely to contain deposits?
NO
YES
YES
NO
YES
YES
Install a defoaming device on the flowtube’s upstream side.
Replace the valve(s).
Completely ground the converter and flowtube (Refer to the section on grounding in the relevant user's manual.)
Ensure that the fluid’s conductivity
changes as little as possible.
Do not use the meter when fluid
conductivity is out of limits.
Whenever possible, reduce the flow
velocity to being in the vicinity of the lower conductivity limit.
Remove dirt and scale of and near
electrodes.
Use a soft brush or cloth to perform
scale removal, and make sure that the lining is not damaged.
Is the flowmeter
located near motors, transformers,
or electric equipment?
NO
Contact a service center.
YES
Provide the meter with sufficient shielding or move it away from the electrical equipment
F0504.ai
IM 01E25D11-01EN
<5. MAINTENANCE>

5.4.3 Disagreement Between Indication and Actual Flow

START
5-5
Are parameters
set correctly?
YES
Examine the condition of the fluid in the flowtube, of bubbles, and of grounding.
Was zero
adjustment carried out
correctly?
YES
Is the tube
filled completely with
fluid?
YES
Does the fluid
contain bubbles?
NO
Is the
flowmeter completely
grounded?
YES
Is the
signal cable terminal
treatment of
complete?
YES
Does the
conductivity stay within the
specified range?
YES
Is the
fluid likely to contain
deposits?
NO
Confirm that a valve is located
immediately upstream of the flowtube (i.e., on the upstream side).
Is a valve
located immediately upstream
of the flowtube?
NO
Remove the flowtube and examine the insulation resistance.
NO
NO
NO
YES
NO
NO
NO
YES
YES
Set the parameters correctly.
Execute zero adjustment when the flowtube is filled completely with fluid and when the fluid is not moving.
● Change the mounting position or piping
so that the flowtube is completely filled with fluid.
● Switch to vertical mounting.
Install a defoaming device on the flowtube’s upstream side.
Completely ground the converter and
flowtube (Refer to the section on grounding in the relevant user's manual.)
Fully terminate the signal cable using
PVC tubing or insulation tape, thus
insuring that conductors, inner shields, and outer shields do not make contact with each other or with the case.
Use within the specified conductivity range.
● Remove scales. Especially clean the
electrodes and their vincinity.
● Use a soft brush or cloth to perform
scale removal, and make sure that the lining is not damaged.
● If any valve located immediately
upstream of the flowtube is used in a half-open condition, the indication may be affected by turbulence in the flow.
● Relocate the valve to the downstream
side.
● If the valve must be located on the
upstream side, ensure that the minimum distance to the flowmeter is 10 times the flow-tube diameter; alternatively, use the valve fully open.
Signal terminals A-C and B-C:
100 MΩ or more
Excitation terminals EX1-C:
1 MΩ or more
YES
1
*
Examine the operation of the converter using an AM012 calibrator in order to determine whether the fault lies in the converter or in the flowtube.
Contact a service center.
NO
Dry the tube fully to restore insulation resistance.
*1: Refer to Section 5.3 for how to check
the resistance of the flowtube.
F0505.ai
IM 01E25D11-01EN
Blank Page
<6. OUTLINE>

6. OUTLINE

6-1

n STANDARD SPECIFICATIONS

Protection:
General-purpose type: IP66, IP67 Submersible type: IP68 (conforms to continuous
immersion under the following test condition)
Test Condition: 50 m below the surface of the water, equivalent to
0.5 MPa hydraulic pressure, for one month.Cable should be protected at customer site.
Material (non-wetted parts):
Flowtube:
Housing: Carbon steel Flange: Carbon steel Pipe: Stainless steel Terminal box: Aluminum alloy
Material (wetted parts):
Lining:
Fluorocarbon PTFE Natural hard rubber (plus EPDM for sealing) Natural soft rubber Polyurethane rubber Contact Yokogawa ofce for others.
Electrode:
JIS SUS316L(AISI 316L SS Equivalent) Hastelloy C276 Equivalent
Grounding ring (option):
JIS SUS304 or SUSF304 (AISI 304 SS Equivalent)
Gasket (for option GR2):
Mixture of SBR and NR
Coating:
General-purpose type:
Pipe, Housing, Flange, Terminal Box:
Corrosion-resistant coating Coating color: Mint green
Submersible type:
Pipe, Housing, Flange, Terminal Box:
Non-tar epoxy coating (black)
Wiring:
Electrical connection:
ANSI 1/2 NPT female ISO M20 x 1.5 female JIS G1/2 (PF1/2) female
Direction of Electrical Connection:
The direction can be changed even after delivery except for submersible type and DHC option type.
Wiring Terminal:
M4 screw
Grounding:
Grounding resistance 100 Ω or less
Combined Converter:
AXFA11 converter
Signal Cable:
AXFC, Maximum cable length to AXFA11 converter up to 200m (660 ft)

n STANDARD PERFORMANCE

Accuracy (Pulse Output):
0.35% of rate for sizes 500 mm (20 in.) to 1000 mm (40 in.)
0.5% of rate for sizes 1100 mm (44 in.) to 1800 mm (72 in.)
Size mm(in.)
500(20) to 1000(40)
1100(44) to 1800(72)
For sizes 500mm (20 in.) to 1000mm (40 in.)
% of rate
1.2
1.0
0.8
0.6
0.4
0.2
0.0 0 1 2 3 4 5 6 7 8 9 10
For sizes 1100mm (44 in.) to 1800mm (72 in.)
% of rate
1.2
1.0
0.8
0.6
0.4
0.2
0.0 0 1 2 3 4 5 6 7 8 9 10
Flow Velocity
V m/s (ft/s)
V < 0.3 (1.0) ±2.0mm/s
0.3 ≤ V ≤ 10 (1.0) (33)
V < 0.3 (1.0) ±3.0mm/s
0.3 ≤ V < 1 (1.0) (3.3)
1 ≤ V ≤ 10 (3.3) (33)
Pulse Output Accuracy
Pulse Output Accuracy
±0.35% of rate ±1.0mm/s
±0.4% of rate ±1.8mm/s
±0.5% of rate ±1.0mm/s
V [m/s]
V [m/s]
Accuracy
F0601.ai
F0602.ai
IM 01E25D11-01EN
<6. OUTLINE>
6-2
Note: The accuracy of a product before shipment is dened
as totalized value at the result of calibration test in our water actual ow test facility. Calibrated conditions in our water actual test facility are as follows:
Fluid temperature: 20 ± 10°C Ambient temperature: 20 ± 5°C Length of straight runs:
10 D or more on the upstream side 5 D or more on the downstream side
Reference conditions:
Similar to BS EN29104, ISO 9104
Accuracy (Current Output):
Accuracy (Pulse Output) plus ±0.05% of span
Repeatability:
±0.2% of rate (V ≥ 1m/s (3.3ft/s)) ±0.1% of rate ± 1mm/s (V < 1m/s (3.3ft/s))
Maximum Power Consumption:
Combined with AXFA11: 20W
Insulation Resistance:
Between excitation current terminal and signal / common terminals : 100MΩ at 500V DC Between signal terminals : 100MΩ at 500V DC Between signal terminals and common termi­nal (C) : 100MΩ at 500V DC
CAUTION
*1: When performing the Insulation Resistance
Test, please obey the following caution.
• Following the relevant test, wait for more than 10 seconds after the power supply has been turned off before removing the cover.
• Remove all wires from terminals before testing.
• After testing, be sure to discharge by using a resistance and return all wires to its correct position.
• Screws must be tightened to a torque of
1.18 N-m or more.
• After closing the cover, the power supply can be restored.
EMC Conformity Standards:
EN61326-1 Class A, Table2 (For use in indus­trial locations) EN61326-2-3 EN61000-3-2 Class A EN61000-3-3
CAUTION
This instrument is a class A product, and it is designed for use in the industrial environment. Please use this instrument in the industrial environment only.

n NORMAL OPERATING CONDITIONS

Ambient Temperature:
–10 to +60°C (+14 to +140°F)
Note: Minimum temperature should also be limited accord-
ing to minimum uid temperature of ow tube’s speci­cation. Refer to description of “Fluid Temperature and Pressure”. Contact Yokogawa ofce for lower temperature.
Ambient Humidity:
0 to 100%
Note: Lengthy continuous operation at 95% or more is not
recommended.
Fluid Conductivity:
20 µS /cm or larger for sizes 1000 mm and below 50 µS /cm or larger for sizes 1100 mm and above
Measurable Flow Rate Range:
Size
mm (in.)
500 (20)
600 (24)
700 (28)
800 (32)
900 (36)
1000 (40)
Size
mm (in.)
1100 (44)
1200 (48)
1350 (54)
1400 (56)
1500 (60)
1600 (64)
1800 (72)
Fluid Temperature and Pressure:
Note: The following values show maximum allowable uid
pressure for the owtube. Further uid pressure should also be limited according to ange rating.
Lining Material Fluid Temperature Fluid Pressure Fluorocarbon PTFE -10 to 120°C
Natural hard rubber
Natural soft rubber
Polyurethane rubber
Min. Span
0.1m/s (0.33ft/s) 0 to 70.69 m
(0 to 311.3 GPM)
0 to 101.79 (0 to 448.2)
0 to 138.55 (0 to 610.0)
0 to 180.96 (0 to 796.8)
0 to 229.03 (0 to 1,009)
0 to 282.75 (0 to 1,245)
Min. Span
0.3 m/s (1 ft/s)
0 to 1,026.4 m
(0 to 4,519 GPM)
0 to 1,221.5
(0 to 5,378)
0 to 1,545.9
(0 to 6,807)
0 to 1,662.5
(0 to 7,320)
0 to 1,908.6
(0 to 8,403)
0 to 2,171.5
(0 to 9,561)
0 to 2,748.3
(0 to 12,101)
(14 to 248°F)
-5 to 80°C (23 to 175°F)
-10 to 70°C (14 to 158°F)
-10 to 40°C (14 to 104°F)
3
/h
3
(0 to 31,122 GPM)
/h
(0 to 150,630 GPM)
Max. Span
10m/s (33ft/s)
0 to 7,068 m3/h
0 to 10,178
(0 to 44,815)
0 to 13,854
(0 to 60,999)
0 to 18,095
(0 to 79,672)
0 to 22,902
(0 to 100,835)
0 to 28,274
(0 to 124,488)
Max. Span
10 m/s (33 ft/s)
0 to 34,211 m3/h
0 to 40,715
(0 to 179,262)
0 to 51,529
(0 to 226,879)
0 to 55,418
(0 to 243,997)
0 to 63,617
(0 to 280,098)
0 to 72,382
(0 to 318,689)
0 to 91,608
(0 to 403,341)
0 to 1 MPa (0 to 145 psi)
0 to 1 MPa (0 to 145 psi)
0 to 1 MPa (0 to 145 psi)
-0.1 to 1 MPa (-14.5 to 145 psi)
IM 01E25D11-01EN
<6. OUTLINE>
6-3

n MODEL AND SUFFIX CODE

For Process Connections other than JIS F12 (JIS 75M)
Model Sufx Code Description Available Size / Model
AXW500 Size 500 mm (20 in.) Remote Flowtube
AXW600 Size 600 mm (24 in.) Remote Flowtube
AXW700 Size 700 mm (28 in.) Remote Flowtube
AXW800 Size 800 mm (32 in.) Remote Flowtube
AXW900 Size 900 mm (36 in.) Remote Flowtube
AXW10L Size 1000 mm (40 in.) Remote Flowtube
AXW12L Size 1200 mm (48 in.) Remote Flowtube
AXW14L Size 1400 mm (56 in.) Remote Flowtube
AXW16L Size 1600 mm (64 in.) Remote Flowtube
AXW18L Size 1800 mm (72 in.) Remote Flowtube
Use G General-purpose type
W Submersible type
Converter -N
Power Supply
Lining (*1) F Fluorocarbon PTFE
Electrode Material (*1) L JIS SUS316L (AISI 316L SS Equivalent)
Electrode Structure 1 Non-replaceable
Grounding Structure (*2) N None (*3), available as optional feature (GR1)
Process Connection (*4)
Lay Length N Standard
Electrical Connection -0 JIS G1/2 female
Indicator N None
Calibration B Standard
Optional Specications
*1:
Users must consider the characteristics of selected wetted parts material and inuence of process uids. The use of inappropriate materials can result in the leakage of corrosive process uids and cause injury to personnel and/or damage to plant facilities. It is also possible that the instrument itself can be damaged and that fragments from the instrument can contaminate the user’s process uids.
Be very careful with highly corrosive process uids such as hydrochloric acid, sulfuric acid, hydrogen sulde, sodium hypochlorite, and high-
temperature steam (150°C [302°F] or above). Contact Yokogawa for detailed information of the wetted parts material.
*2: Select optional grounding rings (code GR1) if necessary. For example, grounding rings are necessary for plastic piping. *3: “None” is applicable only for metal piping and wiring for grounding will be necessary so that the electric potentials between owtube and piping
ange should be the same.
*4: Contact Yokogawa ofce for ISO ange connection.
N Remote Flowtube
H Natuarl Hard Rubber
D Natuarl Soft Rubber
U Polyurethane Rubber
H Hastelloy C276 Equivalent
-CA1
-CB1 AWWA C207 Class D (Carbon Steel)
-CEJ
-CEK
-CE1
-CE2
-CJ1 JIS B2220 10K Flange (Carbon Steel)
-CS1 AS2129 Table D (Carbon Steel)
-CS2 AS2129 Table E (Carbon Steel)
-CT1 AS4087 PN16 (Carbon Steel)
-2
-4
Remote Flowtube for Combined Use with AXFA11
See “Proces Connection”. See “Proces Connection”. See “Proces Connection”. See “Proces Connection”.
ASME B16.5 Class 150 Flange (Carbon Steel)
ASME B16.47 Series A Class 150 Flange (Carbon Steel)
500 mm (20 in.) and 600 mm (24 in.) for lining code F/H/D/U
700 mm (28 in.) to 1000 mm (40 in.) for lining code F/H/D/U
700 mm (28 in.) to 1000 mm (40 in.) for lining code F/H/D/U
1200 mm (48 in.) for lining code H EN1092-1 PN6 Flange (Carbon Steel) EN1092-1 PN10 Flange (Carbon Steel)
(uid pressure up to 0.6 MPa)
1200 mm (48 in.) to 1800 mm (72 in.)
for lining code H
500 mm (20 in.) to 1000 mm (40 in.) EN1092-1 PN10 Flange (Carbon Steel) (uid pressure up to 1 MPa)
for lining code F/H/D/U
1200 mm (48 in.) to 1800 mm (72 in.)
for lining code H
EN1092-1 PN16 Flange (Carbon Steel)
(uid pressure up to 1 MPa)
500 mm (20 in.) to 1000 mm (40 in.)
for lining code F/H/D/U
500 mm (20 in.) to 1000 mm (40 in.)
for lining code F/H/D/U
1200 mm (48 in.) for lining code H
ANSI 1/2 NPT female Not available for Submersible type ISO M20 x 1.5 female Not available for Submersible type
Optional code
/
IM 01E25D11-01EN
<6. OUTLINE>
6-4
For Process Connection JIS F12 (JIS 75M)
Model Sufx Code Description Available Size / Model
AXW500 Size 500 mm (20 in.) Remote Flowtube AXW600 Size 600 mm (24 in.) Remote Flowtube AXW700 Size 700 mm (28 in.) Remote Flowtube AXW800 Size 800 mm (32 in.) Remote Flowtube AXW900 Size 900 mm (36 in.) Remote Flowtube AXW10L Size 1000 mm (40 in.) Remote Flowtube AXW11L Size 1100 mm (44 in.) Remote Flowtube AXW12L Size 1200 mm (48 in.) Remote Flowtube AXW13L Size 1350 mm (54 in.) Remote Flowtube AXW15L Size 1500 mm (60 in.) Remote Flowtube AXW16L Size 1600 mm (64 in.) Remote Flowtube AXW18L Size 1800 mm (72 in.) Remote Flowtube Use G General-purpose type
W Submersible type
Converter -N
Power Supply N Remote Flowtube Lining (*1) U Polyurethane Rubber
Electrode Material (*1)
Electrode Structure 1 Non-replaceable
Grounding Structure (*2) N
Process Connection -CG1 JIS F12 (JIS 75M) Flange (Carbon Steel) Lay Length N Standard Electrical Connection -0 JIS G1/2 female
Indicator N None Calibration B Standard Optional Specications
*1: Users must consider the characteristics of selected wetted parts material and inuence of process uids. The use of inappropriate materials
can result in the leakage of corrosive process uids and cause injury to personnel and/or damage to plant facilities. It is also possible that the instrument itself can be damaged and that fragments from the instrument can contaminate the user’s process uids.
Be very careful with highly corrosive process uids such as hydrochloric acid, sulfuric acid, hydrogen sulde, sodium hypochlorite, and high-
temperature steam (150°C [302°F] or above). Contact Yokogawa for detailed information of the wetted parts material.
*2: Select optional grounding rings (code GR1 or GR2) if necessary. For example, grounding rings are necessary for plastic piping.
The code GR1 is optional only for sizes 500 mm (20 in.) to 1000 mm (40 in.). The code GR2 is optional only for sizes 1100 mm (44 in.) to 1800 mm (72 in.).
*3: “None” is applicable only for metal piping and wiring for grounding will be necessary so that the electric potentials between owtube and piping
ange should be the same.
L JIS SUS316L (AISI 316L SS Equivalent) H Hastelloy C276 Equivalent
-2 ANSI 1/2 NPT female Not available for Submersible type
-4 ISO M20 x 1.5 female Not available for Submersible type
Remote Flowtube for Combined Use with AXFA11
None (*3), available as optional feature (GR1 or GR2)
/
Optional code
IM 01E25D11-01EN
<6. OUTLINE>
6-5

n OPTIONAL SPECIFICATIONS

: Available – : Not available
Applicable Model
Item Specications
General
AXW***G AXW***W
Grounding Rings (*1) JIS SUS304 (AISI 304 SS Equivalent), a set of two rings GR1
Grounding Rings (*2) SUSF304 (AISI 304 SS Equivalent), a set of two rings with gaskets “B”. GR2
For District Heating and Cooling or Condensation-proof
User-specied Signal and Excitation Cable Length
Urethane resin potting is applied in the terminal box of a remote owtube. Select JIS G1/2 for the electrical connections. 30-meter dedicated signal and excitation cables are pre-wired and waterproof glands with union joints are attached at factory.
Available for the submersible type and a model with optional code DHC. The cable length is limited up to 200 meters combined with an AXFA11 converter. Following “L,” specify the cable length in three digits as a multiple of 1 meter (e. g., 001, 002, or 005) for a length up to 5 meters, or as a multiple of 5 meters (i.e., 005, 010, 015, or the like) for a length of 5 meters or more. If this optional code is not selected, a 30-meter length cable is attached.
Mass Unit Setting The ow rate span, transmission pulse weight, and totalizer display pulse weight can be
set in terms of mass unit. Specify the density of the process uid when ordering in addition to the mass ow rate span, transmission pulse weight (for mass unit), and totalizer display pulse weight (for mass unit). When ordering a remote owtube, parameters for 'Mass Unit Setting' will be set in the corresponding converter before shipment.
1. Density a. Available density Numerics:
Specify the numeric within the value of 500 to 2000 kg/m to 124.8 lb/cf. And it can be up to ve digits, to a maximum of 32000 ignoring the decimal point. A fraction is limited to the fourth decimal place.
b. Available density units: kg/m
Example: A water density is about 1000 kg/m3. In this case specify “1000kg/m3”.
However a density is changed by temperature. Specify the actual density. (The 1000 kg/m
3
, lb/gal, lb/cf
3
is equivalent to 8.345lb/gal and 62.43lb/cf.)
3
, 4.2 to 16.7 lb/gal, or 31.2
2. The mass ow rate span, transmission pulse weight, and totalizer display pulse
weight
a. Available density Numerics:
Specify the numeric within the value of 0.0001 to 32000. And it can be up to ve digits, to a maximum of 32000 ignoring the decimal point. A fraction is limited to the fourth decimal place.
b. Mass Units Available mass units: t, kg, g, klb, lb
Available time units: /d, /h, /min, /s
Note1: In case of specifying the mass ow span, calculate the volumetric ow span
by the setting density, and specify the available value in the mass ow span.
Note2: In case of transmission pulse weight and totalizer display pulse weight,
specify the mass unit which was specied as the ow unit.
G3/4 Female Waterproof Glands
Waterproof Glands
Waterproof Glands with Union Joints
Stainless Steel Tag Plate
Waterproof glands for G3/4 conduits or exible tubes are attached to the electrical con­nections. Available only for JIS G1/2 electric connections.
Waterproof glands are attached to the electrical connections. Available only for JIS G1/2 electric connections.
Waterproof glands with union joints are attached to the electrical connections. Available only for JIS G1/2 electric connections.
A pendant tag plate of stainless steel (AISI 304 SS equivalent) is provided in addition to the standard nameplate with the tag number inscribed on it. Dimension (Height x Width): Approx. 12.5 (4.92) x 40 (15.7) mm (inch)
Direction Change of Electrical Connection (*3)
+90 degrees rotated terminal box to change the direction of the electrical connection. RA
+180 degrees rotated terminal box to change the direction of the electrical connection. RB
–90 degrees rotated terminal box to change the direction of the electrical connection. RC
Material Certicate Material certicates are provided for pipe, electrodes, anges, and also optional ground-
ing rings when specied.
Submersible
DHC
L***
MU
EW
EG
EU
SCT
M01
Code
*1: This is not available for models with process connection JIS F12 (JIS 75M) of sizes 1100 mm (44 in.) to 1800 mm (72 in.). Refer to the section
on “Mounting Procedures” on necessary gaskets.
*2: This is available only for models with process connection JIS F12 (JIS 75M) of sizes 1100 mm (44 in.) to 1800 mm (72 in.). Refer to the section
on “Mounting Procedures” on necessary gaskets.
*3: Refer to the image below.
Standard
+90 degree rotation +180 degree rotation –90 degree rotation
Optional Code RA Optional Code RB Optional Code RC
Electrical
Connection
Electrical
Connection
IM 01E25D11-01EN
<6. OUTLINE>
6-6

n OPTIONAL SPECIFICATIONS (continued)

Item Specications
Hydrostatic Test The test veries the absence of leaks by applying the following water pressures (which
Calibration Certi­cate
Five-point Calibra­tion in User-specied Span
are determined under process connection conditions) to lining for ten minutes. Test results are described in the Note column of a test certicate(QIC).
Process Connection: Water Pressure:
EN PN6, EN PN10 (code CEK) 0.9 MPa ASME Class 150, EN PN10 (code CE1), EN PN16, JIS 10K 1.5 MPa AS2129 Table E, AS4087 PN16, JIS F12 (JIS 75M) 1.5 MPa AWWA C207 Class D 1.25 MPa AS2129 Table D 1.05 MPa
Level 2: The Declaration and the Calibration Equipment List are issued. L2
Level 3: The Declaration and the Primary Standard List are issued. L3
Level 4: The Declaration and the Yokogawa Measuring Instruments Control System are issued.
A ow test near 0, 25, 50, 75, and 100% of the user-specied span is performed instead of the ow test of the standard 2m/s span and a test certicate (QIC) is submitted. Specify the span (100% ow span) whose corresponding ow velocity lies between 0.5 to 10 m/s and that is less than the maximum line capacity. Selectable range of ow rate span is shown below.
Size : mm (in.) Selectable range of ow rate span : m (Flow rate span velocity : m/s) 500 (20) 354 (0.5) to 7068 (10.00) 600 (24) 509 (0.5) to 8200 (8.06) 700 (28) 693 (0.5) to 8200 (5.92) 800 (32) 905 (0.5) to 8200 (4.53) 900 (36) 1146 (0.5) to 8200 (3.58) 1000 (40) 1414 (0.5) to 8200 (2.90) 1100 (44) 1711 (0.5) to 8200 (2.40) 1200 (48) 2036 (0.5) to 8200 (2.01) 1350 (54) 2577 (0.5) to 30000 (5.82) 1400 (56) 2771 (0.5) to 30000 (5.41) 1500 (60) 3181 (0.5) to 30000 (4.71) 1600 (64) 3620 (0.5) to 30000 (4.14) 1800 (72) 4581 (0.5) to 30000 (3.27)
: Available – : Not available
Applicable Model
General
AXW***G AXW***W
3
/h
Submersible
T01
L4
SC
Code
IM 01E25D11-01EN
<6. OUTLINE>

n DIMENSIONAL DRAWINGS

AXW500 to AXW10L, Sizes 500 mm (20 in.) to 1000 mm (40 in.)
Ground Terminal (M4)
Eye Bolt
( H2)
ø 86 (3.38)
48 (1.89)
H1
Hr
111 (4.37)
øC
θ°
øD
(ød)
6-7
N- ø h
L (*)
*: The thickness of optional grounding rings (4mm per one) and customer supplied
gaskets are not included in “L” here.
F0603.ai
(1) ASME Flange Type
Unit: mm (approx. in.)
Process Connection Code CA1
Flange Type ASME B16.5 Class150 ASME B16.47 Class150
Size Code 500 600 700 800 900 10L
Size 500 (20) 600 (24) 700 (28) 800 (32) 900 (36) 1000 (40)
Lining Code H, F, U, D
Lay Length L 600 (23.62) 720 (28.35) 840 (33.07) 960 (37.80) 1080 (42.52) 1200 (47.24)
Flange Outer Diameter øD 700 (27.56) 815 (32.09) 927 (36.50) 1060 (41.75) 1168 (46.00) 1289 (50.75)
Bolt Circle Diameter øC 635 (25.00) 749.3 (29.50) 863.6 (34.00) 977.9 (38.50) 1086 (42.75) 1200 (47.25)
Inner Diameter ød Lining H, F, D 477 (18.78) 578 (22.76) 675 (26.57) 777 (30.59) 878 (34.57) 976 (38.43)
Lining U 469 (18.46) 570 (22.44) 667 (26.26) 769 (30.28) 870 (34.25) 968 (38.11)
Bolt Hole Pitch Half Angle θ 6.4° 6.4° 5.6°
Bolt Hole Diameter øh 31.8 (1.25) 34.9 (1.37) 35.1 (1.38) 41.1 (1.62) 41.1 (1.62) 41.1 (1.62)
Number of Bolt Holes N 20 20 28 28 32 36
Height H1 760 (29.92) 875 (34.45) 998 (39.29) 1150 (45.28) 1278 (50.31) 1399 (55.08)
Height H2 408 (16.06) 459 (18.07) 509 (20.04) 560 (22.05) 611 (24.06) 662 (26.06)
Height Hr 812 (31.97) 921 (36.26) 1027 (40.43) 1144 (45.04) 1249 (49.17) 1361 (53.58)
Inner Diameter of Eye Bolt 35 (1.38) 35 (1.38) 40 (1.57) 50 (1.97) 60 (2.36) 60 (2.36)
Approx. Weight, Unit: kg (lb) 212 (467) 305 (672) 479 (1056) 680 (1499) 882 (1944) 1125 (2480)
Note: When submersible type or option code DHC is selected, waterproof glands and a 30-meter length cable are attached. Add 9.5 kg
(20.9 lb) to the weight in the table.
IM 01E25D11-01EN
<6. OUTLINE>
6-8
(2) AWWA Flange Type
Unit: mm (approx. in.)
Process Connection Code CB1
Flange Type AWWA C207 Class D
Size Code 700 800 900 10L
Size 700 (28) 800 (32) 900 (36) 1000 (40)
Lining Code H, F, U, D
Lay Length L 840 (33.07) 960 (37.80) 1080 (42.52) 1200 (47.24)
Flange Outer Diameter øD 927 (36.50) 1060 (41.75) 1168 (46.00) 1289 (50.75)
Bolt Circle Diameter øC 863.6 (34.00) 977.9 (38.50) 1086 (42.75) 1200 (47.25)
Inner Diameter ød Lining H, F, D 675 (26.57) 777 (30.59) 878 (34.57) 976 (38.43)
Lining U 667 (26.26) 769 (30.28) 870 (34.25) 968 (38.11)
Bolt Hole Pitch Half Angle θ 6.4° 6.4° 5.6°
Bolt Hole Diameter øh 34.9 (1.375) 41.3 (1.625) 41.3 (1.625) 41.3 (1.625)
Number of Bolt Holes N 28 28 32 36
Height H1 987 (38.86) 1131 (44.53) 1239 (48.78) 1379 (54.29)
Height H2 509 (20.04) 560 (22.05) 611 (24.06) 662 (26.06)
Height Hr 1027 (40.43) 1144 (45.04) 1249 (49.17) 1361 (53.58)
Inner Diameter of Eye Bolt 35 (1.38) 40 (1.57) 40 (1.57) 50 (1.97)
Approx. Weight, Unit: kg (lb) 288 (635) 387 (853) 485 (1069) 659 (1453)
Note: When submersible type or option code DHC is selected, waterproof glands and a 30-meter length cable are attached. Add 9.5 kg
(20.9 lb) to the weight in the table.
(3) EN PN10 Flange Type
Unit: mm (approx. in.)
Process Connection Code CE1
Flange Type EN1092-1 PN10
Size Code 500 600 700 800 900 10L
Size 500 (20) 600 (24) 700 (28) 800 (32) 900 (36) 1000 (40)
Lining Code H, F, U, D
Lay Length L 600 (23.62) 720 (28.35) 840 (33.07) 960 (37.80) 1080 (42.52) 1200 (47.24)
Flange Outer Diameter øD 670 (26.38) 780 (30.71) 895 (35.24) 1015 (39.96) 1115 (43.90) 1230 (48.43)
Bolt Circle Diameter øC 620 (24.41) 725 (28.54) 840 (33.07) 950 (37.40) 1050 (41.34) 1160 (45.67)
Inner Diameter ød
Bolt Hole Pitch Half Angle θ 7.5° 7.5° 6.4° 6.4°
Bolt Hole Diameter øh 26 (1.02) 30 (1.18) 30 (1.18) 33 (1.30) 33 (1.30) 36 (1.42)
Number of Bolt Holes N 20 20 24 24 28 28
Height H1 730 (28.74) 840 (33.07) 955 (37.60) 1086 (42.76) 1186 (46.69) 1320 (51.97)
Height H2 408 (16.06) 459 (18.07) 509 (20.04) 560 (22.05) 611 (24.06) 662 (26.06)
Height Hr 797 (31.38) 903 (35.51) 1011 (39.80) 1122 (44.17) 1223 (48.15) 1331 (52.40)
Inner Diameter of Eye Bolt 35 (1.38) 35 (1.38) 35 (1.38) 40 (1.57) 40 (1.57) 50 (1.97)
Approx. Weight, Unit: kg (lb) 170 (375) 232 (511) 285 (628) 380 (838) 491 (1082) 646 (1424)
Note: When submersible type or option code DHC is selected, waterproof glands and a 30-meter length cable are attached. Add 9.5 kg
(20.9 lb) to the weight in the table.
Lining H, F, D 477 (18.78) 578 (22.76) 675 (26.57) 777 (30.59) 878 (34.57) 976 (38.43)
Lining U 469 (18.46) 570 (22.44) 667 (26.26) 769 (30.28) 870 (34.25) 968 (38.11)
IM 01E25D11-01EN
<6. OUTLINE>
6-9
(4) EN PN16 Flange Type (uid pressure up to 1 MPa)
Unit: mm (approx. in.)
Process Connection Code CE2
Flange Type EN1092-1 PN16
Size Code 500 600 700 800 900 10L
Size 500 (20) 600 (24) 700 (28) 800 (32) 900 (36) 1000 (40)
Lining Code H, F, U, D
Lay Length L 600 (23.62) 720 (28.35) 840 (33.07) 960 (37.80) 1080 (42.52) 1200 (47.24)
Flange Outer Diameter øD 715 (28.15) 840 (33.07) 910 (35.83) 1025 (40.35) 1125 (44.29) 1255 (49.41)
Bolt Circle Diameter øC 650 (25.59) 770 (30.31) 840 (33.07) 950 (37.40) 1050 (41.34) 1170 (46.06)
Inner Diameter ød
Bolt Hole Pitch Half Angle θ 7.5° 7.5° 6.4° 6.4°
Bolt Hole Diameter øh 33 (1.30) 36 (1.42) 36 (1.42) 39 (1.54) 39 (1.54) 42 (1.65)
Number of Bolt Holes N 20 20 24 24 28 28
Height H1 775 (30.51) 900 (35.43) 970 (38.19) 1096 (43.15) 1196 (47.09) 1345 (52.95)
Height H2 408 (16.06) 459 (18.07) 509 (20.04) 560 (22.05) 611 (24.06) 662 (26.06)
Height Hr 820 (32.28) 933 (36.73) 1018 (40.08) 1127 (44.37) 1228 (48.37) 1344 (52.91)
Inner Diameter of Eye Bolt 35 (1.38) 35 (1.38) 35 (1.38) 40 (1.57) 40 (1.57) 50 (1.97)
Approx. Weight, Unit: kg (lb) 230 (507) 350 (772) 330 (728) 427 (941) 535 (1179) 742 (1636)
Note: When submersible type or option code DHC is selected, waterproof glands and a 30-meter length cable are attached. Add 9.5 kg
(20.9 lb) to the weight in the table.
Lining H, F, D 477 (18.78) 578 (22.76) 675 (26.57) 777 (30.59) 878 (34.57) 976 (38.43)
Lining U 469 (18.46) 570 (22.44) 667 (26.26) 769 (30.28) 870 (34.25) 968 (38.11)
(5) JIS 10K Flange Type
Unit: mm (approx. in.)
Process Connection Code CJ1
Flange Type JIS B2220 10K
Size Code 500 600 700 800 900 10L
Size 500 (20) 600 (24) 700 (28) 800 (32) 900 (36) 1000 (40)
Lining Code H, F, U, D
Lay Length L 600 (23.62) 720 (28.35) 840 (33.07) 960 (37.80) 1080 (42.52) 1200 (47.24)
Flange Outer Diameter øD 675 (26.57) 795 (31.30) 905 (35.63) 1020 (40.16) 1120 (44.09) 1235 (48.62)
Bolt Circle Diameter øC 620 (24.41) 730 (28.74) 840 (33.07) 950 (37.40) 1050 (41.34) 1160 (45.67)
Inner Diameter ød
Bolt Hole Pitch Half Angle θ 7.5° 6.4° 6.4° 6.4°
Bolt Hole Diameter øh 27 (1.06) 33 (1.30) 33 (1.30) 33 (1.30) 33 (1.30) 39 (1.54)
Number of Bolt Holes N 20 20 24 28 28 28
Height H1 735 (28.94) 855 (33.66) 965 (37.99) 1091 (42.95) 1191 (46.89) 1325 (52.17)
Height H2 408 (16.06) 459 (18.07) 509 (20.04) 560 (22.05) 611 (24.06) 662 (26.06)
Height Hr 800 (31.50) 911 (35.87) 1016 (40.00) 1124 (44.25) 1225 (48.23) 1334 (52.2)
Inner Diameter of Eye Bolt 35 (1.38) 35 (1.38) 35 (1.38) 40 (1.57) 40 (1.57) 50 (1.97)
Approx. Weight, Unit: kg (lb) 156 (344) 223 (492) 310 (683) 408 (899) 522 (1151) 689 (1519)
Note: When submersible type or option code DHC is selected, waterproof glands and a 30-meter length cable are attached. Add 9.5 kg
(20.9 lb) to the weight in the table.
Lining H, F, D 477 (18.78) 578 (22.76) 675 (26.57) 777 (30.59) 878 (34.57) 976 (38.43)
Lining U 469 (18.46) 570 (22.44) 667 (26.26) 769 (30.28) 870 (34.25) 968 (38.11)
IM 01E25D11-01EN
<6. OUTLINE>
6-10
(6) AS2129 Table D Flange Type
Unit: mm (approx. in.)
Process Connection Code CS1
Flange Type AS2129 Table D
Size Code 500 600 700 800 900 10L
Size 500 (20) 600 (24) 700 (28) 800 (32) 900 (36) 1000 (40)
Lining Code H, F, U, D
Lay Length L 600 (23.62) 720 (28.35) 840 (33.07) 960 (37.80) 1080 (42.52) 1200 (47.24)
Flange Outer Diameter øD 705 (27.76) 825 (32.48) 910 (35.83) 1060 (41.73) 1175 (46.26) 1255 (49.41)
Bolt Circle Diameter øC 641 (25.24) 756 (29.76) 845 (33.27) 984 (38.74) 1092 (42.99) 1175 (46.26)
Inner Diameter ød
Bolt Hole Pitch Half Angle θ 11.3° 11.3° 7.5° 7.5°
Bolt Hole Diameter øh 26 (1.02) 30 (1.18) 30 (1.18) 36 (1.42) 36 (1.42) 36 (1.42)
Number of Bolt Holes N 16 16 20 20 24 24
Height H1 765 (30.12) 885 (34.84) 970 (38.19) 1131 (44.53) 1265 (49.80) 1345 (52.95)
Height H2 408 (16.06) 459 (18.07) 509 (20.04) 560 (22.05) 611 (24.06) 662 (26.06)
Height Hr 815 (32.09) 926 (36.46) 1018 (40.08) 1144 (45.04) 1253 (49.33) 1344 (52.91)
Inner Diameter of Eye Bolt 35 (1.38) 35 (1.38) 35 (1.38) 40 (1.57) 50 (1.97) 50 (1.97)
Approx. Weight, Unit: kg (lb) 157 (346) 225 (496) 290 (639) 433 (977) 594 (1310) 728 (1605)
Note: When submersible type or option code DHC is selected, waterproof glands and a 30-meter length cable are attached. Add 9.5 kg
(20.9 lb) to the weight in the table.
Lining H, F, D 477 (18.78) 578 (22.76) 675 (26.57) 777 (30.59) 878 (34.57) 976 (38.43)
Lining U 469 (18.46) 570 (22.44) 667 (26.26) 769 (30.28) 870 (34.25) 968 (38.11)
(7) AS2129 Table E Flange Type
Unit: mm (approx. in.)
Process Connection Code CS2
Flange Type AS2129 Table E
Size Code 500 600 700 800 900 10L
Size 500 (20) 600 (24) 700 (28) 800 (32) 900 (36) 1000 (40)
Lining Code H, F, U, D
Lay Length L 600 (23.62) 720 (28.35) 840 (33.07) 960 (37.80) 1080 (42.52) 1200 (47.24)
Flange Outer Diameter øD 705 (27.76) 825 (32.48) 910 (35.83) 1060 (41.73) 1175 (46.26) 1255 (49.41)
Bolt Circle Diameter øC 641 (25.24) 756 (29.76) 845 (33.27) 984 (38.74) 1092 (42.99) 1175 (45.67)
Inner Diameter ød
Bolt Hole Pitch Half Angle θ 11.3° 11.3° 7.5° 7.5°
Bolt Hole Diameter øh 26 (1.02) 33 (1.30) 33 (1.30) 36 (1.42) 36 (1.42) 39 (1.54)
Number of Bolt Holes N 16 16 20 20 24 24
Height H1 765 (30.12) 885 (34.84) 970 (38.19) 1131 (44.53) 1265 (49.80) 1345 (52.95)
Height H2 408 (16.06) 459 (18.07) 509 (20.04) 560 (22.05) 611 (24.06) 662 (26.06)
Height Hr 815 (32.09) 926 (36.46) 1018 (40.08) 1144 (45.04) 1253 (49.33) 1344 (52.91)
Inner Diameter of Eye Bolt 35 (1.38) 35 (1.38) 35 (1.38) 40 (1.57) 50 (1.97) 50 (1.97)
Approx. Weight, Unit: kg (lb) 184 (406) 288 (635) 354 (780) 508 (1120) 703 (1550) 832 (1834)
Note: When submersible type or option code DHC is selected, waterproof glands and a 30-meter length cable are attached. Add 9.5 kg
(20.9 lb) to the weight in the table.
Lining H, F, D 477 (18.78) 578 (22.76) 675 (26.57) 777 (30.59) 878 (34.57) 976 (38.43)
Lining U 469 (18.46) 570 (22.44) 667 (26.26) 769 (30.28) 870 (34.25) 968 (38.11)
IM 01E25D11-01EN
<6. OUTLINE>
6-11
(8) AS4087 PN16 Flange Type
Unit: mm (approx. in.)
Process Connection Code CT1
Flange Type AS4087 PN16
Size Code 500 600 700 800 900 10L
Size 500 (20) 600 (24) 700 (28) 800 (32) 900 (36) 1000 (40)
Lining Code H, F, U, D
Lay Length L 600 (23.62) 720 (28.35) 840 (33.07) 960 (37.80) 1080 (42.52) 1200 (47.24)
Flange Outer Diameter øD 705 (27.76) 825 (32.48) 910 (35.83) 1060 (41.73) 1175 (46.26) 1255 (49.41)
Bolt Circle Diameter øC 641 (25.24) 756 (29.76) 845 (33.27) 984 (38.74) 1092 (42.99) 1175 (45.67)
Inner Diameter ød
Bolt Hole Pitch Half Angle θ 11.3° 11.3° 7.5° 7.5°
Bolt Hole Diameter øh 26 (1.02) 30 (1.18) 30 (1.18) 36 (1.42) 36 (1.42) 36 (1.42)
Number of Bolt Holes N 16 16 20 20 24 24
Height H1 765 (30.12) 885 (34.84) 970 (38.19) 1131 (44.53) 1265 (49.80) 1345 (52.95)
Height H2 408 (16.06) 459 (18.07) 509 (20.04) 560 (22.05) 611 (24.06) 662 (26.06)
Height Hr 815 (32.09) 926 (36.46) 1018 (40.08) 1144 (45.04) 1253 (49.33) 1344 (52.91)
Inner Diameter of Eye Bolt 35 (1.38) 35 (1.38) 35 (1.38) 40 (1.57) 50 (1.97) 50 (1.97)
Approx. Weight, Unit: kg (lb) 184 (406) 288 (635) 374 (825) 520 (1146) 716 (1579) 826 (1821)
Note: When submersible type or option code DHC is selected, waterproof glands and a 30-meter length cable are attached. Add 9.5 kg
(20.9 lb) to the weight in the table.
Lining H, F, D 477 (18.78) 578 (22.76) 675 (26.57) 777 (30.59) 878 (34.57) 976 (38.43)
Lining U 469 (18.46) 570 (22.44) 667 (26.26) 769 (30.28) 870 (34.25) 968 (38.11)
(9) JIS F12 (JIS 75M) Flange Type
Unit: mm (approx. in.)
Process Connection Code CG1
Flange Type JIS G3443-2 F12
Size Code 500 600 700 800 900 10L
Size 500 (20) 600 (24) 700 (28) 800 (32) 900 (36) 1000 (40)
Lining Code U
Lay Length L 600 (23.62) 720 (28.35) 840 (33.07) 960 (37.80) 1080 (42.52) 1200 (47.24)
Flange Outer Diameter øD 706 (27.80) 810 (31.89) 928 (36.54) 1034 (40.71) 1156 (45.51) 1262 (49.69)
Bolt Circle Diameter øC 639 (25.16) 743 (29.25) 854 (33.62) 960 (37.80) 1073 (42.24) 1179 (46.42)
Inner Diameter ød
Bolt Hole Pitch Half Angle θ 15° 11.3° 11.3° 7.5°
Bolt Hole Diameter øh 27 (1.06) 27 (1.06) 33 (1.30) 33 (1.30) 33 (1.30) 33 (1.30)
Number of Bolt Holes N 12 16 16 20 20 24
Height H1 766 (30.16) 870 (34.25) 988 (38.90) 1105 (43.50) 1227 (48.31) 1352 (53.23)
Height H2 408 (16.06) 459 (18.07) 509 (20.04) 560 (22.05) 611 (24.06) 662 (26.06)
Height Hr 816 (32.13) 919 (36.18) 1028 (40.47) 1132 (44.57) 1245 (49.02) 1349 (53.11)
Inner Diameter of Eye Bolt 35 (1.38) 35 (1.38) 35 (1.38) 40 (1.57) 40 (1.57) 50 (1.97)
Approx. Weight, Unit: kg (lb) 168 (370) 228 (503) 319 (703) 404 (891) 540 (1190) 703 (1550)
Note: When submersible type or option code DHC is selected, waterproof glands and a 30-meter length cable are attached. Add 9.5 kg
(20.9 lb) to the weight in the table.
Lining U 469 (18.46) 570 (22.44) 667 (26.26) 769 (30.28) 870 (34.25) 968 (38.11)
IM 01E25D11-01EN
<6. OUTLINE>
6-12
Optional Grounding Rings (GR1) for sizes 500 mm (20 in.) to 1000 mm (40 in.)
ø25 (0.98)
L2
L1
øD
(ød)
L2
L1
F0604.ai
Unit: mm (approx. in.)
Process Connection Code CA1, CB1, CE1, CE2, CJ1, CS1, CS2, CT1, CG1
Size Code 500 600 700 800 900 10L
Size 500 (20) 600 (24) 700 (28) 800 (32) 900 (36) 1000 (40)
Lining Code H, F, U, D
Ring Outer Diameter øD 590 (23.23) 690 (27.17) 799 (31.46) 906 (35.67) 1006 (39.61) 1116 (43.94)
Ring Inner Diameter ød 485 (19.09) 586 (23.07) 683 (26.89) 787 (30.98) 888 (34.96) 986 (38.82)
Length L1 410 (16.14) 477.5 (18.80) 517.5 (20.37) 586 (23.07) 640 (25.20) 697.5 (27.46)
Length L2 390 (15.35) 457.5 (18.01) 497.5 (19.59) 566 (22.28) 620 (24.41) 677.5 (26.67)
Thickness 4 (0.16)
Approx. Weight, Unit: kg (lb) 3.1 (6.8) 3.7 (8.1) 4.6 (10.2) 5.4 (12.0) 6.0 (13.3) 7.3 (16.1)
IM 01E25D11-01EN
<6. OUTLINE>
AXW11L to AXW18L, Sizes 1100 mm (44 in.) to 1800 mm (72 in.)
111 (4.37)
θ°
Eye Plate
ø86 (3.38)Ground Terminal (M4)
48 (1.89)
4-M8 (for Grounding Ring) (Except for JIS F12 flange models)
6-13
N-øh
(H2)
L (*)
Hr
T
*: The thickness of optional grounding rings (5 mm for GR1 and
25 mm for GR2 per one) and customer supplied gaskets are
not included in “L” here.
øC2 (M8)
øC1 (øh)
øD
(ød)
F0605.ai
(1) AWWA Flange Type
Unit: mm (approx. in.)
Process Connection Code CB1
Flange Type AWWA C207 Class D
Size Code 12L
Size 1200 (48)
Lining Code H
Lay Length L 1440 (56.69)
Flange Outer Diameter øD 1511.3 (59.50)
Flange Bolt Circle Diameter øC1 1422.4 (56.00)
Ring Bolt Circle Diameter øC2 1426 (56.14)
Inner Diameter ød
Bolt Hole Pitch Half Angle θ 4.1°
Bolt Hole Diameter øh 41.3 (1.625)
Number of Bolt Holes N 44
Height H2 770 (30.31)
Height Hr 1580 (62.20)
Inner Diameter of Eye Plate 60 (2.36)
Approx. Weight, Unit: kg (lb) 930 (2050)
Note: When submersible type or option code DHC is selected, waterproof glands and a 30-meter length cable are attached. Add 9.5 kg
(20.9 lb) to the weight in the table.
Lining H 1189 (46.81)
IM 01E25D11-01EN
<6. OUTLINE>
6-14
(2) EN PN6 Flange Type
Unit: mm (approx. in.)
Process Connection Code CEJ
Flange Type EN1092-1 PN6
Size Code 12L 14L 16L 18L
Size 1200 (48) 1400 (56) 1600 (64) 1800 (72)
Lining Code H
Lay Length L 1440 (56.69) 1680 (66.14) 1920 (75.59) 2160 (85.04)
Flange Outer Diameter øD 1405 (55.31) 1630 (64.17) 1830 (72.05) 2045 (80.51)
Flange Bolt Circle Diameter øC1 1340 (52.76) 1560 (61.42) 1760 (69.29) 1970 (77.56)
Ring Bolt Circle Diameter øC2 1356 (53.39) 1572 (61.89) 1772 (69.76) 1981 (77.99)
Inner Diameter ød
Bolt Hole Pitch Half Angle θ 5.6° 4.5° 4.1°
Bolt Hole Diameter øh 33 (1.30) 36 (1.42) 36 (1.42) 39 (1.54)
Number of Bolt Holes N 32 36 40 44
Height H2 770 (30.31) 873 (34.37) 969 (38.15) 1068 (42.05)
Height Hr 1527 (60.12) 1742 (69.49) 1938 (76.30) 2145 (84.45)
Inner Diameter of Eye Plate 60 (2.36) 70 (2.76) 70 (2.76) 80 (3.15)
Approx. Weight, Unit: kg (lb) 620 (1367) 920 (2028) 1310 (2888) 1670 (3682)
Note: When submersible type or option code DHC is selected, waterproof glands and a 30-meter length cable are attached. Add 9.5 kg
(20.9 lb) to the weight in the table.
Lining H 1195 (47.05) 1398 (55.04) 1586 (62.44) 1784 (70.24)
(3) EN PN10 Flange Type (uid pressure up to 0.6 MPa)
Unit: mm (approx. in.)
Process Connection Code CEK
Flange Type EN1092-1 PN10
Size Code 12L 14L 16L 18L
Size 1200 (48) 1400 (56) 1600 (64) 1800 (72)
Lining Code H
Lay Length L 1440 (56.69) 1680 (66.14) 1920 (75.59) 2160 (85.04)
Flange Outer Diameter øD 1455 (57.28) 1675 (65.94) 1915 (75.39) 2115 (83.27)
Flange Bolt Circle Diameter øC1 1380 (54.33) 1590 (62.60) 1820 (71.65) 2020 (79.53)
Ring Bolt Circle Diameter øC2 1391 (54.76) 1596 (62.83) 1822 (71.73) 2022 (79.61)
Inner Diameter ød
Bolt Hole Pitch Half Angle θ 5.6° 4.5° 4.1°
Bolt Hole Diameter øh 39 (1.54) 42 (1.65) 48 (1.89) 48 (1.89)
Number of Bolt Holes N 32 36 40 44
Height H2 770 (30.31) 873 (34.37) 969 (38.15) 1068 (42.05)
Height Hr 1552 (61.10) 1765 (69.49) 1981 (77.99) 2180 (85.83)
Inner Diameter of Eye Plate 60 (2.36) 70 (2.76) 70 (2.76) 80 (3.15)
Approx. Weight, Unit: kg (lb) 790 (1742) 1120 (2469) 1720 (3792) 2130 (4696)
Note: When submersible type or option code DHC is selected, waterproof glands and a 30-meter length cable are attached. Add 9.5 kg
(20.9 lb) to the weight in the table.
Lining H 1195 (47.05) 1398 (55.04) 1586 (62.44) 1784 (70.24)
IM 01E25D11-01EN
<6. OUTLINE>
6-15
(4) EN PN10 Flange Type
Unit: mm (approx. in.)
Process Connection Code CE1
Flange Type EN1092-1 PN10
Size Code 12L 14L 16L 18L
Size 1200 (48) 1400 (56) 1600 (64) 1800 (72)
Lining Code H
Lay Length L 1440 (56.69) 1680 (66.14) 1920 (75.59) 2160 (85.04)
Flange Outer Diameter øD 1455 (57.28) 1675 (65.94) 1915 (75.39) 2115 (83.27)
Flange Bolt Circle Diameter øC1 1380 (54.33) 1590 (62.60) 1820 (71.65) 2020 (79.53)
Ring Bolt Circle Diameter øC2 1391 (54.76) 1596 (62.83) 1822 (71.73) 2022 (79.61)
Inner Diameter ød
Bolt Hole Pitch Half Angle θ 5.6° 4.5° 4.1°
Bolt Hole Diameter øh 39 (1.54) 42 (1.65) 48 (1.89) 48 (1.89)
Number of Bolt Holes N 32 36 40 44
Height H2 770 (30.31) 873 (34.37) 969 (38.15) 1068 (42.05)
Height Hr 1552 (61.10) 1765 (69.49) 1981 (77.99) 2180 (85.83)
Inner Diameter of Eye Plate 60 (2.36) 70 (2.76) 70 (2.76) 80 (3.15)
Approx. Weight, Unit: kg (lb) 920 (2028) 1340 (2954) 1860 (4101) 2510 (5534)
Note: When submersible type or option code DHC is selected, waterproof glands and a 30-meter length cable are attached. Add 9.5 kg
(20.9 lb) to the weight in the table.
Lining H 1189 (16.81) 1390 (54.72) 1582 (62.28) 1776 (69.92)
(5) AS2129 Table D, AS2129 Table E, AS4087 PN16 Flange Type
Unit: mm (approx. in.)
Process Connection Code CS1 CS2 CT1
Flange Type AS2129 Table D AS2129 Table E AS4087 PN16
Size Code 12L 12L 12L
Size 1200 (48) 1200 (48) 1200 (48)
Lining Code H
Lay Length L 1440 (56.69) 1440 (56.69) 1440 (56.69)
Flange Outer Diameter øD 1490 (58.66) 1490 (58.66) 1490 (58.66)
Flange Bolt Circle Diameter øC1 1410 (55.51) 1410 (55.51) 1410 (55.51)
Ring Bolt Circle Diameter øC2 1426 (56.14) 1426 (56.14) 1426 (56.14)
Inner Diameter ød
Bolt Hole Pitch Half Angle θ 5.6° 5.6° 5.6°
Bolt Hole Diameter øh 36 (1.42) 39 (1.54) 36 (1.42)
Number of Bolt Holes N 32 32 32
Height H2 770 (30.31) 770 (30.31) 770 (30.31)
Height Hr 1570 (61.81) 1570 (61.81) 1570 (61.81)
Inner Diameter of Eye Plate 60 (2.36) 60 (2.36) 60 (2.36)
Approx. Weight, Unit: kg (lb) 1050 (2315) 1210 (2668) 1180 (2601)
Note: When submersible type or option code DHC is selected, waterproof glands and a 30-meter length cable are attached. Add 9.5 kg
(20.9 lb) to the weight in the table.
Lining H 1189 (46.81) 1189 (46.81) 1189 (46.81)
IM 01E25D11-01EN
<6. OUTLINE>
6-16
(6) JIS F12 (JIS 75M) Flange Type
Unit: mm (approx. in.)
Process Connection Code CG1
Flange Type JIS G3443-2 F12
Size Code 11L 12L 13L 15L 16L 18L
Size 1100 (44) 1200 (48) 1350 (54) 1500 (60) 1600 (64) 1800 (72)
Lining Code U
Lay Length L 1320 (51.97) 1440 (56.69) 1620 (63.78) 1800 (70.87) 1920 (75.59) 2160 (85.04)
Flange Outer Diameter øD 1366 (53.78) 1470 (57.87) 1642 (64.65) 1800 (70.87) 1915 (75.39) 2115 (83.27)
Bolt Circle Diameter øC 1283 (50.51) 1387 (54.61) 1552 (61.10) 1710 (67.32) 1820 (71.65) 2020 (79.53)
Grounding Ring Inner Diameter ød
Bolt Hole Pitch Half Angle θ 7.5° 6.4° 6.4° 5.6° 4.1°
Bolt Hole Diameter øh 33 (1.30) 33 (1.30) 39 (1.54) 39 (1.54) 39 (1.54) 39 (1.54)
Number of Bolt Holes N 24 28 28 32 36 44
Height H2 720 (28.35) 770 (30.31) 873 (34.37) 921 (36.26) 969 (38.15) 1068 (42.05)
Height Hr 1457 (57.36) 1560 (61.42) 1723 (67.83) 1875 (73.82) 1981 (77.99) 2180 (85.83)
Inner Diameter of Eye Plate 60 (2.36) 60 (2.36) 70 (2.76) 70 (2.76) 70 (2.76) 80 (3.15)
Approx. Weight, Unit: kg (lb) 910 (2006) 1060 (2337) 1430 (3153) 1770 (3902) 2090 (4608) 2890 (6371)
Note: When submersible type or option code DHC is selected, waterproof glands and a 30-meter length cable are attached. Add 9.5 kg
(20.9 lb) to the weight in the table.
Lining U 1071 (42.17) 1172 (46.14) 1322 (52.05) 1469 (57.83) 1565 (61.61) 1759 (69.25)
IM 01E25D11-01EN
<6. OUTLINE>
Optional Grounding Rings (GR1) for sizes 1200 mm (48 in.) to 1800 mm (72 in.)
ø35 (1.38)
L2
øD
øC
(ød)
ø11 (0.43)
L1
6-17
L1 L1
F0606.ai
Unit: mm (approx. in.)
Process Connection Code
CB1, CS1,
CS2,CT1
CEJ CEK, CE1
AWWA C207-D
Flange Type
AS2129-D,E
EN PN6 EN PN10
AS4087 PN16
Size Code 12L 12L 14L 16L 18L 12L 14L 16L 18L
Size
1200
(48)
1200
(48)
1400
(56)
1600
(64)
1800
(72)
1200
(48)
1400
(56)
1600
(64)
1800
(72)
Lining Code H
Ring Outer Diameter øD
Ring Inner Diameter ød
Bolt Circle Diameter øC
Length L1
Length L2
1370
(53.94)
1195
(47.05)
1426
(56.14)
735
(28.94)
815
(32.09)
1300
(51.18)
1201
(47.28)
1356
(53.39)
700
(27.56)
780
(30.71)
1516
(59.69)
1404
(55.28)
1572
(61.89)
808
(31.81)
888
(34.96)
1716
(67.56)
1592
(62.68)
1772
(69.76)
908
(35.75)
988
(38.90)
1925
(75.79)
1790
(70.47)
1981
(77.99)
1012.5
(39.86)
1092.5
(43.01)
1335
(52.56)
1195
(47.05)
1391
(54.76)
717.5
(28.25)
797.5
(31.40)
1540
(60.63)
1396
(54.96)
1596
(62.83)
820
(32.28)
900
(35.43)
1766
(69.53)
1588
(62.52)
1822
(71.73)
933
(36.73)
1013
(39.88)
1966
(77.40)
1782
(70.16)
2022
(79.61)
1033
(40.67)
1113
(43.82)
Thickness 5 (0.20)
Approx. Weight, Unit: kg (lb)
14.6
(32.2)
8.2
(18.1)
10.7
(23.6)
13.3
(29.3)
16.2
(35.7)
11.6
(25.6)
13.7
(30.2)
19.2
(42.3)
22.1
(48.7)
IM 01E25D11-01EN
<6. OUTLINE>
Optional Grounding Rings (GR2) for sizes 1100 mm (44 in.) to 1800 mm (72 in.)
Unit: mm (approx. in.)
Process Connection Code CG1
Flange Type JIS F12 (JIS 75M)
Size Code 11L 12L 13L 15L 16L 18L
Size
Lining Code U
Thickness 25 (0.98)
Approx. Weight, Unit: kg (lb)
*: Optional grounding rings (GR2) have no protruding brackets and are installed and locked onto the owtube with gaskets B when
shipped from factory. Refer to “CAUTIONS FOR INSTALLATION”.
1100
(44)
59.3
(131)
1200
(48)
65.7
(145)
1350
(54)
75.8
(167)
1500
(60)
88.3
(195)
1600
(64)
92.4
(204)
1800
(72)
114.2 (252)
6-18
IM 01E25D11-01EN
<6. OUTLINE>
Note: Unless otherwise specied, refer to the following table for tolerance in the dimensions.
General tolerance in the dimensional outline drawing.
Unit: mm (approx. in.)
Category of basic dimension
Above Equal or below Above Equal or below
3 (0.12) 3 (0.12) 6 (0.24)
10 (0.39) 18 (0.71) 30 (1.18) 50 (1.97)
80 (3.15) 120 (4.72) 180 (7.09) 250 (9.84)
315 (12.40) 400 (15.75)
6 (0.24) 10 (0.39) 18 (0.71) 30 (1.18) 50 (1.97) 80 (3.15)
120 (4.72) 180 (7.09)
250 (9.84) 315 (12.40) 400 (15.75) 500 (19.69)
Tolerance
±0.7 (±0.03) ±0.9 (±0.04)
±1.1 (±0.04) ±1.35 (±0.05) ±1.65 (±0.06) ±1.95 (±0.08)
±2.3 (±0.09)
±2.7 (±0.11)
±3.15 (±0.12)
±3.6 (±0.14) ±4.05 (±0.16) ±4.45 (±0.18) ±4.85 (±0.19)
Category of basic dimension
500 (19.69) 630 (24.80)
800 (31.50) 1000 (39.37) 1250 (49.21) 1600 (62.99) 2000 (78.74) 2500 (98.43)
1000 (39.37) 1250 (49.21) 1600 (62.99) 2000 (78.74) 2500 (98.43)
3150 (124.02)
630 (24.80) 800 (31.50)
Remarks: The numeric is based on criteria of tolerance class IT18 in JIS B 0401.

n SIZING DATA

Note: Measurable ow velocity is from 0 m/s.
SI Units
10.0
500
600
700
800
Tolerance
±5.5 (±2.17)
±6.25 (±0.25)
±7.0 (±0.28) ±8.25 (±0.32) ±9.75 (±0.38)
±11.5 (±0.45) ±14.0 (±0.55) ±16.5 (±0.65)
1100
900
1000
1200
Size: mm
1350
1400
6-19
1600
1500
1800
1.0
Flow velocity (m/s)
0.3
0.1
10 100 1,000 10,000 100,000
3
Flowrate (m
English Units
33
/h)
64
48
54
40
56
44
36
24
20
28
32
10
1
Flow velocity (ft/s)
0.33 10 100 1,000 10,000 100,000 1,000,000
Flowrate (GPM)
F0607.ai
Size: inch
72
F0608.ai
IM 01E25D11-01EN
Blank Page

Revision Information

Title : AXW Magnetic Flowmeter Remote Flowtube
Manual No. : IM 01E25D11-01EN
Edition Data Page Revised Item
1st Mar. 2012 New publication
2nd Sep. 2013 Addition of sizes from 1100 mm (44 in.) to 1800 mm (72 in.).
Addition of lining material and ange standard.
IM 01E25D11-01EN
Loading...