Follow the Installation Instructions before proceeding.
Set the thermostat mode to “OFF” prior to changing
settings in setup or restoring Factory Defaults.
This device complies with Part 15 of the FCC Rules. Operation is
subject to the following two conditions: (1) this device may not cause
harmful interference, and (2) this device must accept any interference
received, including interference that may cause undesired operation.
Thermostat T5800
Tested to Comply
c
with FCC Standards
C
F
4Z95
FOR HOME OR OFFICE USE
Page i
Page 3
Glossary of Terms
Auto-Changeover: A mode in which the thermostat will turn on the
heating or cooling based on room temperature demand.
Cool Setpoint: The warmest temperature that the space should rise
to before cooling is turned on (without regard to deadband).
Deadband: The number of degrees allowed past setpoint, before
energizing heating or cooling.
Differential: The forced temperature difference between the heat set-
point and the cool setpoint.
Heat Setpoint: The coolest temperature that the space should drop
to before heating is turned on (without regard to deadband).
Icon: The word or symbol that appears on the thermostat display.
Mode: The current operating condition of the thermostat (i.e. Off,
Heat, Cool, Auto, Program On).
Non-Programmable Thermostat: A thermostat that does not have
the capability of running Time Period Programming.
Programmable Thermostat: A thermostat that has the capability of
running Time Period Programming.
Temperature Swing: Same as Deadband.
Time Period Programming: A program that allows the thermostat to
automatically adjust the heat setpoint and/or the cool setpoint based
on the time of the day. Same as Schedule.
Page ii
Page 4
Table of Contents
Get to Know Your Thermostat
Home Screen
1
1
Menu Screens
Care and use of your thermostat
2
Quick Start
Selecting your desired temperature and mode
3
Using the Fan button
3
Setting the time
5
Setting the date
6
6
8
Daylight Savings setup
The Main Menu Buttons
Schedule
7
Time Period Schedule On/Off
8
View My Schedule
Edit My Schedule
8
Smart Fan
10
Smart Fan On/Off
11
Smart Fan Minimum Runtime
11
Start/Stop Times
11
Days to allow Smart Fan operation.
11
Screensaver
12
Screensaver On/Off
13
Screensaver Setup
13
Screensaver Preview
13
Alerts
14
View Current Alerts
15
Reset Alerts
15
Set/Edit Reminders
15
Service Information (Who To Call For Service)
15
Page iii
Page 5
Table of Contents
Display
16
Active Brightness
17
Idle Brightness
17
Night Dimmer
17
Maintenance
18
Preferences
19
User Interface Themes
20
Custom Wallpaper
20
Heat/Cool Indicator
20
Backdrop On/Off
20
Sound Options
20
Vacation
21
Vacation Mode On/Off
22
Schedule
22
Modes & Setpoints
23
24
Security
Auto Screenlock
25
Setpoint Limits
25
Mode Restrictions
25
Information
26
Who To Call For Service
27
View Runtime Graphs
27
Settings
28
Thermostat Name
31
Available Modes
31
SD Card (Import and Export)
31
General Setup
31
31
32
32
32
33
33
33
33
33
Units (F or C)
Language
Smart Recovery ON/OFF
Simple Thermostat ON/OFF
Installation Settings
Heat & Cool Stages
Heat & Cool Stages
Compressor Stages
Aux Heat Stages
Aux Heat Lockout Enabled/Disabled
Aux Heat Lockout Temp
Dual Fuel Settings
Dual Fuel On/Off
Changeover With Outdoor Temp On/Off
Adjust Balance Point
Fan Off Delay
Calibrate Sensors
Test Outputs
Dealer Information
Reset To Factory Default Settings
Upgrade Firmware
Emergency Heat
ColorTouch Assistant
Installing the ColorTouch Assistant Software
Uploading Photos
Installation Instructions
Remove & Replace the Old Thermostat
Wire Connections
The Color Touch Thermostat Backplate
Explanation Of the Thermostat Dip Switches
Sample Wiring Diagrams
Troubleshooting
Index
Warranty
Page v
Page 7
Get To Know Your Thermostat
Home Screen
Backlit Color Touchscreen Display
Date
&
Time
Fan
Buttons
Main Menu Screen
Menu
Back
Button
Buttons
Scrolling
Buttons
Page 1
Sub Menu Screen
Sub Menu
Buttons
Outdoor Temperature
With high & low temps for the day
(If optional sensor is installed)
Warmer
Button
SD Card
Slot
Cooler
Button
Menu
Button
Mode
Buttons
Scrolling
Indicates Options
Available
Buttons
Home
Button
Page 8
Get To Know Your Thermostat
Care and Use of Your Thermostat
Pencils, pens and other sharp objects should never be used on your ColorTouch
thermostat; these may damage your touchscreen. Only use your finger tip to press
the touchscreen buttons.
Use a soft, damp cloth to clean the screen.
DO NOT USE ABRASIVE CLEANERS OR CLEANERS THAT CONTAIN
SOLVENTS. DO NOT SPRAY ANYTHING DIRECTLY ONTO THE
THERMOSTAT.
TM
Page 2
Page 9
Quick Start
Temperature, Modes & Fan
Selecting Your Desired Temperature and Mode
COOLER
WARMER
MODE
or
or the MODE Icon
Press
The Heat or Cool Setpoint is the
temperature the room has to
reach before heating or cooling
will turn on.
(Without regard to deadband)
Press
HEAT will allow only heat operation.
COOL will allow only cool operation.
AUTO will allow both Heat and Cool operation.
OFF - heating and cooling systems are turned off.
AUTO-CHANGEOVER MODE - Pressing the WARMER or COOLER buttons in Auto
mode will adjust both the heat and cool setpoints simultaneously. To adjust heat and
cool setpoints individually, choose HEAT mode to adjust the heat setpoint and COOL
mode to adjust the cool setpoint, then return to AUTO mode.
HEAT OR COOL MODE - Pressing the WARMER or COOLER buttons in Heat or
Cool mode will adjust only the heat or cool setpoints.
Using the Fan Button
FAN
Press
FAN ON fan runs constantly even in OFF Mode.
FAN AUTO fan only runs with a heating or cooling demand.
or the FAN Icon
to adjust temperature
Fan
Page 3
Cool Setpoint
Heat Setpoint
Warmer
Button
Cooler
Button
Page 10
Quick Start
Set Time & Date
Set Current Time
Use AM/PM - ON
Set Current Date
Daylight Savings Setup
Daylight Savings Time - OFF
Start Schedule
Starts On
Day
Month
Stop Schedule
Ends On
Day
Month
Set Time & Date
(2nd)
(Sun)
(March)
(1st)
(Sun)
(November)
Page 4
Page 11
Quick Start
Setting the Time
MENU
Press
Press
Set Current Time
then
Set Time & Date
to scroll down.
(12:00 AM)
Set Time & Date
Press
Press
Press
Choose
For 12 hour AM/PM clock
For 24 hour clock
Press
hr +
and
hr -
BACK
when finished.
Use AM/PM - ON
Use AM/PM - OFF
BACK
when finished.
min +
min -
Page 5
to set the current time.
Page 12
Quick Start
Set Time & Date
Setting the Date
Set Current Date
Press
Daylight Savings Setup
Turn Daylight Savings
Time on or off.
Adjust when Daylight
Savings Time begins.
Adjust when Daylight
Savings Time ends.
Press
after making a change
to a selection.
Press
or the Home button
when finished.
or
Press the day on the calendar
Su Mo Tu We ThFrSa
27 28 29 30123
45678910
1211
13
18 19 20 21 22 23 24
1234567
BACK
BACK
7/8/2010
to set the current month and year.
17161514
31302928272625
Daylight Savings Time - OFF
Daylight Savings Time - ON
Start Schedule
Starts On
Day
Month
Stop Schedule
Ends On
Day
Month
Press
when finished.
Page 6
Press
(2nd)
(Sun)
(March)
(1st)
(Sun)
(November)
BACK
Page 13
The Main Menu Buttons
The Main Menu Buttons
Schedule
Time Period Schedule - OFF
View My Schedule
Edit My Schedule
Information
Schedule
Page 7
Page 14
The Main Menu Buttons
This thermostat features up to four programmable
time periods per 24 hour day: Morning, Day, Evening,
and Night. The start time for each time period is
Schedule
Press to turn Schedule On or Off
Time Period Schedule - OFF
adjustable. The stop time for each time period is
the start time for the next period.
Schedule
Time Period Schedule - ON
View My Schedule
Press a day of the week to view its settings. This may be repeated for each day.
Edit My Schedule
Press and select day(s) to program
Select individual day(s)
Select groups of day(s)
Then press NEXT
or
Page 8
Continued
Page 15
The Main Menu Buttons
Schedule
Edit My Schedule
Press and select a Time Period (Morning, Day, Evening, or Night) to edit.
(Continued)
Next
Adjust Mode, Start Time, and Heat and Cool Setpoints to desired settings.
The Time Period may also be Enabled or Disabled. Un-check the Enabled
box for Time Periods you don’t want to use. Press DONE when finished.
Mode
TIP:
For a simpler schedule that only uses 2
time periods, un-check Enabled for Day
and Evening Time Periods.
Heat and Cool Setpoints
Enable/Disable
Start Time
When you are finished editing the
four time periods press
Review your program. Press SAVE to
keep your program. Press EDIT to
make further changes.
NEXT
Page 9
Done
Edit
Time Period
Save
Page 16
The Main Menu Buttons
The Main Menu Buttons
Smart Fan
Who To Call For Service
Smart Fan - OFF
View Runtime Graphs
Smart Fan Min Runtime
Who To Call For Service
Start/Stop Times
View Runtime Graphs
Days To Run Fan
Information
Smart Fan
Page 10
Page 17
The Main Menu Buttons
The fan may be programmed to turn on
automatically for a specified period
Smart Fan
Press to turn fan schedule on or off
Smart Fan - OFF
Smart Fan - ON
during the day.
Smart Fan
Smart Fan Min Runtime
Set the minimum number of minutes the fan will run from the top
of each hour. Set runtime to 60 minutes to be on continuously
from Start Time to Stop time. (5 - 60 mins.)
Start/Stop Times
Set when the Smart Fan schedule will start and stop. For example,
you may not want Smart Fan to run during sleeping hours.
Days To Run Fan
Choose which days of the week Smart Fan will run.
(7:00AM - 9:00PM)
(0m)
Page 11
Page 18
The Main Menu Buttons
Screensaver
Who To Call For Service
Screensaver - OFF
View Runtime Graphs
Screensaver Setup
Screensaver Turn On Delay
Screensaver Type
Slideshow
Digital Clock
Analog Clock
Change Image After...
Use Theme Images - On
Show Clock - OFF
Home Screen Info - OFF
View Runtime GraphsScreensaver Preview
Screensaver
Page 12
Page 19
The Main Menu Buttons
The Screensaver allows you to create custom
slideshows.
Screensaver
Screensaver
Screensaver - OFF
Screensaver - ON
Screensaver Setup
Screensaver Turn On Delay
How long after a button press for the Screensaver to appear.
1, 3, 5, or 30 minutes
Screensaver Type
Slideshow
Digital Clock
Analog Clock
Change Image After...
15, 30 seconds - 1, 5, or 10 minutes
Show Clock - OFF
Shows the time and date every 5 photos. Off or On
Home Screen Info - OFF
Shows the mode, setpoints, and temperature after every 10 photos. Off or On.
(5m)
(Slideshow )
Screensaver Preview
Press this button to preview your screensaver operation before
returning to the Home Screen.
After the preview, press anywhere on the screen to return to the sub menu.
Page 13
Page 20
The Main Menu Buttons
Alerts
View Current Alerts
Reset Alerts
Reset Air Filter Alert
Reset UV Lamp Alert
Set/Edit Reminders
Service Call - OFF
Days Until Service Call
Air Filter Reminder - OFF
Set Max Filter Runtime
Set Max Filter Days
UV Lamp Reminder - OFF
Max UV Lamp Runtime
Service Information...
Alerts
(360 days)
(500 hrs)
(180 days)
(360 days)
Page 14
Page 21
The Main Menu Buttons
The alerts let you know when your system
needs service.
Alerts
View Current Alerts
View and reset current
service alerts here.
Reset Alerts
Clear and reset current service alerts.
Set/Edit Reminders
Set service alert runtimes and turn reminders on or off.
Service Call Reminder - OFF
Days Until Service Call
Air Filter Reminder - OFF
Set Max Filter Runtime
Set Max Filter Days
UV Lamp Reminder - OFF
Set Max UV Lamp Runtime
Alerts will appear
on the bottom bar
of the Home Screen.
Press to view and
reset current alerts.
(360 days)
(500 hrs)
(180 days)
(360 days)
Dealer’s
Logo
here
Alerts
Service Information...
View your service company’s contact information.
Page 15
Page 22
The Main Menu Buttons
Display
Active Brightness
Idle Brightness
Night Dimmer
Auto Night Dimmer - OFF
Set Idle Brightness
Set Dimmer Schedule
Maintenance
Screen Cleaning
Touch Calibration
Display
Page 16
Page 23
The Main Menu Buttons
The display brightness options may be
adjusted in this menu.
Display
Display
Active Brightness
You may select how bright the backlight is while the thermostat is active. The
display is active for 3 minutes after last touch, it then goes Idle.
Idle Brightness
You may select how bright the backlight is while the thermostat is idle.
(80%)
(30%)
Night Dimmer
You may dim the brightness of the ColorTouch screen at night.
Auto Night Dimmer - OFF
The screen can be set to dim automatically at night. Dimming the
display can prolong the life of the backlight.
Set Idle Brightness
Set the screen brightness for the Night Dimmer. When Night Dimmer
is On, the display will go idle after 8 seconds after last touch.
Set Dimmer Schedule
Set the schedule for the Night Dimmer.
(20%)
Page 17
Page 24
The Main Menu Buttons
Display
Maintenance
Maintenance allows you to clean and calibrate the ColorTouch Screen.
Screen Cleaning
Screen Cleaning Mode disables the touch feature for 15 seconds
so the screen may be cleaned without altering any settings.
Use a soft cloth without solvents or abrasive cleaners
Touch Calibration
Under normal circumstances, the ColorTouch touchscreen should not
need to be calibrated.
Touch the center of the targets as they appear on the screen.
Touch Screen Calibration
FINISH
Press when done.
When calibration is complete, the thermostat will automatically restart
and return to the Home Screen.
Page 18
Page 25
The Main Menu Buttons
Preferences
User Interface Themes
Custom Wallpaper
Heat/Cool Indicator
Heat/Cool Indicator OFF
Taskbar red/white OFF
Room Temp red/blue OFF
Mode Status red/blue OFF
Backdrop OFF
Sound Options
Beep - OFF
Beep Sound
Show Outdoor Hi/Lo - OFF
Preferences
Page 19
Page 26
The Main Menu Buttons
You may set the type of background that
appears on the thermostat Home Screen.
Preferences
Preferences
User Interface Themes
This thermostat has several high quality background themes to choose from.
NOTE: At 7 PM, the background will change to an evening scene and the
moon will replace the sun. At 7 AM it will return to a daytime scene.
(ocean)
Custom Wallpaper
You may choose your own background image by selecting a photo that you
have uploaded from an SD memory card.
Heat/Cool Indicator
You may choose an enhanced indicator of the current status of the HVAC
equipment.
3rd Stage Deadband
3rd Stage Timer
3rd Stage Turnoff Point
Deadband
Setpoint
4th Stage Deadband
4th Stage Timer
4th Stage Turnoff Point
Deadband
Setpoint
Information
(Continued)
Settings
(Continued next page)
Page 29
Page 36
The Main Menu Buttons
The Main Menu Buttons
Settings
Installation Settings
Heat Pump Settings
Heat Pump Lockout - Enabled/Disabled
HP Lockout Outdoor Temp
Aux Heat Lockout - Enabled/Disabled
Aux Heat Lockout Temp
Dual Fuel Settings
Dual Fuel - On/Off
Changeover With Outdoor - On/Off
Adjust Balance Point
Fan Off Delay
Calibrate Sensors
Thermostat
Outdoor Sensor
Test Outputs
Dealer Information
Dealer Name
Contact Name
Dealer Phone
Dealer Email
Dealer Website
Factory Defaults
Information
(Continued)
Settings
Delete Custom Images
Upgrade Firmware
Page 30
Page 37
The Main Menu Buttons
Thermostat heating and cooling options are
found in this menu
Settings
Thermostat Name
Use keypad to name
your thermostat. The
name is displayed on
the Home Screen.
(Up to 14 characters)
Name appears here
Settings
Available Modes
Choose the desired modes the thermostat will use: Heat, Cool, Heat & Cool,
or Auto (All). For example, if you only have a heater, choose Heat, and only
Heat & Off modes will be available. This will simplify the operation for the user.
(all)
SD Card
Import and export files to and from the thermostat. See the ColorTouch
Assistant instructions for further details.
Import Settings from SD Card
Upload files from ColorTouch Assistant or another
thermostat.
Export Settings to SD Card
Export files from one thermostat and import them into others.
General Setup
Units
Fahrenheit (F)
Celsius (C)
(F)
Page 31
*NOTE: A 2GB SD card is
recommended. To import and
export files, the SD card must
contain the same version of the
firmware as the thermostat.
Page 38
The Main Menu Buttons
Settings
General Setup
Language
English
Spanish/Espanol
French/Francais
Smart Recovery - OFF
Smart Recovery - ON
Smart Recovery turns on the heat before the Morning
start time to bring the room temperature to the Morning
setpoint at the start of the Morning time period. Please
allow 4-8 days for Smart Recovery time to adjust. When
used with a heat pump, electric strip heat will be disabled
while Smart Recovery is active.
Simple Thermostat - OFF
Simple Thermostat - ON
(en)
(Continued)
Turn on Simple Thermostat for the most basic user interface.
When Simple Thermostat is on, alerts will appear in the top bar of the
main screen. Press on the top yellow alert bar to view alerts.
Top Bar
Room
Temperature
Press
for
Heat
Press
to
turn
Off
Press
for
Cooling
Press
to turn
Fan
On or Auto
Warmer
Button
Single
Setpoint
Cooler
Button
Menu
Button
Page 32
Page 39
The Main Menu Buttons
Installation Settings
Settings
(1h1c)
(1h1c)
(1h1c)
(6)
(2 )
(1h1c)
Only available when
dip switch is set for
Heat Pump operation.
}
Heat & Cool Stages
Heat & Cool Stages
Up to 2 Stages Cooling and 4 stages Heating.
Compressor Stages
Up to 2 compressors.
Aux Heat Stages
0 to 2 stages of Aux Heating.
Timers & Deadbands
Cycles Per Hour
At 6 cycles per hour, the HVAC unit will only be allowed to energize
once every 10 minutes. The Cycles Per Hour limit may be overridden
and reset by pressing the WARMER or COOLER buttons.
(2, 3, 4, 5, 6, No Limit)
Min Heat/Cool Difference
The minimum gap between Heat and Cool setpoints. (0 - 6 deg. F)
Compressor Min OFF Time
None, 1 minute, or 5 minutes.
(5m)
Page 33
Page 40
The Main Menu Buttons
Settings
Installation Settings
(2 )
(2mins )
(Deadband )
(Continued)
(2 )
Timers & Deadbands
The Deadband is the number of degrees or minutes that the
thermostat waits before it initiates the stages of heating or cooling.
1st Stage Deadband Specifies the minimum temperature difference
between the room temperature and the desired setpoint before the first stage
of heating or cooling is allowed to turn on. For example, if the heat
setpoint is 68 and the 1st Stage deadband is set to 2 degrees, the room
temperature will need to drop to 66 degrees before the heat turns on.
1st Stage Deadband
(1 - 6 deg. F)
2nd Stage Deadband
2nd Stage Deadband
Number of degrees past 1st stage before 2nd stage turns on. (0 - 10 deg. F)
2nd Stage Timer
Number of minutes past 1st stage before 2nd stage turns on. (0 - 60 mins.)
(The 2nd stage deadband must also be met)
2nd Stage Turnoff Point
Deadband or Setpoint.
3rd Stage Deadband
4th Stage Deadband
(Continued)
3rd and 4th stage
deadband settings
are the same as
2nd stage.
Page 34
Page 41
The Main Menu Buttons
Settings
Installation Settings
Free Cooling
Free Cooling is an energy saving way to boost the efficiency of your air conditioning
system by bringing in cool air from the outside. The installation of a Free Cooling
damper(s) and outdoor temperature sensor is required.
(Continued)
Free Cooling - DISABLED
Free Cooling - ENABLED
Turns on Free Cooling.
Usable Outdoor Temp
Free Cooling shuts off above this outdoor temperature. (40 - 80 degrees F)
Mechanical Cooling? - NO
(65 )
Mechanical Cooling? - YES
If you don’t have a compressor, set Mechanical Cooling to “NO”, Y1 will then be
used to control the Free Cooling Damper(s) and Y2 will be disabled. If set to
“YES”, mechanical (compressor) cooling will be controlled by the Y2 terminal.
(See page 48 for wiring diagram)
Mechanical air conditioning is turned on with a 2nd stage demand for cooling
and the Free Cooling, outdoor air damper is closed.
Supply Grilles
Return Grille
AirFlow
AirFlow
ReturnAir Grill
Barometric
Damper
AirFlow
FREE
Free Cooling
HVAC Unit
Supply
Coil
Furnace
Plenum
Air
Barometric
Vent to Attic
AirFlow
(To relieve building pressure)
Filter
Outdoor Air Grille
Damper
Damper1
Open
Return
Plenum
Damper2
Closed
Return
Damper
Outdoor
AirGrill
AirFlow
Free Cooling
Page 35
Page 42
The Main Menu Buttons
Settings
Installation Settings
Heat Pump Settings
Heat Pump Lockout - DISABLED
Heat Pump Lockout - ENABLED
Turns on Heat Pump Lockout.
HP Lockout Outdoor Temp
Heat Pump will not run below this temp. (20 - 75 deg. F)
Aux Heat Lockout - DISABLED
Aux Heat Lockout - ENABLED
Turns on Aux Heat Lockout.
Aux Heat Lockout Temp
Aux Heat will not run above this temp. (20 - 75 deg. F) GAS/EL or HP dip
switch must be set for HP and GAS or ELEC dip switch must be set for ELEC.
Dual Fuel Settings
This feature is for heat pump applications only.
This will only appear if the GAS/EL or HP is set for HP and the GAS
dip switch
or ELEC is set for Gas.
When Dual Fuel is ON, an outdoor temperature or a demand for third stage
heat will be used to stop running the heat pump and switch to a fossil fuel
source of heat. NOTE: Once the change to fossil fuel is made, the heat
demand must finish with fossil fuel. Additional heat demands within 10 minutes
will also use fossil fuel, regardless of outdoor temperature or stage demand.
Dual Fuel - ON/OFF
Changeover With Outdoor - ON/OFF
Uses outdoor sensor for changeover.
Adjust Balance Point
Choose the temperature for changeover to fossil fuel. (5 - 60 deg. F)
Page 36
(Continued)
(65 )
(65 )
dip switch
(Only available
when dip switch
is set for Heat
Pump operation.)
Page 43
The Main Menu Buttons
Settings
Installation Settings
Fan Off Delay
Runs the fan for a short time after Cooling or electric strip heat turns off
to increase system efficiency. (0 - 120 Secs.)
(Continued)
(0s)
Calibrate Sensors
Thermostat
The thermostat sensor may be calibrated -7 to +7 degrees F.
Outdoor Sensor
The outdoor sensor may be calibrated -7 to +7 degrees F.
(0 )
(0 )
Test Outputs
The installer or service technician can use this feature to test the
functions without any time delays of the thermostat and heating and
cooling equipment.
With a 1st stage cooling call, Y1 and G are active
Page 37
Page 44
The Main Menu Buttons
Settings
Dealer Information
The Dealer may enter their company contact information for the
customer to use when they need service. This will appear in the
“Who To Call For Service” button is pressed in the Information Menu.
Press the buttons
below and use the
keyboard to enter
your information
Dealer’s
Logo
here
Dealer Name
Contact Name
Dealer Phone
Dealer Email
Dealer Website
Please use ColorTouch
Assistant to add Dealer’s
logo. (See Page 40)
Factory Defaults
Press to reset the thermostat back to the factory settings.
Delete Custom Images
Press to delete the custom photos you uploaded to the thermostat.
Upgrade Firmware
Press to upgrade the thermostat firmware. The SD Card must be in the thermostat
SD Card reader and contain the valid firmware. If an error message appears, confirm
with ColorTouch Assistant that firmware is up to date or simply try reinserting the SD
card.
Page 38
Page 45
The Main Menu Buttons
The Emergency Heat function is only
available if your thermostat is set to
Emergency Heat
To initiate the Emergency Heat feature, Press the Emergency Heat button.
During Emergency Heat operation the thermostat will turn on the fan and
auxiliary stages of heat when there is a demand for heat. The 1st stage of
heating and all stages of cooling will be unavailable. To exit Emergency
Heat, press the Emergency Heat button.
control a Heat Pump.
Emergency Heat
Page 39
Page 46
ColorTouch Assistant
ColorTouch Assistant may be downloaded at no charge at:
www.venstar.com/thermostats/colortouch/assistant/
Every time the user runs the ColorTouch Assistant software, it automatically
connects to Venstar’s ColorTouch Web site in the background and updates
the software and firmware (the operating system for ColorTouch) at no cost.
The ColorTouch Assistant allows you to use your computer to:
Upload photos for background
and slideshow images
Configure installation settings
Update thermostat firmware
Page 40
Program a time period schedule
Upload dealer and service contact
information and company logo
Page 47
The ColorTouch Assistant
Uploading Photos and Settings to your thermostat
When you are finished adding and editing photos and settings,
click on Save to SD. When prompted, remove the SD card
from the SD card reader on your computer.
Save to SD
*NOTE: A 2GB SD card is
recommended.
At the thermostat:
Insert the SD card into the SD Card Slot.
MENU
Press
Next, press
then
Settings
SD Card
Slot
Press
Then, press
Select the items to import to your thermostat then press
Your thermostat will automatically save your new photos and settings.
SD Card
Import Settings from SD Card
NEXT
Page 41
Page 48
Installation Instructions
Remove & Replace the Old Thermostat
To install the thermostat properly, please follow these step by
step instructions. If you are unsure about any of these steps,
call a qualified technician for assistance.
Assemble tools: Flat blade screwdriver, wire cutters and wire
strippers.
Make sure your Heater/Air Conditioner is working properly
before beginning installation of the thermostat.
Carefully unpack the thermostat. Save the screws, any brackets, and instructions.
Turn off the power to the Heating/Air Conditioning system at
the main fuse panel. Most residential systems have a separate
breaker for disconnecting power to the furnace.
Remove the cover of the old thermostat. If it does not come off
easily, check for screws.
Loosen the screws holding the thermostat base or subbase to the
wall and lift away.
Disconnect the wires from the old thermostat. Tape the ends
of the wires as you disconnect them, and mark them with the
letter of the terminal for easy reconnection to the new thermostat.
Keep the old thermostat for reference purposes, until your new
thermostat is functioning properly.
Page 42
Page 49
Installation Instructions
Wire Connections
Wire Connections
If the terminal designations on your old thermostat
do not match those on the new thermostat, refer
to the chart below or the wiring diagrams
that follow.
Wire from the
old thermostat
terminal marked
G or FFanG
Y1, Y or C
W1, W or H
C
O/B
W2
Y2Y2
OUT -
OUT +
Function
CoolingY1
Heating
PowerRh, R, M, Vr, AR
Common
Rev. Valve
2nd Stage Heat
2nd Stage Cooling
3rd Stage Heat
Outdoor Sensor
Outdoor Sensor
Install on the
new thermostat
connector marked
W1/O/B
C
W1/O/B*
W2
W3W3
OUTDOOR
OUTDOOR
* O/B is used if your system is a Heat Pump.
Page 43
Page 50
Installation Instructions
The Color Touch Thermostat Backplate
NOTE:
The backplate does not fully cover a
full size vertical junction box. The
ACC-WPLWH ColorTouch Wallplate
or
a single-gang, horizontally mounted
would be needed for that
junction box
type of installation.
OUTDOOR
OUTDOOR
Y1Y2W1/O/B
W2
W3
CRG
To remove the thermostat backplate:
Using the Finger Pull Areas, pull the front
housing away from the backplate.
Look for these tabs to locate the pull areas
3rd stage heat circuit/2nd stage aux heat
W3
2nd stage heat circuit/1st stage aux heat
W2
1st stage heat circuit/reversing valve
W1/O/B
2nd stage compressor relay
Y2
1st stage compressor relay
Y1
Backplate
Pull out with thumbs in these areas
G
R
C
OUTDOOR
IMPORTANT:This thermostat requires both
R (24 VAC Return) and C (24 VAC Common) be
connected to the backplate terminals.
Page 44
Front Housing
Fan relay
24 VAC return
24 VAC common
Outdoor sensor
connections
Page 51
Installation Instructions
Explanation of Thermostat Dip Switches
Dip switches are located on the back of the thermostat
GAS/EL
O
GAS
GAS/EL
HPHP
ON
1 2 3
OB
ON
1 2 3
ON
1 2 3
GAS
ELECGAS ELEC
ON
GAS/EL
OR
OR
OR
HP
B
1 2 3
ELEC
This dip switch configures the thermostat to control a
conventional gas/electric system or a heat pump. If
your system is anything other than a heat pump,
leave this switch set for GAS/EL.*
ON
O
ON
ON
*For some commercial heat pumps, this switch may need to
1 2 3
be set for GAS/EL. Consult the commercial heat pump
literature.
When the GAS/EL or HP dip switch is configured for HP,
this dip switch (O or B) must be set to control the
appropriate reversing valve. If O is chosen, the W1/O/B
terminal will energize in cooling. If B is chosen, the
B
1 2 3
W1/O/B terminal will energize in heating.
*When GAS/EL or HP is set for GAS/EL:
This switch (GAS or ELEC) controls how the thermostat
will control the Fan (G) terminal in heating mode. When
GAS is chosen, the thermostat will not energize the
Fan (G) terminal in heating. When ELEC is chosen
the thermostat will energize the fan in heating.
1 2 3
*When GAS/EL or HP is set for HP:
This switch (GAS or ELEC) defines the Aux Heat type.
When GAS is chosen, the auxiliary heat will not be
allowed to run during heat pump operation. When
using a Dual Fuel system, set this switch for GAS.
When ELEC is chosen, up to two stages of auxiliary
strip heat will be allowed to run.
GAS/EL
O
ON
GASBELEC
HP
1 2 3
OUT+
OUTCR
G
Y1Y2W1-O-BW2W3
Page 45
Page 52
Installation Instructions
Sample Wiring Diagrams with Dip Switch Positions
Conventional Heating and Cooling Systems
3 Wire, Heat Only
Residential & Commercial 1 Stage Heating
with no Fan.
GAS
O
24VAC Power
24VAC Common
1st Stage Heat
ON
B
1 2 3
ELEC
R
C
W1/O/B
GAS/ELHP
4 Wire, Cool Only
Residential & Commercial 1 Stage Cooling.
R
C
Y1
G
GAS/ELHP
GAS
O
24VAC Power
24VAC Common
1st Stage Cool
Fan
ON
B
1 2 3
ELEC
5 Wire, 1 Stage Cooling, 1 Stage Heat
Residential & Commercial 1 Stage Cooling,
with 1 stage Gas Heat.
GAS
O
24VAC Power
24VAC Common
1st Stage Heat
1st Stage Cool
Fan
ON
B
1 2 3
ELEC
8 Wire, 2 Stage Cooling, 3 Stage Heat
Residential & Commercial 2 Stage Cooling,
with 3 stage Gas Heat.
R
C
W1/O/B
W2
W3
Y1
Y2
G
GAS/ELHP
GAS
O
24VAC Power
24VAC Common
1st Stage Heat
2nd Stage Heat
3rd Stage Heat
1st Stage Cool
2nd Stage Cool
Fan
ON
R
C
W1/O/B
Y1
G
GAS/ELHP
Page 46
5 Wire, 1 Stage Cooling, 1 Stage Heat
Residential & Commercial 1 Stage Cooling,
with 1 stage Electric Heat.
GAS
O
24VAC Power
24VAC Common
1st Stage Heat
1st Stage Cool
Fan
HP
ON
ON
B
123
1 2 3
ELEC
1 2 3
B
ELEC
R
C
W1/O/B
Y1
G
GAS/EL
Page 53
Installation Instructions
Sample Wiring Diagrams with Dip Switch Positions
Heat Pump Systems
5 Wire, 1 Stage Cooling, 1 Stage Heat
Residential & Commercial Heat Pump with
‘O’ Reversing Valve
R 24VAC Power
C 24VAC Common
W1/O/B Reversing Valve
Y1 1st Stage Compressor
(Cool or Heat)
G Fan
GAS/ELHP
GAS
ON
O
1 2 3
B
ELEC
6 Wire, 1 Stage Cooling, 2 Stage Heat
Residential & Commercial Heat Pump with
‘O’ Reversing Valve
R 24VAC Power
C 24VAC Common
W1/O/B Reversing Valve
Y1 1st Stage Compressor
(Cool or Heat)
W2 Aux Heat
G Fan
GAS/ELHP
GAS
ON
O
1 2 3
B
ELEC
7 Wire, 2 Stage Cooling, 3 Stage Heat
Residential & Commercial Heat Pump with
‘O’ Reversing Valve.
R 24VAC Power
C 24VAC Common
W1/O/B Reversing Valve
W2 3rd Stage Heat
Y1 1st Stage Compressor
(Cool or Heat)
Y2 2nd Stage Compressor
(Cool or Heat)
G Fan
GAS/ELHP
(Number of Compressor Stages set to 2)
GAS
ON
O
1 2 3
B
ELEC
Page 47
8 Wire, 2 Stage Cooling, 4 Stage Heat
Residential & Commercial Heat Pump with
‘O’ Reversing Valve.
R 24VAC Power
C 24VAC Common
W1/O/B Reversing Valve
W2 3rd Stage Heat
W3 4th Stage Heat
Y1 1st Stage Compressor
(Cool or Heat)
Y2 2nd Stage Compressor
(Cool or Heat)
G Fan
GAS/ELHP
(Number of Compressor Stages set to 2)
GAS
ON
O
1 2 3
B
ELEC
Page 54
Installation Instructions
Sample Wiring Diagrams with Dip Switch Positions
Heat Pump Systems with Dual Fuel
7 Wire, 2 Stage Cooling, 3 Stage Heat
Residential & Commercial Heat Pump with
‘O’ Reversing Valve and Fossil Fuel furnace.
R 24VAC Power
C 24VAC Common
W1/O/B Reversing Valve
W2 3rd Stage Heat
(connected to furnace)
Y1 1st Stage Compressor
(Cool or Heat)
Y2 2nd Stage Compressor
(Cool or Heat)
G Fan
GAS/ELHP
Number of Compressor Stages
set to 2
(see Compressor Stages, pg. 33)
Dual Fuel set to On
(see Dual Fuel Settings, pg. 36)
GAS
ON
O
1 2 3
B
ELEC
Free Cooling
Free Cooling
Damper
10K Thermistor
Outdoor Sensor
ACC-TSEN
Free Cooling utilizes the Y1 terminal for the operation of 1st stage cooling. If
mechanical (compressor) cooling is also present, the mechanical cooling is
connected to the Y2 terminal in this instance.
Use 18-22 gauge thermostat wire.
Y1Y2W1/O/B
W2
W3
CRG
OUTDOOR
OUTDOOR
Free Cooling may be used with a Gas/Electric or Heat Pump system.
Outdoor Sensor: ACC-TSEN Temperature Sensor 10K ohm sensor at
77F/25C. Negative Temperature Coefficient.
Page 48
Page 55
Troubleshooting
SYMPTOM: The thermostat touchscreen buttons are not responsive.
CAUSE: The touchscreen is out of calibration.
REMEDY: Remove the thermostat from the backplate. Push the
thermostat back onto the backplate, while keeping your finger
pressed firmly against the center of the touchscreen, until the
Calibration screen appears. Re-calibrate the Touchscreen.
SYMPTOM: The display is blank.
CAUSE: Lack of proper power.
REMEDY: Make sure the power is on to the furnace and that you have 24vac between R & C.
SYMPTOM: The air conditioning does not attempt to turn on.
CAUSE: The cooling setpoint is set too high.
REMEDY: Lower the cooling setpoint or lower the cooling set-
point limit. See Setpoint Limits (page 25).
SYMPTOM: The heating does not attempt to turn on.
CAUSE: The heating setpoint is set too low.
REMEDY: Raise the heating setpoint or raise the heating set-
point limit. See Setpoint Limits (page 25).
SYMPTOM: When controlling a residential heat pump, and
asking for cooling, the heat comes on.
CAUSE: The thermostat reversing valve dip switch is set for “B”.
REMEDY: Set the reversing valve dip switch for “O”.
SYMPTOM: When calling for cooling, both the heat and cool
come on.
CAUSE: The thermostat equipment dip switch is configured
for “HP” and the HVAC unit is a Gas/Electric.
REMEDY: Set the equipment dip switch for “Gas”.
SYMPTOM: Air handler control board fuse blows when thermostat
is attached to backplate with power on, but does not blow until the
thermostat is placed onto the backplate.
CAUSE: The Outdoor sensor and/or sensor wiring is shorted.
REMEDY: Check/replace Outdoor sensor and/or sensor wiring.
Page 49
Page 56
Index
A
Active Brightness, 17
Alerts, 14
view current, 15
reset, 15
set/edit reminders, 15
See also Runtime
Aux Heat Lockout, 36
Auto
adjust temperature, 3
changeover, 3
fan, 3
mode, 3
Auto Screenlock, 25
Available Modes, 31
B
B Reversing Valve, 45
Backdrop, 20
Backlight, 17
Backplate, 44
Balance Point, 36
Beep, 20
One-Year Warranty - This Product is warranted to be free from defects in material and
workmanship. If it appears within one year from the date of original installation, whether or not
actual use begins on that date, that the product does not meet this warranty, a new or
remanufactured part, at the manufacturer’s sole option to replace any defective part, will be
provided without charge for the part itself provided the defective part is returned to the distributor
through a qualified servicing dealer.
THIS WARRANTY DOES NOT INCLUDE LABOR OR OTHER COSTS incurred for diagnosing, repairing,
removing, installing, shipping, servicing or handling of either defective parts or replacement
parts. Such costs may be covered by a separate warranty provided by the installer.
THIS WARRANTY APPLIES ONLY TO PRODUCTS IN THEIR ORIGINAL INSTALLATION LOCATION AND
BECOMES VOID UPON REINSTALLATION.
LIMITATIONS OF WARRANTIES – ALL IMPLIED WARRANTIES (INCLUDING IMPLIED WARRANTIES OF
FITNESS FOR A PARTICULAR PURPOSE AND MERCHANTABILITY) ARE HEREBY LIMITED IN DURATION TO
THE PERIOD FOR WHICH THE LIMITED WARRANTY IS GIVEN. SOME STATES DO NOT ALLOW LIMITATIONS
ON HOW LONG AN IMPLIED WARRANTY LASTS, SO THE ABOVE MAY NOT APPLY TO YOU. THE
EXPRESSED WARRANTIES MADE IN THIS WARRANTY ARE EXCLUSIVE AND MAY NOT BE ALTERED,
ENLARGED, OR CHANGED BY ANY DISTRIBUTOR, DEALER, OR OTHER PERSON WHATSOEVER.
ALL WORK UNDER THE TERMS OF THIS WARRANTY SHALL BE PERFORMED DURING NORMAL WORKING
HOURS. ALL REPLACEMENT PARTS, WHETHER NEW OR REMANUFACTURED, ASSUME AS THEIR
WARRANTY PERIOD ONLY THE REMAINING TIME PERIOD OF THIS WARRANTY.
THE MANUFACTURER WILL NOT BE RESPONSIBLE FOR:
1. Normal maintenance as outlined in the installation and servicing instructions or owner’s
manual, including filter cleaning and/or replacement and lubrication.
2. Damage or repairs required as a consequence of faulty installation, misapplication, abuse,
improper servicing, unauthorized alteration or improper operation.
3. Failure to start due to voltage conditions, blown fuses, open circuit breakers or other
damages due to the inadequacy or interruption of electrical service.
4. Damage as a result of floods, winds, fires, lightning, accidents, corrosive environments or
other conditions beyond the control of the Manufacturer.
5. Parts not supplied or designated by the Manufacturer, or damages resulting from their use.
6. Manufacturer products installed outside the continental U.S.A., Alaska, Hawaii, and
Canada.
7. Electricity or fuel costs or increases in electricity or fuel costs for any reason whatsoever
including additional or unusual use of supplemental electric heat.
8. ANY SPECIAL INDIRECT OR CONSEQUENTIAL PROPERTY OR COMMERCIAL
DAMAGE OF ANY NATURE WHATSOEVER. Some states do not allow the exclusion of
incidental or consequential damages, so the above may not apply to you.
This warranty gives you specific legal rights and you may also have other rights which may vary
from state to state.
Page 56
Page 63
Printed on recycled paper.
P/N 88-860 Rev. 5b
Page 57
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.