Installation instructions for PU-Overvoltage in Mains Control.
This equipment may only be installed by fully qualified personnel. Please note:
the local installation regulations specific to the country of use must be observed.
1. Application
The PU-C overvoltage serves for the protection of low voltage consumer’s installations and electronic
devices against surges resulting from atmospheric discharges (lightning) or switching operations. The
PU-C meets the requirements of IEC 61643-1 01/02 Class II, VDE 0675, part 6, class C 11/89, draft and
DIN VDE 0675. Part 6, A2, 10/96 and ÖVE SN 60 part 4 and part 1 and the Ö Norm 8001. Highly
efficient metal-oxide varistors are used for voltage limiting components. For the PU 3+1C we use a spark
gap between L-PE or PE-N.
2. Notes on installation
2.1 Site of installation
The PU-C
The PU-C must be installed in the meter cubicle or distributing cabinet in such a way that the terminal
room is protected against unauthorised access. The overvoltage protection must be installed by trained
service personnel. The regulations covering the construction of a installation with overvoltage protective
equipment is described in VDE V 0100 part 534; 4/99: Selection and construction of operating
equipment. This norm (in preparation) is in conjunction with the following norms.
1 IEC 60364-4-43 “Protection from overvoltage resulting from atmospheric conditions and resulting
from switching activity.“
2 IEC 61024-1 “Protection of buildings against lightning strikes“.
3 IEC 61312-1 “Protection against electromagnetic lightning impulse“.
2.2 Electrical connection
The PU-C overvoltage protection must be connected with short lines between the (outer) supply
conductor (L1, L2, L3) and the neutral conductor (N) and the earth (PE) of the consumer’s installation.
The parallel routing of non-protected lines and protected lines must be avoided. For connection
examples, see figures 1 and 2.
2.2.1 Connection to (outer) supply conductor and neutral conductor.
As a rule, the same conductor cross-section is selected for the connecting lines to the PU arrester as for
the (outer) supply conductor (L1, L2, L3) and the neutral conductor (N). In the event of a reduction of the
cross-section, a protective device (e.g. service fuse) must be provided for short-circuit protection of the
connecting lines. The arrester terminals must not be used as tee-off terminals. The PU-C back-up fuse
can be selected up to a maximum of 125 A. Series connected residual-current devices (RCD) must be
surge proof.
Notes:
Use a 3-pole PU-C in a TN-C-S network, (see picture 1/ if the PEN line is used separately as PE and N,
then select a 4-pole PU 4 C or the PU 3+1 C).
According to DIN VDE 0100-534/A1 10/96, it is possible in a TT network to install a 4-pole PU-C
protector, together with an arrester disconnector. The module PU 3+1C (old name PU 4 C TT ) catalogue
number 841637, offers the best installation prerequisites if a potential transfer is to be avoided without
the use of an arrester disconnector.
The PU 3 C for 385 V is to be installed in IT networks with 230 V line-to-line voltage.
2.2.2 Connection to earth
The arrester’s earth conductor must be connected by the shortest possible route (≤ 0,5m) to the earth
terminal of the consumer’s installation. Longer connection lines reduce the efficiency of the overvoltage
protector. Parallel routing with other electrical lines must be avoided. The earthed equipotential bonding
strip is available for connection with the equipotential bonding of electrical consumer’s installations (see
figures 1 and 2).
° It must always be ensured that the arrester earth is connected with the consumers installation.
° For TN systems, the PEN conductor and the earth conductor of the arrester must be interconnected.
° The PEN conductor of the electricity supply company must not be used as an earth electrode.
° Where the PE rail or PEN rail of a distribution board is used as an earth terminal, these must be
connected via a separated earth conductor to the earth electrode of the consumer’s installation.
The cross-section of the arrester earth conductor is determined, as with the main equipotential bonding
conductors, according to table 1. The conductor must have 0,5 times the cross-section of the main
protective conductor, the upper limit is fixed at 25 mm2 Cu. A lower limit of 10 mm2 Cu is required.
Cross section mm
Main protective conductor
- from the power source or
≤ 16 25 ≤ 35
2
- house service box or main distribution board
outgoing protective conductor.
Supply conductor ≤ 35 50 ≥ 70
Earth conductor of arrester 10 16 25
Table 1
3. Functional check
PU overvoltage arresters must be subjected to a visual inspection, especially during thunderstorms. If
the colour of the inspection window turns red, the arrester must be replaced by trained service personal.
3.1 Maintenance
If the charge eliminator shows a red window as in 3., it must be replaced with a new one by trained
service personal. The individual charge eliminators are pluggable and encoded according to their
voltage. The varistor arrester must be removed when measuring the insulation resistance according to
DIN VDE 0100 part 610. To remove, pull on the upper parts of the varistor.
The charge eliminator compatible with the rated voltage of the plant must be re-installed.
Technical Data: PU xC PU xC PU xC PU xC PU xC PU 3+1 C PU 3+1 C
Max. Voltage V~ U
280 385 75 130 550 280 385
c
Rated diversion current i
20 kA 20 kA 15 kA 20 kA 20 kA 20 kA 20 kA
sn
of top part
Max. test current per Unit
1-way block i
2-way block i
3-way block i
4-way block i
Operating temperature range. - 40 °C to + 80
Conductor size 16- 25 mm
10 - 25 mm
40 kA 40 kA 15 kA 40 kA 40 kA 40 kA 40 kA
smax
70 kA 70 kA 40 kA 70 kA 70 kA
smax
100 kA 100 kA 100 kA 100 kA 100 kA
smax
100 kA 100 kA 100 kA 100 kA 100 kA 100 kA 100 kA
smax
°
C
2
(stranded wire) 6- 10 mm2 (solid wire)
2
(flexible )
Assembly Snap-on mounting on 35 mm top-hat rails
according to DIN 43 880 A1. draft 6.81
Colour. Light grey, RAL 7035 orange orange
Material. Polyamide 6.6
Protection IEC 529 : IP 20
Dimensions
1-way block complete width 18 mm
2-way block complete width 36 mm
3-way block complete width 54 mm
4-way block complete. width 72 mm
Depth. 55.0 mm
• For DC-Applications please contact the manufacturer.
4. Connection of remote signalling unit