Yaskawa RS-232C User Manual

YASKAWA AC Drive-J1000 Option
RS-232C Interface
Technical Manual
Type
SI-232/J, SI-232/JC
J1000オプションユニット
RS-232C
オプションユニット
取扱説明書
形式 
SI-232/J, SI-232/JC
製品を安全にお使い頂くために,本書を必ずお読みください。 また,本書をお手元に保管していただくとともに,最終的に本製品をご使用になる ユーザー様のお手元に確実に届けられるよう,お取り計らい願います。
MANUAL NO. TOBP C730600 32A
インタフェース
J1000

Contents

1 PREFACE AND SAFETY . . . . . . .5
2 RECEIVING . . . . . . . . . . . . . . . . . . 9
3 PRODUCT OVERVIEW . . . . . . . .11
4 OPTION COMPONENTS. . . . . . .12
5 INSTALLATION PROCEDURE . .14 6 RELATED DRIVE PARAMETERS . . .20
7 TROUBLESHOOTING. . . . . . . . .21
8 SPECIFICATIONS . . . . . . . . . . . .22
9 YASKAWA LOCATIONS. . . . . . . 23
10 REVISION HISTORY . . . . . . . . .24
TOBPC73060032A RS-232C Interface Technical Manual 3
Copyright © 2007 YASKAWA ELECTRIC CORPORATION
All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form or by any means, mechanical, electronic, photocopying, recording, or otherwise, without the prior written permission of Yaskawa. No patent liability is assumed with respect to the use of the information contained herein. Moreover, because Yaskawa is constantly striving to improve its high-quality products, the information contained in this manual is subject to change without notice. Every precaution has been taken in the preparation of this manual. Yaskawa assumes no responsibility for errors or omissions. Neither is any liability assumed for damages resulting from the use of the information contained in this publication.
4 YASKAWA ELECTRIC TOBPC73060032A RS-232C Interface Technical Manual

1 Preface and Safety

J1000
1 Preface and Safety

Applicable Documentation

The following manuals are available for the RS-232C Interface Option:
Option Unit
Yaskawa AC Drive -RS-232C Interface Option Technical Manual
Read this manual first. The Technical Manual is packaged with the RS-232C Interface Option and contains a basic overview of wiring, settings, functions, and fault diagnoses.
YASKAWA ELECTRIC TOBPC73060032A RS-232C Interface Technical Manual 5
1 Preface and Safety
Yaskawa Drive
U.S. and Europe: Yaskawa AC Drive J1000 Quick Start Guide Other areas: Yaskawa AC Drive J1000 Installation & Start-Up Manual
Yaskawa AC Drive­J1000 Technical Manual
To obtain instruction manuals for Yaskawa products access these sites: U.S.: http:// www.yaskawa.com Europe: http:// www.yaskawa.eu.com Japan: http://www.e­mechatronics.com Other areas: contact a Yaskawa representative. For questions, contact the local Yaskawa sales office or the nearest Yaskawa representative.

Terms

Note: Indicates a supplement or precaution that
does not cause drive damage.
Drive: Yaskawa AC Drive -J1000 Series
Option:
6 YASKAWA ELECTRIC TOBPC73060032A RS-232C Interface Technical Manual
Yaskawa AC Drive -J1000 RS-232C Interface Option
1 Preface and Safety
DANGER
W ARNING

Registered Trademarks

• Other company names and product names listed in this manual are registered trademarks of those companies.

Supplemental Safety Information

Read and understand this manual before installing, operating, or servicing this option unit. The option unit must be installed according to this manual and local codes.
The following conventions are used to indicate safety messages in this manual. Failure to heed these messages could result in serious or possibly even fatal injury or damage to the products or to related equipment and systems.
Indicates a hazardous situation, which, if not avoided, will result in death or serious injury.
Indicates a hazardous situation, which, if not avoided, could result in death or serious injury.
YASKAWA ELECTRIC TOBPC73060032A RS-232C Interface Technical Manual 7
1 Preface and Safety
CAUTION
NOTICE
Indicates a hazardous situation, which, if not avoided, could result in minor or moderate injury.
Indicates an equipment damage message.
8 YASKAWA ELECTRIC TOBPC73060032A RS-232C Interface Technical Manual

2 Receiving

2 Receiving

Receiving

Confirm the packaging after receiving the RS-232C Interface Option. If the wrong model is received or the RS-232C Interface Option does not function properly, contact your supplier.
Components packaged with the option:
• The RS-232C Interface for copy unit/PC communication (SI­232/J or SI-232/JC)
• Technical manual

Additional Parts (Sold Separately)

Option
Drive Wizard Plus
PC Interface Cable
USB Copy Unit JVOP-181
YASKAWA ELECTRIC TOBPC73060032A RS-232C Interface Technical Manual 9
Part
Number
-
WV103 D-sub 9 pin - RJ-45
Comments
Available for download from e-mechatronics. www.e-mechatronics.com for or at www.yaskawa.com in the U.S.
Provided with an RJ-45 cable and a USB cable
2 Receiving
Blade width
3.0 mm max.
0.6 mm max.
Blade thickness
Option
LED Operator JVOP-182
LED Operator Cable
Part
Number
1 meter: WV001 3 meter: WV003
Comments
Available soon (Contact Yaskawa for detail)
CAT5e UTP straight-through cable with RJ-45 8 pin connector

Tool Requirements

Use a flat-blade screwdriver with the dimensions below for installation or removal of the option cover and RS-232C option.
10 YASKAWA ELECTRIC TOBPC73060032A RS-232C Interface Technical Manual

3 Product Overview

3 Product Overview

About this Product

The RS-232C Interface Option allows the drive to be connected to a network or external device.
Possible connected devices include:
• LED Operator
• Personal computer using DriveWizard Plus
•USB Copy Unit
These devices can be used to edit, view, and copy parameter settings in the drive.
SI-232/JC can be more easily connected and disconnected than SI­232/J. This is useful when copying parameter settings between multiple drives.

Applicable Models

The RS-232C Option can be used with Yaskawa drive models in the table below.
Drive Drive Software Version <1>
CIMR-JABA 1010
<1> See “PRG” on the drive nameplate for software version
number.
YASKAWA ELECTRIC TOBPC73060032A RS-232C Interface Technical Manual 11

4 Option Components

4 Option Components
Figure1
A
J1000
B
C
D
A – RJ-45 Port C – Option
B–Option
Model
<1> Connection tabs are found only on the RS-232C interface (SI-
232/J).
12 YASKAWA ELECTRIC TOBPC73060032A RS-232C Interface Technical Manual
Number
Connector to Drive
D – Connection
Tab s
<1>
4 Option Components

Dimensions

The installed Option interface adds 17.8 mm (0.70 in) to the total depth of the drive.
2.8(0.11) 15(0.60)
YASKAWA ELECTRIC TOBPC73060032A RS-232C Interface Technical Manual 13
mm(in)

5 Installation Procedure

DANGER
5 Installation Procedure

Section Safety

Electrical Shock Hazard
Disconnect all power to the drive, before servicing.
Failure to comply will result in death or serious injury. Wait at least one minutes after all indicators are off. The drive
has internal capacitors that remain charged even after the 24 V Power Supply option is disconnected. The drive charge LED will extinguish when the DC bus voltage is below 50Vdc. Measure drive DC bus voltage to confirm safe level.
14 YASKAWA ELECTRIC TOBPC73060032A RS-232C Interface Technical Manual
5 Installation Procedure
NOTICE
Damage to Equipment
Use only Yaskawa connection cables or recommended cables.
Failure to comply may cause the drive or option to function incorrectly.
Properly connect the connectors.
Failure to comply may prevent proper operation and possibly damage equipment.
Do not exceed communication cable bend radius specifications.
Failure to comply may result in broken wires or loose connections.
YASKAWA ELECTRIC TOBPC73060032A RS-232C Interface Technical Manual 15
5 Installation Procedure
Ta b
CN5 port
flat-blade screwdriver
TababTa b

Attaching the Option Interface

1. Insert a flat-blade screwdriver into the
opening as shown in the diagram below to remove the option cover from the drive.
2. Insert the connector on the back of the
interface into the CN5 port on the drive so that it clicks into place.
Note: The RS-232C Interface (SI-232/J) has three
additional connection tabs that must also click into place to properly mount the option.
16 YASKAWA ELECTRIC TOBPC73060032A RS-232C Interface Technical Manual
5 Installation Procedure
J1000
underside of interface unit
flat-blade screwdriver

Removing the option interface

1. Use a flat-blade screwdriver as shown in
the diagram to press gently against the small openings and disconnect the option unit.
YASKAWA ELECTRIC TOBPC73060032A RS-232C Interface Technical Manual 17
5 Installation Procedure
Copy
Ver
ify
Read
LOCK
YASKAWA
JVOP-181
USB Copy Unit
COM ERR
CN5
<2>
<3>
<4> <1>
SI-232/JC
USB Copy Unit
SI-232/J
or
LED Operator
(Available soon)
DriveWizardPlus
connect
AC drive J1000
J1000J1000
Connecting Peripheral Devices to the
RS-232C Interface Option
NOTICE: Only use specific cables recommended by
Yaskawa. Yaskawa cannot guarantee proper operation if non-specified cables are used.
18 YASKAWA ELECTRIC TOBPC73060032A RS-232C Interface Technical Manual
5 Installation Procedure
<1> Use the LED operator cable, WV001 or WV003. <2> Only use the RJ-45 cable supplied with the USB Copy Unit. <3> Only use the USB cable supplied with the USB Copy Unit. <4> Only use the cable, PN: WV103, when connecting the drive
to a PC.
YASKAWA ELECTRIC TOBPC73060032A RS-232C Interface Technical Manual 19

6 Related Drive Parameters

6 Related Drive Parameters
No. Name Description Default
Determines if the drive will stop when the digital operator
Operation Selection
o2-06
when Digital Operator is Disconnected
20 YASKAWA ELECTRIC TOBPC73060032A RS-232C Interface Technical Manual
is removed in Local mode or with b1-02 set to zero. 0: Disabled - The drive will
not stop when the digital operator is removed.
1: Enabled - The drive will
fault (OPR) and coast to stop when the digital operator is removed.
0

7 Troubleshooting

7 Troubleshooting
Problems with the option interface may trigger an operator error. Refer to the J1000 Technical Manual for all other errors.

Fault

LED Operator
Display
oPr Digital operator connection fault
Cause Possible solution
LED operator is not properly connected to the drive or cables are damaged
YASKAWA ELECTRIC TOBPC73060032A RS-232C Interface Technical Manual 21
• Check the connection between the LED operator and the drive
• Replace the cable if damaged
• Turn off the drive input power and disconnect the LED operator
• Next reconnect the operator and turn the drive input power back on
Fault Name

8 Specifications

8 Specifications

Drive Specification

Item Specification
Model Number
Storage/ Installation Area
Ambient Temperature
Humidity 95% RH or less with no condensation
Storage Temperature
Altitude 1000 m or less
22 YASKAWA ELECTRIC TOBPC73060032A RS-232C Interface Technical Manual
SI-232/J: RS-232C Interface for use with remote
digital operator
SI-232/JC: RS-232C Interface for use with copy
Indoors (an area free from oil mist and dust)
-10 to +50°C
-20 to +60°C allowed for short-term transport of the product
unit and PC communication

9 Yaskawa Locations

9 Yaskawa Locations
DRIVE CENTER (INVERTER PLANT)
2-13-1, Nishimiyaichi, Yukuhashi, Fukuoka, 824-8511, Japan Phone: 81-930-25-3844 Fax: 81-930-25-4369 http://www.yaskawa.co.jp
YASKAWA ELECTRIC CORPORATION
New Pier Takeshiba South Tower, 1-16-1, Kaigan, Minatoku, Tokyo, 105-6891, Japan Phone: 81-3-5402-4502 Fax: 81-3-5402-4580 http://www.yaskawa.co.jp
YASKAWA AMERICA, INC.
2121 Norman Drive South, Waukegan, IL 60085, U.S.A. Phone: (800) YASKAWA (927-5292) or 1-847-887-7000 Fax: 1-847-887-7310 http://www.yaskawa.com
YASKAWA ELÉTRICO DO BRASIL LTDA.
Avenda Fagundes Filho, 620 Bairro Saude, São Paulo, SP04304-000, Brazil Phone: 55-11-3585-1100 http://www.yaskawa.com.br
YASKAWA EUROPE GmbH
Hauptstrasse 185, 65760 Eschborn, Germany Phone: 49-6196-569-300 Fax: 49-6196-569-398 http://www.yaskawa.eu.com
YASKAWA ELECTRIC UK LTD.
1 Hunt Hill Orchardton Woods, Cumbernauld, G68 9LF, United Kingdom Phone: 44-1236-735000 http://www.yaskawa.co.uk
YASKAWA ELECTRIC KOREA CORPORATION
9F, Kyobo Securities Bldg., 26-4, Yeouido-dong, Yeongdeungpo-gu, Seoul, 150-737, Korea Phone: 82-2-784-7844 http://www.yaskawa.co.kr
YASKAWA ELECTRIC (SINGAPORE) PTE. LTD.
151 Lorong Chuan, #04-01, New Tech Park, 556741, Singapore Phone: 65-6282-3003 http://www.yaskawa.com.sg
YASKAWA ELECTRIC (CHINA) CO., LTD.
12F, Carlton Bld., No.21 HuangHe Road, HuangPu District, Shanghai 200003, China Phone: 86-21-5385-2200 http://www.yaskawa.com.cn
YASKAWA ELECTRIC (CHINA) CO., LTD. BEIJING OFFICE
Room 1011, Tower W3 Oriental Plaza, No. 1 East Chang An Ave., Dong Cheng District, Beijing, 100738, China Phone: 86-10-8518-4086
YASKAWA ELECTRIC TAIWAN CORPORATION
9F, 16, Nanking E. Rd., Sec. 3, Taipei, 104, Taiwan Phone: 886-2-2502-5003
YASKAWA ELECTRIC INDIA PRIVATE LIMITED
#17/A Electronics City, Hosur Road Bangalore 560 100 (Karnataka), India Phone: 91-80-4244-1900 http://www.yaskawaindia.in
YASKAWA ELECTRIC TOBPC73060032A RS-232C Interface Technical Manual 23
Fax: 55-11-5581-8795
Fax: 44-1236-458182
Fax: 82-2-784-8495
Fax: 65-6289-3003
Fax: 86-21-5385-3299
Fax: 86-10-8518-4082
Fax: 886-2-2505-1280
Fax: 91-80-4244-1901
(Address revision No.: 12-7-9)

10 Revision History

MANUAL NO. TOBP C730600 32A
Published in Japan May 2008 07-12
Date of publication
Date of original publication
Revision number
1
65432
1
10 Revision History
The revision dates and numbers of the revised manuals are given on the bottom of the back cover.
Date of
Publication
January 2013 Chapter 9 Revision: Address
July 2011
September 2010 Chapter 9 Revision: Address
April 2010 Chapter 9 Revision: Address
July 2008 Chapter 9 Revision: Address
May 2008 Chapter 1
December 2007 – First edition
24 YASKAWA ELECTRIC TOBPC73060032A RS-232C Interface Technical Manual
Rev.
Section Revised Content
No.
Front cover,
back cover
Revision: Format
Revision: Applicable Documentation
YASKAWA AC Drive-J1000 Option
RS-232C Interface
Technical Manual
J1000オプションユニット
RS-232C
オプションユニット
取扱説明書
Any inquiries related to the product can be directed to the address listed at chapter 9.
この製品に関するお問い合わせ先については,9章お問い合わせ先をご覧ください。
In the event that the end user of this product is to be the military and said product is to be employed in any weapons systems or the manufacture thereof, the export will fall under the relevant regulations as stipulated in the Foreign Exchange and Foreign Trade Regulations. Therefore, be sure to follow all procedures and submit all relevant documentation according to any and all rules, regulations and laws that may apply.
Specifications are subject to change without notice for ongoing product modifications and improvements.
© 2007-2013 YASKAWA ELECTRIC CORPORATION. All rights reserved.
本製品の最終使用者が軍事関係であったり,用途が兵器などの製造用である場合には,「外国為替及び外国貿易法」の定める輸出規制の対象となることがあります ので,輸出される際には十分な審査及び必要な輸出手続きをお取りください。
製品改良のため,定格,仕様,寸法などの一部を予告なしに変更することがあります。
インタフェース
YASKAWA ELECTRIC CORPORATION
MANUAL NO. TOBP C730600 32A
Published in Japan January 2013 07-12
6 -0