Veris H608 Installation Instructions

0 (0)

Installation Guide

Current Monitoring

TM

RoHS

Compliant

DANGER

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

Followsafeelectricalworkpractices.SeeNFPA70EintheUSA,orapplicablelocalcodes.

Thisequipmentmustonlybeinstalledandservicedbyqualifiedelectricalpersonnel.

Read,understandandfollowtheinstructionsbeforeinstallingthisproduct.

Turno allpowersupplyingequipmentbeforeworkingonorinsidetheequipment.

Useaproperlyratedvoltagesensingdevicetoconfirmpoweriso . DONOTDEPENDONTHISPRODUCTFORVOLTAGEINDICATION

Onlyinstallthisproductoninsulatedconductors.

Failure to follow these instructions will result in death or serious injury.

A quali ed person is one who has skills and knowledge related to the construction and operation of this electrical equipment and the installation, and has received safety training to recognize and avoid the hazards involved. NEC2009 Article 100

No responsibility is assumed by Veris Industries for any consequences arising out of the use of this material.

NOTICE

This product is not intended for life or safety applications.

Do not install this product in hazardous or classified locations.

Theinstallerisresponsibleforconformancetoallapplicablecodes.

Mount this product inside a suitable fire and electrical enclosure.

TM

H608

Split-Core Current Switch, Adjustable Trip Point

Product Overview

The H608 is a current-sensitive switching device that monitors current (amperage) in the conductor passing through it. A change in amperage in the monitored conductor that crosses the switch (setpoint) threshold plus the hysteresis value causes the resistance of the FET status output to change state, similar to the action of a mechanical switch. In this model, the setpoint is adjustable through the action of a twenty (20) turn potentiometer (see the Calibration section). The status output is suitable for connection to building controllers or other appropriate data acquisition equipment operating at up to 30 volts. The H608 requires no external power supply to generate its output.

Specifications

Sensor Power

Induced from the monitored conductor

 

 

Amperage Range

0.5 to 175 A continuous

 

 

Status Output Ratings

N.O. 1.0 A@30 VAC/DC, not polarity sensitive

Insulation Class

600 VAC RMS (UL); 300 VAC (CE)

 

 

Setpoint

Adjustable, 0.5 A or less

 

 

Frequency Range

50/60 Hz

 

 

Temperature Range

-15° to 60°C (5° to 140°F)

 

 

Humidity Range

10-90% RH non-condensing

 

 

Hysteresis

10% typical

 

 

Off State Resistance

Open switch represents >1 MΩ

 

 

On State Resistance

Closed switch represents < 200 mΩ

 

 

Terminal Block Max. Wire Size

24 to 14 AWG (0.2 to 2.1 mm2)

Terminal Block Torque

3.5 to 4.4 in-lbs (0.4 to 0.5 N-m)

 

 

COMPLIANCE INFORMATION

Agency Approvals UL508 open device listing, CE: EN61010-1

Installation Category Cat. III, pollution degree 2

For applications requiring double or reinforced insulation, please contact the factory.

The product design provides basic insulation only.

Do not use the LED indicators as evidence of applied voltage.

Z201757-0H

Page 1 of 4

©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com

07131

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries. Other companies’ trademarks are hereby acknowledged to belong to their respective owners.

Veris H608 Installation Instructions

Installation Guide

Current Monitoring

H608

TM

Dimensions

 

Removable Mounting Bracket

 

 

0.6"

 

 

(16 mm)

1.2"

 

 

2.1"

0.7"

(31 mm)

(18 mm)

 

(54 mm)

 

 

2.5" *

 

0.5"

 

(64 mm)

 

(13 mm)

 

 

2.1" (54 mm)

1.0" *

(26 mm)

0.4” x 0.2”

(10 mm x 5 mm) Slot (2x) 2.9"

(74 mm)

3.5" (89 mm)

Installation

 

Disconnect and lock out power to the enclosure containing the conductor to be

 

monitored.

Insulated Conductor ONLY

1. Locate a mounting surface for the removable mounting bracket

 

 

that will allow the monitored conductor to pass through the center

CONTACTOR

 

window when it is installed and that will keep the product at least

 

DDC CONTROLLER

 

½” (13 mm) from any uninsulated conductors. Determine cable

 

 

 

routing for the controller connection, allowing the wiring to reach

 

 

the mounting location.

DI

2.

Drill holes to mount the bracket to the chosen surface using the

 

 

included screws.

 

3.

Wire the output connections from the sensor to the controller (solid-

 

 

state contact).

 

4.

Snap the sensor over the conductor and clip the assembly to the

Fan

 

mounting bracket.

 

5.

Secure the enclosure and reconnect power.

 

6.

Calibrate the sensor with the load running normally.

Motor

Z201757-0H