5.3 Checking the measuring cable ......................................... 10
Safety information
Please read this manual carefully, and also take
note of country-specific installation standards
as well as all prevailing safety regulations and
accident prevention rules.
For safety and warranty reasons, any internal
work on the instruments, apart from that involved in normal installation and electrical connection, must be carried out only by qualified
VEGA personnel.
2VEGASTAB 690
Note Ex area
Please note the attached approval documents
(yellow binder) and especially the included
safety data sheet.
Product description
1 Product description
1.1 Function and configuration
VEGASTAB 690 power supply unit is a module instrument with plug-in socket, suitable for
carrier rail mounting DIN 46 277.
Function
The power supply unit provides two galvanically separated supply circuits. Both circuits
are shortcircuit proof (current limitation
approx. 26 mA) and are equipped with interlock diodes for control.
Configuration
VEGASTAB 690 power supply unit can power
- hydrostatic pressure transmitters
- process pressure transmitters or
- differential pressure transmitters
and ensures the configuration of a complete
measuring system per circuit in conjunction
with one of these sensors.
1243
+
–
2
1
on
VEGASTAB 690
56 78
91011121314
1.2 Types and versions
Standard application
A power supply unit powers max. two sensors. Both, i.e. power supply unit and sensor
form one measuring system.
e.g.
DCS
Standard application
Application in Ex area
A power supply unit powers via max. two ia
safety barriers type 145 two sensors in Ex
area. Together they form one measuring
system.
Ex area
Non-Ex area
p
p
p
Safety barrier
type 145
VEGASTAB …
e.g.
DCS
Ex application
VEGASTAB 6903
1.3 Technical data
Power supply
Operating voltage20 … 250 V AC, 50/60 Hz
Power consumptionmax. 3 W (3 … 16 VA)
Fuse
- supply rangeT 1 A, 250 V
20 … 72 V DC
with backup power supply curve form
deviating considerably from mains sine:
U
Permissible ambient temperature-20°C … +60°C
Storage and transport temperature-40°C … +70°C
Output
Output voltage2 x 24 V DC floating
Current limitationapprox. 26 mA (shortcircuit proof)
Load
- non-Ex circuitmax. 500 Ohm
- intrinsically safe circuitmax. 75 Ohm
(in conjunction with safety barrier type 145)
Interlock diodefor output 1 and 2
max. instrument load 15 Ohm
Indicating elements
LED in front plategreen on: operating voltage on
Electrical separation measures
Reliable separation acc. to
VDE 0106, part 1 betweenpower supply output 1 and output 2
- reference voltage250 V
- isolation resistance3 kV
CE conformity
VEGASTAB 690 power supply unit meets the protective regulations of EMC (89/336/EWG)
and NSR (73/23/EWG). Conformity has been judged acc. to the following standards:
EMCEmissionEN 50 081 - 1
SusceptibilityEN 50 082 - 2
NSREN 61 010
4VEGASTAB 690
Product description
1.4 Dimensions
Transparent cover
134
Carrier rail 35 x 7.5 or
35 x 15 acc. to EN 50 022
54,5
12 34
118,5
on
56 78
9 1011121314
36
VEGASTAB 6905
2 Mounting and installation instructions
Mounting and installation instructions
Mounting
Each series 600 instrument consists of a
terminal socket for carrier rail mounting DIN
46 277 and a module unit.
You can connect the supply voltage to terminals 9 and 10.
If there are adjoining series 600 instruments,
it is possible to continue the connection L1
and N directly via the supplied jumpers.
Note!
The jumpers must never be used for single
instruments or at the end of an instrument
row.
Disregard of this warning could lead to coming into contact with the operating voltage, or
could generate a short circuit.
Coding
The terminal socket is provided with pins and
the instrument with appropriate gaps (mechanical coding) to prevent inadvertent
swapping of the different instruments.
Instrument coding by means of differently
placed coded pins prevents inadvertent
swapping of the different signal conditioning
instruments and this power supply unit.
Instrument coding
VEGASTAB 690 (pin 5)
Direct connection for supply
voltage
124
A o
B o
C o
1 o
2 o
3 o
o
o
o
7 o
8 o
9 o
o
o
o
0¼10 V
DISBUS
N
L1
3
VEGA
5678
9 1011121314
6VEGASTAB 690
Electrical connection
3 Electrical connection
3.1 Connection instructions
The following connection plan is valid for
standard as well as for Ex measuring systems. Please observe the following instructions:
- If strong electromagnetic interferences are
expected, screened cable is recommended for the signal cables.
- The screening must be earthed only on
one (sensor) end.
- If overvoltages are expected, we recommend the use of VEGA overvoltage arresters.
- The connection must be made according
to the appropriate national installation
standards (e.g. in Germany acc. to the
VDE regulations).
3.2 Connection instructions
for approved applications
In Ex applications, the voltage supply of the
sensor must be provided only via an intrinsically safe circuit.
By using ia safety barriers type 145, intrinsically safe circuits can be prepared, see „3.4
Connection examples“.
3.3 Connection plan
–+
+
124
VEGASTAB 690
910
+
–
N
L1
–
3
Output 1 for sensor 1
Output 2 for sensor 2
Voltage supply
Please also note the official document of the
ia safety barrier.
VEGASTAB 6907
Electrical connection
3.4 Connection examples
Sensors in non-Ex area
e.g. hydrostatic pressure
transmitters or process
pressure transmitters
2
1
–
+
–+
+
1243
1
2
+
–
–
e.g. VEGADIS
–
+
Load max. 500 Ohm
e.g. differential pressure
transmitter
e.g. VEGADIS
–
+
Load max. 500 Ohm
VEGASTAB 690
power supply unit
+
+
e.g.
DCS
e.g.
DCS
Sensors in Ex area
1
2
+
–
–
–
+
1
11
+
Typ e
145
–
2
12
–
e.g. hydrostatic pressure
transmitters or process
pressure transmitters
Ex area
Non-Ex area
ia safety barrier
Meas. instrument
Load max. 75 Ohm
e.g. differential pressure
transmitter
1
2
+
–
e.g.
DCS
–
+
–
+
Ex area
Non-Ex area
ia safety barrier
–
+
2
Mixed applications can also be connected to
the two outputs of the power supply unit, e.g.
- output 1, sensor in non-Ex area
- output 2, sensor in Ex area.
1
Typ e
145
12
11
–
+
Meas. instrument
–
+
+
e.g.
DCS
–
Load max. 75 Ohm
+
1243
VEGASTAB 690
power supply unit
–
–+
8VEGASTAB 690
Setup
4 Setup
4.1 Indicating and adjustment ele-
ments
2
1243
+
±
2
1
1
1 LED secondary voltage available
2 Separating wall
3 Terminals output 1 and 2
4 Interlock connection sockets output 2
5 Interlock connection sockets output 1
6 Terminals supply
on
VEGASTAB 690
5678
9 1011121314
3
4
5
6
4.2 Setup sequence
The following listing shows the main setup
steps
- mount the terminal socket
- wire the socket acc. to your requirements
- cover the input terminals with the separating wall (2)
- mount the module unit to the terminal
socket
- switch on the supply voltage, the green
LED (1) lights
VEGASTAB 6909
5 Diagnostics
Diagnostics
5.1 Maintenance
The instrument is maintenance-free.
5.2 Repair
For safety and warranty reasons, any internal
work on the instruments, apart from that
required in normal installation and connection,
must be carried out only by VEGA personnel.
In case of defect, please return the respective instrument with a short description of the
fault to our repair department.
5.3 Checking the measuring cable
A measuring instrument connected to the
interlock sockets is switched without interruption into the circuit of the measuring cable
(series connection). This enables diagnostic
checking of the measuring cable. The
measuring instrument shows the actual
current.
The same procedure is also valid for output
2, measuring cable 2 on the interlock sockets
2.
Sensor
2
1
–
+
–+
+
1243
–
VEGASTAB 690
power supply unit
1
2
e.g. VEGADIS
–
+
mA
Measuring instrument
load max. 15 Ohm
+
e.g.
DCS
–
Note!
In Ex systems make sure that the Ex protection is not degraded by the measuring instrument.
The statements on types, application, use and operating conditions of
the sensors and processing systems correspond to the latest information at the time of printing.
Technical data subject to alterations
19959-EN-000701