White Rodgers 8A04-1 Installation Instructions

TYPE 8A04-1
CAUTION
WHITE-RODGERS
Operator: Save these instructions for future use!
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE.
The Type 8A04-1 Fan Relay is for use with low voltage thermo­stat to provide a 24 volt control circuit for operating a line voltage fan motor or other load.
The relay has SPDT switch action to permit use with either single or two-speed motor.
Diagrams presented on back of this sheet show various systems that provide the required 24 volt power supply for operating the coil of the Fan Relay.
If in doubt about whether your wiring is millivolt, line, or low votage, have it inspected by a qualified heating and air condi­tioning contractor, electrician, or someone familiar with basic electricity and wiring.
Do not exceed the specification ratings. All wiring must conform to local and national electrical codes and
ordinances. This control is a precision instrument, and should be handled
carefully. Rough handling or distorting components could cause the control to malfunction.
FAN RELAY
24V Coil, SPDT Switch Action
INST ALLA TION INSTRUCTIONS
DESCRIPTION
PRECAUTIONS
To prevent electrical shock and/or equipment dam­age, disconnect electric power to system, at main fuse or circuit breaker box, until installation is complete.
WARNING
Do not use on circuits exceeding specified voltages. Higher voltages will damage control and could cause shock or fire hazard.
ELECTRICAL DATA Switch Action: Single-Pole, Double-Throw
Norm. Open (N.O.): Black - Red Norm. Closed (N.C.): Black - Brown
Coil Current: 0.28A. @ 24V.A.C., 60Hz Mounting: By means of mounting tabs or 1/2" conduit hub. Replaces: Honeywell R8225; General R4
All wiring should be done in accordance with local and national electrical codes and ordinances.
HI
COM
LO
TYPE 8A04A-1 FAN RELAY
N.C.
N.O.
RED
PLENUM FAN SWITCH OR OTHER SWITCHING DEVICE
BROWN
BLUE
BLUE
HOT
LINE
N
TWO-SPEED
MOTOR
Fig. 1 Using Type 8A04-1 with Two-Speed Motor
WHITE-RODGERS DIVISION
EMERSON ELECTRIC CO. 9797 REAVIS RD., ST. LOUIS, MO. 63123 (314) 577-1300, Fax (314) 577-1517
9999 HWY. 48, MARKHAM, ONT. L3P 3J3 (905) 475-4653, FAX (905) 475-4625
TO 24 VOLT CONTROL CIRCUIT
WIRING
Contacts: Silver cadmium oxide Contact Rating:
AMPS.
N.O. N.C. N.O. N.C. FULL LOAD 16 9.8 8 6.9 LOCKED ROTOR 96 58.8 48 41.4
TYPE 8A04-1 FAN RELAY
RED
PLENUM FAN SWITCH OR OTHER SWITCHING DEVICE
LINE VOLTAGE LOW VOLTAGE
HOT
LINE
N
SINGLE-SPEED
MOTOR
Fig. 2 Using Type 8A04-1 with Single Speed Motor
Printed in U.S.A.
SPECIFICATIONS
120VAC 240VAC
WIRING
BLUE
TO 24 VOLT
CONTROL CIRCUIT
COIL
N.C.
N.O.
BROWN
BLUE
PART NO. 37-5493A
Replaces 37-9234
9514
WIRING CONT.
All wiring should be done in accordance with local and national electrical codes and ordinances.
The diagrams given below show the use of White-Rodgers Heating-Cooling Thermostat Combinations on various systems that provide the required 24 volt power supply for operating the coil (blue leads) of the Type 8A04-1 Fan Relay.
THERMOSTAT
SWITCH
COOL
Internal Wiring Field Wiring
FAN
SWITCH
TYPE 8A04-1
FAN RELAY
AUTO ON
FAN
COOLING
RCG
24VAC
COOL
TRANSFORMER
SYSTEM SWITCH
OFF
120VAC
HEAT
RHY
FIELD-INSTALLED
JUMPER
BIMETAL
COOLING
ANTICIPATOR
COOL
OFF
HEAT
HEATING
SYSTEM
HEAT
ADJUSTABLE
ANTICIPATOR
FIXED
SYSTEM SWITCH
W
HEATING
Fig. 3 For installations where heating and cooling systems are powered by same transformer
THERMOSTAT
SUBBASE
SYSTEM
DO NOT USE JUMPER WIRE ON TWO TRANSFORMER SYSTEM
TYPE 8A04-1
FAN RELAY
G RC
FAN
COOLING
24VAC
COOLING
TRANSFORMER
120VAC
TRANSFORMER
120VAC
HEATING
RHY
24VAC
Fig. 4 For installations where heating systems are powered by a separate transformer
DO NOT USE JUMPER WIRE ON TWO TRANSFORMER SYSTEM
RHY WG RC
TYPE 8A04-1
FAN RELAY
FAN
COOLING
24VAC
TRANSFORMER
120VAC
COOLING
Fig. 5 For Oil-Fired installations using low voltage Oil Burner Control
2 37-5493B
W
HEATING
SYSTEM
SYSTEM
SYSTEM
TO T1-T2 TERMINALS
ON OIL BURNER
CONTROL TYPE 668