VEGA CAP60 User Manual

Operating Instructions
Electronics module
VEGACAP series 60
Document ID:
30174
Capacitive

Contents

Contents
1 About this document
1.2 Target group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.3 Symbolism used . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2 For your safety
2.1 Authorised personnel . . . . . . . . . . . . . . . . . . . . . . . .
2.2 Appropriate use . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.3 Safety instructions for Ex areas . . . . . . . . . . . . . . . . .
2.4 Environmental instructions. . . . . . . . . . . . . . . . . . . . .
3 Product description
3.1 Structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.2 Principle of operation . . . . . . . . . . . . . . . . . . . . . . . .
3.3 Packaging, transport and storage . . . . . . . . . . . . . . .
4 Mounting
4.1 Instructions for installation . . . . . . . . . . . . . . . . . . . . .
4.2 Mounting preparations . . . . . . . . . . . . . . . . . . . . . . .
4.3 Mounting steps. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5 Setup
5.1 Setup. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6 Maintaining
6.1 Instrument repair . . . . . . . . . . . . . . . . . . . . . . . . . . .
3 3 3
4 4 4 4
5 5 5
6 6 6
8
9
7 Dismounting
7.1 Dismounting steps . . . . . . . . . . . . . . . . . . . . . . . . . .
7.2 Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8 Supplement
8.1 Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Editing status: 2012-01-17
2 Electronics module VEGACAP series 60
10 10
11
30174-EN-120124

1 About this document

1 About this document

1.1 Function

This operating instructions manual has all the information you need for quick mounting and setup of a replacement module. Please read this manual before you start setup.

1.2 Target group

This operating instructions manual is directed to trained qualied personnel. The contents of this manual should be made available to these personnel and put into practice by them.

1.3 Symbolism used

Information, tip, note
This symbol indicates helpful additional information.
Caution: If this warning is ignored, faults or malfunctions can result. Warning: If this warning is ignored, injury to persons and/or serious damage to the instrument can result. Danger: If this warning is ignored, serious injury to persons and/or destruction of the instrument can result.
Ex applications
This symbol indicates special instructions for Ex applications.
l List
The dot set in front indicates a list with no implied sequence.
à Action
This arrow indicates a single action.
1 Sequence
Numbers set in front indicate successive steps in a procedure.
30174-EN-120124
Electronics module VEGACAP series 60 3

2 For your safety

2 For your safety

2.1 Authorised personnel

All operations described in this operating instructions manual must be carried out only by trained specialist personnel authorised by the plant operator.
During work on and with the device the required personal protective equipment must always be worn.

2.2 Appropriate use

Electronics module CP60 is a replacement module for VEGACAP series 60 level switches.

2.3 Safety instructions for Ex areas

Please note the Ex-specic safety information for installation and operation in Ex areas. These safety instructions are part of the operating instructions manual and come with the Ex-approved instruments.

2.4 Environmental instructions

Protection of the environment is one of our most important duties. That is why we have introduced an environment management system with the goal of continuously improving company environmental protection.
The environment management system is certied according to DIN EN ISO 14001.
Please help us full this obligation by observing the environmental
instructions in this manual:
l Chapter "Packaging, transport and storage" l Chapter "Disposal"
4 Electronics module VEGACAP series 60
30174-EN-120124

3 Product description

3.1 Structure

3 Product description
Scope of delivery
Application area
Packaging
Transport
Transport inspection
The scope of delivery encompasses:
l Electronics module for VEGACAP series 60 (CP60) l Documentation
- this operating instructions manual

3.2 Principle of operation

The electronics module CP60 is suitable for replacement in VEGACAP series 60 capacitive level switches.

3.3 Packaging, transport and storage

Your instrument was protected by packaging during transport. Its capacity to handle normal loads during transport is assured by a test according to DIN EN 24180.
The packaging of standard instruments consists of environment­friendly, recyclable cardboard. For special versions, PE foam or PE foil is also us ed. Dispose of the packaging material via specialised recycling companies.
Transport must be carried out under consideration of the notes on the transport packaging. Nonobservance of these instructions can cause damage to the device.
The delivery must be checked for completeness and possible transit damage immediately at receipt. Ascertained transit damage or concealed defects must be appropriately dealt with.
Storage
Storage and transport
temperature
Up to the time of installation, the packages must be left closed and stored according to the orientation and storage markings on the outside.
Unless otherwise indicated, the packages must be stored only under the following conditions:
l Not in the open l Dry and dust free l Not exposed to corrosive media l Protected against solar radiation l Avoiding mechanical shock and vibration
l Storage and transport temperature see chapter "Supplement -
Technical data - Ambient conditions"
l Relative humidity 20 85 %
30174-EN-120124
Electronics module VEGACAP series 60 5
2
1

4 Mounting

4 Mounting

4.1 Instructions for installation

If the electronics module is defective, it can be replaced by the user.
In Ex applications only one instrument and one electronics module with respective Ex approval may be used.

4.2 Mounting preparations

In general, all electronics modules of series CP60 can be inter- changed. If you want to use an electronics module with a dierent signal output, you can download the corresponding operating instructions manual from our homepage under Downloads.

4.3 Mounting steps

Mounting steps
To exchange the electronics module, proceed as follows:
1 Switch opower supply
2 Unscrew the housing cover
3 Lift the opening levers of the terminals with a screwdriver
4 Pull the connection cables out of the terminals
5 Loosen the two screws with a screw driver (Torx size T10 or slot 4)
Fig. 1: Loosening the holding screws
1 Electronics module 2 Screws (2 pcs.)
6 Pull out the old electronics module
7 Compare the new electronics module with the old one. The type
label of the electronics module must correspond to that of the old electronics module. This applies particularly to instruments used in hazardous areas.
30174-EN-120124
6 Electronics module VEGACAP series 60
2
1
4 Mounting
8 Compare the settings of the two electronics modules. Set the
adjustment elements of the new electronics module to the same setting of the old one.
Information:
Make sure that the housing is not rotated during the electronics exchange. Otherwise the plug may be in a dierent position later.
9 Insert the electronics module carefully. Make sure that the plug is
in the correct position.
10 Screw in the two holding screws and tighten them
11 Insert the wire ends into the open terminals according to the wiring
plan
12 Press down the opening levers of the terminals, you will hear the
terminal spring closing
13 Check the hold of the wires in the terminals by lightly pulling on
them
14 Check cable gland on tightness. The seal ring must completely
encircle the cable.
15 Mount the probe into the vessel. Make sure that the probe is
uncovered.
Fig. 2: Compensation key
1 Measuring range selection switch (compensation key) 2 Control lamp
16 Push the measuring range selection switch (1) as long as the
control lamp (2) ashes green.
17 Hence the probe is compensated to the modied length.
18 Carry out the adjustment again. See chapter "Set-up, adjustment
elements".
19 Screw the housing cover back on
The electronics exchange is now nished.
As a rule, an exchange of electronics must be documented internally when Ex applications are involved.
30174-EN-120124
Electronics module VEGACAP series 60 7

5 Setup

5 Setup

5.1 Setup

Setup
Make sure that all adjustment elements are set to the settings of the old electronics module. Hence the sensor is immediately ready for operation.
In general, all oscillators of series CP60 can be interchanged.
If you want to use an electronics module with a dierent signal output,
you can download the corresponding operating instructions manual from our homepage under Downloads.
8 Electronics module VEGACAP series 60
30174-EN-120124

6 Maintaining

6 Maintaining

6.1 Instrument repair

If a repair is necessary, please proceed as follows:
You can download a return form (23 KB) from our homepage at www.
vega.com under: "Downloads - Forms and certicates - Repair form".
By doing this you help us carry out the repair quickly and without having to call back for needed information.
l Print and ll out one form per instrument l Clean the instrument and pack it damage-proof
l Attach the completed form and, if need be, also a safety data
sheet outside on the packaging
l Please ask the agency serving you for the address of your return
shipment. You can nd the respective agency on our website www.vega.com under: "Company - VEGA worldwide"
30174-EN-120124
Electronics module VEGACAP series 60 9

7 Dismounting

7 Dismounting

7.1 Dismounting steps

Take note of chapters "Mounting" and "Connecting to power supply" and carry out the listed steps in reverse order.

7.2 Disposal

The replacement module consists of materials which can be recycled by specialised recycling companies. We have purposely designed the electronic modules to be easily separable.
WEEE directive 2002/96/EG
This instrument is not subject to the WEEE directive 2002/96/EG and the respective national laws (in Germany e.g. ElektroG). Pass the instrument directly on to a specialised recycling company and do not use the municipal collecting points. These may be used only for privately used products according to the WEEE directive.
Correct disposal avoids negative eects on humans and the environ­ment and ensures recycling of useful raw materials.
Materials: see chapter "Technical data"
If you have no way to dispose of the replacement module properly,
please contact us concerning return and disposal.
10 Electronics module VEGACAP series 60
30174-EN-120124

8 Supplement

8.1 Technical data

Technical data
are stated in the operating instructions manual of the respective sensor.
8 Supplement
30174-EN-120124
Electronics module VEGACAP series 60 11
VEGA Grieshaber KG
ISO 9001
Am Hohenstein 113 77761 Schiltach
Germany Phone +49 7836 50-0 Fax +49 7836 50-201 E-mail: info.de@vega.com
www.vega.com
Printing date:
All statements concerning scope of delivery, application,
practical use and operating conditions of the sensors and
processing systems correspond to the information avail-
able at the time of printing.
© VEGA Grieshaber KG, Schiltach/Germany 2012
Subject to change without prior notice 30174-EN-120124