INSTALLATION INSTRUCTIONS
SUPERVISED SELF-AMPLIFIED SPEAKER STROBE
Use this product according to this instruction manual. Please keep this instruction manual for future reference.
(CEILING MOUNT VERSION)
MODEL NUMBERS:
Speaker Strobe SA-S90-24MCC-FR Supervised Self-Amplified Speaker with Multi-Candela
Speaker Strobe SA-S90-24MCC-FW Sync/Non-Sync Strobe, Ceiling Mount
GENERAL:
The Multi-Candela Supervised Self-Amplified Speaker Strobe provides a choice of 6 different sound output levels and operates with
audio input levels of 0.5 V RMS (e.g., from Wheelock’s SALL-15S or any other 0.5V-RMS audio output source Listed for Fire
Protective Signaling Service) and 25 V RMS, all by means of selectable switch settings. The Low Profile design incorporates a high
efficiency speaker for maximum output at minimum power across a frequency range of 400Hz to 4000Hz, and features a sealed back
construction for extra protection and improved audibility. The appliance mounts onto a 4” square deep backbox with an extension
ring. (See Mounting Options.) All inputs are polarized for compatibility with standard reverse polarity supervision of circuit wiring
via a Control Panel.
The SA Series Multi-Candela Speaker Strobe provides four selectable light output intensities in one unit and can provide a
non-synchronized strobe appliance when connected directly to a Fire Alarm Control Panel (FACP), or provide a synchronized strobe
appliance when used in conjunction with a Sync Module (SM), Dual Sync Module (DSM) or Wheelock’s Power Supplies listed for
synchronization. The Strobe uses a Xenon flashtube with solid-state circuitry enclosed in a rugged Lexan lens to provide maximum
visibility and reliability for effective visible signaling. The SA Series is listed for indoor use, ceiling mount only
with the backboxes
specified in these instructions (see Mounting Options).
NOTE: “Lexan” is a registered trademark of General Electric Company.
NOTE: All CAUTIONS and WARNINGS are identified by the symbol
. All warnings are printed in bold capital letters.
WARNING: THE SPEAKER STROBE APPLIANCE IS A "FIRE ALARM DEVICE - DO NOT PAINT."
WARNING: PLEASE READ THESE INSTRUCTIONS CAREFULLY BEFORE USING THIS PRODUCT. THE
SUPERVISED SELF-AMPLIFIED SPEAKER STROBE MUST BE FIELD SET TO THE DESIRED SOUND OUTPUT
LEVEL BEFORE IT IS INSTALLED. THIS IS DONE BY PROPERLY ADJUSTING A FOUR-POSITION SWITCH IN
ACCORDANCE WITH THESE INSTRUCTIONS. INCORRECT SETTINGS WILL RESULT IN IMPROPER
PERFORMANCE AND MAY DAMAGE THE PRODUCT, WHICH COULD RESULT IN PROPERTY DAMAGE AND
SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
NOTE: THE MAXIMUM WIRE IMPEDENCE BETWEEN STROBES SHALL NOT EXCEED 35 OHMS. THE
MAXIMUM NUMBER OF STROBES ON A SINGLE NOTIFICATION APPLIANCE CIRCUIT SHALL NOT EXCEED 47.
WARNING: THIS APPLIANCE WAS TESTED TO THE OPERATING VOLTAGE LIMITS OF 16-33 VOLTS USING
FILTERED (DC) OR UNFILTERED FULL-WAVE-RECTIFIED (FWR) POWER FOR THE STROBE. THE AMPLIFIER
WAS TESTED TO THE OPERATING VOLTAGE LIMITS OF 16-33 VOLTS REGULATED POWER. DO NOT APPLY
80% AND 110% OF THESE VOLTAGE VALUES FOR SYSTEM OPERATION.
Copyright 2004 Wheelock, Inc. All rights reserved.
P84503 C
Sheet 1 of 8
WARNING: CHECK THE MINIMUM AND MAXIMUM OUTPUT OF THE POWER SUPPLY AND STANDBY
BATTERY AND SUBTRACT THE VOLTAGE DROP FROM THE CIRCUIT WIRING RESISTANCE TO DETERMINE
THE APPLIED VOLTAGE TO THE STROBES.
SPECIFICATIONS (AMPLIFIER):
Table 1A: Sound Output Level
Sound
Level
10 ft per UL 1480 for 0.5-V and 25-V Settings
Rated Reverberant dBA at
6 84
5 81
4 77
3 74
2 71
1 68
NOTE: See Table 5 Sound Output Level Selection for use of settings “A” and “B”.
Power Input Voltage: 16.0 to 33.0 VDC, regulated
Current Consumption: 120 mA RMS maximum
Appliance Input Level: 0.5 V RMS or 25 V RMS (Switch selectable)
Appliance Input Impedance: 0.5-V Setting:
Greater than 400 Ohms, or equivalent to less than
1/1000 W (0.001 W or 1 mW) load
25-V Setting:
Greater than 20 kOhms, or equivalent to less than
1/32 W (0.03125 W or 31.25 mW) load
Sound pressure level measurements were made at 16 VDC with audio inputs of 0.5 V RMS in the 0.5-V setting and with 25 V RMS
in the 25-V setting. Current measurements were made at 33 VDC with audio inputs of 0.5 V RMS in the 0.5-V setting and with
25 V RMS in the 25-V setting.
Reverberant dBA is a minimum UL rating based on sound measurements in a reverberant test room.
Table 1B: Strobe
Regulated Voltage
VDC/VRMS
24 16.0-33.0 15/30/75/95 A,B
Voltage Range
VDC/VRMS
Candela Mounting
NOTES:
1. The strobe will produce 1 flash per second over the "Regulated Voltage" range.
Options
P84503 C
Sheet 2 of 8
WARNING: CANDELA SETTING WILL DETERMINE THE CURRENT DRAW OF THE PRODUCT.
Table 2: UL Current Ratings (AMPS)
Maximum RMS Current
UL Voltage 15cd 30cd 75cd 95cd
DC 16-33.VDC 0.065 0.105 0.189 0.249
FWR 16-33.VRMS 0.110 0.170 0.280 0.375
WARNING: MAKE SURE THAT THE TOTAL RMS CURRENT REQUIRED BY ALL APPLIANCES THAT ARE
CONNECTED TO THE SYSTEM’S PRIMARY AND SECONDARY POWER SOURCES, NAC CIRCUITS, SM, DSM
SYNC MODULES OR WHEELOCKS POWER SUPPLIES DO NOT EXCEED THE POWER SOURCES’ RATED
CAPACITY OR THE CURRENT RATINGS OF ANY FUSES ON THE CIRCUITS TO WHICH THESE APPLIANCES
ARE WIRED. OVERLOADING POWER SOURCES OR EXCEEDING FUSE RATINGS COULD RESULT IN LOSS OF
POWER AND FAILURE TO ALERT OCCUPANTS DURING AN EMERGENCY, WHICH COULD RESULT IN
PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
When calculating the total currents: Use Table 2 to determine the highest value of “RMS Current” for an individual strobe (across the
expected operating voltage range of the strobe), then multiply these values by the total number of strobes; be sure to add the currents
for any other appliances, including audible signaling appliances, powered by the same source and include any required safety factors.
If the peak current exceeds the power supplies’ peak capacity, the output voltage provided by the power supplies may drop below the
listed voltage range of the appliances connected to the supply and the voltage may not recover in some types of power supplies. For
example, an auxiliary power supply that lacks filtering at its output stage (either via lack of capacitance and/or lack of battery backup
across the output) may exhibit this characteristic.
CAUTION: The Speaker Strobe is not designed to be used on coded systems in which the applied voltage is cycled on and off.
LIGHT DISTRIBUTION:
Table 3A: Horizontal Plane
Horizontal 15cd 30cd 75cd 95cd
Angle (in deg.) UL Min. Typ. 15cd UL Min. Typ. 30cd UL Min. Typ. 75cd UL Min. Typ. 95cd
0 15.0 20.5 30.0 43.3 75.0 102.6 95.0 146.0
5 13.5 20.5 27.0 43.3 67.5 102.6 85.5 146.0
10 13.5 20.1 27.0 43.0 67.5 102.0 85.5 145.0
15 13.5 20.2 27.0 42.7 67.5 102.0 85.5 145.0
20 13.5 18.8 27.0 40.0 67.5 97.1 85.5 134.1
25 13.5 16.9 27.0 35.0 67.5 85.5 85.5 121.3
30 11.3 15.3 22.5 32.7 56.3 80.0 71.3 111.6
35 11.3 14.8 22.5 31.1 56.3 74.0 71.3 106.3
40 11.3 14.1 22.5 29.0 56.3 70.6 71.3 100.7
45 11.3 12.8 22.5 25.9 56.3 62.3 71.3 90.7
50 8.3 11.3 16.5 23.3 41.3 57.1 52.3 81.2
55 6.8 11.9 13.5 23.8 33.8 57.7 42.8 84.5
60 6.0 11.3 12.0 22.3 30.0 52.2 38.0 78.1
65 5.3 10.1 10.5 20.9 26.3 48.9 33.3 69.1
70 5.3 9.7 10.5 19.8 26.3 44.7 33.3 64.7
75 4.5 12.3 9.0 25.0 22.5 57.8 28.5 81.7
80 4.5 10.6 9.0 21.9 22.5 51.3 28.5 69.4
85 3.8 5.4 7.5 12.1 18.8 28.7 23.8 37.2
90 3.8 7.6 7.5 16.6 18.8 39.8 23.8 49.7
P84503 C