Vaisala MMT310 Technical data

www.vaisala.com
MMT310 Series Moisture and Temperature Transmitter for Oil
Water content as ppm calculation for transformer oils
PPM units are traditionally used in transformer applications. They indicate the average mass concentration of water in oil. The ppm calculation for mineral oil based transformer oil is optional in the MMT310 series.
Diverse applications and demanding conditions
The MMT310 series can be used in lubrication and hydraulic systems as well as in transformers. It can be used for on-line moisture monitoring and as a control function, allowing separators and oil puriers to be
Two probe options: MMT317 and MMT318
Features/Benefits
Continuous measurement of
moisture in oil
Proven Vaisala HUMICAP®
sensor, 10 years in oil applications
Measurements in lubrication,
hydraulic and transformer oils
Excellent pressure and
temperature tolerance
Measuring water activity - ppm
calculation for transformer oil
Small size, easy to integrate
NIST traceable calibration
Applications: e.g. monitoring
of transformer oil and of lubrication systems in marine and paper industry
The Vaisala HUMICAP® Moisture and Temperature Transmitter Series for Oil MMT310 is a fast and reliable on­line detector for moisture in oil.
Reliable Vaisala HUMICAP® technology
The MMT310 series incorporates the latest generation of the Vaisala HUMICAP demanding moisture measurement in liquid hydrocarbons. The sensor’s excellent chemical tolerance provides accurate and reliable measurement over the wide measurement range.
®
Sensor, developed for
Measuring water activity
The MMT310 series measures moisture in oil in terms of the water activity (aw) and temperature (T).
Water activity directly indicates if there is a risk of free water formation. The measurement is independent of oil type, age, and temperature.
started only when necessary.
Installation options
The MMT318 has two adjustable probe lengths. The transmitter can be ordered with a ball valve set that enables the insertion and removal of the moisture probe for calibration, without the need to empty the oil system.
The MMT317 has a small pressure­tight probe with optional Swagelok ttings.
Several outputs, one connector
The MMT310 series has two analog outputs and an RS-232 serial output. The output signals and the supply power travel in the same cable, the only cable connected to the unit.
Technical data
Measured values
WATER ACTIVITY
Measurement range a
w
0 ... 1 Accuracy (including non-linearity, hysteresis and repeatability)
0 ... 0.9 ±0.02
0.9 ... 1.0 ±0.03
Response time (90 %) at +20 ˚C in still oil
10 min (with stainless steel filter) Sensor Vaisala HUMICAP
TEMPERATURE
Measurement range -40 ... +180 ˚C (-40 ... +356 ˚F) Typical accuracy at +20 ˚C ±0.1 ˚C (±0.18 ˚F) Typical temperature dependence of electronics ±0.05˚C/ ˚C (±0.005 ˚F/˚F) Sensor Pt100 IEC751/3 class B
Electrical connections
Two analog outputs, selectable and scalable 0 ... 20 mA or 4 ... 20 mA Typical accuracy of analog output at +20 ˚C ±0.05 % full scale Typical temperature dependence of analog output Serial output RS-232C Connections 8-pole connector with RS-232C, current
Operating voltage U Minimum operating voltage U
in
in
with RS-232C 10 VDC
0 ... 20 mA, 4 ... 20 mA 11 VDC + (R
I
out
Power consumption at +20 ˚C, U
= 24 VDC
in
with RS-232C 20 mA
2 x 0 ... 20 mA 60 mA
I
out
0.005 %/˚C (0.003 %/˚F) full scale
outputs (two channels) and U
24 VDC (10 ... 35 VDC)
/60) VDC
load
General
Operating temperature range for electronics -40 ... +60 ˚C (-40 ... +140 ˚F) Storage temperature -55 ... +80 ˚C (-67 ... +176 ˚F) Pressure range for MMT318 with ball valve up to 120 ˚C 0 ... 40 bar Pressure range for MMT317 0 ... 10 bar External load R Material
®
in
transmitter housing G-AlSi 10 Mg transmitter base ABS/PC
Housing classification IP65
to be protected from direct rain
Cable feed through alternatives 8-pole connector with 5 m cable,
female 8-pin connector screw
joint for cable diameter 4 ... 8 mm Sensor protection stainless steel grid Probe cable length
MMT317 0.5, 2, 5 or 10 meters MMT318 2, 5 or 10 meters
Probe installation MMT317
Swagelok
®
NPT 1/2”, ISO 3/8” or ISO 1/2”
Probe installation MMT318
Fitting bodies ISO 1/2”, NPT 1/2” Ball Valve Set BALLVALVE-1
Complies with EMC standard EN61326-1, Industrial environment
Note: When using the current output, the RF field susceptibility level according to standard EN61000-4-3 with a frequency band of 110 ... 165 MHz, is only 3 V/m (generic environment) with the specified accuracy.
®
HUMICAP
is a registered trademark of Vaisala.
<500 Ohm
1
For more information, visit www.vaisala.com or contact us at sales@vaisala.com
Ref. B210831EN-A ©Vaisala 2009
This material is subject to copyright protection, with all copyrights retained by Vaisala and its individual partners. All rights reserved. Any logos and/or product names are trademarks of Vaisala or its individual partners. The reproduction, transfer, distribution or storage of information contained in this brochure in any form without the prior written consent of Vaisala is strictly prohibited. All specifications — technical included — are subject to change without notice.