White Rodgers 1F89-211, 1F82-261 Reference Guide

1F82-261, -2XX / 1F89-211, -2XX TERMINAL CROSS-REFERENCE
SYSTEM AND
TERMINAL
DESIGNATIONS
COMMON
24 VAC
NEUTRAL
HOT
24 VAC
HOT
C/O
COOL
SWITCH
IN “O”
POSITION
1F82 or 1F89 C R O/B O/B G L E Y W2 NEW THERMOSTAT
ARCO /Snyder General C R O G X E Y W1 B.D.P. C R O G F E Y W1
CARRIER 50YQ C R O G L E Y W2 COLEMAN BLCK RED V G Y W2 G.E. BAY B R O G X2 Y W
HEIL-QUAKER B R O G Y W2 JANITROL C R O G E Y W2 LENNOX TYPICAL HP6 X V/VR R F M Y LENNOX HP8 X V/VR R F E M Y LENNOX HP9, 10 X V/VR R F L E M Y LENNOX HP16, 18, 19 X V/VR R F L E M Y MAGIC CHEF PE C R O G E Y W RHEEM/RUDD X R B G L E Y W2 SNYDER GENERAL
C R O G W1 H-R811/Y594R1375 TRANE TW B R O G F X2 Y W
TRANE TYPICAL B R O G F X2 Y W WEATHERKING C R Y1 G W1 E
WESCO C R Y1 G E W1 W2 WESCO/Addision X R O G E W1 WESTINGHOUSE H50 X R O G L1 E Y W WESTINGHOUSE HE X V Z F C H2 WHITE-RODGERS C R O G L E Y W2 WHITE-RODGERS X1 R O G E Y W2 YORK B R O G X Y W
TECH NOTES:
The shaded row above indicates the termi nal s available on the 1F82 and 1F89. The terminals below the shaded row are corresponding terminals used by various manufacturers on typical systems . If there is any question about the ident i fication or function of any terminal encountered during inst al l ation contact the manufacturer of the equipment before proceeding.
The 1F82-261, -2XX and 1F89-211, -2XX are designed for use on typical heat-pump systems with two stages of heat and one stage of c ool i ng. They require 24 volts hot to the “R” terminal and 24 volts neutral to the “C” terminal. Heat and Cool will not work without 24 volts applied to “R” and “C”.
Be sure the O/B switch is i n the correct position for the heat-pump the thermost at i s being installed on. If t he system requires both an “O” and a “B” si gnal from the thermostat use a 1F92 or 1F94 model.
C/O
HEAT
SWITCH
IN “B”
POSITION
FAN
INDOOR
BLOWER
MALF
LIGHT
MALFUNCTION
INDICATOR
EMER
EMERGENCY
HEAT
COMPRESSOR
HEAT PUMP
AUX
HEAT
BACK-
UP
HEAT
NOTES
(THIS CROSS-REFERENCE
REPRESENTS TYPICAL SYSTEMS.
ALSO SEE TECH NOTES BELOW)
IF OLD THERMOSTAT USES “Y”, “W1”,
AND “W2”, REPLACE WITH 1F92 OR 1F94.
“T” TERMINAL FROM OLD STAT NOT USED - TAPE
“T” TERMINAL FROM OLD STAT NOT USED - TAPE
“T” TERMINAL FROM OLD STAT NOT USED - TAPE
OFF.
OFF. OFF.
PART NO. 37-6262B