Xylem HYDROQSG User Manual

QUICK START GUIDE
HYDROQSG
HYDROVAR
Pump Control
Quick Start Guide
Startup of a Hydrovar drive or Packaged Hydrovar Pump/Drive. Consult IM223 for recommended sys­tem design, including pump, valves, transducer, and diaphragm tank. For additional applications, consult IM223.
1. Align drive on 3 Ph/TEFC motor and attach to motor using 4 clamps and screws provided. Remove cover.
2. Verify power is off before connecting to drive. Attach power wires to pump mounted fused disconnect (if packaged product) or from wall mounted fused disconnect or breaker box. Use fast acting Class T fuses. Route wires through cable gland, conduit plate – large opening –and through cable gland nut.
3. Attach Power wires to drive: Attach ground wire to ground screw. If 1 Ph, attach L and N to appropri­ately labeled terminals. If 3 Ph, attach wires to ap­propriate L1, L2, L3 terminals. See IOM for terminal locations.
1 Ph 2, 3 HP 3 Ph 3, 5 HP 3 Ph 7.5, 10, 15 HP
(A) Power supply (B) Motor (C) Terminal block:
(D) RS-485 Interface (E) Status-Relays - SOLORUN
- User interface - RS-485 Interface
- Internal interface (F) Optional Relay Card
4. Drive connection to motor: Route wires through cable gland and other large conduit opening as above. Connect wires to appropriate terminals. Use crimp-on spades for sizes 2, 3, 5 HP. Terminate wires at terminals U, V, W for sizes 7.5 HP and up.
*** Route the following low voltage wires through small conduit glands and openings as needed. ***
5. Attach transducer wires to terminals X3: 1-3; Shield, White, Brown respectively.
6. Attach thermal overload switch to motor body at conduit box screw, and terminate at the 2 termi­nals labeled X1 PTC. If not using Thermal overload switch, place jumper between PTC terminals.
7. Provide Emergency stop switch, or jumper between terminals X3: 7, 8.
8. Provide additional on/off switch or jumper between terminals X3: 11, 12
9. If using multiple communicating drives, attach RS485 wires to terminals X4: 4-6, (-, +, Shield re­spectively) on Master drives; X2: 1-3 on Basic drives. Daisy chain communication wires starting at Master drive to all additional drives.
connections
- START/STOP
10. Verify all connections are secure with no stray wires. Attach ground wire from drive to cover and replace cover. Note: Be sure cover sits securely on drive without pinching any wires. Securely HAND TIGHT­EN cover screws. Cover must be firmly attached for buttons to function properly.
11. Connect power. The display should look as follows:
XYLEM 0.0 Hz STOP XXX.X PSI
12. See attached flowchart for available programming options to change.
13. Push Right arrow to next screen to change Setpoint. Use Up/Down arrows to change setpoint, (Required value).
14. Push left arrow once to get back to main screen. Push left arrow again to get to Main menu. Use Down arrow to scroll through menu options. To change any parameter other than set point, you must first enter a password. From main menu, scroll down to Group 60, and push right arrow once to parameter 61. Enter password using up arrow key, (password = 66).
15. For multipump programming, change the highlight­ed parameters in the flowchart. Change: Parameter 105 to “Cascade Serial”; set the pump address to 1, 2, etc in parameter 106.
16. From main screen, press up arrow to start drive. Check rotation on pump. Switch 2 of 3 line wires from the drive at motor if reverse rotation.
BASIC SETTINGS
100 SUBMENU
100 %
75 %
0066
0066
220 RAMP 2
215 RAMP 1
210 INVERTER
205 MAX. UNITS
125 DISP. BRIGHT
120 DISP. CONTR.
115 LOCK FUNCT.
110 SET PASSW.
4 sec
4 sec
ALL
6
20 Hz
60 Hz
2 sec
2 sec
280 SEL.SW.FRQ.
275 POWER RED.
270 KNEE FREQ.
265 BOOST
250 MIN. FREQ
245 MAX. FREQ
240 RAMP FMIN D
235 RAMP FMIN A
Auto
OFF
60 Hz
5 %
CONF INVERTER
200 SUBMENU
291 CURR. LIMIT
100 %
290 CURR. LIMIT
OFF
286 SKIPFRQ RNG
60 Hz
285 SKIPFRQ CTR
0.0 Hz
REGULATION
300 SUBMENU
330 LIFT AMOUNT
0.0 %
325 FRQ. LIFT
30.0 Hz
320 REG. MODE
normal
315 HYSTERESIS
80 %
430 SENS1 CAL 0
0 % = x,xx PSI
425 SENS. CURVE
linear
420 SENS. RANGE
300 PSI
415 SENSOR TYPE
analog I 4-20mA
SENSOR
400 SUBMENU
445 SENS2 CAL X
0 % = xx,xx PSI
440 SENS2 CAL 0
0 % = x,xx PSI
435 SENS1 CAL X
0 % = xx,xx PSI
530 DISABLE FRQ
30.0 Hz
560 SYNCH.LIM.
525 SWITCH DLY
2 sec
555 SWITCH INTV
520 ENABLE DLY
5 sec
550 OVERVAL DLY
515 ENABLE FREQ
48 Hz
545 OVERVALUE
0.0 Hz
24 hours
0 sec
disabled
SEQUENCE CNTR
500 SUBMENU
570 MSTPRIORITY
565 SYNCH.WIN.
600 SUBMENU
ON
2 Hz
615 ERROR RESET
ERRORS
ON
OUTPUTS
700 SUBMENU
720 CONF REL 2
Errors
715 CONF REL 1
Running
825 REQ.VAL.2
50 PSI
820 REQ.VAL.1
50 PSI
815 SW REQ.VAL
Setpoint 1
REQUIRED VALUES
800 SUBMENU
835 ACTUAT.FRQ2
0.0 Hz
830 ACTUAT.FRQ1
0.0 Hz
913 OFFSET Y1
912 OFFSET X1
910 LEVEL 1
0 PSI
0
0
OFFSET
900 SUBMENU
918 OFFSET Y2
0 PSI
917 OFFSET X2
100
915 LEVEL 2
100
1025 SEL.DEVICE
01
1020 TESTR.TIME
5 sec
1015 TESTR.BOOST
10 %
TESTRUN
1000 SUBMENU
1030 TESTRUN MAN
Press > 3 sec
SETUPS
1100 SUBMENU
1135 CLR OPERAT.
Press > 3 sec
1130 CLR MOTORH.
ALL
1125 CLR ERRORS
ALL
RS485-INTERFACE
1200 SUBMENU
1220 PUMP ADDR
1
1215 FORMAT
RTU N81
62 JOG Hz
50 PSI
61 PASSWORD
0000
SETTINGS
60 SUBMENU
106 PUMP ADDR
105 MODE
100 SUBMENU
203 SET VER INV
1
Controller
202 SOFTWARE
BASIC SETTINGS
200 SUBMENU
sel. 01 act. 01
HV V01.3
CONF INVERTER
230 RAMP 4
70 sec
225 RAMP 3
70 sec
260 FMIN TIME
0 sec
255 CONF. FMIN
F > 0
610 DELAY TIME
410 CONF SENSOR
310 WINDOW
10 %
305 JOG Hz
50 PSI
REGULATION
300 SUBMENU
Sensor 1
405 DIMENS. UNIT
PSI
SENSOR
400 SUBMENU
510 ACT.VAL.DEC
2 PSI
540 DROP FREQ
505 ACT.VAL.INC
5 PSI
535 DISABLE DLY
SEQUENCE CNTR
500 SUBMENU
42.0 Hz
605 MIN.THRESH.
5 sec
600 SUBMENU
Xylem, Inc.
2881 East Bayard Street Ext., Suite A, Seneca Falls, NY 13148
Phone: (800) 453-6777 • Fax: (888) 322-5877 www.xyleminc.com/brands/gouldswatertechnology
2 sec
disabled
ERRORS
Actual value
710 ANALOG OUT2
705 ANALOG OUT1
Output frequency
OUTPUTS
700 SUBMENU
810 C.REQ.VAL.2
OFF
805 C.REQ.VAL.1
digital
REQUIRED VALUES
800 SUBMENU
907 OFFS.INPUT
100
905 OFFS.INPUT
OFF
OFFSET
900 SUBMENU
1010 TESTRUN FREQ.
30 Hz
1005 TESTRUN
100 hours
TESTRUN
1000 SUBMENU
1120 PASSWORD 2
0000
1110 FACTORY SET
USA
SETUPS
1100 SUBMENU
1210 BAUDRATE
1205 ADDRESS
RS485-INTERFACE
1200 SUBMENU
Goulds is a registered trademark of Goulds Pumps, Inc. and is used under license.