Operator: Save these instructions for future use!
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE.
These Relay-Hot Water Controls combine into a single enclosure: a high limit control, low limit-circulator control, circulator relay, transformer, together with terminals for wiring. They are for use on boilers equipped with tankless domestic coil.
Although these controls are designed for use with a line voltage gas valve or oil burner control, they may also be used with low voltage primary controls.
The internal transformer supplies power for operating the relay coil and systems zoned with motorized water valves.
If in doubt about whether your wiring is millivolt, line, or low voltage, have it inspected by a qualified heating and air conditioning contractor, electrician, or someone famil­iar with basic electricity and wiring.
Do not exceed the specification ratings. All wiring must conform to local and national electrical
codes and ordinances. This control is a precision instrument, and should be
handled carefully. Rough handling or distorting compo­nents could cause the control to malfunction.
TYPE 8B43A-601
RELA Y -HOT W A TER CONTROL
(Suitable for External Zone Valve Load)
INSTALLATION INSTRUCTIONS
DESCRIPTION
PRECAUTIONS
CAUTION
To prevent electrical shock and/or equipment damage, disconnect electric power to system, at main fuse or circuit breaker box, until installation is complete.
WARNING
Do not use on circuits exceeding specified voltages. Higher voltages will damage control and could cause shock or fire hazard.
ELECTRICAL DATA Input Voltage: 120V.A.C., 60Hz Circulator Motor: 120V.A.C. 8F.L.A. 48L.R.A. Burner Circuit: 120V.A.C. 8F.L.A. 48L.R.A.
Ignition Trans.: 3.0 Amps Burner Motor: 7F.L.A. 42L.R.A. or 125 VA Pilot Duty
Motorized Valve: 1.2A. Max. Room Thermostat:
Set adjustable heat anticipator at 0.25 Amps. For fixed anticipation thermostats, use 0.20 to 0.30 Amp. heater.
If the boiler manufacturer recommends a control location, then follow such recommendations. Otherwise, locate the control as close to the top of the boiler as possible, but not in the same section of the boiler that has fittings for domestic hot water. Never locate the control near a return pipe to the boiler.
WHITE-RODGERS DIVISION
EMERSON ELECTRIC CO. 9797 REAVIS RD., ST. LOUIS, MO. 63123 (314) 577-1300, FAX (314) 577-1517
9999 HWY. 48, MARKHAM, ONT. L3P 3J3 (905) 475-4653, FAX (905) 475-4625
R
Printed in U.S.A.
SPECIFICA TIONS
THERMAL DATA Range: High Limit - 140° to 240°F (60° to 116°C)
Low Limit / Circ. - 100° to 200°F (38° to 94°C)
Differential: High Limit - 10°F Fixed (5.5°C)
Low Limit / Circ. - 10° to 35°F Adj. (5.5° to 19°C)
Switch Action: High Limit - Open on rise
Low Limit / Circ. - SPDT
Well: 1/2" or 3/4" Thread Size
INSTALLATION
Install control as follows:
1. Install well securely into proper tapping.
2. Remove control cover. Then loosen the two screws holding well clamp to back of case. NOTE: Loosen until ends of screws are flush with well clamp for easiest assembly.
PART NO. 37-5488A
Replaces 37-2935-1
37-9333-1
9512
INSTALLATION CONT.
3. Insert sensing bulb into well, forming capillary so bulb bottoms in well. Raise control onto well, slipping flange on well between back of case and well clamp. Be sure well fits snugly into hole in case. Then tighten well clamp screws evenly and securely.
CAUTION
Do not dent or bend the bulb of the temperature sensitive element as this will prevent it from fitting properly into the well.
For best control performance it is recommended that the existing well be replaced with a well shown on page 3. However, by using the heat conductive grease
supplied in tube, these controls will give satisfactory performance when used with larger-diameter existing wells of many controls.
Use of adaptor requires that the existing immersion well be equipped with a set screw. After removing old control, install new one as follows:
DIAL SETTING
When replacing an existing control, adjust settings to correspond with those of the old control.
Setting the High Limit
Set pointer to temperature at which contacts are to open.
Setting the Low Limit-Circulator
1. Set brass pointer to lowest temperature of cycle.
2. Set aluminum pointer to highest temperature of cycle.
NOTE
Always set the high limit 20° or more above the low limit.
WIRING AND OPERATION
All wiring should be done in accordance with local and national electrical codes and ordinances.
The diagram below shows wiring connections for a typical oil-fired installation. Operation is as follows:
When the room thermostat is not calling for heat, the low limit-circulator control operates the burner motor as necessary to maintain the domestic hot water supply at the desired temperature (burner “on” when R-B contacts are closed).
When the room thermostat closes its contacts, the relay coil is energized and closes its two sets of relay contacts. The burner starts as the No. 1 Relay Contacts close. If the R-W contacts of the low limit-circulator control are closed, the circulator motor also starts as the No. 2 Relay Contacts close. If the R-W contacts open while the thermostat is calling for heat, the circulator motor stops but the burner stays on.
When the room thermostat is satisfied, the circulator motor stops as the No. 2 Relay Contacts open. The burner motor also stops as the No. 1 Relay Contacts open, unless the R-B contacts of the low limit-circulator are closed.
WELL CLAMP
ADAPTOR FLANGE
Fig. 1 MOUNTING TO EXISTING WELL (for types with well adaptor)
1.
Remove cover and loosen two screws holding well clamp.
CONTROL CASE
WELL ADAPTOR (F71-0924)
CAPILLARY
BULB
2. Fit capillary into slot in adaptor and push adaptor snugly into opening in back of case so adaptor flange fits between well clamp and case. Then tighten well clamp screws evenly and securely.
3. Apply heat conductive grease (supplied in tube) to fill void between bulb and well.
4. Insert bulb into existing well, forming capillary so bulb contacts bottom and side of well. Attach control to well by tightening set screw securely. (Be sure set screw is not directly above slot in well adaptor before tightening.)
POINTER
HIGH LIMIT LO LIMIT - CIR. 180
140160
240220200
SET HIGH LIMIT 20° OR MORE
ABOVE LOW LIMIT
Fig. 2
200 180
160
100 120 140
BRASS POINTER
If boiler temperature exceeds the setting of the high limit, the burner motor stops. If thermostat is calling for heat, the circulator continues to run.
EXTERNAL WIRING
Line Voltage Low Voltage
HOT
1
LINE
2
N
Fig. 3
INTERNAL WIRING
LOW LIMIT-CIRC. CONTROL
B
R
W
#2 RELAY CONTACT
C1
C2
ZC
ZC
Line Voltage Low Voltage
#1 RELAY CONTACT
S1
S2
B1
B2
CIRCULATOR
TRANSFORMER
HIGH LIMIT
MOTOR
LOW VOLTAGE THERMOSTAT
T2
T1
Z
TYPE 668 OIL
BURNER CONTROL
(LINE VOLTAGE)
2
ALUMINUM POINTER
RELAY COIL
IGNITION
TRANS.
BURNER
MOTOR