Only trained operators shall use the device. All circuit breakers under test shall be
fully isolated.
DO NOT SERVICE OR TEST ALONE
Do not perform test procedures or service unless another person is also present who is capable
of rendering aid and resuscitation.
DO NOT MODIFY TEST EQUIPMENT
Due to the added risk of introducing additional or unknown hazards, do not install substitute parts
or perform any unauthorized modifications to any CT-6500 test unit. To ensure that all designed
safety features are maintained, it is recommended that repairs be performed only by Vanguard
Instruments Company’s factory personnel or by an authorized repair and service center.
Unauthorized modifications can cause serious safety hazards and will nullify the manufacturer's
warranty.
FOLLOW EXACT OPERATING PROCEDURES
Any deviation from the procedures described in the operator’s manual may create one or more
safety hazards, damage the CT-6500, the test circuit breaker or cause errors in the test results.
Vanguard Instruments Company, Incorporated assumes no liability for unsafe or improper use of
the CT-6500.
off line and
WARRANTY
The CT-6500’s warranty is only valid to the original purchaser to be free from defects in material
and workmanship for a period of one year. The warranty does not apply to normal wear or
damage from misuse, abuse, improper storage, installation, accident, unauthorized repair or
alterations.
Page 3
CT-6500 Operating Instructions
Table of Contents
1.0 Introduction
2.0 CT-6500 Description
2.1 Contact Timing Channels
2.2 Analog Voltage Monitoring Channel
2.3 Digital Voltage Monitoring Channel
2.4 Trip/Close Current Monitoring
2.5 Travel Transducer Input Channels
2.6 Breaker Initiate Capability
2.7 Built-in Thermal Printer
2.8 Computer Interface Capabilities
2.9 Timing Shots Storage Capabilities
2.10 Diagnostic Capabilities
2.11 CT-6500 Display and Control Switches
3.0 Test Result Tabulation
3.1 Electrical Measurement Results
3.2 Mechanical Measurement Results
3.3 Analog Voltage Input Results
3.4 Digital Voltage Input Results
3.5 Initiate Current Results
3.6 Slow-Close Test Results
4.0 Test Result Graphics
4.1 Thermal Printer Graphic Printout
5.0 CT-6500 Controls and Display
6.0 CT-6500 Analyzer Specifications
7.0 CT-6500 Special Features
7.1 CT-6500 Supplied Cables
7.2 CT-6500 Operating Voltages
7.3 CT-6500 Main Power Fuse
7.4 CT-6500 Printer and Printer Paper
7.5 CT-6500 Printer Paper Control
7.6 Replacing CT-6500 Thermal Paper
7.7 CT-6500 LCD Contrast Control
8.0 Test Hook-up Connections
8.1 Contact Cable Hookup
8.2 Initiate Cable Hookup
8.3 Analog Voltage Monitor Hookup
8.4 Digital Voltage Monitor Hookup
8.5 External Trigger Input
8.6 Transducer Connection
9.0 OPERATING PROCEDURES
9.1 Timing a Circuit Breaker
9.1.1 Timing an OPEN Operation With No Insertion Resistors
9.1.2 Timing an OPEN Operation With Insertion Resistors
9.1.3 Timing CLOSE-OPEN Operation Using Contact Channel #1
9.1.4 Timing OPEN-CLOSE-OPEN Operation
9.2 Get Tabulated Timing Results Using the Thermal Printer
Figure 1.0 CT-6500 Control Panel
Figure 2.0 Contact Cable Connection
Figure 3.0 Series Contact Cable Connection
Figure 4.0 DC Trip and DC Close, Initiate Circuit Cable Hook-Up
Figure 5.0 DC Trip and AC Close, Initiate Circuit Cable Hook-Up
Figure 6.0 Voltage Monitoring Cable Hook-Up
Figure 7.0 External Trigger Cable Hook-Up
Figure 8.0 Transducer Connection
Figure 9.0 CT-6500 Operating Steps
Figure 10.0 Typical Tabulated Printout of an Open Operation From the Thermal Printer
Figure 11.0 Typical Graphic Result From the Thermal Printer
Figure 12.0 Expansion Graph From 0 to 200ms From the Thermal Printer
Figure 13.0 Graphical Interpretation of an Open Timing Shot
Figure 14.0 Graphical Interpretation of a Close Timing Shot
Figure 15.0 Graphical Interpretations of an Open-Close and a Close-Open Timing Shots
Figure 16.0 Printout of the Timing Shot Directory From the Thermal Printer
Figure 17.0 Typical Slow-Close Test Report
APPENDIX A
APPENDIX B
APPENDIX C
APPENDIX D
APPENDIX E
APPENDIX F
ITE Circuit Breaker model 14.4K Timing Chart
CLOSE-OPEN Timing Chart for ITE Circuit Breaker Model 14.4K
CLOSE-OPEN Tabulated Report for ITE Circuit Breaker Model 14.4K
OPEN-CLOSE Timing Chart for ITE Circuit Breaker Model 14.4K
OPEN-CLOSE Tabulated Report for ITE Circuit Breaker Model 14.4K
The CT-6500 is a microprocessor-based, digital time travel, circuit breaker analyzer. The CT6500 can fully analyze a utility circuit breaker’s performance by measuring: the contact time,
stroke, velocity, over-travel, bounce-back and contact wipe.
The contact motion analysis includes: Open, Close, Open-Close, Close-Open and OpenClose-Open operations. A timing window is selectable between one second, ten second and
twenty second periods. The ten and twenty second windows allow timing of long events such as
circuit switcher contacts.
The CT-6500 is available with the following configurations:
CT-6500-3:
n
Three Contact-Input channels
n
Three Digital Travel Transducer Input channels
n
One Analog Voltage Monitor Input channel
n
One Digital Voltage Monitor Input channel
n
One Trip/Close Current Monitor channel
CT-6500-6:
n
Six Contact-Input channels
n
Three Digital Travel Transducer Input channels
n
One Analog Voltage Monitor Input channel
n
One Digital Voltage Monitor Input channel
n
One Trip/Close Current Monitor channel
CT-6500-12:
n
Twelve Contact-Input channels
n
Three Digital Travel Transducer Input channels
n
One Analog Voltage Monitor Input channel
n
One Digital Voltage Monitor Input channel
n
One Trip/Close Current Monitor channel
There are two different modes of operation for the CT-6500 which are Stand Alone Mode and
Computer Control Mode. The manual will focus on the Stand Alone Mode. The Computer Control
Mode is covered under the CT-6500/7000/7500/DIGITMR PC software manual.
2.0 CT-6500 Description
The CT-6500 applies a test voltage of 35 Vdc to each of the contact channels thus allowing an
analog to digital converter (A/D) to determine if a close, an open or an insertion resistor was the
state of contact. The CT-6500 records into the memory 10,000 readings from the A/Ds and the
transducer position counters. The contact time, circuit breaker stroke and velocity is then derived
from the data that was stored in the memory.
The CT-6500 uses an up-down counter to sense the breaker’s transducer reading. The CT6500 travel transducer employs optical encoders to send quadrature signals to the CT-6500’s
counters. With the use of digital transducers and counters, the need to set up or calibrate the
transducers is eliminated.
A built-in, initiate circuit allows the user to operate the circuit breakers. Since the solid-state
circuit is controlled by a microprocessor, the CT-6500 can perform multiple contact operations
with ease. The initiate circuit is fuse protected for trip and close operations. The user is required
to hold the “ARM” switch during a test to complete the initiate circuit as a safety feature.
Page 9
CT-6500 Operating Instructions
The CT-6500 can also store up to 100 breaker timing test records into the FLASH EEPROM.
Stored timing records can be recalled, printed or transferred to a personal computer.
2.1 Contact Timing Channels
A breaker's interruption of contacts is timed with the dry-contact input channels. Each channel
can detect the main contacts and the insertion resistor contact times in milliseconds and cycles.
NOTE
The CT-6500 can detect insertion resistors ranging from 10 to 7,000 Ohms.
Resistances over 7,000 Ohms are detected as an open contact.
2.2 Analog Voltage Monitoring Channel
One analog voltage, input channel, “V1” is dedicated to monitoring the breaker's DC power
supply or coil voltages from 0 to 255 Vdc or peak Vac.
NOTE
Input voltage ranges from 0 to 300 Vdc or peak Vac. Reading ranges from 0 to 255 Vdc.
2.3 Digital Voltage Monitoring Channel
One digital voltage, input channel, “V2” monitors the status voltage as “ON” or “OFF.” Voltages
from 30 to 255 Vdc is considered as “ON” status. Voltages less than 30 Vdc is considered as
“OFF” status.
2.4 Trip/Close Current Monitoring
A built-in, hall-effect, current sensor records the trip and close coil current levels and duration.
The coil current waveform can be graphically plotted onto a printout. The current reading is also
printed in the tabulated report.
2.5 Travel Transducer Input Channels
Each CT-6500 has one digital transducer, input channel. The CT-6500 will interface with a
linear, a rotary and other special transducers developed by Vanguard Instruments Company,
Incorporated. Please refer to Appendix F for more details.
2.6 Breaker Initiate Capability
A built-in, solid-state, initiate device allows the user to operate a breaker from the CT-6500.
Operational modes include: Open, Close, Open-Close, Close-Open and Open-Close-Open. The
multiple operations of: Open-Close, Close-Open and Open-Close-Open can be initiated with a
programmable delay time or by sensing the breaker's contact state.
The solid-state switching implemented in the initiate circuitry allows the CT-6500 to switch a
breaker's AC or DC control circuit. Two 5 Ampere, slow-blow fuses protect each trip and close
circuits. An interlock, “ARM” switch also protects the initiate circuit.
2.7 Built-in Thermal Printer
The breaker's contact analysis results can be outputted in both tabular and graphical formats
by a built-in, 4.5 inch wide, thermal printer. Refer to paragraph 7.4 for ordering thermal paper.
2.8 Computer Interface Capabilities
A built-in, RS-232C port permits the CT-6500’s EEPROMs to be interfaced with an IBMcompatible personal computer. A Windows-based Breaker Analysis Software is supplied with
each CT-6500. The software is compatible with Windows 95, 98, Me, 2000, NT and XP. The
Page 10
CT-6500 Operating Instructions
software allows the user to:
n
Remotely time circuit breakers from a personal computer.
n
Retrieve timing shots stored in the CT-6500.
n
2.9 Timing Shots Storage Capabilities
store timing-shot data. Unlike other media, EEPROMs are immune to temperature, shock and
humidity. Stored shots can be recalled to reanalyze the test data, to reprint test reports or to
transfer data to a personal computer for record keeping. Up to 100 timing shots can be stored in
the EEPROMs. The number of shots stored in the EEPROMs may vary depending upon the size
of the shot records.
2.10 Diagnostic Capabilities
electronics. Self testing of the contact cable hook-up and transducers permits the user to examine
the CT-6500‘s components whenever verification is required.
2.11 CT-6500 Display and Control Switches
nameplate data such as: the substation name, breaker model and other descriptions. A 4-line by
20-character LCD readout displays user messages and menus. The LCD is backlit to allow
messages can be viewed in low light conditions.
Recall timing shots from a hard drive for reanalysis at an office PC.
The CT-6500 uses Electrically Erasable Programmable Read-Only-Memory (EEPROM) to
The CT-6500 is designed with self diagnostic capability to check the integrity of the
An alphanumeric keypad enables the user to operate the CT-6500 and to enter the breaker’s
3.0 Test Result Tabulation
3.1 Electrical Measurement Results
Under the Time Travel Mode, each CT-6500 contact channel provides the following test
results:
n
Contact Close time
n
Contact Open time
n
Insertion Resistor Contact Open and Close times
n
Contact Bounce time
n
Resistor On time
n
Contact Spread time
Page 11
CT-6500 Operating Instructions
NOTE
The CT-6500 can detect insertion resistors ranging from 10 to 7,000 Ohms.
Resistances over 7,000 Ohms are detected as an open contact.
3.2 Mechanical Measurement Results
Under the Time Travel Mode the digital, transducer channel provides the following test results:
n
Breaker stroke
n
Over travel
n
Bounce back
n
Contact wipe
n
Contact velocity
Breaker contact speed calculations are based upon a contact's travel distance ove r a period
of time, which is defined by the manufacturer's specifications.
3.3 Analog Voltage Input Results
The analog voltage, input channel, “V1” measures the breaker's DC control voltage during an
operation. Printed voltage readings include nominal voltage, when the supply voltage has no load;
and minimum voltage, when the supply voltage is under load or when a coil is energized.
The “V1” connection allows the user to monitor the DC power supply’s voltage fluctuations during
a breaker operation. The feature is effective in detecting the breaker’s power supply problem,
which normally can not be seen by using a voltmeter.
NOTE
Voltage readings can range from 1 to 255 Vdc.
3.4 Digital Voltage Input Results
The digital voltage, input channel, “V2” monit ors the voltage status as “ON” or “OFF” conditions
and graphs the result. A voltage level above 30 Vdc is considered as the “ON” state. The input
channel is dedicated to monitor the breaker’s auxiliary switch action during a breaker operation.
NOTE
Input voltage ranges from 1 to 300 Vac/dc.
3.5 Initiate Current Results
The CT-6500 not only plots the trip or close current waveforms, but also prints the steady-state
current readings of the trip and close coils during an operation. A typical circuit breaker timing
report is shown on Figure 10.0.
Page 12
CT-6500 Operating Instructions
3.6 Slow-Close Test Results
A Slow-Close test determines the contact touch distance and penetration by using the travel
transducer and dry contact channels.
4.0 Test Result Graphics
4.1 Thermal Printer Graphic Printout
A 4.5 inch wide, built-in, thermal printer can output graphic waveforms of the contact channels,
travel curves and actuator-coil currents. Using the Zoom Graphics Mode, the user can enlarge the
graphical outputs by specifying the timing zone. Typical graphical results are shown in Figures
11.0 and12.0.
5.0 CT-6500 Controls and Display
Before using the CT-6500, users should become familiar with all of the controls and display
indications. The keypad and display are used to operate the CT-6500. Figure 1.0 represents the
control panel and the numbered lines pointing to each control and indicator refer to Table 1.0,
which describes the function of each control and indicator.
Figure 1.0 CT-6500 Control Panel
Page 13
CT-6500 Operating Instructions
Table 1.0 CT-6500 Controls and Displays
Fig. 1.0
Index no.
1
2
3
4
5
6
7
PANEL MARKINGFUNCTIONAL DESCRIPTION
CONTACT INPUT
Female connector for the 3 contact channels.
(1 –12)
30-300V
V1 & V2
VOLTAGE INPUT
30-300V
TRIGGER
3-pin connectors. Each input is a voltage detector for
the timing voltages of the trip or close coil switching
during the active period. Voltage detection level ranges
from 30 to 300 Vdc or peak.
3-pin connector triggers timing functions. Voltage levels
ranging from 30 to 300 Vac, dc or peak.
VOLTAGE INPUT
120/240Vac, 2A, 50-60Hz
Fuse: 250Vac, 5A Fast-Blow
GROUND
T1, T2, T3
TRANSDUCER INPUT
(Printer; No panel marking)
3-wire power plug. 3 Ampere, AC fuses. The ON/OFF
switch is a 2-pole rocker.
Safety, ground terminal. 5/16-18 thread stud, with wing
nut.
16-pin connectors. Each input is a travel encoder input
used for contact, motion data.
Thermal printer. Microprocessor controlled printer that
uses specially treated, 4.5 inch wide paper.
8
9
10
11
12
13
14
1-9, 0, ENTER, START,
STOP, CLEAR,
PAPER LCD,
↑
PAPER LCD
↓
“PUSH” TO ARM
(Display; no panel marking)
CLOSE
250V, 5A FAST-BLOW
OPEN
250V, 5A FAST-BLOW
INITIATE
RS-232C
16 button keypad. The keys are momentary-contact,
pushbutton switches. Allows users to make menu
selections, enter alphanumeric data, adjust the LCD
contrast and reposition the printer paper.
Spring-loaded, pushbutton switch. Press and hold to
complete the Trip or Close circuits for breaker tests.
4-line by 20-character, backlit LCD. Displays menus,
options, prompts and test result data.
Close circuit fuse: 5 Ampere, 250V, Fast-Blow.
Open circuit fuse: 5 Ampere, 250V, Fast-Blow.
4-pin connector used for the switching circuit for
operating the circuit breaker under test.
9-pin connector for serial computer interface.
Page 14
CT-6500 Operating Instructions
6.0 CT-6500 Analyzer Specifications
CONTACT TIMINGOpen, Close, Open-Close, Close-Open, and Open-Close-Open
SIZE & WEIGHT16d by 14w by 11h (inches), less than 32 pounds
OPERATING POWER2 Ampere, 90-120 Vac / 200-240 Vac 50/60 Hz
TIMING WINDOWSelectable between: 1, 10, or 20 second
RESOLUTION±100 microseconds at 1 second duration
±1.0 millisecond at 10 second duration
±2.0 millisecond at 20 second duration
DRY-CONTACT INPUT3 or 6 or 12 contact channels. All contact inputs are grounded until testing
is started. Each contact detects main and insertion resistor contacts.
CONTACT RESISTANCECLOSED: less than 20 Ohms
OPEN: greater than 10,000 Ohms
INSERTION RESISTANCERanges from 10 to 7,000 Ohms
TRIGGER INPUTOpen/Close: 30 to 300 Vdc, peak Vac
VOLTAGE INPUTS2 voltage inputs, sensitivity ranging from 1.0 to 300 Vdc, peak Vac
Analog voltage recording ranges from 1.0 to 255 Vdc
CURRENT-SENSOR INPUT1 non-contact, hall-effect sensor ranging from 0.2 to 20 Amperes, DC to 5 kHz
BREAKER INITIATEInitiate Open, Close, Open-Close, Close-Open, Open-Close-Open
TRAVEL TRANSDUCER3 travel-transducer channels, linear motion from 0.0 to 60.0 inches (±0.01) inch
INPUTRotary ranges from 0 to 360o (± 0.36º).
BREAKER SLOW-CLOSE
TESTMeasures the contact point distance.
BREAKER ANALYSISWindows 95, 98, 2000, NT, XP compatible.
SOFTWARE (included)The analysis software can be installed on a IBM-compatible computer for graphical
display, numerical reports and database utility for office use.
COMPUTER INTERFACERS-232C Port
DISPLAYBacklit LCD screen, 4-lines by 20-characters, sunlight viewable
HARD-COPY PRINTOUTContact travel waveforms and tabulated results printout on 4.5 inch thermal paper.
CARRYING CASE (optional)Hard shipping case for CT-6500 and cables.
Hard shipping case for Travel Transducers.
WARRANTYOne year warranty on parts and labor. Post-warranty service contracts available.
Page 15
7.0 CT-6500 Special Features
7.1 CT-6500 Supplied Cables
ITEMDESCRIPTIONQTY
1GND Cable1
2Power Cord1
3Contact Cable3 or 6 or 12
4Contact Extension Cable3 or 6 or 12
5Transducer cable1
6Voltage & Trigger Leads3
7Voltage & Trigger Extension cables3
8Initiate Lead1
9Initiate Extension Cable1
10RS-232C Cable1
CT-6500 Operating Instructions
Table 2.0 CT-6500 Cable set
Page 16
CT-6500 Operating Instructions
7.2 CT-6500 Operating Voltages
The CT-6500 operating voltage is selectable between 110/120 Vac, 50/60 Hz or 220/240
Vac, 50/60 Hz. Voltage selection is set by the JP1 connector on the Power Supply board and the
JP3 connector on the Initiate board of the CT-6500. The jumper settings for the connectors are
shown in Table 3.0.
Table 3.0 Voltage Selection Jumper Setting
VOLTAGE SELECTIONCONNECTOR PIN
110-120 VacPin 1& 2, 3 & 4
220-240 VacPin 2 & 3
An initiate circuit relay with the corresponding operating voltage must also be installed in the
CT-6500 Initiate board.
NOTE
The factory sets the operating voltage.
7.3 CT-6500 Main Power Fuse
The CT-6500 uses an AC input module that contains the AC receptacle, power switch and
protective fuses. The 3 Ampere replacement fuses should be 20mm, 250Vac, fast-blow types.
NOTE
The OPEN and CLOSE initiate are 5 Ampere fuses that should be 3AG, 250Vac,
fast-blow types.
7.4 CT-6500 Printer and Printer Paper
The built-in, thermal printer uses 4.5 inch wide, thermal paper for printing test results. To
maintain the highest, quality printing and to avoid paper jamming, it is highly recommended that
the thermal paper be supplied by the factory. Additional paper can be ordered from either of the
two sources listed below:
Vanguard Instruments Co, Inc.
1710 Grevillea Court
Ontario, CA 91761
Tel: 909-923-9390
Fax: 909-923-9391
Part Number: TP-4 Paper
BG Instrument Co.
13607 E. Trent Avenue
Spokane, WA 99216
Tel: 509-893-9881
Fax: 509-893-9803
Part Number: TP-4 paper
Page 17
CT-6500 Operating Instructions
7.5 CT-6500 Printer Paper Control
To advance the paper from the printer, press and release the “↑ PAPER LCD” button. To
retract the thermal paper from the printer, press and release the “↓ PAPER LCD” button.
7.6 Replacing CT-6500 Thermal Paper
The roll of thermal paper resides inside a pocket underneath the printer cover. To replace the
paper, follow the steps below:
n Remove the printer cover.
n Remove the leftover thermal paper roll from the paper holder.
n Unroll the new thermal paper.
n Feed the thermal paper into the slot between the paper pocket and the rubber
roller. The printer will automatically pull the paper under the thermal head.
n Place the paper roll into the paper holder.
n Lift the thermal head and align the thermal paper if necessary.
n Replace the printer cover back.
NOTE
The thermal paper will show a red stripe in the margin to indicate that the roll is
about to run out of paper.
7.7 CT-6500 LCD Contrast Control
To darken the LCD screen, press and hold the “↑ PAPER LCD” button, while to decrease the
contrast of the LCD screen, press and hold the “↓ PAPER LCD” until the desired contrast is
reached.
Page 18
CT-6500 Operating Instructions
8.0 Test Hook-up Connections
8.1 Contact Cable Hookup
A typical, contact cable connection to a circuit breaker is shown in Figure 2.0. Red clips are
connected to phase A, B and C of the breaker’s bushings. The black clips are connected on the
grounded or common, side of the bushings. For circuit breakers with series contacts, connect the
contact cables as shown in Figure 3.0.
NOTE
It is advisable to ground one side of the contacts for most testing purposes. If a breaker
is floating or ungrounded, ensure that the contact channel inputs are protected against
static discharge.
Figure 2.0 Contact Cable Connection
Page 19
CT-6500 Operating Instructions
Figure 3.0 Series Contact Cable Connection
Page 20
CT-6500 Operating Instructions
8.2 Initiate Cable Hookup
The CT-6500 will trip or close breakers through a solid-state device, which will operate on any
AC or DC control voltage ranging from 10 to 300 Volts. Both the trip and close circuits are
protected by 5 Ampere fuses.
A typical DC trip and DC close, control circuit test hookup is shown in Figure 4.0.
A typical DC trip and AC close, control circuit test hookup is shown in Figure 5.0.
Figure 4.0 DC Trip and DC Close, Initiate Circuit Cable Hook-Up
Figure 5.0 DC Trip and AC Close, Initiate Circuit Cable Hook-Up
Page 21
CT-6500 Operating Instructions
8.3 Analog Voltage Monitor Hookup
The analog, voltage input, “V1” permits the user to monitor a breaker's DC control voltage
during an operation.The analog, voltage input will record the nominal DC voltage at no load and
the minimum DC voltage while the Trip or Close coil is energized.
The nominal and minimal voltage readings will be printed on a tabulated report. Analog
waveforms will also be plotted in a graphical format. Thus, the user is able to see the breaker's
DC control voltage "dip" under load conditions. Problems, such as a poor connection or an
excessive voltage drop, during operation can be easily detected.
A typical voltage monitoring hook up scheme is shown on Figure 6.0.
NOTE
The maximum voltage that can be recorded is set at 255 Vdc.
Figure 6.0 Voltage Monitoring Cable Hook-Up
8.4 Digital Voltage Monitor Hookup
The digital, voltage input channel, “V2” permits the user to monitor the voltage status as “ON”
or “OFF” states. The voltage “ON” or “OFF” states will be plotted on the graphical report. A typical
hook up is shown in Figure 6.0.
Page 22
CT-6500 Operating Instructions
8.5 External Trigger Input
The External Trigger Mode enables the user to start recording data when the CT-6500 senses
a voltage. A typical application for the External Trigger Mode is to time a circuit breaker in a close
operation and to start timing only when the close coil is energized, thus bypassing the 52X relay
delay time.
Since the 52X relay carries the close coil current, the user will need to connect the CT-6500’s
initiate cable to the close terminal shown in Figure 4.0. The CT-6500 will energize the 52X relay
to start the close operation, which will then start the timing when the CT-6500 senses the voltage
across the closing coil. See Figure 7.0 for a typical test hookup. Another application for external
trigger is to start timing the breaker when the user trips or closes the breaker remotely.
NOTE
Minimum trigger voltage is set for 30 Vac/dc. Maximum, continuous voltage is limited at
300 Vac/dc. Different trigger voltages can be set at the factory, based upon specific
requests.
The CT-6500 will start looking for the external trigger voltage when the message,
“AWAITING TRIGGER…” is shown on the LCD screen. The external trigger voltage
needs to be sensed by the CT-6500 within 30 seconds after the initiate sequence has
begun. The CT-6500 will return to the main menu if no voltage is sensed.
Figure 7.0 External Trigger Cable Hook-Up
Page 23
CT-6500 Operating Instructions
8.6 Transducer Connection
A typical transducer connection is shown on Figure 8.0. See Appendix F for more transducer
connections.
Figure 8.0 Transducer Connection
Page 24
CT-6500 Operating Instructions
HOOKUP CT-6500
APPLY POWER
TIMER BREAKER
GET RESULTS
9.0 OPERATING PROCEDURES
The main steps to time a circuit breaker are listed in Figure 9.0.
.
1. GROUND THE CT-6500 (See NOTE)
2. CONNECT CT-6500 CABLES TO BREAKER
3. INSTALL TRANSDUCER WITH CABLE
1. TURN THE CT-6500 ON
2. PERFORM SELF TESTS: HOOK-UP TEST,
CABLE TEST, IF NECESSARY
1. SELECT THE CT-6500 TEST
2. OPERATE THE BREAKER
1. READ OR PRINT THE TABULATED RESULTS
2. PRINT THE GRAPHICAL RESULTS
3. SAVE THE TIMING SHOT
Figure 9.0 CT-6500 Operating Steps
NOTE
To reduce the possibility of damaging the CT-6500 due to static discharge in the
high voltage substations, it is recommend for the contact channels, ground one
side of the breaker’s bushings.
Page 25
CT-6500 Operating Instructions
9.1 Timing a Circuit Breaker
The CT-6500 will initiate the breaker operation and do a timing test on the following
operations:
n
OPEN
n
CLOSE
n
OPEN-CLOSE
n
CLOSE-OPEN
n
OPEN-CLOSE-OPEN
NOTE
1. The CT-6500 can start the OPEN-CLOSE operations without a delay or by using a
programmable delay between the OPEN and CLOSE commands.
2. The CLOSE-OPEN can be started by the CT-6500, using several options.
n
Contact #1 Close
The CT-6500 can initiate a CLOSE command and then an OPEN command after
detecting the breaker’s contact was closed. The CT-6500 detects that the
breaker’s contact was closed through contact channel #1. The selection is
recommended for the CLOSE-OPEN operation since it truly represents when the
circuit breaker closed and then opened.
n
Set DELAY
The CT-6500 can initiate a CLOSE command and then an OPEN command after
a programmable delay that can be set in milliseconds.
n
No DELAY
The CT-6500 can initiate a CLOSE command and then an OPEN command
without any delay. Since the circuit breaker is in the open state, the circuit
breaker’s 52B contact allows the close coil to be energized, which can start the
close command. When the circuit breaker is making the transition from an open
state to a close state, the 52A contact will close allowing the breaker to initiate the
open command.
3. The OPEN-CLOSE-OPEN operations can be initiated by the CT-6500, by using a
programmable delay between each of the operations, where the delays can be set
between the OPEN to CLOSE and between the CLOSE to OPEN commands.
Page 26
CT-6500 Operating Instructions
9.1.1 Timing an OPEN Operation With No Insertion Resistors
Table 4.0 Open Operation With No Insertion Resistors
STEP
1READY TIMER FOR BREAKER OPERATION.PRESS #1 KEY.INSERTION RESISTOR?
2SELECT NO INSERTION RESISTOR.PRESS #1 KEY.TIMING WINDOWS:
TEST IN PROGRESS
Hold "ARM" Until
Test complete.
(Up to 15 seconds)
7OBSERVE BREAKER OPERATED.
ANALYZER IS READY TO OUTPUT RESULTS.
NONE.1.TIME BREAKER
2.GET RESULT
3.SET-UP
4.DIAGNOSTIC
NOTE
One-second timing windows are used for breaker timing. The 10 and 20 second
timing windows are used for circuit-switcher timing.
Page 27
CT-6500 Operating Instructions
9.1.2 Timing an OPEN Operation With Insertion Resistors
The CT-6500 can time breakers with insertion resistors. The insertion resistor can
range from 10 to 7,000 Ohms. Any insertion resistor more than 7,000 Ohms is detected as
an open circuit. The timing window results will show the main contact time and the insertion
resistor contact time. Graphic reports will show the main contact and the resistor contact
activities on each of the channels.
Table 5.0 Open Operation With Insertion Resistor
STEPOPERATIONACTIONDISPLAY
1READY TIMER FOR BREAKER OPERATION.PRESS #1 KEY.INSERTION RESISTOR?
8ANALYZER IS READY TO OUTPUT RESULTS.NONE.1.TIME BREAKER
TEST IN PROGRESS
Hold "ARM" Until
Test complete.
(Up to 15 seconds)
2.GET RESULT
3.SET-UP
4.DIAGNOSTIC
NOTE
The user can set the CT-6500 to print tabulated and graphical reports automatically
after it completes a test. See Paragraph 9.17 for the automatic print setting.
Page 28
CT-6500 Operating Instructions
9.1.3 Timing CLOSE-OPEN Operation Using Contact Channel #1
The CLOSE-OPEN operation of the breaker simulates a condition where a breaker is
closed on a fault. There are 3 choices for the user to setup the CLOSE-OPEN operation:
1. Contact #1 CLOSE
Open operation is initiated after contact channel # 1 is closed. Refer to
Table 6.0 on the next page.
2. Set DELAY
The user can set a delay from 10 to 500 ms between a CLOSE command
to the OPEN command.
3. No DELAY
Both the CLOSE and OPEN commands are initiated by the CT-6500
simultaneously. The OPEN coil is energized when the Open auxiliary switch
makes.
NOTE
If the Contact #1 CLOSE choice is used, the CT-6500 will first initiate a CLOSE
command and then send an OPEN command only when it detects that the main
contact #1 is closed. The mode truly simulates when the breaker is closing on a fault
condition in the field.
Page 29
CT-6500 Operating Instructions
Table 6.0 Close-Open Operation Using Contact Channel #1
STEPOPERATIONACTIONDISPLAY
1READY TIMER FOR BREAKER OPERATION.PRESS #1 KEY.INSERTION RESISTOR?
1.NO
2.YES
2SELECT NO INSERTION RESISTOR.PRESS #1 KEY.TIMING WINDOWS:
8ANALYZER IS READY TO OUTPUT RESULTS.NONE.1.TIME BREAKER
TEST IN PROGRESS
Hold "ARM" Until
Test complete.
(Up to 15 seconds)
2.GET RESULT
3.SET-UP
4.DIAGNOSTIC
NOTE
1. Users can program a delay from 10 to 500 ms between the CLOSE and
OPEN commands. When a delay is used in the operation, it may not
represent a true breaker operating condition.
2. Users can also program in no delay for the operation in which case, the
CLOSE and OPEN commands are initiated at the same time by the CT-
6500.
Page 30
CT-6500 Operating Instructions
9.1.4 Timing OPEN-CLOSE-OPEN Operation
The OPEN-CLOSE-OPEN operation requires the user to enter two time-delays
between the circuit breaker operations. The time delays are in millisecond intervals. The
first delay is from the first OPEN command to the CLOSE command. The second delay is
from the CLOSE command to the second OPEN command. Refer to Table 7.0 for setting
up the OPEN-CLOSE-OPEN operation.
Table 7.0 Open-Close-Open Operation Using Delay
STEPOPERATIONACTIONDISPLAY
1READY TIMER FOR BREAKER OPERATION.PRESS #1 KEY.INSERTION RESISTOR?
1.NO
2.YES
2SELECT NO INSERTION RESISTOR.PRESS #1 KEY.TIMING WINDOWS:
5SELECT OPEN-CLOSE-OPEN OPERATION.PRESS #5 KEY.O-C Delay in mS:
(10 – 350)
mSec
ENTER when done
6SELECT DELAY BETWEEN OPEN-CLOSE
OPERATION.
7SELECT DELAY BETWEEN CLOSE-OPEN
OPERATION.
8INITIATE O-C-O COMMAND.HOLD THE "ARM"
9ANALYZER IS READY TO OUTPUT RESULTS.NONE.1.TIME BREAKER
ENTER DELAY USING 09 KEYS, PRESS THE
“ENTER” KEY TO
CONFIRM.
ENTER DELAY USING 09 KEYS, PRESS THE
“ENTER” KEY TO
CONFIRM.
SWITCH AND
PRESS THE "START"
KEY.
C-O Delay in mS:
(10 – 350)
mSec
ENTER when done
OPEN-CLOSE-OPEN TIMING
Hold "ARM" Switch,
Then "START".
"STOP" to ABORT
TEST IN PROGRESS
Hold "ARM" Until
Test complete.
(Up to 15 seconds)
2.GET RESULT
3.SET-UP
4.DIAGNOSTIC
Page 31
CT-6500 Operating Instructions
9.2 Get Tabulated Timing Results Using the Thermal Printer
The circuit breaker timing results can be printed on the thermal printer by using the steps listed in
Table 8.0.
A typical circuit breaker timing result is shown in Figure 10.0.
Table 8.0 Get Tabulated Results
STEPOPERATIONACTIONDISPLAY
1GET TIMING RESULTS.PRESS #2 KEY.1.PRINT TEST RESULTS
Figure 10.0 Typical Tabulated Printout of an Open Operation From the Thermal Printer
Page 33
CT-6500 Operating Instructions
9.2.1 Tabulated Results Interpretation
1. Timing Record is time and date stamped by the CT-6500.
2. Timing record header information (Company, Substation name, Circuit, etc) is also saved
with test record.
3. Timing test type (OPEN, CLOSE, O-C, C-O, O-C-O) is identified. An OPEN timing shot is
shown in figure 10.0.
4. Contact channel #1 time is shown in both milliseconds and cycles. From Figure 10.0,
contact channel #1 time was 34.20 ms or 2.05 cycles.
5. Contact channel #1 bounce duration was 0.20 ms.
6. Contact channel #1 wipe was measured as 0.72 inches.
7. The slowest contact and fastest contact differential time is shown as contact delta, 3.00 ms.
8. Breaker contact stroke was measured as 7.02 inches.
9. Contact velocity calculation was 8.55 feet per second.
10. Contact over-travel distance was measured as 0.01 inches.
11. Contact bounce-back distance was measured 0.06 inches.
12. Contact velocity calculation was from the two analysis points:
Analysis point # 1 was 1.00 inch from the fully closed position.
Analysis point # 2 was 5.00 inches from the fully closed position.
13. The DC power supply was monitored during the test. The nominal voltage was 47 Volts
and the minimum voltage was 47 Volts.
14. Initiate current was 5.7 Amperes.
15. Timing shot duration was one second.
16. Trigger mode was internal therefore the timing window starts at the same time when the
CT-6500 energized the circuit breaker.
17. There was no insertion resistor in the test, thus no insertion resistor time was measured.
Page 34
CT-6500 Operating Instructions
9.3 Get Graphic Timing Results Using the Thermal Printer
Selecting the “PLOT FULL CHART” command will plot the timing chart as follows:
Timing chart from 0 to 1000 ms with one second window and 50 ms time markers.
•
Timing chart from 0 to 10 seconds with 10 second window and 500 ms time markers.
•
Timing chart from 0 to 20 seconds with 20 second window and one second time markers.
•
Table 9.0 Plot Chart and Tabulated Report
STEPOPERATIONACTIONDISPLAY
1GET TIMING RESULTS.PRESS #2 KEY.1. PRINT TEST RESULTS
2. PLOT FULL CHART
3. PLOT EXPANSION
4. PLOT 0-200 MS
2PLOT FULL CHART.PRESS #2 KEY.PLEASE WAIT
PLOTTING GRAPH
3RETURN TO MAIN MENU AFTER PRINT
CHART.
NO ACTION.1. TIME BRKR
2. GET RSLT
3. SET UP
4. DIAGNOSTIC
NOTE
1. Plot Expansion, which is Selection #3, in Step 1, allows the user to expand the graphic
results in 100 ms increments.
2. Selecting “PLOT 0-200 MS” will automatically plot the timing chart from 0 to 200
milliseconds in the expansion mode with 10 ms timing markers, which can be seen in
Figure 12.0.
3. Graphical result interpretations are shown in Figures 13.0, 14.0 and 15.0.
Page 35
CT-6500 Operating Instructions
Contact Trace
Travel Trace
Initiate Current
V1
Analog Voltage Channel
Digital Voltage Channel V2
Figure 11.0 Typical Graphic Result From the Thermal Printer
Page 36
CT-6500 Operating Instructions
Analysis Point #1
Analysis Point #2
Figure 12.0 Expansion Graph From 0 to 200ms From the Thermal Printer
NOTE
Analysis point # 1 and point #2 are shown on chart.
Page 37
CT-6500 Operating Instructions
Figure 13.0 Graphical Interpretation of an Open Timing Shot
Figure 14.0 Graphical Interpretation of a Close Timing Shot
Page 38
CT-6500 Operating Instructions
Figure 15.0 Graphical Interpretations of an Open-Close and a Close-Open Timing Shots
Page 39
CT-6500 Operating Instructions
9.4 Save Timing Shots in the EEPROM
Use the steps in Table 10.0 to save a timing shot in the FLASH EEPROM.
TEST: CLOSE
DATE: 04/23/03 12:36
"ENTER" TO CONFIRM
4CONFIRM SAVING SHOT.PRESS THE "ENTER"
KEY.
5OBSERVE SHOT BEING SAVED.NONE.SHOT SAVE
6RETURN TO MAIN MENU.PRESS ANY KEY.1. TIME BRKR
SAVE IN PROCESS
PLEASE WAIT
2. GET RSLT
3. SET UP
4. DIAGNOSTIC
NOTE
Timing shot storage capability varies, depending upon the size of the shots.
The CT-6500 will assign an identification number for each of the shots stored in the
EEPROM.
Page 40
CT-6500 Operating Instructions
9.5 Printing Timing Shot Directory Stored in the EEPROM
The user can obtain a timing-shot directory that was stored in the CT-6500’s FLASH
EEPROM by using the following steps in Table 11.0.
Table 11.0 Print Timing Shot Directory
STEPOPERATIONACTIONDISPLAY
1SELECT SETUP MENU.PRESS #3 KEY.1. ANALYSIS POINT
2. MEASUREMENT UNITS
3. SAVE / RESTORE
4. NEXT PAGE
2SELECT SAVE/RESTORE MENU.PRESS #3 KEY.1. SAVE SHOT
2. RESTORE SHOT
3. SHOT DIRECTORY
4. ERASE SHOT
3SELECT SHORT DIRECTORY.PRESS # 3 KEY.1. SHORT DIRECTORY
2. FULL DIRECTORY
"STOP" TO QUIT
4SELECT SHORT DIRECTORY.PRESS #1 KEY.PRINTING ABBREVIATED
DIRECTORY
“STOP” TO QUIT
5RETURN TO MAIN MENU.NO ACTION.1. TIME BRKR
2. GET RSLT
3. SET UP
4. DIAGNOSTIC
NOTE
1. If the "Short Directory" was selected, the CT-6500 will print out the shot
identifications of the last ten timing shots stored in the EEPROM.
2. If the "Full Directory" was selected, the CT-6500 will print out the shot
identifications of all the timing shots stored in the EEPROM.
3. A typical shot directory printout is shown on next page, in Figure 16.0.
Page 41
CT-6500 Operating Instructions
Figure 16.0 Printout of the Timing Shot Directory From the Thermal Printer
Page 42
CT-6500 Operating Instructions
9.6 Recalling a Timing Shot
The following steps in Table 12.0 are used to recall a timing shot stored in the EEPROM to the
working memory. Once a timing shot is recalled, the user can ask for a printout of the test results
from the thermal printer.
Table 12.0 Recalling a Timing Shot
STEPOPERATIONACTIONDISPLAY
1 SELECT SETUP MENU. PRESS #3 KEY.1. ANALYSIS POINT
2. MEASUREMENT UNITS
3. SAVE / RESTORE
4. NEXT PAGE
2 SELECT SAVE/RESTORE SHOT. PRESS # 3 KEY.1. SAVE SHOT
2. RESTORE SHOT
3. SHOT DIRECTORY
4. ERASE SHOT
3SELECT RESTORE SHOT. PRESS #2 KEY.ENTER SHOT NUMBER
4ENTER SHOT NUMBER “1” TO BE
RESTORED.
5 CONFIRM SHOT TO BE RESTORED.PRESS THE "ENTER"
6CONFIRM TEST RESTORED.NONE.RESTORE COMPLETE
7 RETURN TO MAIN MENU. PRESS ANY KEY.1. TIME BRKR
PRESS KEYS 0-9
FOR SHOT ID THEN
PRESS THE "ENTER"
KEY.
KEY.
TO BE RESTORED
XXXX
"ENTER" TO CONFIRM
ENTER SHOT NUMBER
TO BE RESTORED
0001
"ENTER" TO CONFIRM
RESTORING SHOT # 0001
TEST: OPEN
DATE: 03\12\03 09:12
"ENTER" TO CONFIRM
2. GET RSLT
3. SET UP
4. DIAGNOSTICS
Page 43
CT-6500 Operating Instructions
9.7 Deleting a Timing Shot
Users can delete a specific timing shot or all of the timing shots from the CT-6500’s EEPROM
by using the steps described in Table 13.0.
Table 13.0 Deleting a Timing Shot
STEPOPERATIONACTIONDISPLAY
1 SELECT SET UP MENU.PRESS # 3 KEY.1. ANALYSIS POINTS
2. MEASUREMENT UNITS
3. SAVE / RESTORE
4. NEXT PAGE
2SELECT SAVE / RESTORE MENU.PRESS # 3 KEY.1. SAVE SHOT
2. RESTORE SHOT
3. SHOT DIRECTORY
4. ERASE SHOT
3 SELECT ERASE SHOT.PRESS # 4 KEY.1. ERASE SHOT
2. ERASE ALL SHOTS!
4 SELECT ERASE SHOT.PRESS # 1 KEY.ENTER SHOT NUMBER
TO BE ERASED
XXXX
"ENTER" TO CONFIRM
5 ENTER SHOT NUMBER “1” TO BE
ERASED.
6CONFIRM TO ERASE SHOT.PRESS THE "ENTER"
7WAIT FOR SHOT BEING ERASED.NO ACTION.ERASE COMPLETE
8RETURN TO MAIN MENU.PRESS ANY KEY.1. TIME BRKR
PRESS KEYS 0-9 TO
SELECT SHOT
NUMBER, PRESS
THE "ENTER" KEY
TO CONFIRM.
KEY.
ERASE SHOT # 0001
TEST: OPEN
DATE: 03\12\03 09:12
"ENTER" TO CONFIRM
ERASE IN PROCESS
PLEASE WAIT
2. GET RSLT
3. SET UP
4. DIAGNOSTIC
Page 44
CT-6500 Operating Instructions
9.8 Shot Description
The CT-6500 has the capability for users to enter the breaker and other identification
information. The data usually consists of the names of the company, station, circuit and
manufacturer. Other information could be the breaker's model, serial number and the operator's
name. The identification data will print out on the header section of the tabulated report.
If the user saves the timing shot, the identification data will also be saved with the timing shot,
along with the time and date.
The user can input letters of the alphabet by utilizing the alphan umeric keys. To select the letter
"A," the user will need to press key numbered “2,” twice. To select the letter "C," the user will need
to press the key numbered “2,” four times and so on.
To move the cursor forward, press the “UP ARROW” key. To move the cursor backwards, use
the “DOWN ARROW” key. Use the “CLEAR” key to enter a space.
Table 14.0 Entering Shot Identification Header
STEPOPERATIONACTIONDISPLAY
1 SELECT SET UP MENU. PRESS #3 KEY.1. ANALYSIS POINTS
2. MEASUREMENT UNIT
3. SAVE / RESTORE
4. NEXT PAGE
2 SELECT NEXT PAGE. PRESS # 4 KEY.1. SHOT DESCRIPTION
2. NUMBER OF CHANNELS
3. COMPUTER IF
4. SET CLOCK
3 SELECT SHOT DESCRIPTION. PRESS # 1 KEY.ENTER COMPANY NAME
Each CT-6500 has an RS-232C port, where the Breaker Analysis Software package provided
with each CT-6500, enables an IBM-compatible personal computer to communicate with the unit.
The software operating under Windows 95, 98, Me, 2000, NT and XP environments allow the user
to upload timing shots stored in the EEPROM into the computer. From the user's computer, the
user can now reanalyze the breaker’s timing shots and then output the timing reports through an
office printer. Since timing shots are stored in the office computer, users can create a database
of a breaker's timing history.
Follow the steps in Table 15.0 to put the CT-6500 under computer control:
Table 15.0 Selecting or Aborting Computer Control
STEPOPERATIONACTIONDISPLAY
1 SELECT SET UP MENU. PRESS # 3 KEY.1. ANALYSIS POINT
2. MEASUREMENT UNITS
3. SAVE / RESTORE
4. NEXT PAGE
2 SELECT NEXT PAGE. PRESS # 4 KEY.1. SHOT DESCRIPTION
1. An interconnect cable must be run between the CT-6500’s RS-232C port and an
IBM-compatible PC.
2. Refer to the breaker timing software manual to run the unit remotely from an IBMcompatible computer.
3. The CT-6500's RS-232 connector pin layout is in the
chart to the right.
4. The operator is required to put the CT-6500 under the
“Computer ITF Mode” before executing the PC
PIN No.SIGNAL NAME
2Tx
program.
3Rx
5GND
Page 47
CT-6500 Operating Instructions
9.10 Breaker Travel Analysis
The CT-6500’s travel analysis includes the breaker’s stroke, over-travel, bounce-back,
contact-wipe distances and contact velocity calculations.
9.10.1 Breaker Stroke
The CT-6500 uses a digital transducer to measure a breaker's contact stroke, over-travel and
bounce-back. The digital transducer output are 200 counts per linear inch of travel, therefore the
resolution is accurate to about 1/200 inch. The output resolution is ±0.01 inch on the test result
report.
Unlike slide-wire transducers, the CT-6500’s transducer needs no calibration or setup. A user
verifies the transducer’s functionality by selecting a diagnostic test for the transducer, which is
further explained in Paragraph 9.15.
9.10.2 Breaker Over-Travel Distance
Over-travel is the distance the contact moves beyond the resting position. Over-travel is
typically found in the close operation. (See Appendix A for more details).
9.10.3 Breaker Bounce-Back Distance
Bounce-back is the distance the breaker contact moves before the resting position after the
over- travel. Again, bounce-back is typically found in the close operation. (See appendix A for
more details).
9.10.4 Contact Wipe
Contact wipe is the distance measur ed from the close position to the contacts touching or
parting positions. In the close operation, contact wipe is measured from the contacts touching
position to the final close position.
In the open operation, the contact wipe is measured from the close position to the contact
break or parting position.
NOTE
Contact wipe is measured during an operation. The measurement may not be as
accurate as the measurement done using the Slow-Close Mode. It is recommended
that the user use the Slow-Close Test to verify the contact wipe measurement, if
required. Please refer to Paragraph 9.15 for further information on the Slow-Close
Mode.
9.10.5 Breaker Velocity
When used with a travel transducer, the CT-6500 can calculate the breaker contact velocity
through the arc zone. Users will need to program the calculation points or analysis points on the
travel curve for the unit to calculate the contact velocity. Analysis point selections and setup are
discussed in the following paragraphs.
9.10.6 Analysis Point Selections
Analysis points are used to calculate the average contact speed through the contact's arc
zone. The analysis points are usually specified by the breaker’s manufacturers. The analysis
points can programmed into the CT-6500 by the user. The CT-6500 will store the two setup
points for calculating velocity one set each for the open and another set for the close operations.
These setups remain in the CT-6500’s memory until it is changed by the user.
Page 48
CT-6500 Operating Instructions
9.10.7 Analysis Point No.1 (AP1)
Three selections are available to the user for setting analysis point No. 1:
1. PERCENTAGE OF STRK
2. DISTANCE FROM CLOSE
3. CONTACT #1
a. Percentage of Stroke
Percentage of stroke is the distance based upon the percentage of the total breaker’s
stroke distance. The distance is always measured from the starting point at the fully closed
position of the breaker contacts. See appendix A for more detail.
b. Distance From Close
Distance from Close range is selectable from 00.0 inch to 99.99 inches or from 0.0
centimeter to 99.90 centimeters. Again, the distance is referenced from the contact's
closed position. See Appendix A for more detail.
c. Contact Point #1
Contact point is the distance from the contact's closed position to the point where it is in
transition from the close-to-open or the open-to-close position. Contact channel #1 will be
used for the selection.
9.10.8 Analysis Point No. 2 (AP2)
There are three selections for analysis point 2:
1. PERCENTAGE OF STRK
2. DISTANCE FROM CLOSE
3. CONTACT +/- TIME
a. See Paragraph 9.10.7.a for “PERCENTAGE OF STROKE” description.
b. See Paragraph 9.10.7.b for “DISTANCE FROM CLOSE” description.
c. “CONTACT +/- TIME”, is available for both OPEN and CLOSE operation under analysis
point #2 only. For “CONTACT + TIME”, the user enters the millisecond time after the contact
channel #1 made the transition from OPEN to CLOSE or CLOSE to OPEN to define the
Analysis Point No. 2.
For “CONTACT – TIME”, the user enters the millisecond time before the contact channel #1
makes the transition from OPEN to CLOSE or CLOSE to OPEN to define the Analysis
Point No. 2.
Page 49
CT-6500 Operating Instructions
NOTES
1. Average velocity through the arc zone is calculated by using the following formula:
V
= Distance
ave
2. The breaker contact velocity can be recalculated based upon the data stored
inside the memory after any new analysis points were selected. The user does not
need to operate the breaker again to acquire new contact velocity data after
changing the analysis points because the new velocity is then calculated from the
travel data stored in memory from the last operation.
3. For complex velocity calculations, use the CT-6500 the PC software.
÷
Time
Page 50
CT-6500 Operating Instructions
9.11 Set-Up Open Analysis Points
Table 16.0 Setting Up "OPEN" Analysis Points Using Distance
STEPOPERATIONACTIONDISPLAY
1 SELECT SET UP MENU. PRESS # 3 KEY.1. ANALYSIS POINT
2. MEASUREMENT UNITS
3. SAVE / RESTORE
4. NEXT PAGE
2 SELECT ANALYSIS POINT. PRESS # 1 KEY.1. OPEN TIMING
OPEN ANALYSIS PT 1
DISTANCE FROM CLOSE
VALUE: 01.00 in
"ENTER" TO CONFIRM
OPEN ANALYSIS PT 2
1. PERCENTAGE OF STROKE
2. DISTANCE FROM CLOSE
3.CONTACT +/- TIME
DISTANCE FROM CLOSE
VALUE: XX.XX in
"ENTER" TO CONFIRM
OPEN ANALYSIS PT 2
DISTANCE FROM CLOSE
VALUE: 02.00 in
"ENTER" TO CONFIRM
1.TIME BRKR
2.GET RSLT
3.SET UP
4.DIAGNOSTICS
Page 51
CT-6500 Operating Instructions
NOTES
1. If an entry is not correct, re-enter the digits until the screen shows the desired
numbers, then press the “ENTER” key.
2. Analysis Point #1 is 1.00 inch from the fully closed position.
3. Analysis Point #2 is 2.00 inches from the fully closed position.
Page 52
CT-6500 Operating Instructions
9.12 English/Metric or Rotary Transducer Selection
The CT-6500 supports and displays both English and Metric calculations from the breaker's
travel parameters such as the stroke, velocity and other parameters. The user can switch from
one system to the other by following the steps in Table 17.0. Rotary transducer requires the user to
enter the defined linear distance in millimeters or inches, per one degree of rotary motion as seen
in Table 17.1.
Table 17.0 Select Metric Units of Measure
STEPOPERATIONACTIONDISPLAY
1 SELECT SET UP MENU. PRESS # 3 KEY.1. ANALYSIS POINT
2. MEASUREMENT UNITS
3. SAVE / RESTORE
4. NEXT PAGE
2 SELECT MEASUREMENT UNITS. PRESS # 2 KEY.SELECT UNITS
1. ENGLISH
2. METRIC
3. ROTARY TRANSDUCER
3 SELECT METRIC. PRESS # 2 KEY.1. TIME BRKR
2. GET RSLT
3. SET UP
4. DIAGNOSTIC
Table 17.1 Select Rotary Transducer
STEPOPERATIONACTIONDISPLAY
1SELECT SET UP MENU. PRESS # 3 KEY.1. ANALYSIS POINT
2. MEASUREMENT UNITS
3. SAVE / RESTORE
4. NEXT PAGE
2SELECT MEASUREMENT UNITS. PRESS # 2 KEY.SELECT UNITS
4SELECT INCH PER DEGREE.PRESS #1 KEY.INCHES/DEGREE
0.014 in/deg
5ENTER 0.50 INCH PER DEGREE.ENTER 0.50 USING 0-
9 KEYS.
INCHES/DEGREE
0.500 in/deg
6RETURN TO MAIN MENU.PRESS THE “ENTER”
KEY.
1. TIME BRKR
2. GET RSLT
3. SET UP
4. DIAGNOSTIC
Page 53
CT-6500 Operating Instructions
9.13 Set CT-6500 Internal Clock
The CT-6500 has an internal clock with a lithium battery. The clock's time and date is
displayed on the LCD screen. When a timing shot is stored in the EEPROM, the time and date
are also stored along with the shot. To set the clock, perform the steps in the following Table 18.0.
Table 18.0 Setting the Clock and Calendar
STEPOPERATIONACTIONDISPLAY
1 SELECT SET UP MENU. PRESS # 3 KEY.1. ANALYSIS POINT
2. MEASUREMENT UNITS
3. SAVE / RESTORE
4. NEXT PAGE
2 SELECT NEXT PAGE. PRESS # 4 KEY.1. SHOT DESCRIPTION
2. COMPUTER ITF
3. SET CLOCK
4.SET PRINT MODE
3 SELECT SET CLOCK. PRESS # 3 KEY.TIME: HH:MM:00
XX:YY:00
4 ENTER HOURS AND MINUTES. PRESS KEYS 0-9.TIME: HH:MM:00
XX:YY:00
DATE: MM/DD/YY
XX/YY/ZZ
5 ENTER MONTH, DATE, YEAR. PRESS KEYS 0-9.TIME: HH:MM:00
XX:YY:00
DATE: MM/DD/YY
XX/YY/ZZ
6 RETURN TO MAIN MENU. NO ACTION.1. TIME BRKR
2. GET RSLT
3. SET UP
4. DIAGNOSTIC
NOTE
1. The clock battery is good for three years.
2. Loosing the clock battery will not affect the CT-6500’s performance.
Page 54
CT-6500 Operating Instructions
9.14 Slow-Close Test
The CT-6500 offers a unique feature called a "Slow-Close" test. The test permits users to
measure the distance of a breaker's contact travel from the fully opened position to the contact or
"touch" position, to the contact wipe, or penetration distance. The test requires the operator to
manually jack the breaker's contact from the fully open position to the fully closed position.
Contact channel 1, 2, 3 and the transduc er channel 1 will be used for “Slow-Close” test. The
CT-6500 will measure the contact touch and contact wipe for each contact channel.
Contact touch is the distance measured from the contact fully opened to the first position
where the contact channel is electrically closed.
Contact wipe, or penetration, is the distance measured from the contact position first,
electrically closed to the final closed, latching position.
Table 19.0 Performing a Slow-Close Test
STEPOPERATIONACTIONDISPLAY
1 SELECT DIAGNOSTIC MENU.PRESS # 4 KEY.1. SLOW CLOSE TEST
2. PRINT DATA
3. TEST TRANSDUCER
4. CHECK HOOK UP
2 SELECT SLOW CLOSE TEST.PRESS # 1 KEY.BREAKER SLOW CLOSE TEST
RMV CB GND (1 SIDE)
"ENTER" TO BEGIN
3 START SLOW CLOSE TEST.PRESS THE "ENTER"
KEY.
4CONTINUE TO CLOSE BREAKER.NO ACTION.LIFT BRKR TO CLS POS
5RETURN TO MAIN MENU.NO ACTION.1. TIME BRKR
CONTACT 1:OPEN
CONTACT 2:OPEN
CONTACT 3:OPEN
LIFT TO CLS BREAKER NOW
THEN PRESS "ENTER"
TO FIND CONTACT WIPE
2. GET RSLT
3. SET UP
4. DIAGNOSTIC
NOTE
The user can also save a Slow-Close test report in the EEPROM. A typical report
of a Slow-Close test is shown on the next page in Figure 17.0.
Page 55
CT-6500 Operating Instructions
Figure 17.0 Typical Slow-Close Test Report
NOTE
By adding the contact touch and the contact wipe distance, the total is the breaker’ stroke.
9.15 Transducer Self-Test
The operator can check the transducer electronics by connecting the transducer to the CT6500 and running a “Test Transducer” diagnostics.
Table 20.0 Performing a Transducer Self Test
STEPOPERATIONACTIONDISPLAY
1 SELECT DIAGNOSTIC. PRESS # 4 KEY.1. SLOW-CLOSE TEST
2. PRINT DATA
3. TEST TRANSDUCER
4. CHECK HOOKUP
2 SELECT TRANSDUCER. PRESS # 3 KEY.TRANSDUCER TEST
1. The CT-6500 will also print the test report with the thermal printer.
2. A contact closure is shown as "C" on the LCD and printout.
3. An open contact is shown as "-" on the LCD and printout.
Page 57
CT-6500 Operating Instructions
9.17 Automatic Print Setting
The CT-6500 can be set to print graphs and tabulated results automatically after each timing
shot. To turn on the “Auto Print Results” mode, follow the steps in Table 22.0.
Table 22.0 Automatic Print Setting
STEPOPERATIONACTIONDISPLAY
1 SELECT SET UP MENU. PRESS # 3 KEY.1. ANALYSIS POINT
2. MEASUREMENT UNITS
3. SAVE / RESTORE
4. NEXT PAGE
2 SELECT NEXT PAGE. PRESS # 4 KEY.1. SHOT DESCRIPTION
2. COMPUTER ITF
3. SET CLOCK
4. SET PRINT MODE
3 SELECT SET PRINT. PRESS # 4 KEY. SET PRINT MODE
1. AUTOMATIC PRINT
2. BY REQUEST ONLY
4SELECT “AUTOMATIC PRINT”. PRESS # 1 KEY.1. TIME BREAKER
2. GET RESULT
3. SET UP
4. DIAGNOSTIC
NOTE
Select print “BY REQUEST ONLY” will disable the “Automatic Print” mode.
Page 58
CT-6500 Operating Instructions
9.18 CT-6500 Channel Configuration
The CT-6500 is available with 3-, 6-, or 12- contact inputs. Under most common timing
conditions, the user needs to use only 3 contact timing channels and one travel transducer. There
is no need to print more than 3 timing channels and one transducer channel on the graphic and
tabulated report. The CT-6500 will always default to 3 contact channels (channel 1, 2 and 3) and
one transducer channel (transducer channel #1) when the user first turn on the unit. The user can
always turn on the rest of the timing channels and transducer channels by following the steps
shown in table below:
Table 23.0 Channel Configuration
STEPOPERATIONACTIONDISPLAY
1 SELECT SET UP MENU. PRESS # 3 KEY.1. ANALYSIS POINT
2. MEASUREMENT UNITS
3. SAVE / RESTORE
4. NEXT PAGE
2 SELECT NEXT PAGE. PRESS # 4 KEY.1. SHOT DESCRIPTION
2. NUMBER OF CHANNELS
3. COMPUTER ITF
4. SET CLOCK 5. PRINT MODE
3 SELECT NUMBER OF CHANNELS. PRESS # 2 KEY.NUMBER OF CHANNELS
1. 3 CONTACT
2. 6 CONTACT
3. 12 CONTACT
4SELECT 3 CHANNELS OR 6
CHANNELS OR 12 CHANNELS.
5SELECT 1 TRANSDUCER, OR 2, OR 3PRESS #1, OR #2, OR#31. TIME BREAKER
PRESS # 1, OR 2 OR
3 KEY.
1. TRANSDUCER 1
2. TRANSDUCER 1 & 2
3. TRANSDUCER 1 & 2 & 3
2. GET RESULT
3. SET UP
3. DIAGNOSTIC
Page 59
CT-6500 Operating Instructions
9.19 Running CT-6500 in Tandem
For timing application requiring more than 12 timing contact channels, the user can use two or
more CT-6500s to time a circuit breaker. A typical application is to use a CT-6500-12 and a CT6500-6 to time a 18-contact ATB. To time this circuit breaker, the user can use the following
steps:
n
Connect the CT-6500-12 to phase A and B of the circuit breaker.
n
Connect the CT-6500-6 to phase C of the circuit breaker.
n
Connect the CT-6500-12 initiate cable to the breaker control circuit. This CT-6500-12
will operate the circuit breaker.
n
Connect the CT-6500-6 external trigger cable to the OPEN coil for the OPEN test and
CLOSE coil for the CLOSE test. This CT-6500-6 will operate as a slave device.
n
Set the CT-6500-6 to start a test using “EXTERNAL TRIGGER”.
n
Set the CT-6500-12 to start a test using “INTERNAL TRIGGER”.
n
Press “START” key on the CT-6500-6 to start the sequence the press the “START” key
and hold the “ARM” switch on the CT-6500-12.
The CT-6500-12 will operate the circuit breaker and start the timing sequence. The CT-6500-
6 will start its timing sequence as soon as it senses the voltage applied to the breaker coil.
The timing report of the CT-6500-12 will show the contact time of phase A and B. The timing
report of the CT-6500-6 shows contact time for phase C.
If the user downloads the test results of both the CT-6500s to the PC, the user then can
combine the 2 test reports to generate a 18 channel test report. This report now can be printed on
the PC printer.
Page 60
10.0 CT-6500 Trouble Shooting Guide
ProblemsSuggestion
CT-6500 Operating Instructions
1. CT-6500 will not trip nor close the breaker.
2. Getting message “TRIGGER FAULT”
“No Trigger”
When using external trigger
3. Missing timing or transducer channels on report and
graphic output
4. No contact time (0 ms) in Trip or Close test.
5. No contact time (0 ms) in Close-Open.
6. Select Open-Close test. The breaker opens and will
not close.
7. No data or erratic reading on travel transducer.
8. No activity on” V2” voltage input channel.
n
Make sure you hold the “ARM” switch down during
each test.
n
Check the OPEN or CLOSE fuses.
n
Check the initiate leads. For a “Positive Trip” circuit,
one Close lead and one Open lead should be
connected to the Positive side of the power supply.
n
Check the initiate leads. For a “Negative Trip” circuit,
one Close lead and one Open lead should be
connected to the Negative side of the power supply.
n
Trigger voltage was not detected by the CT-6500.
n
Check the external trigger input to the CT-6500.
n
Make sure the external trigger signal is presented
when the CT-6500 displays “AWAITING TRIGGER.”
n
Timing or transducer channels were not turned on.
Turn on channels by going to “SETUP”, “NEXT PAGE”,
“NUMBNER OF CHANNELS”
n
Make sure one side of the breaker in not grounded.
n
Make sure the breaker operates on the Open or
Close test only. A dual operation OPEN-CLOSE or
CLOSE-OPEN will result in 0 ms reading.
n
Damaged CT-6500 contact channels or bad cables.
Try the “CHECK HOOK-UP” test.
n
Make sure the breaker contacts complete the
transition from the Open (initial state) to the Close, then
to the Open (final state). You can see The transition by
looking at the timing chart.
n
Make sure the contact close state is longer than
10 ms. The CT-6500 has a 10ms de-bounce time, any
contact state less than or equal to 10ms is invalid, thus
the delay time is probably too slow.
n
Try the Close-Open using contact channel #1 option.
n
Delay between Open to Close is probably too small.
Increase delay time.
n
Bad transducer. Try “TEST TRANSDUCER”
diagnostics.
n
Transducer slider is not secured to timing rod.
n
Transducer is not secured properly.
n
The “V2” voltage input channel requires a voltage
change from 0 V to above 30 V, to see activities on the
timing chart.
Page 61
ProblemsSuggestion
9. How does one review the current analysis setting?
10. The CT-6500 will not communicate with the PC.
11. Turn on Automatic Print Results mode.
12. Where can one get some thermal paper?
CT-6500 Operating Instructions
n
Go to SETUP (Press key #3).
n
Select Analysis (Press key #1).
n
Select PRINT SETTING (Press key #3). The CT-6500
will print out the current AP1 & AP2 settings.
n
Make sure the CT-6500 is under computer control
mode.
n
Make sure your PC communication port is selected
correctly.
n
Make sure your serial cable is connected properly.
n
See section 9.17.
n
Call the factory at 909-923-9390 or BG Instruments
at 509-893-9881. The CT-6500 uses TP-4 thermal
paper.
13. How does one darken or lighten the LCD?
14. How does one move thermal paper forward or
backward?
n
In case of an emergency, thermal paper can be
purchased at Radio Shack. Radio Shack carries 4.25
inch wide thermal paper. It is not the right size but it will
work.
n
Press and hold the “↑ PAPER LCD” key will darken
the LCD.
n
Press and hold the “↓ PAPER LCD” key will lighten
the LCD.
n
Press and release the “↑ PAPER LCD” key, the
thermal paper will advance.
n
Press and release the “↓ PAPER LCD” key, the
thermal paper will retract.
Page 62
CT-6500 Operating Instructions
AP1= 1.5”
AP2= 3.5”
APPENDIX A
ITE Circuit Breaker model 14.4K Timing Chart
55
Page 63
CT-6500 Operating Instructions
APPENDIX B
CLOSE-OPEN Timing Chart for ITE Circuit Breaker Model 14.4K
56
Page 64
CT-6500 Operating Instructions
APPENDIX C
CLOSE-OPEN Tabulated Report for ITE Circuit Breaker Model 14.4K
57
Page 65
CT-6500 Operating Instructions
APPENDIX D
OPEN-CLOSE Timing Chart for ITE Circuit Breaker Model 14.4K
58
Page 66
CT-6500 Operating Instructions
APPENDIX E
OPEN-CLOSE Tabulated Report for ITE Circuit Breaker Model 14.4K
59
Page 67
CT-6500 Operating Instructions
APPENDIX F
CT-6500 Transducer Illustration
Linear Transducer on an OCB
Rotary Transducer on Alstom HE 1014 Circuit Breaker
60
Page 68
CT-6500 Operating Instructions
Rotary Transducer on ABB HMB Mech
String Transducer on ABB 72PM Circuit Breaker
61
Page 69
www.vanguard-instruments.com
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.