Vaisala GMM20W User Manual

GMM20W CO
Sensor Systems Division U300en-1.1
module
2

INTRODUCTION

Vaisala’s GMM20W module uses a completely new sensor technology. The silicon based CARBOCAP sensor provides for excellent stability and reliability. The GMM20W module requires almost no maintenance: the recommended calibration interval is five years. This combined with the high performance makes the GMM20W modules an ideal choice for OEM applications related to ambient CO measurement.
72 mm

ELECTRICAL CONNECTIONS

The nominal 24 V supply must be connected between terminals + and - on the mother board. The analogue output is available at remaining terminals. The common wire is connected to terminal 0 and the other wire either to terminal V (voltage output) or to terminal mA (current output). The current output is chosen with the jumper 0/4mA (see Figure 3): 4...20mA is chosen by connecting the jumper (default) and the
2
0...20 mA is chosen by disconnecting the jumper. If the relay output of display models is used, note that the wiring is done at the back of the display board. The default relay trigger point has been set to 1000 ppm. This can be changed with the optional software kit 19222GM. For further details, contact your local Vaisala representative.
74 mm
Figure 1 Dimensions
Figure 2 Electrical connections and
leds V7, V10
Note that during normal operation the green led (V10) at the lower righthand corner is blinking. In case the self­diagnostics procedure comes across some abnormality, the red led (V7) lights up (see Figure 2 above).
1999-11-16
GMM20W CO
Sensor Systems Division U300en-1.1
module
2

SERVICE AND MAINTENANCE

The GMM20W module has an excellent stability and requires almost no mainte­nance. A full after sales calibration and service facility is naturally provided by Vaisala and its distributors.
In case the user prefers to do the calibra­tion himself, calibration gases and equipment are also available. Vaisala's portable CO2 meters together with the Calibration Kit provide for easy and convenient on-site calibration checks (see the corresponding manuals for detailed instructions).
GMM20W should be adjusted if the reading differs too much from the reference value during checking (note that in any case, only slight differences are expected). For this purpose, we recommend Vaisala’s Software Kit 19222GM which includes a floppy disk and a serial COM adapter.
Connect the cable to the connector marked “Serial Com” on the main PCB of the module and to the connector A on the serial COM adapter (see Figure 3).
In order to achieve full accuracy, the module has to be calibrated against accurate and traceable calibration gases in stable environmental conditions (temperature, pressure). Accurate cali­brations are usually performed in labora­tories; in these calibrations, temperature and pressure corrections have to be made. For further details, consult your local Vaisala representative.
1999-11-16
Figure 3 Connection of the serial communication cab le
GMM20W CO
Sensor Systems Division U300en-1.1
module
2

POWER SUPPLY REQUIREMENTS

The GMM20W module is designed to operate from a nominal 24 VAC/VDC supply. The power supply should main­tain the voltage between 18...30 VDC or
20...26 VAC for all load conditions and all mains voltages. The power input in­cludes a halfwave rectifier. To avoid current peaks, it is recommended to use a DC supply. The average transmitter current consumption is 85 mA maximum but peak currents of 170 mA may occur during normal operation.
A) NO COMMON LOOP FORMED - RECOMMENDED
24 VAC

CONNECTION TO AN AC SUPPLY

The GMM20W module can also be connected to a 24 VAC supply without an external rectifier. However, when more than one module is connected to one 24 VAC transformer, a common loop is formed and there is an increased risk of a short-circuit. To avoid this, always use separate floating supply for each module (see Figure 4A). However, if several modules have to share one transformer, the phase (∼) must always be connected to + connector in each module (see Figure 4B).
GM M 20W m odule
supply voltage
C o n tr o lle r
signal output
24 VAC
B) COMMON LOOP FORMED - NOT RECOMMENDED!
24 VAC
supply voltage
GM M 20W m odule
GM M 20W m odule
supply voltage
supply voltage
GM M 20W m odule
signal output
C o n tr o lle r
signal output
signal output
Figure 4 AC connections
shared com m on line
1997-07-22
GMM20W CO
Sensor Systems Division U300en-1.1
module
2
TECHNICAL DATA
Carbon dioxide
Measuring range 0...2000 ppm CO2 (nominal) (can be recalibrated for other ranges: 0...5000 ppm, 0...10000 ppm, 0...20000 ppm) Accuracy at 20°C <±[1% FS + 1.5% of the reading] (including non-linearity and calibration uncertainty) Repeatability <+1 % FS Temperature dependence of output < 0.05 %FS / °C Long-term stability (in ambient conditions) <±5 % / 5 years Response time (0...67%) 1 minute
Operating conditions
Operating temperature -5...+45 °C Storage temperature -20...+70 °C Humidity range:
temporarily 0...100 %RH (non-condensing) continuous use 0...85 %RH ( non-co nde nsing)
General
Output signals 0...20 mA or 4...20 mA and 0...10 V Optional outputs relay
LonWorks
Recommended external load: current output max. 500 voltage output min. 1k Relay contact ra tings max. 50 V 0.5A Power supply nominal 24 VDC/VAC (18...30 VDC) Power consumption < 2.5 W Warm-up time < 5 minutes Dimensions: 72 x 74 x 19 mm Weight: 56 g
interface
Accessories
Order code Description
GMI21 Display and relay option GMR20 Relay output option GML20
19222GM Calibration software kit (incl. disk and serial COM adapter) 18192GM Field calibration kit (used with Vaisala’s portable CO2 meter s )
The GMM20W module complies with the following standards and has passed the following tests: EN50081-1 (EN 55022 class B) EN50082-1 (IEC 1000-4-3, IEC 801-4 (1988) )
LonWorks
interface option
1999-11-16
GUARANTEE
Vaisala issues a guarantee for the material and workmanship of this product under normal operating conditions for one (1) year from the
GMM20W CO
Sensor Systems Division U300en-1.1
module
2
date of delivery. Exceptional operating conditions, damage due to careless handling and misapplication will void the guarantee.
1997-07-22
Loading...