wheelock SA-S90-24MCC INSTALLATION INSTRUCTIONS

273 Branchport Avenue Long Branch, N.J. 07740 (800) 631-2148 Thank you for using our products. www.wheelockinc.com
INSTALLATION INSTRUCTIONS
Use this product according to this instruction manual. Please keep this instruction manual for future reference.
(CEILING MOUNT VERSION)
MODEL NUMBERS:
Speaker Strobe SA-S90-24MCC-FR Supervised Self-Amplified Speaker with Multi-Candela Speaker Strobe SA-S90-24MCC-FW Sync/Non-Sync Strobe, Ceiling Mount
GENERAL:
The Multi-Candela Supervised Self-Amplified Speaker Strobe provides a choice of 6 different sound output levels and operates with audio input levels of 0.5 V RMS (e.g., from Wheelock’s SALL-15S or any other 0.5V-RMS audio output source Listed for Fire Protective Signaling Service) and 25 V RMS, all by means of selectable switch settings. The Low Profile design incorporates a high efficiency speaker for maximum output at minimum power across a frequency range of 400Hz to 4000Hz, and features a sealed back construction for extra protection and improved audibility. The appliance mounts onto a 4” square deep backbox with an extension ring. (See Mounting Options.) All inputs are polarized for compatibility with standard reverse polarity supervision of circuit wiring via a Control Panel.
The SA Series Multi-Candela Speaker Strobe provides four selectable light output intensities in one unit and can provide a non-synchronized strobe appliance when connected directly to a Fire Alarm Control Panel (FACP), or provide a synchronized strobe appliance when used in conjunction with a Sync Module (SM), Dual Sync Module (DSM) or Wheelock’s Power Supplies listed for synchronization. The Strobe uses a Xenon flashtube with solid-state circuitry enclosed in a rugged Lexan lens to provide maximum visibility and reliability for effective visible signaling. The SA Series is listed for indoor use, ceiling mount only
with the backboxes
specified in these instructions (see Mounting Options).
NOTE: “Lexan” is a registered trademark of General Electric Company.
NOTE: All CAUTIONS and WARNINGS are identified by the symbol
. All warnings are printed in bold capital letters.
WARNING: THE SPEAKER STROBE APPLIANCE IS A "FIRE ALARM DEVICE - DO NOT PAINT."
WARNING: PLEASE READ THESE INSTRUCTIONS CAREFULLY BEFORE USING THIS PRODUCT. THE SUPERVISED SELF-AMPLIFIED SPEAKER STROBE MUST BE FIELD SET TO THE DESIRED SOUND OUTPUT LEVEL BEFORE IT IS INSTALLED. THIS IS DONE BY PROPERLY ADJUSTING A FOUR-POSITION SWITCH IN ACCORDANCE WITH THESE INSTRUCTIONS. INCORRECT SETTINGS WILL RESULT IN IMPROPER PERFORMANCE AND MAY DAMAGE THE PRODUCT, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
NOTE: THE MAXIMUM WIRE IMPEDENCE BETWEEN STROBES SHALL NOT EXCEED 35 OHMS. THE MAXIMUM NUMBER OF STROBES ON A SINGLE NOTIFICATION APPLIANCE CIRCUIT SHALL NOT EXCEED 47.
WARNING: THIS APPLIANCE WAS TESTED TO THE OPERATING VOLTAGE LIMITS OF 16-33 VOLTS USING FILTERED (DC) OR UNFILTERED FULL-WAVE-RECTIFIED (FWR) POWER FOR THE STROBE. THE AMPLIFIER WAS TESTED TO THE OPERATING VOLTAGE LIMITS OF 16-33 VOLTS REGULATED POWER. DO NOT APPLY 80% AND 110% OF THESE VOLTAGE VALUES FOR SYSTEM OPERATION.
Copyright 2004 Wheelock, Inc. All rights reserved.
P84503 C
Sheet 1 of 8
WARNING: CHECK THE MINIMUM AND MAXIMUM OUTPUT OF THE POWER SUPPLY AND STANDBY BATTERY AND SUBTRACT THE VOLTAGE DROP FROM THE CIRCUIT WIRING RESISTANCE TO DETERMINE THE APPLIED VOLTAGE TO THE STROBES.
SPECIFICATIONS (AMPLIFIER):
Table 1A: Sound Output Level
Sound
Level
10 ft per UL 1480 for 0.5-V and 25-V Settings
Rated Reverberant dBA at
6 84 5 81 4 77 3 74 2 71 1 68
NOTE: See Table 5 Sound Output Level Selection for use of settings “A” and “B”.
Power Input Voltage: 16.0 to 33.0 VDC, regulated Current Consumption: 120 mA RMS maximum Appliance Input Level: 0.5 V RMS or 25 V RMS (Switch selectable) Appliance Input Impedance: 0.5-V Setting:
Greater than 400 Ohms, or equivalent to less than 1/1000 W (0.001 W or 1 mW) load
25-V Setting: Greater than 20 kOhms, or equivalent to less than 1/32 W (0.03125 W or 31.25 mW) load
Sound pressure level measurements were made at 16 VDC with audio inputs of 0.5 V RMS in the 0.5-V setting and with 25 V RMS in the 25-V setting. Current measurements were made at 33 VDC with audio inputs of 0.5 V RMS in the 0.5-V setting and with 25 V RMS in the 25-V setting.
Reverberant dBA is a minimum UL rating based on sound measurements in a reverberant test room.
Table 1B: Strobe
Regulated Voltage
VDC/VRMS
24 16.0-33.0 15/30/75/95 A,B
Voltage Range
VDC/VRMS
Candela Mounting
NOTES:
1. The strobe will produce 1 flash per second over the "Regulated Voltage" range.
Options
P84503 C
Sheet 2 of 8
WARNING: CANDELA SETTING WILL DETERMINE THE CURRENT DRAW OF THE PRODUCT.
Table 2: UL Current Ratings (AMPS)
Maximum RMS Current
UL Voltage 15cd 30cd 75cd 95cd DC 16-33.VDC 0.065 0.105 0.189 0.249 FWR 16-33.VRMS 0.110 0.170 0.280 0.375
WARNING: MAKE SURE THAT THE TOTAL RMS CURRENT REQUIRED BY ALL APPLIANCES THAT ARE CONNECTED TO THE SYSTEM’S PRIMARY AND SECONDARY POWER SOURCES, NAC CIRCUITS, SM, DSM SYNC MODULES OR WHEELOCKS POWER SUPPLIES DO NOT EXCEED THE POWER SOURCES’ RATED CAPACITY OR THE CURRENT RATINGS OF ANY FUSES ON THE CIRCUITS TO WHICH THESE APPLIANCES ARE WIRED. OVERLOADING POWER SOURCES OR EXCEEDING FUSE RATINGS COULD RESULT IN LOSS OF POWER AND FAILURE TO ALERT OCCUPANTS DURING AN EMERGENCY, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
When calculating the total currents: Use Table 2 to determine the highest value of “RMS Current” for an individual strobe (across the expected operating voltage range of the strobe), then multiply these values by the total number of strobes; be sure to add the currents for any other appliances, including audible signaling appliances, powered by the same source and include any required safety factors.
If the peak current exceeds the power supplies’ peak capacity, the output voltage provided by the power supplies may drop below the listed voltage range of the appliances connected to the supply and the voltage may not recover in some types of power supplies. For example, an auxiliary power supply that lacks filtering at its output stage (either via lack of capacitance and/or lack of battery backup across the output) may exhibit this characteristic.
CAUTION: The Speaker Strobe is not designed to be used on coded systems in which the applied voltage is cycled on and off.
LIGHT DISTRIBUTION:
Table 3A: Horizontal Plane
Horizontal 15cd 30cd 75cd 95cd
Angle (in deg.) UL Min. Typ. 15cd UL Min. Typ. 30cd UL Min. Typ. 75cd UL Min. Typ. 95cd
0 15.0 20.5 30.0 43.3 75.0 102.6 95.0 146.0 5 13.5 20.5 27.0 43.3 67.5 102.6 85.5 146.0 10 13.5 20.1 27.0 43.0 67.5 102.0 85.5 145.0 15 13.5 20.2 27.0 42.7 67.5 102.0 85.5 145.0 20 13.5 18.8 27.0 40.0 67.5 97.1 85.5 134.1 25 13.5 16.9 27.0 35.0 67.5 85.5 85.5 121.3 30 11.3 15.3 22.5 32.7 56.3 80.0 71.3 111.6 35 11.3 14.8 22.5 31.1 56.3 74.0 71.3 106.3 40 11.3 14.1 22.5 29.0 56.3 70.6 71.3 100.7 45 11.3 12.8 22.5 25.9 56.3 62.3 71.3 90.7 50 8.3 11.3 16.5 23.3 41.3 57.1 52.3 81.2 55 6.8 11.9 13.5 23.8 33.8 57.7 42.8 84.5 60 6.0 11.3 12.0 22.3 30.0 52.2 38.0 78.1 65 5.3 10.1 10.5 20.9 26.3 48.9 33.3 69.1 70 5.3 9.7 10.5 19.8 26.3 44.7 33.3 64.7 75 4.5 12.3 9.0 25.0 22.5 57.8 28.5 81.7 80 4.5 10.6 9.0 21.9 22.5 51.3 28.5 69.4 85 3.8 5.4 7.5 12.1 18.8 28.7 23.8 37.2 90 3.8 7.6 7.5 16.6 18.8 39.8 23.8 49.7
P84503 C
Sheet 3 of 8
Loading...
+ 5 hidden pages