YOKOGAWA 99025 User Manual

r
User’s Manual
99025 Clamp Adapter
IM 99025
Precautions for Safe Use of the Instrument
When handling the instrument, ALWAYS observe all of the cautionary notes on safety given below. Yokogawa M&C Corporation is not at all liable for damage resulting from misuse of this product by the user that is contrary to these cautionary notes.
The instrument and this manual use the following safety symbols:
WARNING
Indicates that there is a possibility of serious personal injury or loss of life if the operating procedure is not followed correctly and describes the precautions for avoiding such injury or loss of life.
CAUTION
Indicates that there is a possibility of serious personal injury of damage to the instrument if the operating procedure is not followed correctly and describes the precautions for avoiding such injury or damage.
NOTE
Draws attention to information essential for understanding the operation and features.
1st Edition: Apr.2003(MC)
IM 99025
WARNING
Never make measurement on a circuit above 300V AC.
Do not use the instrument in an atmosphere where any flammable or explosive
gas present.
Avoid using the instrument if it has been exposed to rain or moisture or if your hands are wet.
Do not exceed the maximum allowable input of any measurement range.
As to current measurement of more than 1000A, do not make measurement
continuously.
The main unit is heated, so there is danger which damages safety.
Do not use the instrument if there is any damage to the casing or when the casing is removed.
Do not install substitute parts or make any modification to the instrument.
WARNING
To avoid damage to the instrument or electric shock! The restrictions on the maximum voltage level for which the 99025 testers can be used, depend on the over-voltage categories specified by the safety standards. These category specifications are formulated to protect operators against transient impulse voltage in power lines.
Function
A
Over-voltage category I (CAT.I):
Signal level, special equipment or parts of equipment, telecommunication, electronic etc., with smaller transient over-voltages than CAT.II.
Over-voltage category II (CAT.II)
Local level, appliance, portable equipment etc., with smaller transient over-voltages than CAT.III. Over-voltage category III (CAT.III): Distribution level, fixed installation, with smaller transient over-voltages than CAT.IV.
Maximum Allowable Input
OVERVOLTAGE CATEGORY III
Measuring circuit voltage : AC 300V rms
AC 3000A rms
CATION
Do not expose the instrument to the direct sun, extreme temperatures or dew fall.
NOTE
If equipment generating strong electromagnetic interference is located nearly,
the testers may malfunction.
1. Features
Model 99025 are designed to increase the measuring capability of your clamp-on testers. With the use of the Clamp Adapter, you can not only extend current ranges, but clamp on a conductor of a larger diameter.
2. How to Use
(1) Clamp your clamp-on tester on the pick-up coil of the Clamp Adapter. Then
clamp the Clamp Adapter on the conductor as shown bellow.
(2) When you use Clamp Adapter for power or power factor measurement;
Clamp your clamp-on tester on the pick-up coil of the Clamp Adapter, assuming that the arrow mark on the pick-up coil points the load side.
Then clamp the Clamp Adapter on the conductor so that the arrow mark on
the Clamp Adapter jaw points the load side of the conductor.
Conductor
Transformer Jaws
Arrow Mark
Clamp Adapter
Arrow Mark
Clamp-on Tester
Pick-up Coil
3. SPECIFICATIONS
Measuring Range 0 to 3000A AC Input / Output 10 : 1 Accuracy ±2% of input ±0.5A Withstand Voltage 3700V AC for one minute Dimensions Clamp Adapter except Pick-up coil
45(W) X 40(H) X 10(D)mm Weight Approx. 750g Conductor Size 100mm max. Diameter
Frequency 50Hz / 60Hz Duty Cycle Continuous for 0 to 1000A
Safety Standards EN 61010-1 EN 61010-2-032 AC 300V CAT. III / AC 600V CAT. II, Pollution degree2 Accessories Carrying Case (Model 93035) 1
After-sales Service Should any failure occur while you are using the tester, follow the instructions given below. If the adapter still fails to operate correctly and needs repair, contact the vendor from whom you purchased the instrument or the nearest Yokogawa M&C sales office.
150(W) X 317(H) X 33(D)mm Pick-up coil
100 X 150mm Bus-Bar
10 minutes for 1000 to 1500A 30 seconds for 1500 to 3000A
YOKOGAWA M&C CORPORATION International Sales Dept.
2-9-32 Nakacho, Musashino-shi, Tokyo, 180-8750 Japan Phone: 81-422-52-5716 Facs imile: 81-422-55-8654
YOKOGAWA CORPORATION OF AMERICA (U.S.A.)
Phone: 1-770-253-7000 Facs imile: 1-770-251-2088
YOKOGAWA EUROPE B. V. (THE NETHERLANDS)
Phone: 31-334-64-1611 Facsimile: 31-334-64-1610
YOKOGAWA AMERICA DO SUL S. A. (BRAZIL)
Phone: 55-11-5681-2400 Facsimile: 55-11-5681-1274
YOKOGAWA ENGINEERING INSTRUMENTS KOREA CORPORATION (KOREA)
Phone: 82-2-551-0660 to -0664 Facsimile: 82-2-551-0665
YOKOGAWA AUSTRALIA PTY. LTD. (AUSTRALIA)
Phone: 61-2-9805-0699 Facs imile: 61-2-9888-1844
YOKOGAWA BLUE STAR LTD. (INDIA)
Phone: 91-80-227-1513 Facs imile: 91-80-227-4270
LTD. YOKOGAWA ELECTRIC (RUSSIAN FEDERATION)
Phone: 7-095-737-7868 Facs imile: 7-095-737-7869
計測機器営業部
180-8750 東京都武蔵野市中町 2-9-32 電話:0422-52-5984 ファクシミリ:0422-55-8953
関西支店
564-0063 大阪府吹田市江坂町 1-23-101 大同生命江坂ビル 10 階 電話:06-6368-7041 ファクシミリ:06-6368-7045
中部支店
450-0003 名古屋市中村区名駅南 1-27-2 日本生命笹島ビル 12 階 電話:052-581-7490 ファクシミリ:052-581-7664
広島営業所
730-0037 広島市中区中町 8-12 広島グリーンビル8階 電話:082-240-7676 ファクシミリ:082-541-4567
九州営業所
812-0037 福岡市博多区御供所町 3-21 大博通りビジネスセンター7 階 電話:092-262-5740 ファクシミリ:092-262-5741
本社
180-5679 東京都武蔵野市中町 2-9-32 電話:0422-52-5679 ファクシミリ:0422-51-8455
KIM1JE-2003.2
Loading...