Operator: Save these instructions for future use!
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY
BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE
PERSONAL INJURY AND/OR PROPERTY DAMAGE.
Your new White-Rodgres 7-Day Digital Thermostat uses the
technology of a solid-state microcomputer to provide precise
time/temperature control. This thermostat offers you the fl exibility
to design heating and cooling programs that fi t your needs.
Features:
• Separate program for each day of the week with four separate
time/temperature periods per day
• Simultaneous heat and cool program storage
• Preprogrammed temperature control
• Backlit display
• LCD continuously displays setpoint, and alternately displays
time and room temperature
This thermostat is intended for use with a low voltage system;
do not use this thermostat with a line voltage system. If in doubt
about whether your wiring is millivolt, line, or low voltage, have it
inspected by a qualifi ed heating and air conditioning contractor
or electrician.
Do not exceed the specifi cation ratings.
All wiring must conform to local and national electrical codes
and ordinances.
This control is a precision instrument, and should be handled
carefully. Rough handling or distorting components could cause
the control to malfunction.
CAUTION
!
To prevent electrical shock and/or equipment damage,
disconnect electric power to system at main fuse or
circuit breaker box until installation is complete.
875
Programmable Electronic Digital Thermostat
INSTALLATION AND
OPERATION INSTRUCTIONS
DESCRIPTION
• Temperature override until next program period
• Manual program override (HOLD temperature)
• Temporary HOLD
• °F/°C convertibility
• Temperature range 45° to 90°F
• RC, RH, C, W, Y, G, O and B terminals
• Optional C terminal (Dual Power option)
• B and O terminals for single stage heat pumps (no auxiliary
heat) or damper operation
• Program storage in case of power loss
• 2 “AA” alkaline batteries included
PRECAUTIONS
WARNING
!
Do not use on circuits exceeding specifi ed voltage.
Higher voltage will damage control and could cause
shock or fi re hazard.
Do not short out terminals on gas valve or primary
control to test. Short or incorrect wiring will damage
thermostat and could cause personal injury and/or
property damage.
Thermostat installation and all components of the
system shall conform to Class II circuits per the NEC
code.
ELECTRICAL DATA
Electrical Rating:
8 to 30 VAC 50/60 Hz. or D.C.
0.05 to 1.0 Amps (Load per terminal)
1.5 Amps Maximum Total Load (All terminals combined)
THERMAL DATA
Setpoint Temperature Range:
45°F to 90°F (7°C to 32°C)
Operating Ambient Temperature Range:
32°F to 105°F
Operating Humidity Range:
0 to 90% RH (non-condensing)
Shipping Temperature Range:
-4°F to 149°F
SPECIFICATIONS
APPLICATIONS
For use with:
• Standard heat/cool or heat only systems
• Electric heat systems
• Gas or oil fi red systems
• Gas systems with intermittent ignition devices (I.I.D.)
and/or vent dampers
• Hydronic (hot water or steam) systems
• Single-stage heat pump systems (no auxiliary heat)
• Millivolt systems
DO NOT USE WITH:
• Multi-stage systems
• Systems exceeding 30 VAC and 1.5 amps
• 3-wire zoned hydronic heating systems
PART NO. 37-6910A
0806
Mounting
holes
Mounting
holes
Electric/Gas
switch
Screw anchors
INSTALLATION
REMOVE OLD THERMOSTAT
1. Shut off electricity at the main fuse box until installation is
complete. Ensure that electrical power is disconnected.
2. Remove the front cover of the old thermostat. With wires
still attached, remove wall plate from the wall. If the old
thermostat has a wall mounting plate, remove the thermostat
and the wall mounting plate as an assembly.
3. Identify each wire attached to the old thermostat using
the labels enclosed with the new thermostat.
4. Disconnect the wires from old thermostat one at a time. DO
NOT LET WIRES FALL BACK INTO THE WALL.
5. Install new thermostat using the following procedures.
ATTENTION!
This product does not contain mercury. However, this product
may replace a unit which contains mercury.
Do not open mercury cells. If a cell becomes damaged, do not
touch any spilled mercury. Wearing nonabsorbent gloves, take
up the spilled mercury with sand or other absorbent material and
place into a container which can be sealed. If a cell becomes
damaged, the unit should be discarded.
Mercury must not be discarded in household trash. When the
unit this product is replacing is to be discarded, place in a suitable container and return to 2895 Harrison Street, Batesville,
AR 72501 for proper disposal.
ELECTRIC HEAT OR SINGLE-STAGE
HEAT PUMP SYSTEMS
This thermostat is confi gured from the factory to operate a heat/
cool, fossil fuel (gas, oil, etc.), forced air system. It is confi gured
correctly for any system that DOES NOT require the thermostat
to energize the fan on a call for heat. If your system is an electric
heat or heat-pump system that REQUIRES the thermostat to
turn on the fan on a call for heat, locate the ELECTRIC/GAS
switch on the back of the thermostat (see fi g. 1) and switch
it to the ELECTRIC position. This will allow the thermostat
to energize the fan immediately on a call for heat. If you are
unsure if the heating/cooling system requires the thermostat to
control the fan, contact a qualifi ed heating and air conditioning
service person.
ATTACH THERMOSTAT BASE TO WALL
1. Remove the packing material from the thermostat. Gently
pull the cover straight off the base. Forcing or prying on the
thermostat will cause damage to the unit. If necessary, move
the electric heat switch (see ELECTRIC HEAT SYSTEMS,
above).
2. Connect wires beneath terminal screws on base using appropriate wiring schematic (see fi gs. 2 through 7).
3. Place base over hole in wall and mark mounting hole locations on wall using base as a template.
4. Move base out of the way. Drill mounting holes.
5. Fasten base loosely to wall, as shown in fi g. 1, using two
mounting screws. Place a level against bottom of base,
adjust until level, and then tighten screws. (Leveling is for
appearance only and will not affect thermostat operation.)
If you are using existing mounting holes, or if holes drilled
are too large and do not allow you to tighten base snugly,
use plastic screw anchors to secure subbase.
Figure 1. Thermostat Base
6. Push excess wire into wall and plug hole with a fi re-resistant
material (such as fi berglass insulation) to prevent drafts from
affecting thermostat operation.
BATTERY LOCATION
2 “AA” alkaline batteries are included in the thermostat at the
factory with a battery tag to prevent power drainage. You must
remove the battery tag to engage the batteries.
If “BATT” is displayed, the batteries are low and should be replaced. For best results, replace all batteries with new premium
brand batteries such as Duracell® or Energizer®. To replace
batteries, install the batteries along the top of the base (see
Fig. 1). The batteries must be installed with the positive (+) end
to the left.
HYDRONIC (HOT WATER OR STEAM)
HEATING SYSTEMS
This thermostat is set to operate properly with a forced-air heating system. If you have a hydronic heating system (a system
that heats with hot water or steam), you must set the thermostat
to operate properly with your system. Change the second option in the confi guration menu to SL (see CONFIGURATION
MENU, page 4).
CHECK THERMOSTAT OPERATION
If at any time during testing your system does not operate
properly, contact a qualifi ed service person.
Turn on power to the system.
Fan Operation
If your system does not have a G terminal connection, skip to
Heating System.
1. Move FAN switch to ON position. The blower should begin
to operate.
2. Move FAN switch to AUTO position. The blower should
stop immediately.
2
RH
24 VAC
120 VAC
Hot
Neutral
THERMOSTAT
SYSTEM
G W
Figure 2. Typical wiring diagram for
heat only, 3-wire, single transformer systems
TRANSFORMER
Heating
System
Fan
Relay
YC
‡
RC
JUMPER
WIRE
OB
For 2-wire Heat only,
attach to RH and W
NOTE
RH
Y
24 VAC
120 VAC
Hot
Neutral
TRANSFORMER
THERMOSTAT
SYSTEM
G W
Figure 3. Typical wiring diagram for
cool only, 3-wire, single transformer systems
Cooling
System
Fan
Relay
RCOB
C
‡
JUMPER
WIRE
RH
Y
24 VAC
120 VAC
Hot
Neutral
THERMOSTAT
SYSTEM
G W
Figure 4. Typical wiring diagram for
heat/cool, 4-wire, single transformer systems
TRANSFORMER
Heating
System
Fan
Relay
Cooling
System
RC
JUMPER
WIRE
OC‡B
RED jumper wire (provided with thermostat) must be
connected between thermostat RH and RC terminals
for proper thermostat operation with this system.
NOTE
RH
Y
24 VAC
120 VAC
Hot
Neutral
THERMOSTAT
SYSTEM
G W
Figure 5. Typical wiring diagram for
heat/cool, 5-wire, two-transformer systems
HEATING
TRANSFORMER
Heating
System
Fan
Relay
Cooling
System
RC
24 VAC
120 VAC
Hot
Neutral
COOLING TRANSFORMER
OBC
‡
RH
Y
24 VAC
120 VAC
Hot
Neutral
THERMOSTAT
SYSTEM
G W
Figure 6. Typical wiring diagram for heat pump
with reversing valve energized in COOL
TRANSFORMER
Reversing
Valve*
RCOBC
‡
JUMPER
WIRE
Compressor
Contactor
JUMPER
WIRE
* Reversing valve is energized when the
system switch is in the COOL position
Fan
Relay
RH
Y
24 VAC
120 VAC
Hot
Neutral
THERMOSTAT
SYSTEM
G W
Figure 7. Typical wiring diagram for heat pump
with reversing valve energized in HEAT
TRANSFORMER
Reversing
Valve*
RCO
B
C
‡
JUMPER
WIRE
Compressor
Contactor
JUMPER
WIRE
* Reversing valve is energized when the
system switch is in the HEAT position
Fan
Relay
‡
The 24 Volt neutral connection to terminal C on the thermostat is not required if the batteries are replaced once a
year with fresh “AA” alkaline batteries.
Cooling System
Heating System
1. Move SYSTEM switch to HEAT position. If the heating system
has a standing pilot, be sure to light it.
2. Press
ture. The heating system should begin to operate.
3. Press
ture. The heating system should stop operating.
to adjust thermostat setting above room tempera-
to adjust thermostat setting below room tempera-
CAUTION
!
To prevent compressor and/or property damage, if the
outdoor temperature is below 50°F, DO NOT operate
the cooling system.
1. Move SYSTEM switch to COOL position.
2. Press
to adjust thermostat setting below room temperature. The blower should come on immediately on high speed,
followed by cold air circulation
3. Press
to adjust thermostat setting above room temperature. The cooling system should stop operating.
3