Since the use of this manual and the conditions or methods of installation, operation, use and
maintenance of the unit are beyond the control of Xantrex Technology Inc., the company does not
assume responsibility and expressly disclaims liability for loss, damage, or expense arising out of or
any way connected with such installation, operation, use, or maintenance.
This manual contains important safety instructions that should be followed during the installation
and maintenance of this product.
To reduce the risk of electrical shock, and to ensure the safe installation and operation of this
product, the following safety symbols have been placed throughout this manual to indicate
dangerous conditions and important safety instructions.
WARNING - A dangerous voltage or condition exists in this area.
Use extreme caution when performing these tasks.
AVERTISSEMENT - Une tension ou condition dangereuse existe dans cette zone.
Faire preuve d’extrême prudence lors de la réalisation de ces tâches.
CAUTION - This procedure is critical to the safe installation or operation of the unit. Follow these
instructions closely.
ATTENTION - Cette procédure est essentielle à l’installation ou l’utilisation
de l’unité en toute sécurité. Suivre ces instructions de près.
NOTE - This statement is important. Follow instructions closely.
NOTE - Cette déclaration est importante. Suivre les instructions de près.
•All electrical work must be done in accordance with local and national electrical codes.
•Before installing or using this device, read all instructions and cautionary markings located in
(or on) the manual, the STXR and the PV array.
•Do not expose this unit to rain, snow or liquids of any type without the rain/weather shield
hood installed (optional on some models).
•To reduce the chance of short-circuits when installing or working with the inverter or the PV
array, use insulated tools.
•Remove all jewelry such as rings, bracelets, necklaces, etc., prior to installing this system.
This will greatly reduce the chance of accidental exposure to live circuits.
•The ST unit contains more than one live circuit (PV array and AC line). Power may be present
at more than one source even when the circuit breakers are off.
•This product contains no user serviceable parts. Return the unit to a Xantrex Authorized
Service Center for maintenance.
•Wiring to the utility should only be done after receiving prior approval from the utility company
and performed only by a qualified electrician.
•Completely cover the surface of all PV arrays with an opaque (dark) material BEFORE wiring
them. PV arrays produce electrical energy when exposed to light and could create a
hazardous condition.
The Sun Tie solar power conversion center is designed to convert a home or business into a
“green” power generating station. The Sun Tie unit converts solar electric (PV) power into utilitygrade electricity which can be used by the home or sold to the power company. Installing a Sun Tie
unit is as simple as mounting it to the wall and connecting a DC source (PV array), and the AC
output to the utility.
Standard Features
All-in-one Design
All necessary DC input and AC output connections, disconnects and circuit breakers are housed
within the Sun Tie’s easily installed, compact enclosure. A built-in LCD panel provides easy-to-read
system status and daily cumulative energy production information.
Uses Most Types of PV Technology
The Sun Tie is designed to take advantage of most types of solar electric technologies. The
inverter allows up to 120 VDC open circuit PV modules to be used so both crystalline and thin film
PV modules can be used.
Sun Sweep™–Maximum Power Point Tracking (MMPT)
Sun SweepTM is Xantrex’s proprietary Maximum Power Point Tracking technology that allows the
Sun Tie XR to harvest the maximum amount of energy from your solar array. No matter what PV
system you choose, single crystalline, polycrystalline or thin film, SunSweepTM learns your array’s
specific characteristics, maximizing its output, all day, all season, year after year.
High Efficiency and Long Life
The high frequency, solid-state design of the Sun Tie inverter is extremely efficient. Above 500
watts, the inversion process is 90% efficient (or greater) with a peak efficiency of 94%. The Sun Tie
inverter has a design life of over twenty years.
Expandable
Sun Tie XR inverters may be connected in a parallel configuration for increasing net metering
capacity. The modular expandability of the Sun Tie Series allows for system growth.
UL Listed
The Sun Tie XR has complete on-board islanding protection and meets U.S. and Canadian
safety operating standards and code requirements. In North America, it is UL Listed (UL 1741-1999)
and cUL listed to CSA C22.2 No. 107.1-95. NEC 690 building code requirements for PV may be met
with the optional ground fault protection (PVGFP).
Options
These features are included on some models:
•PV array combiner board with six 20 amp maximum protected inputs
Before installing the Sun Tie XR, read all instructions and cautionary markings located in this
manual, on the PV array and on the main service panel.
NOTE: The Sun Tie weighs approximately 35 pounds (depending upon configuration and model).
Always use proper lifting techniques during installation to prevent personal injury.
wood screws and washers (supplied)
conduit and appropriate fittings
anchors for screws (material dependent)
Location
The Sun Tie XR unit can be mounted outdoors with the optional Rain Shield (STRS).
AC Connections
The inverter’s AC output breakers accept wire sizes from #6–14 AWG. Refer to the table below
for minimum recommended wire size.
Inverter
Model
STXR1000
STXR1500
STXR2000
STXR2500
AC Amps
Output per
leg
4.25.214 AWG14 AWG12 AWG
6.37.814 AWG12 AWG10 AWG
8.310.414 AWG12 AWG10 AWG
10.41314 AWG12 AWG8 AWG
NEC Amp
(Amps x 125%)
Recommended Minimum AC Wire Sizes
Minimum Wire Size for Specified Distance
0–50 Ft
One Way
50–100 Ft
One Way
Table 2-1
100–200 Ft
One Way
975-000-001
NOTE: These are the minimum recommended wire sizes in conduit. Installing a large number of wires
in conduit or enclosed locations may require larger wire sizes. Consult your local/national electrical
code for more information.
NOTE: The six-circuit combiner board is rated for 100 amps of maximum real current. Although the 20
amp fuses will theoretically allow 120 amps to be applied, always design for a maximum of 100 amps
maximum current. With appropriate fuse deratings, per NEC code, the maximum allowed current is 16
amps for any of the six circuits.
DC connections are made on the combiner board for models STXR1500 and STXR2500. The
combiner board accepts wire sizes from #6–14 AWG. Refer to the table below for minimum
recommended wire sizes.
DC Amps
1.01 .614 AWG14 AWG14 AWG
3.04.714 AWG12 AWG10 AWG
5.07 .812 AWG10 AWG6 AWG
7.010.912 AWG8 AWG6 AWG
9.014.010 AWG8 AWGNot Recommended
11.017.210 AWG6 AWGNot Recommended
NEC Amp
(Amps x 156%)
Minimum Wire Size for Specified Distance
0–25 Ft
One Way
25–50 Ft
One Way
50–100 Ft
One Way
975-000-002
Table 2-2
Recommended Minimum DC Wire Sizes
NOTE: These are the minimum recommended wire sizes. Installing a large number of wires in
conduit or enclosed locations may require larger wire sizes. Consult your local/national electrical
code for more information.
*NOTE: For installations requiring a two-wire run (positive and negative), the PV array wires can
bypass the individual, fused combiner board terminals and connect directly to the input terminals (via
an externally mounted DC fused combiner box) by using the positive and egative bypass terminals on
the top of the combiner board. Refer to Figure 2-1 and Table 2-3 for connections and wire sizes.
*Positive (+) PV Array
Bypass Terminal
*Negative (-) PV Array
Bypass Terminal
PV array wiring
(note polarity)
+
DC conduit wiring
(from solar arrays)
–
Figure 2-1
Combiner Board Indicating DC PV Array Wire Connection Points
NOTE: The National Electrical Code (NEC) places restrictions on minimum DC wire bending radius. A
#6 AWG wire is the largest that may be used on the STXR1500 and STXR2500 inverters when
connecting to the individual fused circuits of the combiner board.
DC connections are made at the 100 amp DC circuit breaker and the DC negative terminal block
for models STXR1000 and STXR2000. Refer to the table below for minimum recommended wire sizes.
DC Amps
(from PV array)
1015.610 AWG6 AWG4 AWG
1523.48 AWG4 AWG*2 AWG
2031.26 AWG4 AWG*1 AWG
3046.84 AWG*2 AWGNot Recommended
4062.44 AWG*1 AWGNot Recommended
6093.6*2 AWGNot RecommendedNot Recommended
NEC Amp
(Amps x 156%)
Minimum Wire Size for Specified Distance
0–25 Ft
One Way
25–50 Ft One Way
50–100 Ft
One Way
975-000-004
Table 2-3
Recommended Minimum DC Wire Sizes
*NOTE: The National Electrical Code (NEC) places restrictions on minimum DC wire bending radius. If
the enclosure’s side is used for routing the wires to the DC terminals, then the wires must be bent to
make the appropriate connections. A #3 AWG wire is the largest that may be used on the STXR1000
and STXR2000 inverters if the side panel is used. Side knockouts are NOT provided on the unit.
The Sun Tie should be connected to a grounded, permanent wiring system.
DC Grounding
The negative PV conductor should be bonded to the grounding system at only one point in the
system. The size for the conductor is usually based on the size of the largest conductor in the DC
system. Negative/ground bonding is accomplished by factory wired PVGFP breakers (when this
option is installed) or a factory installed grounding block (when PVGFP is not installed).
PV Arrays
The Sun Tie is optimized to work with 4-each, 12 volt nominal crystalline PV modules in series (48
VDC nominal), or various combinations of amorphous, thin film PV modules. Ensure the PV array used
in the system operates within the MPPT operational window.
The solar array connected to the Sun Tie Series inverter should have a minimum of 50 volts DC
open-circuit in full sunlight conditions. Crystalline solar arrays configured for 48 volts DC nominal will
have a open-circuit voltage in the area of 84 volts DC in full sunlight. The maximum peak power tracking
(MPPT) software controls the output of the solar modules, under loaded conditions, in the 42-85 volts
DC range (full inverter output power occurs between 52–85 VDC). Other array voltage will either not
operate the inverter, may cause damage or will not allow maximum harvest of the sun’s energy.
WARNING: WHENEVER A PV ARRAY IS EXPOSED TO SUNLIGHT, A SHOCK HAZARD EXISTS
AT THE OUTPUT CABLES OR EXPOSED TERMINALS. TO REDUCE THE RISK OF SHOCK
DURING INSTALLATION, COVER THE ARRAY WITH AN OPAQUE (DARK) MATERIAL BEFORE
MAKING ANY CONNECTIONS.
The main service panel must dedicate a 15 amp minimum, double pole breaker (120/240 volts AC)
to operate the Sun Tie XR.
Wire Routing
Determine all wire routes both to and from the Sun Tie. Possible routing considerations include:
•AC input wiring from the main service panel to the Sun Tie
•DC input wiring from the PV array to the Sun Tie
•DC ground from the PV array to an external ground rod
•All wiring and installation methods should conform to applicable electrical and building codes.
•Pre-plan the wire and conduit runs. The DC terminal blocks accept up to a #6 AWG wire
(STXR1500 and STXR2500) and #2 AWG* wire (STXR1000 and STXR2000); the AC circuit
disconnects accept cable sizes up to #6 AWG.
•For maximum safety, run AC and DC wires/cables in (separate) conduits.
*NOTE: #2 AWG wire can only be used if the bottom knockouts are used. If punching side walls for
wire routing, the largest wire for acceptable wire bend radius is #3 AWG maximum.
WARNING: CHECK FOR EXISTING ELECTRICAL OR PLUMBING PRIOR TO DRILLING HOLES
IN THE WALLS!