VEGA STAB690 User Manual

Operating Instructions
VEGASTAB 690
12 43
Level and Pressure
+
2 1
on
56 78
9 1011121314
out
in
Contents
Safety information ........................................................................ 2
Note Ex area ................................................................................ 2
1 Product description
1.1 Function and configuration .................................................. 3
1.2 Types and versions ............................................................. 3
1.3 Technical data ....................................................................... 4
1.4 Dimensions ........................................................................... 5
2 Mounting and installation instructions ................................ 6
3 Electrical connection
3.1 Connection instructions ....................................................... 7
3.2 Connection instructions for approved applications .......... 7
3.3 Connection plan ................................................................... 7
3.4 Connection examples .......................................................... 8
4 Setup
4.1 Indicating and adjustment elements .................................. 9
4.2 Setup sequence ................................................................... 9
Contents
5 Diagnostics
5.1 Maintenance ....................................................................... 10
5.2 Repair.................................................................................. 10
5.3 Checking the measuring cable ......................................... 10

Safety information

Please read this manual carefully, and also take note of country-specific installation standards as well as all prevailing safety regulations and accident prevention rules.
For safety and warranty reasons, any internal work on the instruments, apart from that in­volved in normal installation and electrical con­nection, must be carried out only by qualified VEGA personnel.
2 VEGASTAB 690

Note Ex area

Please note the attached approval documents (yellow binder) and especially the included safety data sheet.
Product description

1 Product description

1.1 Function and configuration

VEGASTAB 690 power supply unit is a mod­ule instrument with plug-in socket, suitable for carrier rail mounting DIN 46 277.
Function
The power supply unit provides two galvani­cally separated supply circuits. Both circuits are shortcircuit proof (current limitation approx. 26 mA) and are equipped with inter­lock diodes for control.
Configuration
VEGASTAB 690 power supply unit can power
- hydrostatic pressure transmitters
- process pressure transmitters or
- differential pressure transmitters and ensures the configuration of a complete measuring system per circuit in conjunction with one of these sensors.
12 43
+
2 1
on
VEGASTAB 690
56 78
91011121314

1.2 Types and versions

Standard application
A power supply unit powers max. two sen­sors. Both, i.e. power supply unit and sensor form one measuring system.
e.g. DCS
Standard application
Application in Ex area
A power supply unit powers via max. two ia safety barriers type 145 two sensors in Ex area. Together they form one measuring system.
Ex area
Non-Ex area
p
p
p
Safety barrier type 145
VEGASTAB …
e.g. DCS
Ex application
VEGASTAB 690 3

1.3 Technical data

Power supply
Operating voltage 20 … 250 V AC, 50/60 Hz
Power consumption max. 3 W (3 … 16 VA) Fuse
- supply range T 1 A, 250 V
20 … 72 V DC with backup power supply curve form deviating considerably from mains sine: U
= 125 V AC (rectangle)
max.
Product description
Electrical connection
Screw terminal max. 1.5 mm
2
Electrical protective measures
Protection
- instrument IP 30
- plug-in socket IP 20 Protection class II Overvoltage category II
Ambient conditions
Permissible ambient temperature -20°C … +60°C Storage and transport temperature -40°C … +70°C
Output
Output voltage 2 x 24 V DC floating Current limitation approx. 26 mA (shortcircuit proof) Load
- non-Ex circuit max. 500 Ohm
- intrinsically safe circuit max. 75 Ohm (in conjunction with safety barrier type 145)
Interlock diode for output 1 and 2
max. instrument load 15 Ohm
Indicating elements
LED in front plate green on: operating voltage on
Electrical separation measures
Reliable separation acc. to VDE 0106, part 1 between power supply output 1 and output 2
- reference voltage 250 V
- isolation resistance 3 kV
CE conformity
VEGASTAB 690 power supply unit meets the protective regulations of EMC (89/336/EWG) and NSR (73/23/EWG). Conformity has been judged acc. to the following standards: EMC Emission EN 50 081 - 1
Susceptibility EN 50 082 - 2
NSR EN 61 010
4 VEGASTAB 690
Product description

1.4 Dimensions

Transparent cover
134
Carrier rail 35 x 7.5 or 35 x 15 acc. to EN 50 022
54,5
12 34
118,5
on
56 78
9 1011121314
36
VEGASTAB 690 5

2 Mounting and installation instructions

Mounting and installation instructions
Mounting
Each series 600 instrument consists of a terminal socket for carrier rail mounting DIN 46 277 and a module unit.
You can connect the supply voltage to termi­nals 9 and 10.
If there are adjoining series 600 instruments, it is possible to continue the connection L1 and N directly via the supplied jumpers.
Note!
The jumpers must never be used for single instruments or at the end of an instrument row.
Disregard of this warning could lead to com­ing into contact with the operating voltage, or could generate a short circuit.
Coding
The terminal socket is provided with pins and the instrument with appropriate gaps (me­chanical coding) to prevent inadvertent swapping of the different instruments.
Instrument coding by means of differently placed coded pins prevents inadvertent swapping of the different signal conditioning instruments and this power supply unit.
Instrument coding VEGASTAB 690 (pin 5)
Direct connection for supply voltage
12 4
A o B o C o
1 o 2 o
3 o
o o
o
7 o 8 o 9 o
o o o
0¼10 V DISBUS
N L1
3
VEGA
56 78
9 1011121314
6 VEGASTAB 690
Electrical connection

3 Electrical connection

3.1 Connection instructions

The following connection plan is valid for standard as well as for Ex measuring sys­tems. Please observe the following instruc­tions:
- If strong electromagnetic interferences are expected, screened cable is recom­mended for the signal cables.
- The screening must be earthed only on one (sensor) end.
- If overvoltages are expected, we recom­mend the use of VEGA overvoltage ar­resters.
- The connection must be made according to the appropriate national installation standards (e.g. in Germany acc. to the VDE regulations).
3.2 Connection instructions
for approved applications
In Ex applications, the voltage supply of the sensor must be provided only via an intrinsi­cally safe circuit.
By using ia safety barriers type 145, intrinsi­cally safe circuits can be prepared, see „3.4 Connection examples“.

3.3 Connection plan

–+
+
12 4
VEGASTAB 690
910
+
– N
L1
3
Output 1 for sensor 1
Output 2 for sensor 2
Voltage supply
Please also note the official document of the ia safety barrier.
VEGASTAB 690 7
Electrical connection

3.4 Connection examples

Sensors in non-Ex area
e.g. hydrostatic pressure transmitters or process pressure transmitters
2
1
+
–+
+
12 43
1
2
+
e.g. VEGADIS
+
Load max. 500 Ohm
e.g. differential pressure transmitter
e.g. VEGADIS
+
Load max. 500 Ohm
VEGASTAB 690 power supply unit
+
+
e.g. DCS
e.g. DCS
Sensors in Ex area
1
2
+
+ 1
11 +
Typ e 145
– 2
12 –
e.g. hydrostatic pressure transmitters or process pressure transmitters
Ex area
Non-Ex area
ia safety barrier
Meas. instrument
Load max. 75 Ohm
e.g. differential pressure transmitter
1
2
+
e.g. DCS
+
+
Ex area
Non-Ex area
ia safety barrier
+
2
Mixed applications can also be connected to the two outputs of the power supply unit, e.g.
- output 1, sensor in non-Ex area
- output 2, sensor in Ex area.
1
Typ e 145
12
11
+
Meas. instrument
+
+
e.g. DCS
Load max. 75 Ohm
+
12 43
VEGASTAB 690 power supply unit
–+
8 VEGASTAB 690
Setup

4 Setup

4.1 Indicating and adjustment ele-
ments
2
12 43
+
±
2 1
1
1 LED secondary voltage available 2 Separating wall 3 Terminals output 1 and 2 4 Interlock connection sockets output 2 5 Interlock connection sockets output 1 6 Terminals supply
on
VEGASTAB 690
56 78
9 1011121314
3
4 5
6

4.2 Setup sequence

The following listing shows the main setup steps
- mount the terminal socket
- wire the socket acc. to your requirements
- cover the input terminals with the separat­ing wall (2)
- mount the module unit to the terminal socket
- switch on the supply voltage, the green LED (1) lights
VEGASTAB 690 9

5 Diagnostics

Diagnostics

5.1 Maintenance

The instrument is maintenance-free.

5.2 Repair

For safety and warranty reasons, any internal work on the instruments, apart from that required in normal installation and connection, must be carried out only by VEGA personnel.
In case of defect, please return the respec­tive instrument with a short description of the fault to our repair department.

5.3 Checking the measuring cable

A measuring instrument connected to the interlock sockets is switched without interrup­tion into the circuit of the measuring cable (series connection). This enables diagnostic checking of the measuring cable. The measuring instrument shows the actual current.
The same procedure is also valid for output 2, measuring cable 2 on the interlock sockets
2.
Sensor
2
1
+
–+
+
12 43
VEGASTAB 690 power supply unit
1
2
e.g. VEGADIS
+
mA
Measuring instrument load max. 15 Ohm
+
e.g. DCS
Note!
In Ex systems make sure that the Ex protec­tion is not degraded by the measuring instru­ment.
10 VEGASTAB 690
Notes
VEGASTAB 690 11
VEGA Grieshaber KG Am Hohenstein 113 D-77761 Schiltach Phone (0 78 36) 50 - 0 Fax (0 78 36) 50 - 201 E-Mail info@de.vega.com www.vega.com
ISO 9001
The statements on types, application, use and operating conditions of the sensors and processing systems correspond to the latest infor­mation at the time of printing.
Technical data subject to alterations
19959-EN-000701