Weidmuller PT 100-4 User Manual

WAVESERIES
PT 100/4 Signal Conditioners
for Current Output
Type Cat. No.
Screw-type connection WTS4 PT100/4 Select C 843227
Tension clamp connection WTZ4 PT100/4 Select C 843228
and retain for future information.
19
1 General instructions The WAVESERIES signal conditioner PT 100 should only be in­stalled by qualified staff. The signal conditioner PT 100 should only be powered up following professional installation.
2 Application The WAVESERIES signal conditioner PT 100 can be used to connect PT 100 sensors as well as converting temperature data into standard linear current signals. The temperature range can be set by DIP switches on the printed circuit board. The signal conditioner PT 100/4 can be connected to 2-, 3- and 4-wire temperature sensors.
3 Mounting and dismounting Warning!! Mounting and dismounting may only be carried out
3.1 Mounting onto TS 35 DIN rails
20
when the power supply has be disconnected. Failure to observe will lead to considerable damage!
(Figure 1)
3.2 Pluggable electronic components for range alteration (depending on model) (Figure 2)
1. Remove connector , (depending on model either screw -type or tension clamp).
2. Press locking clips on both sides of the enclosure.
3. Pull out the circuit board.
Warning!! The circuit board can only be inserted in one position.
The connectors have been coded by the manufactur ­er , ensuring that they cannot be reversed.
3.3 Setting the potentiometer (depending on model) (Figure 3)
The module has been exactly calibrated by the manufacturer . Should nevertheless a follow-up adjustment be necessary, open the hinged cover upwards. The potentiometers are on the front panel.
21
3.4 Pluggable cross-connections for voltage supply (Figure 4)
A maximum feed through of 2 A is possible. If a signal conditioner is accidently rotated through 180°, the cross-connection cannot be inserted.
3.5 Labelling possibilities Figure 5
WS 10 connector markers can be used to label module. 4 Calibration Warning!! The power supply must be disconnected, before
4.1 Equipment
– Power supply 24 Vdc, 50 mA – Simulator for PT 100 or precision resistance decade – Current meter/voltmeter that can be so calibrated, as to allow
22
changing the signal conditioner settings using the DIP switches. Failure to observe will lead to considerable damage!
an accuracy of > 0.1 % fr om the upper range value
4.2 Basic calibration with a signal output from 0 ... 20 mA
1. Select the temperature range on the printed circuit board using the DIP switch, see table on the module or pages 41 and 42. The DIP switches 1, 2 and 3 set the minimum input tempera­ture ϑ
.
min
The span (difference between minimum and maximum input temperature) is set using the DIP switches 4, 5 and 6.
2. Professionally install module.
3. Add 1 % of the temperatur e span to the selected “ minimum” temperature and set this value on a PT 100 simulator (when using a pr ecision resistance decade, where necessary ob­serve DIN IEC 751 conversion table fr om °C to !) and cali­brate the signal conditioner output signal to 0.200 mA using the null potentiometer. (The potentiometers are located be­hind the hinged cover).
4. Set the “maximum” selected temperature on a PT 100 simu­lator (or precision resistance decade) and calibrate the signal output to 20.000 mA using the S pan potentiometer.
5. Repeat steps 3 and 4 (approx. 2-3 times), until the required accuracy is achieved.
23
Example Input range: -50 ... +150 °C Minimum input temperature: = -50 °C Choose next lower or equal value according to table for ϑ
min
.
Table value -60 °C
Set DIP switch 1 to OFF; DIP switches 2 and 3 to
ON. The span is 200 K (150 °C - (-50 °C)). The table value lies between 165 ... 245 °C
Set DIP switch 4 to OFF; DIP switches 5 and 6 to
ON. The input range must be raised by 10 K (-60 °C + 50 °C). The 10 K corresponds to 5 % of the span (see calculation). The input range can be raised by up to 25 % using the "null" potentiometer. Calculation:
Should the 25 % be exceeded using the above calculation, then an adjustment to the temperature input range is not possible.
24
4.3 Linearity calibration
1. Proceed with basic calibration, see above.
2. Add 1 % of the temperature span to the selected " minimum"
temperature and set this value on a PT 100 simulator (when using a precision resistance decade, where necessary ob­serve DIN IEC 751 conversion table from °C to !) and cali­brate the signal conditioner output signal to 0.200 mA using the null potentiometer.
3. Set the mean temperatur e "(ϑ
max
+ ϑ
)/2" on a PT 100 simu-
min
lator. Determine the difference to the desired value: "I = shown value on measuring instrument - 10.000 mA" and calibrate the output signal to (10.000 mA - I) using the span potentiometer.
4. Set the "maximum" selected temperature ϑ
on a PT 100
max
simulator and calibrate the signal output to 20.000 mA using the lin potentiometer.
5. Repeat steps 2 to 4 until the required accuracy is achieved.
25
Example Chosen measurement -50 ... +150 °C 200 K span range: 1 % from 200 K span = 2 K Set minimum temperature -50 °C + 2 K = -48 °C on the PT 100 simulator and calibrate the signal conditioner out­put signal to 0.200 mA using the null potentiometer. Mean temperature = (ϑ
max
+ ϑ
min
)/2 = (150 °C + (-50 °C))/2 = 50 °C
Set the 50 °C value on a PT 100 simulator Then determine ∆I: ∆I = measured value from measuring
instrument - 10.000 mA
∆I = 9.940 mA - 10.000 mA
= -0.060 mA
Then calibrate the output signal to (10.000 mA - I) using the span potentiometer i.e. her e an example.
"10.000 mA - (-0.060 mA) = 10.060 mA"
Then set the maximum temperature on the PT 100 simulator (150 °C) and calibrate the output signal to 20.000 mA using the lin potentiometer.
26
4.4 Basic calibration with an output signal from 4 ... 20 mA
1. Set the required temperature range on the printed circuit board using the DIP switch, see the table on the module or sides 41 and 42. The DIP switches 1, 2 and 3 set the minimum input tempera­ture ϑ
.
min
The span (dif ference between minimum and maximum input temperature) is set using the DIP switches 4, 5 and 6.
2. Professionally install module.
3. Set the "minimum" selected temperature on a PT 100 simula­tor (when using a pr ecision resistance decade, wher e neces­sary observe DIN IEC 751 conversion table from °C to Ω !) and calibrate the signal conditioner output signal to 4.000 mA using the null potentiometer. (The potentiometers ar e located behind the hinged cover).
4. Set the "maximum" selected temperature on a PT 100 simu­lator (or precision resistance decade) and calibrate the signal output to 20.000 mA using the span potentiometer.
5. Repeat steps 3 and 4 (appr ox. 2-3 times), until the required accuracy is achieved.
27
Example Input range: -50 ... +150 °C Minimum input temperature: = -50 °C Choose next lower or equal value according to table for ϑ
min
.
Table value -60 °C
Set DIP switch 1 to OFF; DIP switches 2 and 3 to
ON. The span is 200 K (150 °C - (-50 °C)). The table value lies between 165 ... 245 °C
Set DIP switch 4 to OFF; DIP switches 5 and 6 to
ON. The input range must be raised by 10 K (-60 °C + 50 °C). The 10 K correspond to 5 % of the span (see calculation). The input range can be raised by up to 25 % using the "null" po­tentiometer. Calculation:
Should the 25 % be exceeded using the above calculation, then an adjustment to the temperature input range is not possible.
28
4.5 Linearity calibration
1. Carry out a basic calibration, see above.
2. Set the selected "minimum" temperature on a PT 100 simula-
tor (when using a pr ecision resistance decade, wher e neces­sary observe DIN IEC 751 conversion table from °C to Ω !) and calibrate the signal conditioner output signal to 4.000 mA using the null potentiometer.
3. Set the mean temperature "(ϑ
max
+ ϑ
)/2" on a PT 100 simu-
min
lator. Determine the difference to the desired value: "I = shown value on measuring instrument - 12.000 mA" and calibrate the output signal to (12.000 mA - I) using a span potentiometer.
4. Set the "maximum" selected temperature ϑ
on the PT 100
min
simulator and calibrate the signal output to 20.000 mA using the lin potentiometer.
5. Repeat steps 2 to 4 until the required accuracy is achieved.
29
Example Chosen measuring range: -50 ... +150 °C Set minimum temperature (-50 °C) on the PT 100 simulator and calibrate the signal conditioner out­put signal to 4.000 mA using the null potentiometer. Mean temperature = (ϑ
max
+ ϑ
min
)/2 = (150 °C + (-50 °C))/2 = 50 °C
Set the 50 °C value on the PT 100 simulator Then determine ∆I: ∆I = measured value from measuring
instrument - 12.000 mA
∆I = 11.940 mA - 12.000 mA
= -0.060 mA
Then calibrate the output signal to (12.000 mA - I) using the span potentiometer i.e. her e an example.
"12.000 mA - (-0.060 mA) = 12.060 mA"
Then set the maximum temperature on the PT 100 simulator and calibrate the output signal to 20.000 mA using the lin potentiome­ter.
30
4.6 Setting the DIP switches
Warning!! The signal conditioner PT 100 must be protected
against a direct electrostatic discharge when setting the DIP switches.
DIP switches
8910 2-wire ON ON ON 3-wire ON OFF ON 4-wire OFF ON OFF
DIP switches
ϑ
min
123 0 °C ON ON ON
-10 °C ON ON OFF
-20 °C ON OFF ON
-40 °C ON OFF OFF
-60 °C OFF ON ON
-80 °C OFF ON OFF
-100 °C OFF OFF ON
-200 °C OFF OFF OFF
31
Span 4 5 6 40 ... 50 °C ON ON ON 50 ... 75 °C ON ON OFF 75 ... 110 °C ON OFF ON 110 ... 165 °C ON OFF OFF 165 ... 245 °C OFF ON ON 245 ... 360 °C OFF ON OFF 360 ... 540 °C OFF OFF ON 540 ... 800 °C OFF OFF OFF
DIP switches
Output 7 0 ... 20 mA OFF 4 ... 20 mA ON
5 Electrical connection
(4-wire technology)
6 Dimensions
32
DIP switches
7 Notes on CE labelling of WAVESERIES modules WAVESERIES modules, that carry CE-labelling, fulfil the r equirements of the EU-Guidelines 89/336/EU “electromagnetic compatibility” and the therein listed harmonised European Norms (EN). The declarations of conformity are, in accordance with the above­mentioned EU-Guideline, Article 10, held at the following address for the relevant authorities:
8 T echnical data Input Sensor types PT 100/4 Select C accor ding to DIN
Input current 1.35 mA ... 1.45 mA ... 1.60 mA Connection type selection using DIP switches Conductor resistance ≤ 50 Ω (3- and 4-wir e connection) Influence of conductor resistance max. ± 0.005 °C/ Ω for 3- and 4-wir e
Input range -200 ... +800 °C adjustable using Offset input range up to +25 % possible
Weidmüller Interface GmbH & Co. Postfach 3030 32720 Detmold
IEC 751
connection DIP switches
33
Output Current output adjustable using DIP switches Load resistance ≤ 500 Ω Accuracy Measurement range accuracy
100 K; < 600 K; ϑ
-100 °C ± 0.1 from measurement range
min
100 K ± 0.1 K 600 K ± 0.2 % fr om measurement range
Temperature coefficient Measurement range
200 K 200 ppm/K (typ. 80 ppm/K) 100 K; < 200 K 225 ppm/K (typ. 90 ppm/K) 40 K; < 100 K 450 ppm/K (typ. 180 ppm/K)
Connection data Connection BLZ/SL Insulating stripping length 8 ± 0.5 mm Solid core 0.5 ... 2.5 mm Flexible core 0.5 ... 2.5 mm With ferrules 0.5 ... 1.5 mm
2 2 2
34
EMC specification according to EN 55011, class B,
group 1 according to EN 50081-1 according to EN 50082-2
General Current consumption 30 mA ... 38 mA ... 48 mA
I
= 20 mA
out
Voltage supply 19.2 Vdc ... 24 Vdc ... 28.8 Vdc Cross-connection, upper 24 V, max. 2 A Cross-connection, lower 0 V, max. 2 A Operating temperature 0 ... +55 °C Storage temperature -20 ... +85 °C
Approvals CE, CSA, UL
35
9 Accessories Cross-connection ZQV 2,5N/2 black 171808 Cross-connection ZQV 2,5N/2 red 171790 Cross-connection ZQV 2,5N/2 blue 171799 Cross-connection ZQV 2,5N/2 yellow 169380
Terminal connector, 2-pole for screw-type connection BLZ 5,08/2
- orange 152646
- black 152641 Terminal connector, 2-pole for tension clamp connection BLZ 5,08/2
- orange 170746
- black 170770 Connector markers
WS 10/5 Multicard for plotter labelling 163501 WS 10/5 blank 106086
In the interest of protecting the envir onment, return any spare operating instructions to your local stockist for re-use. Printed on chlorine-free bleached paper.
36
Loading...