Whirlpool 99044506A, W10240582A User Manual

0 (0)
30" (76.2 CM) AND 36" (91.4 CM) RANGE HOOD
Installation Instructions and Use & Care Guide
HOTTE D’ASPIRATION DE
30" (76,2 CM) ET 36" (91,4 CM)
Instructions d’installation et Guide d’utilisation et d’entretien
Table of Contents/Table des matières.............................................................................2
IMPORTANT: READ AND SAVE THESE INSTRUCTIONS. FOR RESIDENTIAL USE ONLY. IMPORTANT : LIRE ET CONSERVER CES INSTRUCTIONS. POUR UTILISATION RÉSIDENTIELLE UNIQUEMENT.
99044506A/W10240582A
TABLE OF CONTENTS
TABLE DES MATIÈRES
RANGE HOOD SAFETY .................................................................2
INSTALLATION REQUIREMENTS................................................3
Tools and Parts ............................................................................3
Location Requirements................................................................ 4
Venting Requirements..................................................................5
Electrical Requirements ...............................................................6
INSTALLATION INSTRUCTIONS..................................................7
Prepare Location..........................................................................7
Install Range Hood.......................................................................8
Make Electrical Connection .......................................................10
Complete Installation .................................................................11
RANGE HOOD USE......................................................................12
Range Hood Controls ................................................................12
RANGE HOOD CARE...................................................................12
Cleaning......................................................................................12
ASSISTANCE OR SERVICE.........................................................13
In the U.S.A. ...............................................................................13
In Canada ...................................................................................13
WARRANTY ..................................................................................14
SÉCURITÉ DE LA HOTTE DE CUISINIÈRE ...............................15
EXIGENCES D'INSTALLATION...................................................17
Outils et pièces...........................................................................17
Exigences d'emplacement.........................................................17
Exigences concernant l'évacuation ...........................................18
Spécifications électriques ..........................................................20
INSTRUCTIONS D'INSTALLATION.............................................20
Préparation de l'emplacement...................................................20
Installation de la hotte ................................................................22
Raccordement électrique...........................................................24
Achever l'installation ..................................................................24
UTILISATION DE LA HOTTE .......................................................26
Commandes de la hotte de cuisinière .......................................26
ENTRETIEN DE LA HOTTE..........................................................26
Nettoyage ...................................................................................26
ASSISTANCE OU SERVICE.........................................................27
GARANTIE.....................................................................................28
RANGE HOOD SAFETY
Your safety and the safety of others are very important.
We have provided many important safety messages in this manual and on your appliance. Always read and obey all safety messages.
This is the safety alert symbol. This symbol alerts you to potential hazards that can kill or hurt you and others. All safety messages will follow the safety alert symbol and either the word “DANGER” or “WARNING.”
These words mean:
You can be killed or seriously injured if you don't immediately
DANGER
WARNING
All safety messages will tell you what the potential hazard is, tell you how to reduce the chance of injury, and tell you what can happen if the instructions are not followed.
follow instructions.
can be killed or seriously injured if you don't
You instructions.
follow
2
IMPORTANT SAFETY INSTRUCTIONS
WARNING: TO REDUCE THE RISK OF FIRE, ELECTRIC
SHOCK, OR INJURY TO PERSONS, OBSERVE THE FOLLOWING:
Use this unit only in the manner intended by the
manufacturer. If you have questions, contact the manufacturer.
Before servicing or cleaning the unit, switch power off at
service panel and lock the service disconnecting means to prevent power from being switched on accidentally. When the service disconnecting means cannot be locked, securely fasten a prominent warning device, such as a tag, to the service panel.
Installation work and electrical wiring must be done by
qualified person(s) in accordance with all applicable codes and standards, including fire-rated construction.
Sufficient air is needed for proper combustion and
exhausting of gases through the flue (chimney) of fuel burning equipment to prevent backdrafting. Follow the heating equipment manufacturer's guideline and safety standards such as those published by the National Fire Protection Association (NFPA), the American Society for Heating, Refrigeration and Air Conditioning Engineers (ASHRAE), and the local code authorities.
When cutting or drilling into wall or ceiling; do not damage
electrical wiring and other utilities.
Ducted fans must always be vented outdoors. CAUTION: For general ventilating use only. Do not use
to exhaust hazardous or explosive materials and vapors.
CAUTION: To reduce risk of fire and to properly exhaust
air, be sure to duct air outside - do not vent exhaust air into spaces within walls or ceilings, attics or into crawl spaces, or garages.
WARNING: TO REDUCE THE RISK OF FIRE, USE ONLY
METAL DUCTWORK.
WARNING: TO REDUCE THE RISK OF A RANGE TOP
GREASE FIRE:
Never leave surface units unattended at high settings.
Boilovers cause smoking and greasy spillovers that may ignite. Heat oils slowly on low or medium settings.
Always turn hood ON when cooking at high heat or when
flambeing food (i.e. Crepes Suzette, Cherries Jubilee, Peppercorn Beef Flambé).
Clean ventilating fans frequently. Grease should not be
allowed to accumulate on fan or filter.
Use proper pan size. Always use cookware appropriate for
the size of the surface element.
WARNING: TO REDUCE THE RISK OF INJURY TO
PERSONS IN THE EVENT OF A RANGE TOP GREASE FIRE, OBSERVE THE FOLLOWING:
SMOTHER FLAMES with a close fitting lid, cookie sheet, or
metal tray, then turn off the burner. BE CAREFUL TO PREVENT BURNS. If the flames do not go out immediately, EVACUATE AND CALL THE FIRE DEPARTMENT.
NEVER PICK UP A FLAMING PAN - you may be burned.
DO NOT USE WATER, including wet dishcloths or towels -
a violent steam explosion will result.
Use an extinguisher ONLY if:
– You know you have a class ABC extinguisher, and you
already know how to operate it.
– The fire is small and contained in the area where it
started. – The fire department is being called. – You can fight the fire with your back to an exit.
a
Based on "Kitchen Fire Safety Tips" published by NFPA.
WARNING: To reduce the risk of fire or electrical shock,
do not use this fan with any solid-state speed control device.
a
SAVE THESE INSTRUCTIONS
INSTALLATION REQUIREMENTS
Tools and Parts
Gather the required tools and parts before starting installation. Read and follow the instructions provided with any tools listed here.
Tool s ne ed ed
Drill
1¹⁄₄" (3.0 cm) drill bit
¹⁄₈" (3.0 mm) drill bit for pilot holes
Pencil
Wire stripper or utility knife
Tape measure or ruler
Caulking gun and weatherproof caulking compound
Flat-blade screwdriver
Phillips screwdriver
For vented installations, you also need:
Saber or keyhole saw
Vent clamps
Metal snips
Compass or 8" (20.3 cm) circle template
Parts supplied
Remove parts from package. Check that all parts are included.
2 - Aluminum filters
4 - #10 x ⁵⁄₈" mounting screws
2 - ¼" black damper screws
3¹⁄₄" x 10" (8.3 x 25.4 cm) damper/vent connector
3
Parts needed
For direct wire installation
UL listed or CSA approved ¹⁄₂" (12.5 mm) strain relief
2 - 75-watt max incandescent light bulbs
or 1 - 75-watt max and 1 - 25-watt max incandescent light bulb
(for use as a night light)
Power supply cable (if needed, for direct wire installation)
For power supply cord installation
UL Listed Power Supply Cord Connection Kit marked for
range hood use.
2 - 75-watt max incandescent light bulbs
or 1 - 75-watt max and 1 - 25-watt max incandescent light bulb
(for use as a night light)
For vented installations you also need:
3¹⁄₄" x 10" (8.3 x 25.4 cm) or 6" (15.2 cm) or larger round metal
venting
6" (15.2 cm) or larger round damper, if using 6" (15.2 cm) or
larger round vent system
3¹⁄₄" x 10" (8.3 x 25.4 cm) to 6" (15.2 cm) or larger diameter
transition piece
For cabinets with recessed bottoms:
Two 2" (5.1 cm) wide filler strips. Length and thickness
determined by recess dimensions.
Four flat head wood screws or machine screws with washers
and nuts (to attach filler strips).
Location Requirements
IMPORTANT: Observe all governing codes and ordinances.
It is the installer’s responsibility to comply with installation
clearances specified on the model/serial rating plate. The model/serial rating plate is located inside the range hood on the left wall.
Range hood location should be away from strong draft areas,
such as windows, doors and strong heating vents.
Cabinet opening dimensions that are shown must be used.
Given dimensions provide minimum clearance. Consult the cooktop/range manufacturer installation instructions before making any cutouts.
Grounded electrical outlet is required. See “Electrical
Requirements” section.
The hood is factory-set for vented installations. For non-
vented (recirculating) installations, charcoal filter pad Part Number 4396390 is available. See the “Assistance or Service” section for information on ordering.
All openings in ceiling and wall where range hood will be
installed must be sealed.
Product Dimensions
1¹⁄₂"
(3.8 cm)
9"
2"
(5.1 cm)
³⁄₄"
7¹⁄₂"
(19.1 cm)
(30.5 cm)
9"
(22.9 cm)
12"
(22.9 cm)
(1.9 cm)
29 ⁷⁄₈" (75.9 cm) - 30" (76.2 cm) model 35 ⁷⁄₈" (91.1 cm) - 36" (91.4 cm) model
Installation Clearances
24" (61.0 cm) min.
30" (76.2 cm)
suggested max. bottom of cabinet to cooking surface
18" (45.7 cm)
min. clearance
upper cabinet
to countertop
36" (91.4 cm)
base cabinet
height
1"
(2.5 cm)
³⁄₈"
(9.5 mm)
30" (76.2 cm) or
36" (91.4 cm) min.
cabinet opening width
13" (33.0 cm)
cabinet depth
1¹⁄₂"
(3.8 cm)
20"
(44.5 cm)
For Mobile Home Installations
The installation of this range hood must conform to the Manufactured Home Construction Safety Standards, Title 24 CFR, Part 328 (formerly the Federal Standard for Mobile Home Construction and Safety, title 24, HUD, Part 280) or when such standard is not applicable, the standard for Manufactured Home Installation 1982 (Manufactured Home Sites, Communities and Setups) ANSI A225.1/NFPA 501A*, or latest edition, or with local codes.
4
Venting Requirements
E
(Vented Models Only)
Vent system must terminate to the outdoors, except for non-
vented (recirculating) installations.
Do not terminate the vent system in an attic or other enclosed
area.
Do not used a 4" (10.2 cm) laundry-type wall cap.
Use a 6" (15.2 cm) or larger round metal vent or a 3¹⁄₄" x 10"
(8.3 x 25.4 cm) rectangular metal vent. Rigid metal vent is recommended. Plastic or metal foil vent is not recommended.
The length of vent system and number of elbows should be
kept to a minimum to provide efficient performance.
For the most efficient and quiet operation:
Use no more than three 90° elbows.
Make sure there is a minimum of 24" (61 cm) of straight vent
between the elbows if more than 1 elbow is used.
Do not install 2 elbows together.
Use clamps to seal all joints in the vent system.
The vent system must have a damper. If roof or wall cap has a
damper, do not use damper supplied with the range hood.
Use caulking to seal exterior wall or roof opening around the
cap.
Cold Weather Installations
An additional back draft damper should be installed to minimize backward cold air flow and a thermal break should be installed to minimize conduction of outside temperatures as part of the vent system. The damper should be on the cold air side of the thermal break.
The break should be as close as possible to where the vent system enters the heated portion of the house.
Roof Venting Wall Venting
A
B
E
A
B
C
C
D
D
A. 6" (15.2 cm) or larger round
vent or a 3¹⁄₄" x 10" (8.3 x
25.4 cm) rectangular vent through roof
B. Round vent: use 6" (15.2 cm)
or larger round damper (purchased separately)
C. Round vent: use 3¹⁄₄" x 10"
(8.3 x 25.4 cm) to 6" (15.2 cm) or larger diameter transition piece (purchased separately)
D. 24" (61.0 cm) - 30" (76.2 cm)
above cooking surface
E. Roof cap
A. 6" (15.2 cm) or larger round
vent or a 3¹⁄₄" x 10" (8.3 x
25.4 cm) rectangular vent through the wall
B. Round vent: use 3¹⁄₄" x 10" (8.3
x 25.4 cm) to 6" (15.2 cm) or larger diameter transition piece (purchased separately)
C. 3¹⁄₄" x 10" (8.3 x 25.4 cm)
through the wall
D. 24" (61.0 cm) - 30" (76.2 cm)
above cooking surface
E. Wall cap
Calculating Vent System Length
To calculate the length of the system you need, add the equivalent feet (meters) for each vent piece used in the system.
Makeup Air
Local building codes may require the use of make up air systems when using ventilation systems greater than specified CFM of air movement. The specified CFM varies from locale to locale. Consult your HVAC professional for specific requirements in your area.
Venting Methods
Vent system can terminate either through the roof or wall. Use 3¹⁄₄" x 10" (8.3 x 25.4 cm) with a maximum vent length of 35 ft (10.7 m) or 6" (15.2 cm) or larger round vent with a maximum length of 50 ft (15.2 m) for vent system.
NOTE: Flexible vent is not recommended. Flexible vent creates back pressure and air turbulence that gently reduces performance.
6" (15.2 cm) or Larger Round Vent System
Vent Piece Round
45° elbow 2.5 ft
90° elbow 5.0 ft
6" (15.2 cm) or larger wall cap
3¹⁄₄" x 10" (8.3 cm x 25.4 cm) to 6" (15.2 cm) or larger
3¹⁄₄" x 10" (8.3 cm x 25.4 cm) to 6" (15.2 cm) or larger 90° elbow
(0.8 m)
(1.5 m)
0.0 ft (0.0 m)
4.5 ft (1.4 m)
5.0 ft (1.5 m)
5
Example vent system
90˚ elbow
2 ft (0.6 m)
6 ft (1.8 m)
Maximum Recommended Length = 50 ft (15.2 m)
1 - 90° elbow = 5.0 ft (1.5 m) 1 - wall cap = 0.0 ft (0.0 m) 8 ft (2.4 m) straight = 8.0 ft (2.4 m) Length of 7" (17.8 cm) system = 13.0 ft (3.9 m)
Wall cap
3¹⁄₄" x 10" (8.3 cm x 25.4 cm) Vent System
Vent Piece
3¹⁄₄" x 10" (8.3 cm x 25.4 cm) 90° elbow
3¹⁄₄" x 10" (8.3 cm x 25.4 cm) flat elbow
3¹⁄₄" x 10" (8.3 cm x 25.4 cm) wall cap
5.0 ft (1.5 m)
12.0 ft (3.7 m)
0.0 ft (0.0 m)
Example vent system
Electrical Requirements
Observe all governing codes and ordinances. Ensure that the electrical installation is adequate and in
conformance with National Electrical Code, ANSI/NFPA 70 (latest edition), or CSA Standards C22.1-94, Canadian Electrical Code, Part 1 and C22.2 No. 0-M91 (latest edition) and all local codes and ordinances.
If codes permit and a separate ground wire is used, it is recommended that a qualified electrician determine that the ground path is adequate.
A copy of the above code standards can be obtained from:
National Fire Protection Association
One Batterymarch Park
Quincy, MA 02269
CSA International
8501 East Pleasant Valley Road
Cleveland, OH 44131-5575
A 120 Volt, 60 Hz., AC only, 15-amp, fused electrical circuit is
required.
If the house has aluminum wiring follow the procedure below:
1. Connect a section of solid copper wire to the pigtail
leads.
2. Connect the aluminum wiring to the added section of
copper wire using special connectors and/or tools designed and UL listed for joining copper to aluminum.
Follow the electrical connector manufacturer's recommended procedure. Aluminum/copper connection must conform with local codes and industry accepted wiring practices.
Wire sizes and connections must conform with the rating of
the appliance as specified on the model/serial rating plate. The model/serial plate is located behind the filter on the rear wall of the range hood.
Wire sizes must conform to the requirements of the National
Electrical Code, ANSI/NFPA 70 (latest edition), or CSA Standards C22. 1-94, Canadian Electrical Code, Part 1 and C22.2 No. 0-M91 (latest edition) and all local codes and ordinances.
3
¹⁄₄" x 10"
elbow
6 ft (1.8 m)
Wall cap
(8.3 x 25.4 cm)
2 ft
(0.6 m)
Maximum Recommended Length = 35 ft (10.7 m)
1 - 90° elbow = 5.0 ft (1.5 m) 8 ft (2.4 m) straight = 8.0 ft (2.4 m) 1 - wall cap = 0.0 ft (0.0 m) Length of 3¹⁄₄" x 10" (8.3 cm x 25.4 cm)
= 13.0 ft (3.9 m)
system
6
INSTALLATION INSTRUCTIONS
Prepare Location
NOTE: For vented installations, it is recommended that the vent system be installed before hood is installed.
Before making cutouts, make sure there is proper clearance within the ceiling or wall for exhaust vent.
1. For vented installations, determine which venting method to
use: roof or wall.
2. Select a flat surface for assembling the range hood. Place
covering over that surface.
2. To wire through top:
Mark a line 7½" (19.0 cm) from the right of the centerline on the underside of the cabinet. Mark the point on this line that is 2" (5.0 cm) from back wall. Drill a 1¼" (3.0 cm) diameter hole through the cabinet at this point.
WARNING
Excessive Weight Hazard
Use two or more people to move and install range hood.
Failure to do so can result in back or other injury.
3. Using 2 or more people, lift the range hood and set it upside
down onto covered surface.
4. If cabinet has recessed bottom, add wood filler strips on each
side. Install screws to attach filler strips in locations shown.
Wood filler strips (recessed cabinet
3" (7.6 cm)
3" (7.6 cm)
Determine Wiring Hole Location
Cut only one 1¹⁄₄" (3.2 cm) diameter wiring access hole. See Step 2 for wiring hole location instructions. Either wiring hole can be used.
1. Determine and clearly mark a vertical centerline on the wall
and cabinet in the area the vent opening will be made.
bottoms only)
Cabinet bottom
Wall
7 ¹⁄₂" (19 cm)
Centerline
2" (5.1 cm) from wall, not cabinet frame
To wire through rear wall: Mark a line 7½" (19.0 cm) from the right of the centerline on
the wall. Mark the point on this line that is ¾" (1.9 cm) from underside of cabinet. Drill a 1¼" (3.0 cm) diameter hole through wall at this point.
³⁄₄" (1.9 cm)
7 ¹⁄₂" (19 cm)
Centerline
Style 1 - Cut Openings for 3¼" x 10" (8.3 cm x 25.4 cm) Rectangular Vent System
Roof Venting
To make a 4" x 10½" (10.2 cm x 26.7 cm) rectangular cutout on the underside of cabinet top and bottom:
1. Mark lines 1½" (3.8 cm) and 5½" (14.0 cm) from the back wall
on the centerline of the underside of cabinet.
2. Mark lines 5¼" (13.3 cm) to the right and left of the centerline
on the underside of cabinet.
3. Use saber or keyhole saw to cut a rectangular opening for
vent.
4. Repeat steps 1-3 for the underside of the top of the cabinet.
A
A. Centerline
Cabinet cutouts
*1¹/" (3.8 cm)
*5¹/"
(14 cm)
(13.3 cm)
*From wall, not cabinet frame
5¹/"
5¹/"
(13.3 cm)
7
Wall Venting
A
A
A
B
To make a 4" x 10½" (10.2 cm x 26.7 cm) rectangle in the wall:
1. Make 2 lines by measuring from floor 65⁷⁄₈" (167.3 cm) and
62³⁄₈" (158.4 cm) or ¹⁄₈" (3.2 mm) and 3⁵⁄₈" (9.2 cm) down from underside of cabinet and mark on the centerline on the back wall.
2. Mark lines 5¼" (13.3 cm) to the right and left of the centerline
on the wall.
3. Use saber or keyhole saw to cut a rectangular opening in the
wall for the vent.
Centerline
5
¹⁄₄"
(13.3 cm)
3 ⁵⁄₈"
(9.2 cm)
¹⁄₈"
(3.2 mm)
Cabinet
front
4. Use saber or keyhole saw to cut the circular vent opening.
Circular vent opening
*5"
(12.7 cm)
Cabinet
cutouts
*From wall, not
cabinet frame
Install Vent System
Style 2 - Cut Openings for 3¼" x 10" (8.3 x 25.4 cm) Rectangular Vent to 7" (17.8 cm) Round Vent Transition
Roof Venting
To make a 4" x 10½" (10.2 x 26.7 cm) rectangular cutout on the underside of cabinet bottom:
1. Mark lines 1½" (3.8 cm) and 5½" (14.0 cm) from the back wall
on the centerline of the underside of cabinet.
2. Mark lines 5¼" (13.3 cm) to the right and left of the centerline
on the underside of cabinet.
3. Use saber or keyhole saw to cut a rectangular opening for
vent.
*1¹/" (3.8 cm)
*5¹/"
(14 cm)
(13.3 cm)
*From wall, not cabinet frame
To make a circular vent opening on the underside of the cabinet top:
1. Mark a centerline on the underside of the top of cabinet.
2. Mark a line 5" (12.7 cm) from the back wall on the underside
of the top of cabinet.
3. Use a compass or a circle template to draw a circle with a
diameter that is ¼" (0.64 cm) larger than the vent.
5¹/"
5¹/"
(13.3 cm)
1. Install vent through the vent opening in upper cabinet or wall.
Complete venting system according to the selected venting method. See “Venting Requirements” section.
2. Use caulking to seal exterior wall or roof opening around the
cap.
Install Range Hood
1. Remove bottom cover screws and bottom cover.
A
B
A. Bottom cover screws
B. Bottom cover
2. Remove filters. See “Range Hood Care” section.
3. Remove terminal box cover.
A. Terminal box cover screws
B. Terminal box cover
8
4. It is recommended that the blower assembly be removed to
A
make the range hood lighter and easier to install.
To remove:
Disconnect blower wiring plug.
If using rectangular vent, attach rectangular damper/vent
connectors to the range hood using 2 black sheet metal screws.
A
B
C
D
E
B
A. Blower B. Blower wiring plug
Loosen, but do not remove, knurled nuts on mounting
rods. Slip rods out of blower mounting brackets.
B
A
A. Mounting rod B. Knurled nut
IMPORTANT: To avoid damage, do not grasp blower by blower wheels.
Lift blower out and set aside.
5. Depending on your installation, remove either back or top
wiring knockout.
6. For vented installations:
Check that the louver cover is installed in front of hood.
Depending on your installation, remove either top or rear
rectangular vent knockout. If using round vent, remove top rectangular knockout.
NOTE: Do not remove rectangular knockouts if installation of range hood is to be non-venting (recirculating).
B
A. Vertical vent B. Black sheet metal screws C. Hinge pin D. Vent knockouts
E. Horizontal vent
If using round vent, attach vent transition piece
C
(purchased separately) to range hood top using 2 black sheet metal screws.
NOTE: If the wall cap is directly behind the vent connector, the dampers in the connector and wall cap must not interfere with each other. Remove the vent connector damper if they interfere.
7. Lift the range hood up under cabinet and determine final
location by centering beneath cabinet. Mark on the underside of cabinet the location of the 4 keyhole mounting slots on the range hood. Set range hood aside on a covered surface.
A
A. Keyhole slot
8. Use ¹⁄₈" (3 mm) drill bit and drill 4 pilot holes as shown.
A
A. Drill pilot hole
9
Loading...
+ 19 hidden pages