Xantrex, Xanbus, and Smart choice for power are trademarks of Schneider
Electric Services International sprl, registered in the U.S. and other countries. Other
trademarks, registered trademarks, and product names are the property of their
respective owners and are used herein for identification purposes only.
The purpose of this Owner’s Guide is to provide explanations and
procedures for installing, troubleshooting, operating and maintaining the
Xanbus Automatic Generator Start (AGS).
Scope
The Guide provides safety and operating guidelines, procedures for
installing the AGS, as well as information on configuring the AGS. It also
provides information about troubleshooting the unit. It does not provide
details about configuring every Xanbus-enabled device to which the SCP
connects to within the Xanbus network. You need to consult these other
Xanbus-enabled devices’ owner’s and installation guides.
Audience
The Guide is intended for users and operators of the Xanbus Automatic
Generator Start (AGS). The Installation section is primarily intended for
qualified installers who need to install and configure an AGS. The installer
should have knowledge and experience in installing electrical equipment,
knowledge of the applicable installation codes, and awareness of the
hazards involved in performing electrical work and how to reduce those
hazards. A qualified technician or electrician has this knowledge and
experience.
Conventions Used
The following conventions are used in this guide.
STATEMENT OF HAZARD
Contains statements of avoidance or strict compliance.
Failure to follow these instructions will result in death or serious
injury.
STATEMENT OF HAZARD
Contains statements of avoidance or strict compliance.
Failure to follow these instructions can result in death or serious
injury.
STATEMENT OF HAZARD
Contains statements of avoidance or strict compliance.
Failure to follow these instructions can result in minor or moderate
injury.
Contains statements of avoidance or strict compliance.
Failure to follow these instructions can damage the unit and/or
damage other equipment.
IMPORTANT:
know, however, they are not as serious as a danger, warning, or caution.
These notes describe things which are important for you to
Related Information
Y ou can find more information about Xantrex Technology USA Inc. as well
as its products and services at www.xantrex.com.
The product marking on the left when found imprinted on
electrical and electronic units and appliances means that you
are to refer to this guide for cautions and warnings.
975-0082-01-01iii
Important Safety Instructions
IMPORTANT: READANDSAVETHIS OWNER’S GUIDEFORFUTURE
REFERENCE.
This chapter contains important safety, operation, and installation
instructions for the Xanbus Automatic Generator Start (AGS). Each time,
before using the AGS, READ ALL instructions and cautionary markings on
or provided with the AGS and all appropriate sections of this guide.
IMPORTANT:
1.If the Xanbus Automatic Generator Start (AGS) is inoperative, see
“W arranty and Return Information” on page 38 for guidance.
2.The Xanbus Automatic Generator Start (AGS) contains no userserviceable parts. For obtaining service, see “Warranty and Return
Information” on page 38 for guidance.
3.Protect the Freedom SW Automatic Generator Start from rain, snow,
spray, and water.
4.Disable the generator’s starting circuit by disconnecting the starter
battery, spark plug, et cetera, before wiring this device.
5.To reduce the risk of electrical shock, put the Xantrex Xanbus system
into Standby before working on any circuits connected to it.
See “Putting the AGS in Standby Mode” on page 67.
6.Disable the automatic starting circuit and/or disconnect the generator
from its starting battery to prevent accidental starting while
performing maintenance.
EXPLOSION HAZARD
This equipment is not ignition protected. To prevent fire or explosion, do
not install the unit in compartments containing flamma ble ma terial s or in
locations that require ignition-protected equipment. This includes any
space containing gasoline-powered machinery, fuel tanks, as well as
joints, fittings, or other connections between components of the fuel
system.
Failure to follow these instructions can result in death or serious
injury.
SAFETY HAZARD
Disable the Xanbus Automatic Generator Start (AGS) if the generator or
vehicle equipped with the generator is in an enclosed building or area
where the generator exhaust is not vented to the outside.
Failure to follow these instructions can result in death or serious
injury.
The Xanbus Automatic Generator Start (AGS) shall not be used in
connection with life support systems or other medical equipment or
devices.
Failure to follow these instructions can result in death or serious
injury.
This equipment has been tested and found to comply with the limits for a
Class B digital device, pursuant to part 15 of the FCC Rules. Thes e limits
are designed to provide reasonable protection against harmful interference
in a residential installation. This equipment generates, uses, and can radiate
radio frequency energy and, if not installed and used in accordance with the
instructions, may cause harmful interference to radio communications.
However, there is no guarantee that interference will not occur in a
particular installation. If this equipment does cause harmful interference to
radio or television reception, which can be determined by turning the
equipment off and on, the user is encouraged to try to correct the
interference by one or more of the following measures:
•Reorient or relocate the receiving antenna.
•Increase the separation between the equipment and receiver.
•Connect the equipment into an outlet on a circuit different from that to
which the receiver is connected.
•Consult the dealer or an experienced radio/TV technician for help.
Unauthorized changes or modifications to the equipment could void the
user’s authority to operate the equipment.
The Xanbus Automatic Generator Start (AGS) is designed
for use in a Xanbus-enabled Freedom SW Power System only.
The Xanbus AGS requires the additional use of a Xanbus System Control
Panel (SCP) for configuration and monitoring. For details see "System
Requirements".
AC Panel
Shore
Power
System Control Panel
Xanbus System Control Panel
network terminatornetwork terminator
Figure 1
Automatic Generator Start
Xanbus Automatic Generator Start
Generator
Xanbus Automatic Generator Start (AGS) Basic Function
Freedom Sequence
AC Loads
Freedom SW Inverter/Charger
FREEDOMSW3012
BATTERY
C/
ge Fault
r
ter A
ha
r
C
nve
I
On
er
t
r
e
nv
I
Reset Enable
FREEDOMSW3012
Inverter
Load Panel
Function The Xanbus AGS continuously monitors battery voltage and
starts, or stops, the generator when battery voltage drops below or exceeds
the preset limits. It also starts the generator to assist the system’s inverter/
charger when output power demands are high.
Start and Stop Triggers The Xanbus AGS requires a source of start and
stop triggers for automatic operation. The Xanbus AGS monitors the
Xanbus network and starts or stops the generator based on the preset limits
programmed into it.
975-0082-01-011
Introduction
System Requirements
Minimum basic system components include the following:
❐ Freedom SW Series Inverter/Charger
❐ AC Generator or DC Generator
❐ Xanbus System Control Panel (SCP)
❐ Xanbus Automatic Generator Start (AGS)
Network Communication Protocol The AGS uses Xanbus, a network
communications protocol developed by Xantrex, to communicate its
settings and activity to other Xanbus-enabled devices. All network
components used in the system must be Xanbus-enabled.
Network Power Supply The Xanbus AGS requires three watts of power
(maximum) to operate. This power supply is provided by the Freedom SW
Series Inverter/Charger through the Xanbus network.
Generator The generator should be a 2-wire or 3-wire generator with
Auto Start capability.
The generator should also supply a Generator Run signal. The Generator
Run signal is connected to the Xanbus AGS and used by the Xanbus AGS
to detect whether the generator is running. Some generator manufacturers
refer to this signal as the Hour Meter Signal or Switched B+.
Connecting the Generator Run signal is optional and only used for
redundancy. The Xanbus AGS requests generator voltage from the Xanbus
in addition to checking the Generator Run signal to detect if the generator is
running.
Generator Compatibility The Xanbus AGS supports most two and
three-wire generator starters. Some manufacturers include, but are not
limited to, Onan (Quiet Diesel, gasoline, and LP), Power Tech, Generac,
Northern Lights, Fisher Panda, Westerbeke, Kohler, Honda, and Yamaha.
Check with the generator manufacturer to ensure the generator in question
includes automatic starting capabilities.
Xanbus System Control Panel (SCP) A Xanbus System Control Panel
(SCP) is required to configure the AGS and monitor generator starting and
stopping activity.
The Xanbus System Control Panel (SCP) also provides real-time clock
information for the AGS Quiet Time and Exercise Time features.
The AGS can automatically start a generator in response to:
•a low battery voltage,
•large AC loads when inverter is operating,
•a thermostat signal, or
•a pre-programmed exercise period at a specified time of day.
Generator Stopping Triggers
The AGS can automatically stop a generator in response to:
•the introduction of qualified grid power (grid power within acceptable
parameters),
•high battery voltage,
•battery charge stage (float or absorb stage),
•reduction in AC loads when inverter is operating,
•a thermostat signal, or
•a pre-programmed quiet time period.
The AGS can also be used to manually start and stop the generator at any
time.
Programmable Features
Quiet Time The AGS features a quiet time setting, wh ich prevents the
generator starting at night or during other inconvenient periods.
Exercise PeriodDuring times of prolonged generator inactivity, the
AGS can be programmed to run (or “exercise”) the generator for a predefined period. This ensures the generator remains operational and that the
starting battery stays charged.
Status Reporting
The AGS reports its operating mode, its settings, generator activity, and the
reason for generator starts to the Xanbus system. This information can be
viewed on the Xanbus System Control Panel (SCP).
Installation Options
The AGS can be installed with an external shutdown input, a manual
generator ON/OFF switch, and an external ON/OFF indicator light.
975-0082-01-013
Introduction
Material List
The AGS ships with the following items:
•one Xanbus Automatic Generator Start (AGS) unit,
•owner’s guide,
•wiring harness (20-pin connector),
•mounting template, and
•mounting screws (4).
NOTE: Keep the carton and packing material in case you need to return
the AGS for servicing.
Freedom SW Series Inverter/Charger815-2012 (2kW power rating),
Freedom Sequence Intelligent Power
Manager
Xanbus System Control Panel (SCP)809-0921
25-ft network cable for SCP809-0940
75-ft network cable for SCP809-0942
The Freedom SW Inverter/Charger is a true sine wave inverter/charger that
can be used for mobile, marine and commercial applications. The Freedom
SW Inverter/Chargers are designed to operate with a wide variety of
generators and are capable of operating in parallel with a generator for short
durations to assist with starting large loads. The Freedom SW is a
convenient combination of an inverter, multistage battery charger, and
transfer switch in one electronic device.
The Xanbus SCP provides configuration and monitoring capability for a
Xanbus system. It monitors activity throughout your power system,
displays the settings and status, as well as, adjusting the settings for each
Xanbus-enabled device.
The Freedom Sequence Intelligent Power Manager is a fully integrated
power management system that provides automatic power and load
management for use in recreational vehicles (RV) while receiving power
from a generator or shore power.
815-3012 (3kW power rating)
809-0913 (four-circuit model),
809-0912 (six-circuit model)
SCP
25-ft cable
75-ft cable
Freedom SW
Inverter/Charger
TM
Introduction
ter
r
e
v
n
I
Reset Enable
FREEDOM SW3012
Freedom Sequence
power manager
nverter AC/
I
On
FREEDOMSW
Charge Fault
3012
975-0082-01-015
Features
The AGS has important features on the front and back of the unit. Features
on the front of the AGS are the indicator lights for reporting statuses on
power, generator, network, and faults (see Figure 2). The back of the unit
features the inputs where the AGS connects to the Xanbus system and the
20-contact wiring harness connector port (see Figure 3).
Front panel features
1
2
3
4
Xanbus Automatic Generator Start (AGS)
Power
Generator On
Network
Fault
FGA: 809-0915
Item Description
1Power light (green) indicates that the AGS is receiving power from the
Xanbus network.
2Generator On light (green) indicates that the generator is up and
running.
3Network light (green) indicates that the Xanbus network is
maintaining a good connection with all Xanbus-enabled components.
4Fault light (red) indicates the generator is experiencing a fault and
Explosion hazar d.
Do n ot ins tall in A
loc ation requiring
ignition pr otected
equipmen t. see
man ual .
!
CAUTION
CONNECT ONLY TO
CLASS 2 ELV CIRCUITS.
SEE MANUAL.
Figure 3
XANBUS
Two 8-pin RJ-45 Xanbus
network ports
AGS Bottom Panel
C
CSA 107.1
UL 458
LR 86581
MARINE
RR
US
EQUIPMENT DAMAGE
Only connect the Xanbus Automatic Generator Start (AGS) to other
Xanbus-enabled devices.
Although the cabling and connectors used in this network system are the
same as those used for Ethernet, this network is not an Ethernet system.
Equipment damage may result from attempting to connect these two
different systems.
Failure to follow these instructions can result in minor or moderate
injury.
Network Ports Each network port can accept an eight-pin RJ45 plug
attached to a Category 5 (CAT 5) Xanbus network cable. Depending on the
installation, both ports may be required.
20-contact wiring harness
connector
Figure 4
Wiring Harness Connector
Wiring Harness Connector The 20-contact connector supports a wiring
harness (supplied) that connects the AGS to a generator and thermostats.
The wiring harness also provides lines for connecting external generator
shutdown sensors or switches and external generator ON/OFF controls.
975-0082-01-017
Xanbus Automatic Generator Start Installation
Before installing the A GS, consider how and where the unit will be mounted.
Pre-plan the connection routes between the AGS, the generator, thermostats,
and the Xanbus System Control Panel (SCP).
Materials and Tools Required
The following materials and tools are required to complete the installation:
❐ Mounting template (supplied)
❐ Wiring harness (manufacturer part number 809-0917, supplied)
❐ Four mounting screws (supplied)
❐ #16 or #18 AWG wire (see “Wire Size and Length” on page 12)
❐ Xanbus network cables or equivalent (CAT 5 or CAT 5e cable with RJ-
45 connectors wired to T568A standard.
❐ Two network terminators
(supplied with the Freedom SW Inverter/Charger)
❐ Phillips head screwdriver
❐ Wire cutters and wire strippers
Choosing a Location
The AGS should be installed in a location that meets the following
requirements:
Dry
Cool
Safe
Close to
generator
The unit is intended for use in a dry location. The AGS
complies with UL458 Marine Supplement drip-test
requirements, but the location should be as dry as
possible.
The AGS operation is guaranteed between
-4 and 122 °F (-20 and 50 °C).
The AGS is not ignition protected. Do not install it in
areas requiring ignition-protected equipment, such as
compartments housing gasoline engines.
Avoid excessive wire lengths and use the
recommended wire lengths and sizes (see “Wire Size
and Length” on page 12). It is more important for the
AGS
to be close to the generator than close to the
inverter, although for safety reasons, the AGS should
not be installed in the same compartment as a gasolinepowered generator.
This equipment is not ignition protected. To prevent fire or explosion, do
not install the AGS in locations that require ignition-protected equipment.
This includes any space containing gasoline-powered machinery, fuel
tanks, as well as joints, fittings, or other connections between
components of a fuel system.
Follow all relevant instructions exactly before installing or using your
AGS.
SHOCK AND ENERGY HAZARDS
Before making any connections to the generator, ensure that the
generator’s starter is disabled and the generator’s start battery is
disconnected.
Failure to follow these instructions will result in death or serious
injury.
Connection Types Because the AGS will be part of a Xanbus system, it
is necessary to consider how to route two types of connections:
•connections to the generator, thermostats, and other external devices
and switches, using the included 20-contact connector and wiring
harness.
•connections to other Xanbus-enabled devices, using network cables.
Network ports
Network cables
to other Xanbusenabled devices
Figure 5
Xanbus Automatic Generator Start Installation
AGS External Connections
20-contact
connector
Wiring harness
(connection to
generator,
thermostats, and
external switches)
975-0082-01-019
Xanbus Automatic Generator Start Installation
Installation Overview
Installing the AGS involves the following steps:
1.Mounting the unit.
2.Connecting the wiring harness to:
•the generator (page 14)
•thermostats (optional) (page 29)
•external shutdown switch (optional) (page 30)
•external ON/OFF switch and LED (optional) (page 30)
ELECTRICAL SHOCK HAZARD
Before installing the AGS as part of a pre-existing Xanbus system, put
the system in Standby in order to disable the electrical operation of
networked devices. See “Putting the AGS in Standby Mode” on page 67.
Failure to follow these instructions can result in death or serious
injury.
3.Connecting the wiring harness to the 20-contact connector on the
AGS.
4.Connecting the AGS to the Xanbus System Control Panel (SCP) and
other network-enabled devices (page 33).
IMPORTANT:
the type of generator, and the overall complexity of the Xanbus system,
these instructions can offer only general guidelines for the many
installation options available.
Because each installation varies according to the location,
Mounting the Unit
The AGS is to be mounted vertically on a wall with the connectors facing
downwards.
To mount the AGS:
1.Hold the unit flush and square against the wall, panel, or horizontal
surface.
•If the mounting surface requires pre-drill holes for the screws, use
the supplied mounting template to mark, then drill, four holes.
2.With a Phillips screwdriver and the supplied mounting screws, secure
each corner of the AGS to the mounting surface.
All installation wiring should be performed by a qualified installer or
electrician.
The 20-contact connector is intended for connection to Class 2 ELV
(Extra Low Voltage) circuits only. Do not exceed the circu it limitations
specified in the following section.
Failure to follow these instructions can result in death or serious
injury.
ELV Circuits ELV (Extra-Low Voltage) circuits have an open-circuit
voltage of not more than 30 V
not a shock hazard.
Class 2 Circuits As per the US National Electrical Code (NEC) and the
Canadian Electrical Code (CEC), available power in Class 2 circuits is
limited to 100 VA, usually by current limiting by means of overcurrent
protection or series resistance. The current is limited to 5 A for circuits with
open-circuit voltage of 20 V, and to I=100/V
voltage between 20 V and 30 V.
or 42.2 VDC or peak, and are therefore
rms
for circuits with open circuit
oc
Xanbus Automatic Generator Start Installation
Circuit Limitations The relay contacts in the AGS are rated at 5 A
maximum and all circuits on the 20-contact connector are rated at 30 V
maximum.
Ensure that all circuits connected to the 20-contact connec tor comply with
the following limits:
Circuit ParameterCircuit Maximum
Open circuit voltage (Voc)30 V maximum
Overcurrent protection
(fuse size for open circuit voltage up to 20 V)
Overcurrent protection
(fuse size for open circuit voltage from 20 V to
30 V)
Wiring Harness Connections to the generator, thermostats, and external
ON/OFF switches are made using a wiring harness that plugs into the 20contact connector (see Figure 5).
The wires on the wiring harness can be extended to meet installation
requirements. When extending the wire harness, ensure that the extension
wires are the same color as the wires on the harness.
5 A maximum
5 A to 3.33 A
(100/V
maximum)
amps
oc
975-0082-01-0111
Xanbus Automatic Generator Start Installation
To install the AGS using the wiring harness:
1.Connect each wire on the harness to its intended wire or contact on the
generator, thermostats, or external sw itches. Tape, or otherwise secure,
the unused wires to ensure they do not make unintended connections.
2.Plug the harness into the connector on the bottom panel of the AGS.
Wire Identification Each wire on the harness is identified by a number
and a color. The wire numbers are shown in Figure 6 and their colors and
functions are described in the next table.
Wire Size and Length Required wire sizes for the external connections
to the wiring harness are:
0–30 ft. (9 m)Over 30 ft. (9 m)
18 AWG16 AWG
When planning the routing for external connections, ensure that wire
lengths are sufficient to plug the wiring harness into the AGS once all the
external connections are complete.
To generator,
thermostats, and
external switches
To 20-contact
connector on AGS
Figure 6
Wire
NumberFunction
1Thermostat 1 inputYellow
2Thermostat 1 returnGray
3Thermostat 2 inputOrange
4Thermostat 2 returnGray
5External shutdown inputWhite/Black
6External shutdown returnGray
7External manual on inputWhite/Green
8External manual off inputWhite/Red
9External ON/OFF LED Indicator outputWhite/Blue
10Constant 12/24 V B+ (battery positive) for External ON/
internally to wire number 13)
Generator run signal (switched B+) sense input
Generator run signal (switched B+) sense return
Relay 1 (Generator run/stop) Normally open contact
Relay 1 (Generator run/stop) Normally closed contact
Relay 1 (Generator run/stop ) C om m o n co nt act
Relay 2 (Generator start) Normally open contact
Relay 2 (Generator start) Common contact
Relay 3 (Preheat/cool-down) Normally open contact
Relay 3 (Preheat/cool-down) Common contact
Wiring Harness
Wire Color
Black
Violet
Black
Blue
White/Violet
Gray
White
Gray
Brown
Gray
Xanbus Automatic Generator Start Installation
975-0082-01-0113
Xanbus Automatic Generator Start Installation
Connecting the Generator
EQUIPMENT DAMAGE
Before connecting the AGS to your generator, read the Generator Type
descriptions in this section and consult your generator manufacturer to
ensure that Gen Type settings and connections are compatible with your
generator. Damage to the generator can result from selecting an inc o rre ct
Gen Type and following the connection diagram for an incorrect Gen
Type when connecting the AGS to the generator. Xantrex assumes no
responsibility or liability for loss or damage that might arise out of the use
of this information.
Failure to follow these instructions can damage the unit and/or
damage other equipment.
To connect the AGS to a generator , identify the start wiring configuration of
the generator to be used. Generators must be auto-start capable, and
generators equipped with remote operation connections are ideal.
If the generator is equipped for remote operation, examine the wiring of the
remote cable and connector (or read the generator’s documentation, if
available) and identify the following wires:
•Ground
•Start
•Stop
•Generator run signal, also known as the Hour Meter or Switched B+
(battery positive)
Wiring Requirements Either #16 or #18 AWG wire is required to
connect to the wiring harness. How many of these wires you connect and in
which combination depends on your generator type.
Generator Types The AGS has 14 preset generator configurations, or
“Gen Types” (see “Gen T ype” on page 42). After installing the hardware, it
will be necessary to select one of these Gen Types from the AGS
Configuration Menu on the Xanbus System Control Panel (SCP).
IMPORTANT:
Type". See “Putting the AGS in Standby Mode” on page 67.
The following section describes the preset generator configurations and
provides diagrams for connecting the wiring harness to the generator’s start
wiring.
IMPORTANT:
following section, refer to Appendix 1, “Appendix A: Generator Auto
Start Requirements and Types”. For more information about AGS
internal relay activity and timing, see Appendix 1, “Appendix B: Relay
Timing”.
IMPORTANT:
B+ Gen Run signal is not connected, it may be necessary to adjust the
Gen Run Signal hold time parameter on the AGS. See “Gen Run Hold
Time” on page 57.
Put the system in Standby BEFORE changing the "Gen
For an explanation of the terminology used in the
Connecting the B+ Gen Run signal is optional. It the
Type 1 is a three-wire GlowStop configuration recommended for “threewire” generators with glow plugs that need to be operated before a start is
attempted.
AGS Har ness WiresGenerator W ires
12
13
14
Relay1
16
17
Relay2
18
For additional information, see “Circuit Limitations” on page 11.
Figure 7
Type 1 Connection Diagram
GENERATOR RUN SIGNAL
GENERATOR RUN SIGNAL RETURN
5A fuse
PREHEAT/STOP
5A fuse
START
Relay FunctionPreset Configuration Setting
Relay 1 modeGlowStop
Relay 3 modeNo function
Gen Run signal hold time0.5 s
Preheat time20 s
Preheat to crank delay1 s
Crank time15 s
Relay FunctionPreset Configuration Setting
Crank retry time30 s
Gen Cool Down30 s
Gen Spin Down3 s
Shutdown bypass time0 s
Start tries3
975-0082-01-0115
Xanbus Automatic Generator Start Installation
Type 2
Type 2 is a three-wire GlowStop configuration recommended for “threewire” generators that don’t require a dedicated preheat signal. In this
configuration, the start signal is applied for longer because the generator
does its own preheat and cranking while the start signal is applied.
AGSHarnessWiresGenerator Wires
12
13
14
Relay1
16
17
Relay2
18
For additional information, see “Circuit Limitations” on page 11.
Figure 8
Type 2 Connection Diagram
GENERATOR RUN SIGNAL
GENE RATOR RUN SIGNAL RETURN
5A fuse
STOP/PREHEAT
5A fuse
START
Relay FunctionPreset Configuration Setting
Relay 1 modeGlowStop
Relay 3 modeNo function
Gen Run signal hold time0.5 s
Preheat time0 s
Preheat to crank delay0 s
Relay FunctionPreset Configuration Setting
Crank time30 s
Crank retry time40 s
Gen Cool Down30 s
Gen Spin Down3 s
Shutdown bypass time0 s
Start tries3
Type 3 is a three-wire GlowStop with shutdown bypass configuration. The
configuration shown in Figure 9 uses a shutdown bypass output to
temporarily disable the generator’s low oil pressure shutdown functionality
during cranking. Generators with this functionality often have a manual
means of disabling it during cranking.
AGS Harness W iresGenerator Wires
12
13
Relay 1
Relay 2
For additional information, see “Circuit Limitations” on page 11.
Figure 9
14
16
17
18
Type 3 Connection Diagram
5A fuse
5A fuse
GENERATOR RUN SIGNAL
GENERATOR RUN SIGNAL RETURN
PREHEAT
STOP
BYPASS SHUTDOWN
START
Relay FunctionPreset Configuration Setting
Relay 1 modeGlowStop/Shutdown bypass
Relay 3 modePreheat/Shutdown bypass
Gen Run signal hold time0.5 s
Preheat time20 s
Relay FunctionPreset Configuration Setting
Preheat to crank delay0 s
Crank time15 s
Crank retry time30 s
Gen Cool Down30 s
Gen Spin Down3 s
Shutdown bypass time10 s
Start tries3
975-0082-01-0117
Xanbus Automatic Generator Start Installation
Type 4
Type 4 is a three-wire StartStop configuration that uses relay 3 to provide a
60-second preheat signal.
AGS Harness W ires
12
13
Relay 1
Relay 2
Relay 3
For additional information, see “Circuit Limitations” on page 11.
Figure 10
14
16
17
18
19
20
Type 4 Connection Diagram
5A fuse
5A fuse
5A fuse
Generator Wires
GENERATOR RUN SIGNAL
GENERATOR RUN SIGNA L RETURN
STOP/PREHEAT
START
FUEL PRIME (PREHEAT)
12V GENERATOR BATTERY+
Relay FunctionPreset Configuration Setting
Relay 1 modeStartStop
Relay 3 modePreheat
Gen Run signal hold time10 s
Preheat time60 s
Relay FunctionPreset Configuration Setting
Preheat to crank delay5 s
Crank time15 s
Crank retry time15 s
Gen Cool Down30 s
Gen Spin Down3 s
Shutdown bypass time0 s
Start tries3