VEGA KLD2-GT-DP1PA User Manual

Gateway
KLD2-GT-DP.1PA
Gateway for PROFIBUS DP/PA segment coupler SK2
1-channel gateway without redundancy
• PROFIBUS DP transmission rate up to 12 MBit/s
• Transparent, need no PROFIBUS address
• PROFIBUS master independent
• Up to 125 PA devices can be connected
• No configuration necessary
• Supply via Power Rail
• Removable terminals and Power Rail
• EMC acc. to NAMUR NE 21
Function
Together with at least one Power-Link, the Gateway provides a segment cou­pler for the connection of a PROFIBUS PA segment to PROFIBUS DP. On the PROFIBUS DP site, all transfer rates up to 12 MBit/s are supported in accordance with. EN 50170/2.
Service
RxD TxD GND
Composition
PROFIBUS-DP
connection
3568
VP
DGND
B R/TxD-P
+
-
CH1
Connection to Power Link
CH
A R/TxD-N
+FE
-
Power
supply 24 V
096765_ENG.xml 2003-02-27
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
1
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
Technical Data
Supply
Connection Power Rail or terminals +, -, FE Rated voltage 20 ... 35 V DC Ripple 10 % Rated current 138 mA ... 84 mA (without load) Power loss 3 W
Fieldbus connection
Profibus DP 1 RS485 interface
Connection 9-pin sub-D socket Baudrate 45,45 kBit/s ... 12 MBit/s Protocol PROFIBUS DP V1
Connection to power link
Connection Power Rail or terminals CH1+ at 28+, CH1- at 29- of KLD2-PL1.PA
Baudrate 31,25 kBit/s
Electrical isolation
CH/PROFIBUS DP function insulation, rated insulation voltage 50 V PROFIBUS DP/Supply function insulation, rated insulation voltage 50 V All circuits/FE function insulation, rated insulation voltage 50 V
Standard conformity
Electrical isolation EN 50178 Electromagnetic compatibility NAMUR NE 21 Protection degree IEC/EN 60529 Fieldbus standard EN 50170/2 Climatic conditions DIN IEC 721
Directive conformity
Electromagnetic compatibility standards
Directive 89/336/EG EN 61326, EN 50081-2
Ambient conditions
Classification 3K3 Ambient temperature -20 ... 60 °C (253 ... 333 K) Relative humidity < 75 % Degree of soiling max. 2, according to IEC 664
Mechanical specifications
Connection type terminals Core cross-section
Housing 60 mm x 115 mm x 107 mm Protection degree IP20 Mass 600 g Mounting DIN rail mounting
Data for application in conjunction with hazardous areas
Statement of conformity TÜV 02 ATEX 1819 X
Group, category, type of protection, Temperature classification
Connection to power link Connection to the data interface CH of KLD2-PL-Ex1.PA (Konf. TÜV 00 ATEX 1531X)
Directive conformity standards
Directive 94/9 EU EN 50021
Operating principle
Together with at least one power link, the gateway forms a segment coupler for connecting a PROFIBUS PA segment to the PROFIBUS DP. The PROFIBUS is standardised to EN 50 170/2. The gateway supports all transfer rates thus defined up to 12 MBit/s. The gateway can make one, two or four channels available. The channels work completely independently of each other in terms of time. This makes it possible to reduce response times considerably. Up to 5 power links can be connected to each channel, of which each forms its own PROFIBUS PA segment. Communication between the gateway and the power links takes place over the power rail for Channel 1 and over the terminals for the other channels. The communication process is transparent. Each PA station is addressed directly and planning for them is like a PROFIBUS DP station. The planning does not include the gateway and power links. The gateway can be mounted in Zone 2. Power Links are also permitted for this type of installation. Version KLD2-GT-DPR.xPA allows for operation with a redundant transmission line on the PROFIBUS DP side. The channels work directly at 31.25 kBaud (Manchester coded). This saves additional delay times in the power links. For additional information, please consult the segment coupler manual/operating instructions (Part. No. 105085).
Power Rail or terminals CH1+ at 40+, CH1- at 41- of KLD2-PL-Ex1.PA
eff
eff
eff
up to 2.5 mm
¬ II 3 G EEx nA II T4
Connection to the data interface CH of KLD2-PL-1.PA (Konf. TÜV 00 ATEX 1788X)
2
KLD2-GT-DP.1PA
096765_ENG.xml 2003-02-27
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
2
Loading...
+ 1 hidden pages