Weidmuller PT 100-3 User Manual

WAVESERIES PT 100/2 and PT 100/3 Signal Conditioners for Current Output
Type Cat. No.
Screw-type connection WTS4 PT100/2 Select C 8432210000 WTS4 PT100/3 Select C 8432150000
Tension clamp connection WTZ4 PT100/2 Select C 8432220000 WTZ4 PT100/3 Select C 8432160000
Read these instructions before using the product and retain for future information.
15
1 General instructions
The WAVESERIES signal conditioner PT 100 should only be installed by qualified staff. The signal conditioner PT 100 should only be powered up following professional installation.
2 Application
The WAVESERIES signal conditioner PT 100 can be used to connect PT 100 sensors as well as converting temperature data into standard linear current signals. The temperature range can be set by DIP switches on the printed circuit board.
3 Mounting and dismounting
Warning!! Mounting and dismounting may only be carried out
16
when the power supply has be disconnected. Failure to observe will lead to considerable damage!
3.1 Mounting onto TS 35 DIN rails
(s. Fig. 1)
3.2 Pluggable electronic components for range alteration (depending on model)
(s. Fig. 2)
1. Remove connector, (depending on model either screw-type or tension clamp).
2. Press locking clips on both sides of the enclosure.
3. Pull out the circuit board.
Warning!! The circuit board can only be inserted in one position.
The connectors have been coded by the manu­facturer, ensuring that they cannot be reversed.
17
3.3 Setting the potentiometer (depending on model)
(s. Fig. 3)
The module has been exactly calibrated by the manufacturer. Should nevertheless a follow-up adjustment be necessary, open the hinged cover upwards. The potentiometers are on the front panel.
3.4 Pluggable cross-connections for voltage supply
(s. Fig. 4)
A maximum feed through of 2 A is possible. If a signal conditioner is accidently rotated through 180°, the cross-connection cannot be inserted.
3.5 Labelling possibilities
(s. Fig. 5)
WS 10 connector markers can be used to label module.
18
4 Calibration
Warning!! The power supply must be disconnected, before
changing the signal conditioner settings using the DIP switches. Failure to observe will lead to considerable damage!
4.1 Equipment
– Power supply 24 Vdc, 50 mA – Simulator for PT 100 or precision resistance decade – Current meter/voltmeter that can be so calibrated, as to allow
an accuracy of > 0.1 % from the upper range value
4.2 Calibration with a signal output from 0 ... 20 mA
1. Select the temperature range on the printed circuit board using the DIP switch, see table on the module or pages 22 and 23. The DIP switches 1, 2 and 3 set the minimum input tempera­ture ϑ
.
min
The span (difference between minimum and maximum input temperature) is set using the DIP switches 4, 5 and 6.
19