Vaisala PDT101 Quick Start Guide

Vaisala Differential Pressure Transmitter
Performance
Measurement range (bidirectional)
±60 Pa, ±125 Pa,
Overpressure
Proof pressure
1.0 bar
Burst pressure
1.7 bar
Static pressure
1.7 bar
Pressure type
Differential, gauge,
vacuum and compound
Accuracy
(incl. non-linearity, hysteresis,
calibration settings)
0.4 % span
Long-term stability
≤0.5 % span/year
Response time (10...90 %)
250 ms
Warm-up time
15 s
Compensated temperature range
+2...+54 °C
(+35.6...+129.2 °F)
Temperature dependence
±(0.065 Pa + 0.054 % of reading) / °C
O + 0.03 % of reading) / °F
(reference 21 °C or 70 °F)
Mounting position error (zero adjustable)
≤1 %/g (calibration in vertical
position is standard)
Adjustments (front accessible):
Zero (span low)
±5 % span
Span (span high)
±3 % span
Operating environment
Operating temperature
-18...+70 °C (-0.4...+158 °F)
Storage temperature
-40...+82 °C (-40...+179.6 °F)
Electromagnetic compatibility
EN61326-1, Basic immunity
test requirements
Note: If used in an electromagnetic field of 3 V/m, with narrow frequency area
max. 0.8% (with accuracy specified 0.4%).
Inputs and outputs
Process connection
1/4" barbed fittings
Output signal
2-wire
4...20 mA
3-wire
0...5 VDC
(user selectable 0...10 VDC)
Operating voltage
2-wire output 4...20 mA
12...36 VDC
3-wire output 0...5 VDC
11.5...36 VDC or 24 VAC
3-wire output 0...10 VDC
14...36 VDC or 24 VAC
Max. loop resistance for 4...20 mA
(Supply voltage - 12V)/0.022 A
Supply current
max. 20 mA for 4...20 mA output signal
Optical process diagnostics
LED visual indicator
Electrical connection
Euro style pluggable terminal block accepts
12...26 AWG wire (0.13 up to 3.31 mm2)
Mechanics
Medium (measured gas)
Clean and dry air, non-conducting and
non-corrosive gases
Material
Process connection
Brass
Sensor element
Silicon, aluminum, glass
Case
NEMA type 1 fire-retardant ABS 1
(meets UL94-5VA)
Mounting
Threaded fastener for wall mounting
or DIN rail type EN50022
Housing classification
IP40
Weight
0.07 kg
POWER
HI LO
SPAN
ZERO
ø
5
ø
4
37
48
74 84.6
9.4
33.6
POW ER
HI LO
SPAN
ZERO
Zero adjust potentiometer
Span adjust potentiometer
Power LED
Terminal block
Die deutschsprachige Version kann von www.vaisala.com/PDT101 heruntergeladen werden.
Vous pouvez télécharger la version française sur www.vaisala.com/PDT101.
日本語版は www.vaisala.com/PDT101 からダウンロードできます。
WARNING - READ BEFORE INSTALLATION
Vaisala Differential Pressure Transmitter PDT101 is a high-performance instrument designed primarily for use in life science and cleanroom applications. PDT101 is not authorized for use as a critical component in life support devices or systems. Consult Vaisala before installing if there are any questions or concerns.
Overpressure: Pressure spikes in excess of the rated overpressure capability of the transmitter may cause irreversible electrical and/or mechanical damage to the transmitter.
Static electrical charges: To avoid damage to the transmitter the operator/installer should follow proper ESD (electrostatic discharge) protection procedures.
TECHNICAL SPECIFICATION
PDT101
MOUNTING
The transmitter can be mounted on an EN550022 rail or with M4 (#8) or M5 (#10) screws using the mounting holes provided.
of 80 - 120 Mhz, it is possible that the current output of PDT101 can deviate
repeatability and zero/span
±(0.00015 inH
±0.25 inH2O, or ±0.5 inH2O
2
or
Figure 1 Dimensions (in mm)
Figure 2 PDT101 Transmitter
M211284EN-H ___________________________________________________________________________________ 1
Quick Guide _______________________________________________________________________________ PDT101
+
+
+
BCS
Power Supply
Loop Resistance (Ω)
Supply Voltage (V)
Vmin = 12V+ [.022A*(R L)]
*includes a 10% safety factor RL = RS + RW RL = Loop Resist ance (ohms)
RS = Sense Resistance (ohms)
RW = Wire Resistance (ohms) Loop Supply Voltage (Vdc)
OPERATI NG REGIO N
+
Output signal
Common (V-)
V
out Vin (V+, Supply)
Power Supply
Jumper (orange or red)
Housing tabs (2 pcs)
0...5 Vdc
0...10 Vdc
SETUP
Transmitters are calibrated in a vertical position at the factory. Mounting in a horizontal position may cause a zero shift of as much as +/-1 % of span. To check for zero shift, see section Calibration below.
ELECTRICAL WIRING
1. Remove the terminal block on the front of the transmitter.
2. Follow the terminal block label markings on the PDT101 to identify the
terminals, and connect the wires.
3. Firmly reinstall the terminal block plug to its mating connector.
Current Output Wiring (Black Terminal Block)
The left, negative (-), and right, positive (+) terminals are used, ignore the center terminal which is not used. Connect the power supply positive lead to the PDT101 positive terminal, connect the negative power supply lead to the negative terminal of the BCS 4...20 mA input. Last, connect the (-) negative terminal on the PDT101 to the (+) positive BCS input.
Use of a shielded cable, with the shield grounded, is required. Do not connect the shield to the transmitter.
Figure 5 Voltage Output Wiring
The PDT101 voltage output model is supplied as standard with 0...5 VDC output. You can convert the unit to 0...10 VDC output by moving a jumper inside the transmitter. Access the jumper by simultaneously pushing both housing tabs away from the housing. Change jumper (orange or red) to the left as shown below, and carefully reattach the housing cover. When finished, mark the checkbox on front label indicating that the unit now provides a 0...10 VDC output.
Figure 6 Voltage Output Jumper
Figure 3 Current Output Wiring
Figure 4 Load Limitations
Voltage Output Wiring (Green Terminal Block)
The left terminal is the common (supply and output negative), the right terminal is the Vin (supply positive). The middle terminal is the Vout (output signal).
Use of a shielded cable, with the shield grounded, is required. Do not connect the shield to the transmitter. Maximum cable length for voltage output wiring is 30 m (98.4 ft).
CALIBRATION
1. Pneumatically connect the transmitter’s pressure ports to each other.
The barbed pressure connections accept 1/4” O.D. 1/8” I.D. tubing.
2. Measure the analog output of the transmitter to establish the zero offset
reading in the as-installed position.
3. If the reading is not at the middle of the output range (for example, 12 mA
for 4 … 20 mA output), the zero point of the transmitter has shifted. To remove the zero shift, adjust the transmitter as described below.
ADJUSTMENT
Note: You need a high accuracy pressure standard and high quality electrical meter to adjust the PDT101.
1. Connect the pressure standard to the ports of the PDT101.
2. Bring the pressure to 0 % of the transmitter’s span.
3. Adjust the zero potentiometer (on the front, left side of the transmitter) so
that the analog output value is at the low end of its range. Use a 3/32” or
2.5 mm slotted or Phillips screwdriver to turn the potentiometer.
4. Now bring the pressure to 100 % of the transmitter’s span.
5. Adjust the span potentiometer (on the front, right side of the transmitter) so
that the analog output value is at the high end of its range.
REMOVAL FROM DIN RAIL
1. Unplug the wiring terminal block from the transmitter.
2. Insert a small slotted screwdriver into the black plastic clip extending
slightly below the transmitter case.
3. Raise the screwdriver handle up thereby forcing the spring clip down.
WARRANTY
For warranty information, visit our Internet pages at:
www.vaisala.com/warranty
DISPOSAL
Dispose of the unit according to local regulations. Do not dispose of with regular household waste. Recycle all applicable material.
.
© Vaisala 2020. All rights reserved. ___________________________________________________________________ 2
Loading...