Whirlpool 311433 User Manual

hisialkitkHi liiiiiriiclkNis
ELEQRK SET-IN
UNIT
(STARTING WITH 1982 MODELS)
Part No. 311433 Rev. C
■ A" = 30" MIN. CLEARANCE BETWEEN THE TOP OF THE COOKING PLATFORM AND THE BOTTOM OF AN UNPROTECTED WOOD OR METAL CABINET.
"A" = 24" MIN. WHEN BOTTOM OF WOOD OR METAL CABINET IS PROTECTED BY NOT LESS THAN FLAME RETARDANT MILLBOARD COVERED WITH NOT LESS THAN NO. 28 MSG. SHEET STEEL, 0.015" STAINLESS STEEL, 0.024" ALUMINUM OR
0.020" COPPER.
CAUTION: To eliminate the hazard of reaching over heated surface units, cabinet storage space located above the surface units should be avoided. If cabinet storage is to be provided, the hazard can be reduced by installing a range hood that projects horizontally a minimum of 5 inches beyond the bottom of the cabinets.
FOR COUNTERTOP AND CABI JET FRONT CUT-OUT DIMENSIONS —SEi: F RONT AND TOP VIEWS OF CABINET SHO' VN BELOW
LOCATE electrical
SUPPLY JUNCTION IlOX
ON FLOOR OR 0 J
REAR WALL NEA 1
FLOOR LINE.
28%" WRAP TO WRAP
INCLUDING SCREW HEADS
NOTE: ON CABINET TOPS WITH
FORMED FRONT EDGE, SHAVE
RAISED SECTION TO CLEAR
30" WIDE RIM. (SEE SKETCH BELOW)
48" CABLE
28-1/2" MINIMUM. IF 28-5/8" IS AVAILABLE THE CUTOUT SHOULD BE MADE 28-5/8".
FIGURE 1-ROUGH-IN DIMENSIONS
23"
T FRONT
i
CABINET
FRONT
%" MIN. REQUIRED BETWEEN
CUTOUT AND HINGE OR DOOR
WALL LINE
^
___________
COUNTEFtTOP OPENING
i
----
29-1/16"—i
CABINET OPENING ♦*
-28-1/2'
FRONT VIEW
C JJNTERTOP

NOTE:

The Installation must conform to any local codes. The Set-In Unit may be mounted and secured to the cabinet similar to regular built-in equipment.

1. CARPENTRY

Prepare the cut-out space, shown in
desired location in the counter top and cabinet. The support surface
(AVz”
high) must be solid and level from side to side and front to rear. A minimum of %” of cabinet area on either side of cut-out should be clear of handles, hinges or any other obstruction.
Figure 1,
in the

2. ELECTRICAL REQUIREMENTS

IMPORTANT: OBSERVE ALL GOVERNING CODES
AND ORDINANCES
SAVE THESE INSTRUCTIONS FOR THE LOCAL
ELECTRICAL INSPECTOR'S USE
A. A three-wire or four-wire single phase 120/240 vo t
60Hz AC only electrical supply (or three-wire cr four-wire 120/208 volt if specified on nameplate) ii > required on a separate circuit fused on both side; of the line (time-delay fuse or circuit breaker Ii > recommended). Do NOT fuse neutral. The fuse siz:; must not exceed the circuit rating of the appliance; specified on the nameplate.
NOTE: Wire sizes and connections must conforn with the fuse size and rating of the appliance i i accordance with the National Electrical Code an( 1 local codes and ordinances. Do not use an extension cord.
Loading...
+ 2 hidden pages