INSTALLATION 
Do not install the transmitter on the ceiling. Avoid placing the transmitter near heat 
sources, ventilation,
76.9
123.7
9 
5
5.5
24
81
127.3
77.9
60.3
59
Ø4.4 Ø4.4
32.4
20
1.  Find a suitable mounting location for the transmitter. The conditions at the location 
should represent well the area of interest. 
NOTE 
2.  Use the mounting holes to attach the mounting base securely. Use at least two 
screws (not included). The arrow on the mounting base must point straight up after 
installation. Proper orientation is important, so that air will flow through the vents 
on the bottom and top. 
3.  Connect the wiring to the screw terminals on the mounting base. The supply voltage 
and terminal assignments are model-specific; see Wiring on page 2. 
4.  After completing the wiring, connect the cover over the mounting base. 
Vaisala INTERCAP® Humidity and 
Temperature Transmitter Series HMW80 
 and direct sunlight. 
Dimensions (in mm) 
Find Quality Products Online at: sales@GlobalTestSupply.com
M211328EN-C  _______________________________________________________________________  1 
www.GlobalTestSupply.com
 

Quick Guide ____________________________________________________________________ HMW80 
-T
4...20 mA
(-5 ... +55 ºC)
-RH
4...20 mA
(0 ... 100% RH)
+T +RH
Power supply 
10 ... 28 VDC 
R
L
 = 0 ... 500 Ω
Power supply 
10 ... 28 VDC 
R
L
 = 0 ... 500 Ω
mA
mA
-T
4...20 mA
(-5 ... +55ºC)
-RH
4...20 mA
(0 ... 100% RH)
+T +RH
Power supply 
10 ... 28 VDC 
R
L
 = 0 ... 500 Ω
Power supply 
10 ... 28 VDC 
RL = 0 ... 500 Ω
mA
mA
2 11
Pt100
t+
-T
4...20 mA
(-5 ... +55 ºC)
+T
Power supply 
10 ... 28 VDC 
R
L
 = 0 ... 500 Ω
mA
WIRING 
HMW82 
You must connect the RH channel 
of the HMW82, even if you only 
want to measure temperature. 
Connecting the T channel is optional. 
HMW82P100 
TMW82 
HMW82P100 
Includes a passive Pt100 temperature 
sensor (Class F 0.1 IEC 60751) with 
a 3-wire connection. 
Leave the two terminals on the left 
unconnected. 
Find Quality Products Online at: sales@GlobalTestSupply.com
© Vaisala 2016. All rights reserved. _______________________________________________________  2 
www.GlobalTestSupply.com
 

Quick Guide ____________________________________________________________________ HMW80 
-T
0...10 V
(0...100 %RH)
-VS+T +VS
Power supply 
15 ... 35 VDC 
or 24 VAC ±20% 
R
L
 = 10 kΩ min.
-RH +RH
0...10 V 
(-5...+55 ºC)
V
V
-T -VS+T +VS
Power supply 
15 ... 35 VDC 
or 24 VAC ±20% 
R
L
= 10 kΩ min.
-RH +RH
V
V
0...10 V
0...10 V
Recommended wiring for long cables. 
3-wire connection with -VS as common 
-T
0...10 V
(-5 ... +55 ºC)
-VS+T +VS
V
Power supply 
15 ... 35 VDC 
or 24 VAC ±20% 
R
L
 = 10 kΩ min.
-T -VS+T +VS
V
Power supply 
15 ... 35 VDC 
or 24 VAC ±20% 
R
L
 = 10 kΩ min.
0...10 V
Recommended wiring for long cables. 
3-wire connection with -VS as common 
HMW83 
TMW83 
ground. Not recommended if cable resistance is 
ground. Not recommended if cable resistance is 
Find Quality Products Online at: sales@GlobalTestSupply.com
© Vaisala 2016. All rights reserved. _______________________________________________________  3 
www.GlobalTestSupply.com