Vaisala HMW60, HMW70 Technical data

www.vaisala.com
HMW60/70 Humidity and Temperature Transmitters for wall mounting in HVAC applications
Vaisala HUMICAP® Humidity and Temperature Transmitters HMW60 and HMW70 are designed for use in air conditioning applications where accurate and stable control of relative humidity and temperature are required.
Features/Benefi ts
Accuracy up to ±2 %RH
True two-wire transmitters
with 4 ... 20 mA loop powered output (HMW60)
Selectable signal output of
0 ... 1 V, 0 ... 5 V or 0 ... 10 V (HMW70)
Vaisala HUMICAP® Sensor
for excellent accuracy and long-term stability, negligible hysteresis and resistance to dust and most chemicals.
Temperature compensated
Also available as temperature-
only transmitters HMW 60T/70T
NIST traceable
(certifi cate included)
The wall mounted Vaisala HUMICAP® Humidity and Temperature Transmitters HMW60 and HMW70 are designed for monitoring relative humidity and temperature in building energy management systems. The combination of high accuracy, stability and reliable operation, make these products the ideal choice for demanding applications.
Measures both humidity and temperature
The HMW60 and HMW70 transmitters are available in three models: U for humidity measurement-only,
Y for humidity and temperature measurement, and T for temperature only.
Fast, on-site calibration
The accuracy of the transmitters is simple to check using either the Vaisala HUMICAP Humidity and Temperature Meter HM70 or the Vaisala HUMICAP Humidity Indicator HMI41. The calibration can be done in seconds with a single potentiometer without disturbing the operation, resulting in great savings both in maintenance time and costs.
Hand-Held
Technical data
C
60 series: 2-wire, 4 to 20 mA output
Wall mount RH only HMW60U
RH & T HMW60Y T only HMW60T
70 series: 3-wire, variable voltage output
Wall mount RH only HMW70U
RH & T HMW70Y T only HMW70T
Relative humidity
Measurement range 0 ... 95 %RH* Accuracy at +20 °C
Temperature dependence
Response time at +20 °C (+68 °F), 90 % response 15 s Stability Sensor HUMICAP * Output signal corresponds to 0 ... 100 %RH
%RH
3
2
1
0
0 90 100
10 4020 605030 8070 %RH
-1
-2
-3
1.0
0.5
0
-0.5
-1.0
%RH
-5 °C, + 1 %
-10
20
10
0
30
+55, + 0,5 %
40
50
60 °
+2 % RH / 2 years
®
180
General - 60 series
Supply voltage 10 ... 35 VDC (RL = 0 ohm)
20 ... 35 VDC (RL = 500 ohm)
Output signal 4 ... 20 mA
General - 70 series
Supply voltage range depends on the selected output signal
DC AC 0 ... 1V 10 ... 35 V 9 ... 24 V 0 ... 5 V 14 ... 35 V 12 ... 24 V 0 ... 10 V 19 ... 35 V 16 ... 24 V Power consumption @ 24 VAC
HMW70U 10 mA typical HMW70Y 12 mA typical
General
Operating temperature range
electronics -5 ... +55 °C (+23 ... +131 °F) Storage temperature range -40 ... +80 °C (-40 ... +176 °F) Long-term humidity range for
electronics 0 ... 85 %RH Housing
material ABS plastic IP Class 30
Fire resistance UL94-HB
Colour NCS-2502-R Connections screw terminals 0.5 ... 1.5 mm
Complies with EMC standard EN61326 and EN55022
2
Temperature (Y and T models)
Linearity better than 0.1 °C Sensor Pt 1000 IEC 751 class B Measurement range -5 ... +55 °C (+23 ... 131 °F) ** Accuracy'
** Optional temperature scales are available on request.
0.5
0.4
0.3
0.2
0.1
-0.1
-0.2
-0.3
-0.4
-0.5
• C
0
-10 100
206030
40
50
For more information, visit www.vaisala.com or contact us at sales@vaisala.com
• C
Ref. B210840EN-A ©Vaisala 2009
This material is subject to copyright protection, with all copyrights retained by Vaisala and its individual partners. All rights reserved. Any logos and/or product names are trademarks of Vaisala or its individual partners. The reproduction, transfer, distribution or storage of information contained in this brochure in any form without the prior written consent of Vaisala is strictly prohibited. All specifi cations — technical included — are subject to change without notice.