Vanguard Crown V1100E Installation And Operating Instructions Manual

Page 1
Crown™
Non-Circulating (Smooth Face)
®
Wood Burning Firebox V1100E
INSTALLATION AND OPERATING INSTRUCTIONS
SAVE THIS BOOK
This book is valuable. In addition to instructing you on how to install and maintain your appliance, it also contains information that will enable you to obtain replacement parts or optional accessory items when needed. Keep it with your other important papers.
f i r e - p a r t s . c o m
• Do not store or use gasoline or any other flam­mable vapors or liquids in the vicinity of this or any other appliance.
• Due to high temperatures, the appliance should be located out of traffic and away from furniture and draperies.
• Do not place clothing or other flammable materials on or near the appliance.
• NEVER leave children unattended when a fire is burning in the firebox.
WARNING: IMPROPER INSTALLATION, ADJUST­MENT, ALTERATION, SERVICE OR MAINTENANCE CAN CAUSE INJURY, PROPERTY DAMAGE, OR LOSS OF LIFE. REFER TO THIS MANUAL. FOR ASSIS­TANCE OR ADDITIONAL INFORMATION CONSULT A QUALIFIED INSTALLER OR LOCAL DISTRIBUTOR.
WARNING: THIS FIREBOX IS INTENDED FOR USE WITH WOOD, OR IF A VENT-FREE OR DECORATIVE GAS APPLIANCE IS INSTALLED, BURN PROPANE OR NATURAL GAS ONLY.
FOR YOUR SAFETY
®
DESA INTERNATIONAL, 2701 INDUSTRIAL DRIVE P.O. BOX 90004 BOWLING GREEN, KY 42102-9004
Model Serial No. Date Purchased
CHECK LOCAL CODES PRIOR TO INSTALLATION
55507 Rev. C 07/99
Page 2
C O N T E N T S
1. INTRODUCTION......................................PG. 3
2. CLEARANCES ........................................PG. 3
3. ASSEMBLING AND INSTALLING PIPE.PG. 4
4. FIRESTOP SPACERS.............................PG. 4
5. SUPPORT SECTIONS ............................PG. 4
6. CHIMNEY AND OFFSET.........................PG. 5
7. PENETRATING THE ROOF....................PG .6
8. TERMINATIONS ......................................PG. 6
9. GAS LINE INSTALLATION .....................PG. 6
38 5/8"
(981mm)
12 1/8"
BACK AND SIDES 1" (25mm) AIR SPACE CLEARANCE
31"
(787mm)
(803mm)
(308mm)
f i r e - p a r t s . c o m
5/8"
(16mm)
15"
(381mm)
10. HEARTH EXTENSIONS ..........................PG. 7
11. OUTSIDE COMBUSTIBLE AIR............... PG. 7
12.
COMBUSTIBLE AIR OPERATION..............
13. FIREBOX ENCLOSURE........................... PG. 7
14.
FINISHING YOUR FIREPLACE .............. PG. 8
15. OPTIONAL GLASS DOORS .................... PG. 8
16. OPERATION OF FIREBOX EQUIPPED WITH
GLASS DOORS........................................ PG. 8
REPLACEMENT & ACCESSORY PARTS .....
17.
1
28
/4"
(718mm)
HEARTH
REFRACTORY
5
31
/8"
1
/2"
42
(1080mm)
5
17
/8"
(448mm)
PG. 7
PG. 8
25"
(635mm)
Figure 1
NAILING FLANGE
1
/2"
1
(38mm)
1
43
/2"
(1105mm)
1
/2"
47
(1207mm)
29"
(737mm)
(1181mm)
9"
(229mm)
46
2
1
64
/2"
(1638mm)
1
/2"
14"
(356mm)
1
/4"
16
(413mm)
COMBUSTION AIR INLET
(RT. SIDE ONLY)
GAS LINE KNOCK-OUT
(BOTH SIDES)
1
/4"
18
1
(464mm)
11
/4"
(286mm)
55507
Page 3
INSTALLATION INSTRUCTIONS
STEP 3: Check the level of the firebox and shim with sheet metal if necessary.
INTRODUCTION
Before beginning the installation of your firebox, read these instruc­tions through completely. These VANGUARD components and firebox are safe when installed according to this installation manual. Unless you use VANGUARD components that have been designed and tested for the firebox system, you may cause a fire hazard.
STEP 4: When the firebox is installed upon a combustible floor a galvanized steel ember protector (provided) must be installed be­tween the firebox and the hearth extension as illustrated in Figure 16, page 7.
STEP 5: Secure the firebox to the framing through the flanges
located on the sides on the firebox with 8-penny nails. The DESA INTERNATIONAL warranty will be voided by, and DESA INTERNATIONAL disclaims any responsibility for the following actions:
HEADER
a) Modification of the firebox, components, doors, air inlet system
and the damper control.
b) Use of any component part not manufactured or approved by
FALSE HEADER
DESA INTERNATIONAL in combination with a DESA INTER­NATIONAL firebox system.
Refer to your Homeowners guide for warranty information.
This wood burning fireplace complies with UL 127 as a FACTORY BUILT FIREPLACE and is listed and tested by
Underwriters Laboratory Inc.
48"
(1219)mm)
This model is not for use in mobile homes.
WARNING: DO NOT INSTALL A FIREPLACE INSERT IN THIS FIREBOX UNLESS THE MANUFACTURER'S INSTRUCTIONS WITH THE INSERT SPECIFICALLY STATE THIS FIREBOX HAS BEEN TESTED FOR USE WITH THE INSERT.
PROPER INSTALLATION is the most important step in ensuring safe and continuous operation of this firebox. Consult the local
f i r e - p a r t s . c o m
building codes as to the particular requirements concerned with the
Figure 2
HEADER
FALSE HEADER
3
15
/8"
(391mm)
installation of all factory built fireboxes. Although grounding may not be required by code the manufacturer recommends it.
1
48
/2"
(1232mm)
65"
(1651mm)
This firebox is not intended to be used as a substitute for a furnace
to heat an entire home. Use for supplementary heating only.
MINIMUM CLEARANCES TO COMBUSTIBLES
Framing materials may safely make direct contact with the spacers on the top of the firebox. The firebox may sit directly on combus­tible flooring. The firebox opening must not be less than 30 inches from a combustible, perpendicular sidewall. A 2-inch minimum air space clearance between combustible materials and the chimney must be absolutely maintained. A 19-inch inside chase dimension is required as a minimum size. A 1-inch airspace is required around back and sides of firebox.
WARNING: DO NOT PACK REQUIRED AIR SPACES WITH INSULATION OR OTHER MATERIALS.
HEIGHT
The minimum height of the chimney, measured from the base of the firebox to the flue gas outlet, is 16 feet for straight flues or a flue with one elbow set. For systems with 2 elbow sets, the minimum height is 16 feet. The maximum height of any system is 60 feet. This measurement includes the firebox, chimney sections and the effec­tive height of the termination assembly.
INSTALLING THE FIREBOX
STEP 1: Frame the opening for the firebox using the dimensions shown in Figure 2 or Figure 3.
STEP 2: Sit the firebox directly in front of this opening and slide the unit back until the mounting flanges touch the side framing.
Figure 3
Figure 4
1
/4"
74
(1886mm)
(813mm)
48"
(1219mm)
105"
(2667mm)
32"
3
24
(614mm)
/16"
1
52
/2"
(1334mm)
31"
(784mm)
55507
3
Page 4
ASSEMBLING AND INSTALLING YOUR DOUBLE-WALL CHIMNEY SYSTEM
The Vanguard chimney system is a snap-lock, double-wall pipe. It consists of a stainless steel inner flue pipe, a galvanized outer pipe, and a wire spacer. Each section comes in lengths of 12, 18, 24, 36, and 48 inches but the actual lineal gain is the actual measurable length of a part after two or more parts are connected.
LINEAL GAIN
MODEL NO. DESCRIPTION GAIN
V1100E MONARCH 64
1
/2 (1638mm)
FIRESTOP SPACERS
Firestop spacers are required at each point where the chimney
penetrates a floor or ceiling, joist space. Their purpose is twofold;
they establish and maintain the required clearance between the outer
pipe and combustible materials, and they also serve as a shield
between floors as required by most codes.
When the pipe passes through a framed opening into a living space
above, a firestop must be placed on the ceiling below (Figure 6).
LIVING SPACE ABOVE CEILING
FIREBOX V48-10DM FLUE PIPE 46 V36-10DM FLUE PIPE 34 V24-10DM FLUE PIPE 22 V18-10DM FLUE PIPE 16 V12-10DM FLUE PIPE 10
3
/8 (1178mm)
3
/8 (873mm)
3
/8 (568mm)
3
/8 (416mm)
3
/8 (264mm)
VETL-10D CHASE STYLE 7 (178mm) TO 17
TERMINATION (432mm)
VRTL-10D ROUND TOP 6 (152mm)
TERMINATION
Place pipe assembly (inner and outer with wire spacer) over starting collar. Inner pipe fits inside inner pipe, outer pipe fits outside outer pipe. Begin by aligning hemmed-end of inner flue pipe into the inner
Figure 6
When the pipe passes through a framed opening into an attic space above, a firestop must be placed on the attic floor above (Figure 7)
SCREW (TYP. OF 8)
ATTIC SPACE ABOVE CEILING
starting flue pipe of firebox. Push down until hem "snap-locks" with lances. The outer pipe is just the opposite; female end has the lances. Continue the same procedure for the outer pipe.
f i r e - p a r t s . c o m
FIRESTOP SPACER
EXISTING CEILING FRAME
FIRESTOP SPACER
SCREW (TYP. OF 8)
V12S-10DM SUPPORT REQUIRED
15" (381 mm)
DIA. GALVANIZED
HEMMED
END
Figure 5
OUTER PIPE
10" (254 mm)
STAINLESS
INNER PIPE
LANCED SIDE UP
It is important to assure the joint between the chimney sections is fully locked. Check by pulling chimney upward after locking. The chimney should not come apart if properly locked. It is not necessary to add screws to keep vertical or angled chimney runs together.
WARNING: THE OPENINGS AROUND THE START­ING COLLAR ON TOP OF THE FIREBOX MUST NEVER BE OBSTRUCTED. NEVER USE BLOWN INSULA­TION TO FILL THE CHIMNEY ENCLOSURE.
Figure 7
EXISTING CEILING FRAME
SUPPORT SECTIONS
The chimney support section is a 4 strap, 12 inch length of pipe. A chimney support is required every 30 feet above the firebox after a straight chimney run, or above a return elbow after a straight chimney run (Figure 8).
This support is designed to relieve the extra weight load on the firebox and elbows when high chimneys are installed.
V12S-10DM
SUPPORT
REQUIRED
30 FT.
(9.14m)
30 FT.
(9.14m)
RETURN
ELBOW
Figure 8
4
55507
Page 5
INSTRUCTIONS WHEN OFFSET OF CHIMNEY IS NEEDED
TO INSTALL ELBOWS
1. To achieve desired offset, you may install combinations of 12", 18", 24", 36" or 48" lengths of double wall pipe (see Rise and Offset chart and Figures 9 and 11).
2. Chimney weight above offset rests on return elbow . Straps must be securely nailed to rafters or joists (see Figure 10, details A and B).
3. Maximum length of pipe between supports (return elbow or V12S-10DM) 6 foot of angled run. Maximum of two (2) 6 foot angled run sections per chimney systems (Figure 11).
6 ft.
max.
B
RISE AND OFFSETS
A B 48 36 18 12
3
4
/8 (111mm) 163/8(416mm)
1
9
/2(241mm) 251/4(641mm) 1
1
12
/2(318mm) 303/8(772mm) 1
3
14
/8(365mm) 34(864mm) 2
5
17
/8(448mm) 391/4(997mm) 1 1
1
21
/2(546mm) 46(1168mm) 1
3
22
/4(578mm) 481/8(1219mm) 1 2
3
26
/8(670mm) 547/8(1394mm) 1
3
29
/8(746mm) 60(1524mm) 1 1
3
31
/4(806mm) 633/4(1619mm) 1 1
3
34
/4(883mm) 69(1753mm) 1 1
5
38
/8(981mm) 755/8(1921mm) 2
397/
8(1013mm)
433/
4(1111mm) 84
463/
4(1187mm) 87
487/
8(1241mm) 93
777/
8(1978mm) 1 1 1
1
/2(2146mm) 1 1
3
/4(2229mm) 2 1
3
/8(2372mm) 2
CEILING SUPPORT PIPE
f i r e - p a r t s . c o m
Figure 9
A
V12S-10DM
DETAIL B
DETAIL A
RETURN ELBOW
Figure 10
6' MAX
(1829mm)
RETURN ELBOW
RETURN ELBOW
OFFSET ELBOW
CEILING SUPPORT PIPE V12S-10DM
(1829mm)
6' MAX
(1829mm)
6' MAX
OFFSET ELBOW
RETURN ELBOW
OFFSET ELBOW
6' MAX
(1829mm)
6' MAX
(1829mm)
RETURN ELBOW
OFFSET ELBOW
OFFSET ELBOW
6' MAX
(1829mm)
2" (51mm) MINIMUM
ANGLE FIRESTOP
INSTALL SUPPORT V12S-10DM AT 30 FT. LEVEL
RETURN ELBOW
DETAIL A
SEE
DETAIL B
SEE
Figure 11
55507
CBA
5
Page 6
NOTE: ANY OFFSET GREATER THAN 6 FEET MUST USE A V12S-10DM.
IMPORTANT: If an exposed portion of chimney is greater than 5 feet above the roof line, use support wires to keep chimney secured. The support wires may be attached to the outer pipe of the chimney
PENETRATING THE ROOF
To maintain a 2-inch clearance to the pipe on a roof with a pitch, a
with screws. Provided the screws are not long enough to penetrate the inner flue pipe.
rectangular opening must be cut.
FLASHING
STORM
COLLAR
STEP 1: Determine the center point through which the pipe will penetrate the roof.
STEP 3: From the center point determined in STEP 1, measure an opening 20 inches wide (10 inches to each side of the center point). For a roof pitch between 0/12 (flat) and 6/12, measure and opening
1
24
/4 inches long (121/4 inches above and below). 12/12 to 18/12
pitches: Measure 30 inches (18
1
/4 above and below).
18/12 to 24/12 pitches: Measure 44 inches (22 above and below).
NAIL ONLY OUTER PERIMETER OF FLASHING
STEP 4: Remove the shingles around the opening measured and cut out this section.
STEP 5: Add the next sections of pipe until the end penetrate the roof line. Check to see that proper clearance is maintained. Extend chimney by adding sections of double wall pipe until pipe are a minimum of 30 inches above highest point of roof cutout. Termina­tion and chimney must extend a minimum of 36 inches above highest point where it passes through roof (see 10-foot Rule and Figure 12).
Figure 13
UNDERLAP SHINGLES AT BOTTOM
TERMINATIONS
The firebox and chimney system must be vented to the out-of-doors and must be terminated with the listed round top or chase termina­tions. If a chase termination is desired, refer to the instructions supplied with the termination.
f i r e - p a r t s . c o m
FOR ROUND TOP TERMINATION
STEP 1: Slide the flashing over the pipe (no firestop is needed at the roof level). Tack the flashing down at the top two corners with roofing nails. Lay tiles over the top and sides of the flashing and secure them to the roof through the flashing with roof nails. Lay tiles under the lower edge and secure these to the roof. Mastic all nail heads.
STEP 2: Install storm collar on double wall chimney, apply water­roof caulking around flashing top and push storm collar down securely on sealer and flashing (see Figure. 13).
STEP 3: Place the round termination onto the pipe end as illustrated and secure with the screws provided.
10 FOOT RULE
All chimney terminations must extend a minimum of 3 feet in height above the highest point where it passes through the roof and must be at least 2 feet above the peak of the roof if within a horizontal distance of 10 feet from the peak (see Figure 12).
WITHIN 10'
(3.048m)
2' MIN.
(609mm)
3' MIN.
(914mm)
LEVEL OF FLUE
GAS OUTLET
WITHIN 10'
(3.048m)
2' MIN.
(609mm)
3' MIN.
(914mm)
GAS LINE INSTALLATION
A gas line may be installed for the purpose of installing a gas appliance available through your local distributor. Use only 1/2" black iron pipe and appropriate fittings. When installing a gas line, a shut-off valve designed for installation outside the firebox is recommended.
To install, remove the gas line plug located in side firebrick approx. 2" above the bottom. The plug must be tapped out from the finished side towards the unfinished side (see Figure 14, page 7). Insert the gas line parallel to the face. Fill any gap between the gas line and the hole in the firebrick with refractory cement or commercial furnace cement (see Figure 15, page 7).
WARNING: All gas piping and connections must be tested for leaks after the installation is completed. Be sure gas valve is turned on. Apply soap suds solution to all connections and joints. If bubbles appear, leaks can be detected and corrected. DO NOT use a match or open flame of any kind to test for leaks. Never operate any appliance with leaky connections.
The gas pipe is intended for connection to an unvented gas log set or to a decorative gas appliance.
If you will install an unvented gas log set, ONLY UNVENTED GAS LOG SETS WHICH HAVE BEEN FOUND TO COMPLY WITH THE STANDARD FOR UNVENTED ROOM HEATERS, ANS/IAS/ AGA Z21.11.2, ARE TO BE INSTALLED IN THIS FIREPLACE.
NOTE: An appropriate Vanguard hood must be installed when using an unvented gas log set.
WARNING: DO NOT OPERATE AN UNVENTED GAS LOG SET IN THIS FIREPLACE WITH THE CHIMNEY REMOVED.
CHIMNEY PIPE
OVERLAP SHINGLES TOP AND SIDES ONLY
Figure 12
If you will install a decorative gas appliance, the decorative gas appliance must comply with the Standard for Decorative Gas
Appliances for Installation in solid Fuel burning Fireplaces, ANS Z21.60-1996 and shall also be installed in accordance with the National Fuel Gas code, ANS Z223.1-1996.
6
55507
Page 7
WARNING: WHEN USING A DECORATIVE APPLIANCE, THE DAMPER MUST BE REMOVED OR PERMANENTLY LOCKED IN THE FULLY OPEN POSITION.
COMBUSTIBLE AIR KIT (MODEL VAK4) (OPTIONAL)
Remove air inlet cover plate and attach the air inlet collar onto the 4 inch hole on right side only.
SIDE FIREBRICK FINISHED SIDE
REFRACTORY KNOCKOUT PLUG REMOVE BY TAPPING LIGHTL Y WITH A 1/2" DOWEL
SIDE FIREBRICK FINISHED SIDE
PROVIDE ENOUGH THREADED END FOR FITTING CONNECTION
MAX HEIGHT
3 FEET (914mm)
BELOW THE
CHIMNEY TERMINATION
Figure 17
The outside air vent can be installed through an outside wall or a ventilated crawl space. A plaster ground is provided for use of unfinished walls prior to applying finish surface. Attach combustible air inlet duct to outside air inlet (see Figure 17).
REMOVE INSULATION TEMPORARILY (DO NOT DISCARD)
Figure 14
OUTSIDE OF FIREPLACE
OUTSIDE OF FIREPLACE
GAS LINE CONDUIT
GAS LINE CONDUIT
REMOVE KNOCKOUT
AFTER REMOVING GAS LINE COVER PLATE, REPLACE SCREWS
INCOMING 1/2" BLACK IRON PIPE
WARNING: AIR INLET DUCTS ARE NOT TO TERMI-
REPACK INSULATION
Figure 15
1
9
/4" (235mm) APPROX.
SEAL OPENING WITH REFRACTORY CEMENT
HEARTH EXTENSION
f i r e - p a r t s . c o m
A hearth extension projecting a minimum of 24 inches in front of and a minimum of 12 inches beyond each side of the firebox opening is required to protect combustible floor construction in front of the firebox. Use a layer of noncombustible, inorganic material having a thermal conductivity K=0.84 BTU IN./FT. HR F (or less) at 1" thick. Example of determining hearth extension equivalent: If the material selected has a K Factor of 0.25, such as glass fiber, then the following formula would apply: 0.25/0.84x1"=.30" thick. This must be cov­ered by any noncombustible material such as tile, slate, brick, concrete, metal, glass, marble, stone, etc. Fasten the hearth extension to the floor to prevent shifting and seal the gap between the firebox frame and hearth extension with a noncombustible material (see Figure 16). (Not required when using ember protector).
SEAL GAP (NOT REQUIRED WHEN
STANDARD HEARTH
EMBER PROTECTOR
SEAL GAP
USING EMBER PROTECTOR
NATE IN ATTIC SPACE.
Avoid installing outside air eyebrow in areas where inlet opening may be blocked by snow, bushes or other obstacles. Maximum height of air inlet above platform of firebox is 3 feet below the termination exhaust height.
COMBUSTION AIR DAMPER OPERATION
This model firebox is equipped with a barometric damper which allows air flow in one direction only. To unlock the damper door push the metal handle down that is protruding through the first slotted opening on the right side of the firebox. Push the handle up to lock the damper door closed when not using the firebox. This is important when installed in cold weather areas to prevent the entry of cold air through the combustion air system.
NOTE: The handle can be operated by tapping LIGHTLY with a poker The total movement is approx. 1-inch.
FIREBOX ENCLOSURE
Before finishing the enclosure around the firebox, inspect all joints around the firebox. Any gaps between the nailing flanges and the framing should be sealed with noncombustible insulation or caulking. Inspect the firebox joints for possible gaps caused by shipping or mishandling during installation. These should be sealed with noncom­bustible materials. If the firebox is mounted on a raised platform insulate below the platform to prevent the entry of cold air through the firebox bottom by means of conduction. The above steps are important espe-
Figure 16
RAISED HEARTH
EMBER PROTECTOR
ELEVATED FIREPLACE
EMBER PROTECTOR
MIN
9"
cially if the firebox is installed in cold weather climate (see Figure 18).
1/4" (6mm) AIR SPACE AT NAILING FLANGE ONLY
SIDE FRAMING
FIREPLACE SIDE FRAME
PACK INSULATION
HERE
NORMAL FRAMING
CAULK HERE
WARNING: HEARTH EXTENSION IS TO BE IN­STALLED ONLY AS ILLUSTRATED.
55507
7
Figure 18
FIREPLACE SIDE FRAME
SIDE FRAMING
WIDE FRAMING
Page 8
FINISHING YOUR FIREBOX
Combustible materials may make direct contact with the sides of the firebox face nailing flange. It is important that combustible materi­als do not overlap the face itself. Brick, tile or other noncombustible materials may be applied to the face provided that any gap between the material around the firebox opening be caulked to prevent the seepage of combustion products.
MANTEL
A mantel may be installed if desired. Refer to Figure 19 for limita­tions if using wood or other combustible materials.
WARNING: FIREBOX EQUIPPED WITH DOORS SHOULD BE OPERATED ONLY WITH DOORS FULLY OPEN OR FULLY CLOSED.
DAMPER OPERATION
The flue gas damper is located inside the firebox similar to a conventional masonry fireplace. Look within the top of the firebox and locate the damper handle extending from the damper. Pushing the handle opens the damper. Pulling the handle closes it.
NEVER CLOSE THE DAMPER UNTIL YOUR ARE CER­TAIN THAT THERE ARE NO MORE WARM EMBERS.
COMBUSTIBLE
MATERIAL
WARNING: BEFORE STARTING YOUR FIRST FIRE IT IS IMPORTANT TO READ AND FOLLOW THE GUIDE­LINES OUTLINED IN THE WARRANTY AND OPERAT­ING INSTRUCTIONS INCLUDED IN THE FIREBOX. IF THE WARRANTY AND OPERATING INSTRUCTIONS ARE MISSING, WRITE DESA INTERNATIONAL AT THE ADDRESS ON THE COVER OF THIS BOOKLET.
WARNING: 4 handles located on the outer surround of the firebox are used for lateral movement only. DO NOT LIFT FIREBOX BY THESE HANDLES.
NOTE: Handles may be removed after use.
REPLACEMENT AND ACCESSORY PARTS
18"
(457mm)
Figure 19
(203mm)
NONCOMBUSTIBLE
FILLER
TOP OF
FIREPLACE
OPENING
8"
MAX.
FALSE HEADER
HEAT SHIELD
METAL FACE
Purchase replacement parts or accessories from your local dealer. If
OPTIONAL GLASS DOORS
Vanguard glass door models VDG1100E (Brushed Brass over
f i r e - p a r t s . c o m
Aluminum) and VDP110E (Polished Brass over Aluminum) are available for use with Vanguard model V1100E firebox. Instructions for the installation of the glass kit are included with the glass door cartoning. Use of any other glass door assembly not tested with Vanguard model V1100E may constitute a potential fire hazard. Read and follow the maintenance instructions for your glass door included with your installation manual.
they can not supply these accessories, call DESA International's Parts Department at 1-800-972-7879 for referral information. You can also write to the address listed on the front cover of this manual. When calling DESA International, have ready
• model number of your heater
• the replacement part number
NOTE: USE OF ANY OTHER GLASS DOOR ASSEM­BLY NOT TESTED WITH THIS FIREPLACE MAY CONSTITUTE A FIRE HAZARD AND WILL VOID THE DESA INTERNATIONAL WARRANTY.
STORM COLLAR VSC2-20-10DM (20 PACK)
FLASHING
DOUBLE WALL CHIMNEY PIPE V12-10DM (12" LONG) V18-10DM (18" LONG) V24-10DM (24" LONG) V36-10DM (36" LONG) V48-10DM (48" LONG)
CHIMNEY PIPE ASSY. (INCLUDES OUTER AND INNER PIPES)
EMBER PROTECTORS (INCLUDED) 20651
ADJUSTABLE HOOD BLACK - GA6050 POLISHED BRASS - GA6052 ANTIQUE BRASS - GA6053
ROOF PITCH
V6F-10DM - 0 to 6/12
V12F-10DM - 6/12 to 12/12
RETURN ELBOW
STARTER ELBOW
OUTSIDE AIR KIT VAK4
CONNECTOR DUCT - 4" X 3'
ROUND TOP TERMINATION VRTL-10D
DOUBLE WALL 3O° ELBOW/ OFFSET V30E-10DM
VENT HOOD
DOUBLE WALL PIPE SUPPORT ASSEMBLY V12S-10DM
8
ECONO-TOP TERMINATION WITH SLIP SECTION VETL-10D
FIRESTOP SPACERS
VFS-10DM (STRAIGHT PIPE)
BI-FOLD GLASS DOOR KITS: VDG1100E BRUSHED BRASS VDP1100E POLISHED BRASS
55507
Loading...