Guarantee, service policy, etc. ..................................................rear cover
To check the product suitability for commercial and multiple installations, please contact Tr iton’s
specification advisory service before installation.
Telephone:
Facsimile:
0870 067 3767
0870 067 3334
E mail:
technical@tritonshowers.co.uk
Page 3
Spellbind
PLEASE READ THIS IMPORTANT SAFETY INFORMATION
Products manufactured by Triton are safe and without risk provided they are installed, used and
maintained in good working order in accordance with our instructions and recommendations.
WARNING: DO NOT operate shower if frozen, or suspected of being frozen. It must thaw
out before using.
DO NOT operate the unit if the showerhead or spray hose becomes damaged.
DO NOT restrict flow out of shower by placing showerhead in direct contact with your body.
DO NOT operate the shower if water ceases to flow during use or if water has entered inside
the unit because of an incorrectly fitted cover.
WARNING: If restarting the shower immediately after stopping, be aware that a slug of
hot water will be expelled for the first few seconds.
GENERAL
1
Isolate the electrical and water supplies before
1.1
removing the cover.
Read all of these instructions and retain them
1.2
for later use.
DO NOT take risks with plumbing or electrical
1.3
equipment.
Isolate electrical and water supplies before
1.4
proceeding with the installation.
The unit must be mounted onto the finished
1.5
wall surface (on top of the tiles). Do not tile up
to unit after fixing to wall.
Contact Customer Service (see back page), if
1.6
any of the following occur:
If it is intended to operate the shower at
a)
pressures above the maximum or below the
minimum stated.
If the unit shows a distinct change in
b)
performance.
If the shower is frozen.
c)
If it is intended to operate the shower in areas
1.7
of hard water (above 200 ppm temporary
hardness), a scale inhibitor may have to be
fitted. For advice on the Triton Scale Inhibitor,
contact Triton Customer Service.
The showerhead must be cleaned regularly
1.8
with descalent to remove scale and debris,
otherwise restrictions to the flow on the outlet
of the unit will result in higher temperatures
and could also cause the Pressure Relief Device
in the unit to operate.
This product is not suitable for mounting into
1.9
steam rooms or steam cubicles.
PLUMBING
2
The plumbing installation must comply with
2.1
Water Regulations, Building Regulations or any
particular regulations as specified by Local
Water Company or Water Undertakers and
should be in accordance with BS 6700.
The supply pipe must be flushed to clear
2.2
debris before connecting to the shower unit.
DO NOT solder pipes or fittings within
2.3
A-001-A
300mm of the shower unit, as heat can
transfer along the pipework and damage
components.
DO NOT fit any form of outlet flow control as
2.4
the outlet acts as a vent for the heater can.
DO NOT use excessive force when making
2.5
connections to the flexible hose or
showerhead, finger tight is sufficient.
All plumbing connections must be completed
2.6
before making the electrical connections.
ELECTRICAL
3
The installation must comply with BS 7671
3.1
‘Requirements for electrical installations’ (IEE
wiring regulations), building regulations or any
particular regulations as specified by the local
Electrical Supply Company.
This appliance MUST be earthed.
3.2
In accordance with ‘The Plugs and Sockets etc.
3.3
(Safety) Regulations 1994’, this appliance is
intended to be permanently connected to the
fixed wiring of the electrical mains system.
Make sure all electrical connections are tight
3.4
to prevent overheating.
Fuses do not give personal protection against
3.5
electric shock.
A 30mA residual current device (RCD) MUST
3.6
be installed in all UK electric and pumped
shower circuits. This may be part of the
consumer unit or a separate unit.
Switch off immediately at isolating switch if
3.7
water ceases to flow during use.
Other electrical equipment i.e. extractor fans,
3.8
pumps must not be connected to the circuits
within the unit.
Switch off at isolating switch when not in use.
3.9
This is a safety procedure recommended with
all electrical appliances.
3.10
As with all electrical appliances it is
recommended to have the shower and
installation checked at least every two years by
a competent electrician to ensure there is no
deterioration due to age and usage.
1
Page 4
Spellbind
UNDERSTANDING YOUR SHOWER
INTRODUCTION
SPECIFICATIONS
Introduction
This book contains all the necessary fitting and
operating instructions for your Triton Spellbind
thermostatic electric shower. Please read them
carefully.
The shower installation must be carried out by a
suitably qualified person and in the sequence of
this instruction book.
Care taken during the installation will ensure a
long, trouble-free life from your shower.
Specifications
Electrical
Nominal power Nominal power
rating at 240V rating at 230V
9.5kW – (40A MCB rating) 8.7kW – (40A MCB rating)
10.5kW– (45A MCB rating) 9.6kW – (45A MCB rating)
Water
Inlet connection – 15 mm diameter.
Outlet connection – ½” BSP male thread.
Entry Points
Water – Right: middle back, bottom, top.
Cable – Right: middle back, bottom, top.
Materials
Backplate, cover, controls, showerhead – ABS.
Sprayplate – Acetal.
Elements – Minerally insulated corrosion resistant
metal sheathing.
Dimensions
Height – 335 mm
Width – 225 mm
Depth – 95 mm
Standards and Approvals
Splashproof rating IPX4.
Complies with the requirements of current British
and European safety standards for household
and similar electrical appliances.
Complies with requirements of the British
Electrotechnical Approvals Board (BEAB).
Meets with Compliance with European
Community Directives (CE).
Understanding your shower
IMPORTANT: When first installed the unit
will be empty. It is essential the unit should
contain water before the elements are
switched on. It is vital that the
commissioning procedure is followed.
Failure to carry out this operation will result
in damage to the unit and will invalidate the
guarantee.
I-001-A
Temperature/flow rate
The temperature control on the unit can be
adjusted to provide shower temperatures
nominally between 35°C and 47°C. The unit
will give higher and lower temperatures if given
extreme supply conditions.
Note: The maximum flow rate for the given
temperature will be greater in the summer
than in winter because of ambient temperature
variance of the mains water supply.
It is strongly advised to select economy power
during periods of hot weather, otherwise at all
other times leave the power setting at full to
provide the maximum flow rate.
Safety cut-out
The unit is fitted with a non-resettable overtemperature safety device. In the event of
abnormal operation which could cause unsafe
temperatures within the unit, the device will
disconnect the heating elements. It will require a
visit from a qualified engineer to determine the
nature of the fault and replace the safety device,
once the unit has been repaired.
Replacement parts can be ordered from Customer
Service. See ‘spare parts’ for details and part numbers.
Y-003-A
2
Page 5
Spellbind
MAIN COMPONENTS
Main components
Inside unit (fig.1)
1.Top cable / pipe entry
2.Bottom cable / pipe entry
3.Wall screw fixings
4.Power printed circuit board
5.Thermal cut-out
6.Can and element assembly
7.Ribbon cable connector
8.Terminal block
9.Earth connection
10. PRD
11. Solenoid valve
12. Trim plate
13. Thermostatic valve
14. Scale trap
15. Pressure switch
16. Shower outlet
17. Guide pockets
Inside cover (fig.2)
18. Control printed circuit board
19. Start/stop printed circuit board
20. Cover tags
21. Ribbon cable
NOTE: Not all wiring shown for reasons of clarity
17
4
10
14
5
17
7
13
16
6
3
17
9
11
15
3
Fig.1
1
8
3
12
2
Fig.2
20
21
20
18
19
20
3
Page 6
Meter
Incoming
supply
fuse
Meter
tails
Consumer
unit
Pull cord
isolating switch
Shower
unit
Fuse or
MCB
RCD
(can be part of
consumer unit)
80A or 100A
main switch
Shepperton Park,
Triton Road, Nuneaton,
Warwickshire, CV11 4NR
MCB
30/32A
32A
40A
40A
40A
40/45A
45A
cartridge
fuse
30A
35A
35A
45A
45A
45A
45A
unit
rating
7.0kW
7.5kW
8.0kW
8.5kW
9.0kW
9.5kW
10.5kW
CIRCUIT PROTECTION
ELECTRICAL REQUIREMENTS
The installation, supply cable and circuit protection must conform with BS 7671 (IEE wiring regulations) and be sufficient for the amperage required.The following notes are for guidance only:
1The shower must only be connected to a
230-240V ac supply. If you are installing a shower with a kilowatt rating above 9kW, it is advisable to contact the local electricity supply company.
1.1The electrical rating of the shower is shown on the rating label (Fig.3) within the unit.
switch off the whole installation at the mains
, then the
Electrical requirements
ELECTRICAL REQUIREMENTS
W-006-A
WARNING!
THIS APPLIANCE MUST BE EARTHED
Spellbind
2 Before making any sort of electrical
connection within the installation make sure
that no terminal is live. If in any doubt,
The installation, supply cable and circuit
protection must conform with BS 7671 (IEE
wiring regulations) and be sufficient for the
amperage required.
The following notes are for guidance only:
1 The shower must only be connected to a
230-240V ac supply. If you are installing a
shower with a kilowatt rating above 9kW, it
is advisable to contact the local electricity
supply company.
1.1 The electrical rating of the shower is shown
on the rating label (Fig.3) within the unit.
Fig.3
Fig.4 Schematic of installation circuit
supply and remove the correct fuse.
3 The shower must be connected to its own
independent electrical circuit. IT MUST NOT
be connected to a ring main, spur, socket
outlet, lighting circuit or cooker circuit.
3.1 The electrical supply must be adequate for
the loading of the unit and existing circuits.
4 Check your consumer unit (main fuse box)
has a main switch rating of 80A or above
and that it has a spare fuse way which will
take the fuse or Miniature Circuit Breaker
(MCB) necessary for the shower (Fig.4).
4.1 If your consumer unit has a rating below
80A or if there is no spare fuse way
installation will not be straightforward and
may require a new consumer unit serving
the house or just the shower.
4.2 You will need to contact the local electricity
company. They will check the supply and
carry out what is necessary.
5 For close circuit protection DO NOT use a
rewireable fuse. Instead use a suitably rated
Miniature Circuit Breaker (MCB) or cartridge
fuse (see Table A).
5.1 A 30mA residual current device (RCD) must
be installed in all UK electric and pumped
shower circuits. This may be part of the
consumer unit or a separate unit.
Table A
4
Page 7
Note: Cable selection is dependent on
derating factors
Twin and earth PVC insulated cable
Current carrying capacity
In conduit
trunking
6 mm²
38A
10 mm²
52A
16 mm²
69A
Installed in an
insulated wall
6 mm²
35A
10 mm²
47A
16 mm²
63A
Clipped direct
or buried in a
non-insulated
wall
6 mm²
47A
10 mm²
64A
16 mm²
85A
switch off the whole installation at the mains supply and remove the correct fuse.
3The shower must be connected to its own
independent electrical circuit. IT MUST NOT be connected to a ring main, spur, socket outlet, lighting circuit or cooker circuit.
3.1The electrical supply must be adequate for
the loading of the unit and existing circuits.
4Check your consumer unit (main fuse box)
has a main switch rating of 80A or aboveand that it has a spare fuse way which willtake the fuse or Miniature Circuit Breaker (MCB) necessary for the shower (Fig.4).
4.1If your consumer unit has a rating below
80A or if there is no spare fuse way, then the installation will not be straightforward and may require a new consumer unit serving the house or just the shower.
4.2 You will need to contact the local electricity
company. They will check the supply and carry out what is necessary.
5For close circuit protection DO NOT use a
rewireable fuse. Instead use a suitably rated Miniature Circuit Breaker (MCB) or cartridge fuse (see Table A).
5.1A 30mA residual current device (RCD) must
be installed in all UK electric and pumped shower circuits. This may be part of the consumer unit or a separate unit.
6 A 45 amp double pole isolating switch with
It must have a mechanical indicator showing
must be at least that of the shower circuit protection (see Table B).
8.1To obtain full advantage of the power
provided by the shower, use the shortest cable route possible from the consumer unit to the shower.
cuit should be separated from
will unavoidably be placed in one or more
a minimum contact gap of 3 mm in both
poles must be incorporated in the circuit.
6.1
when the switch is in the OFF position, and
the wiring must be connected to the switch
without the use of a plug or socket outlet.
6.2 The switch must be accessible and clearly
7 Where shower cubicles are located in any
8 The current carrying capacity of the cable
8.1 To obtain full advantage of the power
identifiable, but out of reach of a person
using a fixed bath or shower, except for the
cord of a cord operated switch, and should
be placed so that it is not possible to touch
the switch body while standing in a bath or
shower cubicle. It should be readily
E-002-A
accessible to switch off after using the
shower.
rooms other than bathrooms, all socket
outlets in those rooms must be protected by
a 30mA RCD.
must be at least that of the shower circuit
protection (see Table B).
provided by the shower, use the shortest
cable route possible from the consumer unit
to the shower.
Table B
Spellbind
8.2 It is also necessary to satisfy the
disconnection time and thermal constraints
which means that for any given combination
of current demand, voltage drop and cable
size, there is a maximum permissible circuit
length.
9 The shower cir
other circuits by at least twice the diameter
of the cable or conduit.
9.1 The current rating will be reduced if the
cabling is bunched with others, surrounded
by thermal loft or wall insulation or placed in
areas where the ambient temperature is
above 30°C. Under these conditions,
derating factors apply and it is necessary to
select a larger cable size.
9.2 In the majority of installations, the cable
of the above conditions. This being so, it
is strongly recommended to use a
minimum of 10mm cabling throughout
the shower installation.
9.3 In any event, it is essential that individual
site conditions are assessed by a competent
electrician in order to determine the correct
cable size and permissible circuit length.
5
Page 8
WATER REQUIREMENTS
Isolating
stopvalve
Mains
water
supply
Shower
unit
Switch may
be wall
mounted
in accordance
with IEE regs.
Mains electric supply (via double pole switch)
Double
pole
isolating
switch
Separate
permanently
connected
supply from
consumer unit
Fig.5 Diagrammatic view (not to scale)
WARNING!
If planning to use a silicon seal
around the backplate edge, do not
place sealant in the area of the PRD
exit channel.
Spellbind
Water requirements
The installation must be in accordance with
Water Regulations/Bylaws.
To guarantee activating the heating elements,
the shower must be connected to a mains water
supply with a minimum running pressure of
100kPa (1.0 bar) at a minimum flow rate of nine
litres per minute with a maximum static pressure
of 1 000kPa (10 bar).
Note: For the 10.5kW rated shower, the
minimum running pressure must be 150kPa
(1.5 bar) at a minimum flow rate of eleven litres
per minute with a maximum static pressure of
1 000kPa (10 bar).
If the stated flow rates are not available, it may
not be possible to achieve optimum performance
from the unit throughout the year.
For guidance on the running and static pressures
contact the local Water Authority or consult a
competent plumber.
Under site conditions where the power supply is
below 220 volts and the mains water pressure is
above 5 bar, it is recommended to fit a pressure
reducing valve set at 3.5 bar.
A typical system layout is shown in fig.5.
DO NOT use jointing compounds on any pipe
fittings for the installation.
During periods of high ambient water
temperatures it may be necessary to select a low
power setting to achieve your preferred shower
temperature. The water supply can be taken
from a cold water storage cistern provided there
is a minimum head of ten metres above the
showerhead (fifteen metres for the 10.5kW rated
shower). It must be an independent supply to
the shower only.
If it is intended to operate the shower at
pressures above the maximum or below the
minimum stated, contact Customer Service.
6
Page 9
Spellbind
SITING OF THE SHOWER
Outline of bath
or shower tray
Riser rail can
be mounted either
side of shower
25mm minimum
Soap dish
retaining
ring
Spillover
level
Height of
showerhead
and
shower
to suit
user's
requirement
Shower unit
must not
be within
an area
1 metre
from base
Siting of the shower
IMPORTANT: If installing onto a tiled wall
always mount the unit on the surface of the
tiles. NEVER tile up to the unit.
Refer to fig.6 for correct siting of the shower.
Position the unit where it will NOT be in direct
contact with water from the showerhead.
Position the shower unit vertically.
Allow enough room between the ceiling and the
shower to access the cover top screws.
Note: Water regulations require the showerhead
be ‘constrained by a fixed or sliding attachment
so that it can only discharge water at a point
not less than 25 mm above the spill-over level
of the relevant bath, shower tray or other fixed
appliance’. The use of the supplied soap dish will
in most cases meet this requirement, but if the
showerhead can be placed within a bath, basin
or shower tray, then a double check valve, or
similar, must be fitted in the supply pipework to
prevent back-flow.
Liquid Crystal Display
This shower unit has a LCD which has an
optimum viewing angle that is slightly below eye
level. Position the unit so the display is at nose
level. For multiple users of varying heights, an
optimum shower height must be arrived at.
WARNING!
The shower must not be positioned
where it will be subjected to freezing
W-008-A
conditions.
Fig.6 Diagrammatic view (not to scale)
IMPORTANT: The unit must be mounted on
a flat surface which covers the full width
and length of the backplate. It is important
that the wall surface is flat otherwise
I-002-A
difficulty may be encountered when fitting
the cover and subsequent operation of the
unit may be impaired.
7
Page 10
Spellbind
Area to keep clear
WARNING!
If using a silicon seal around the
backplate edge, make sure the PRD
exit behind the outlet pipe is kept
clear.
Fig.7
Fig.8
Pressure relief safety device
A pressure relief device (PRD) is designed into
the shower unit which complies with European
standards. The PRD provides a level of appliance
protection should an excessive build up of
pressure occur within the shower.
DO NOT operate the shower with a damaged
or kinked shower hose, or a blocked
showerhead which can cause the PRD to
operate.
Make sure the PRD outlet at the bottom of the
unit is not blocked (fig.7).
When commissioning, the showerhead must be
removed from the flexible hose. Failure to follow
this procedure may cause the PRD to operate.
Make sure the shower is positioned over a bath
or shower tray because if the PRD operates, then
water will eject from the bottom of the unit.
Should this happen, turn off the electricity and
water supplies to the shower at the isolating
switch and stopvalve. Contact Customer Service
for advice on replacing the PRD.
Fig.9
8
Page 11
Spellbind
FITTING THE SHOWER TO THE WALL
21mm
Fitting the shower to the wall
WARNING!
Check there are no hidden cables or
pipes before drilling holes for wall
plugs. Use great care when using power
tools near water. The use of a residual
current device (RCD) is recommended.
Note: The control knob is an integral part of the
cover — DO NOT attempt to remove it.
Unscrew the two top and one bottom retaining
screws. There is no need to completely remove
the screws, just enough to lift the cover from the
backplate. To allow access to the pipe and cable
connections remove the trimplate by lifting away
from the backplate.
Entry positions for the mains water are from the
top, bottom or back. Cable entry is via the top,
bottom or back.
Note: Deviations from the designated entry
points will invalidate product approvals.
If bottom surface entry is required, then the
necessary hole will need to be cut out in the
‘thinned section’ of the trimplate using a junior
hacksaw and file (fig.8). Make sure the hole is
large enough to allow the trimplate to fit over
the pipework and to fit snugly back onto the
backplate to prevent water ingress.
If bottom or rear entry is chosen, the pipe trim
will need to be fitted in the top entry position on
the backplate (fig.9).
If installing a supply pipe from the rear or
bottom, the centre of the inlet valve to the wall
surface is 21 mm (fig.10).
Note: If entry is from the rear, the nut of the
compression fitting will be partially behind the
surface of the wall. This area MUST be left clear
when plastering over the pipework in order to
make the nut accessible for future adjustments.
IMPORTANT: Using a suitable sealant,
always seal around the incoming pipework to
prevent water entering the wall.
W-005-A
Fig.10
Fig.11
9
Page 12
Spellbind
WARNING!
If using a silicon seal around the
backplate edge, make sure the PRD
exit behind the outlet pipe is kept
clear (fig.7).
After choosing the site for the shower, use the
backplate as a template and mark the three wall
fixing holes (fig.11).
Drill and plug the wall.
(An appropriate drill bit should be used. If the
wall is brick, plasterboard or a soft building block,
appropriate wall plugs and screws should be fitted).
Screw the top left-hand fixing screw into
position leaving the base of the screw head
protruding 6 mm out from the wall.
Hook the backplate over this screw, then fit the
other two fixing screws into position.
DO NOT fully tighten the screws at this stage,
as the fixing holes are elongated to allow for
out of square adjustment after the plumbing
connections have been completed.
10
Page 13
Spellbind
PLUMBING CONNECTIONS
Inlet
filte
r
Plumbing connections
Plumbing to be carried out before wiring
DO NOT use jointing compounds on any pipe
fittings for the installation.
DO NOT solder fittings near the shower unit
as heat can transfer along the pipework and
damage components.
Compression fittings MUST be used to connect
to the inlet of the shower.
Note: An additional stopvalve (complying with
Water Regulations) MUST be fitted in the mains
water supply to the shower as an independent
means of isolating the water supply should
maintenance or servicing be necessary.
IMPORTANT: Before completing the
connection of the water supply to the inlet
of the shower, and in compliance with Water
Regulations, flush out the pipework to remove
all swarf and system debris. This can be
done by connecting a hose to the pipework
and turning on the mains water supply long
enough to clear the debris to waste.
Procedure
Turn off the water supply either at the mains
stopvalve or the isolating stopvalve. Connect
the mains water supply to the inlet (fig.12) of
the shower via 15 mm copper, stainless steel
or plastic pipe using a 15 mm x 15 mm elbow
compression fitting. The plastic filter protrudes
from the inlet so check it is in place before
connection.
The compression fitting must be pushed fully
home onto the inlet to ensure full engagement.
Note: The inlet fitting is designed to enter a
compression fitting only. DO NOT use push
fit connectors as full engagement cannot be
guaranteed. DO NOT use excessive force when
making these connections.
Make sure the backplate is square on the wall
and tighten the three retaining screws which
hold it to the wall. Check the backplate is not
distorted when screws are fully tightened.
Turn on the mains water supply and check for
leaks in the pipework connection to the shower.
Note: At this stage no water can flow through
the unit.
Fig.12
11
Page 14
Spellbind
ELECTRICAL CONNECTIONS
Cable sheath
stripped back
to minimum
L
N
E
Start/stop
switch
Control
PCB
Power
PCB
Connector
socket
Terminal
block
Thermal
cut-out
Pressure
switch
Thermistor
Earth
post
inlet
Solenoid
valve
outlet
Elements
Fig.13
Fig.14
Electrical connections
SWITCH OFF THE ELECTRICITY SUPPLY AT
THE MAINS.
Fig.13 shows a schematic wiring diagram.
The cable entry points are top, bottom or back.
The cable can be surface clipped, hidden or via
20 mm conduit.
Note: Conduit entry can only be from rear.
Route the cable into the shower unit and
connect to the terminal block as follows:
Earth cable to terminal marked E
Neutral cable to terminal marked N
Live cable to terminal marked L
IMPORTANT: Fully tighten the terminal block
screws and ensure that no cable insulation is
trapped under the screws. Loose connections
can result in cable overheating.
Note: The supply cable earth conductor must be
sleeved (fig.14). The outer sheath of the supply
cable must be stripped back to the minimum.
The supply cable must be secured either by
routing through conduit or in trunking or by
embedding in the wall, in accordance with
BS 7871 (IEE wiring regulations).
The use of connections within the unit to supply
power to other equipment i.e. extractor fans,
pumps etc. will invalidate the guarantee.
DO NOT switch on the electricity supply until
the cover has been fitted.
Note: The elements on UK models are to 240V
specifications and will give a lower kW rating if
the supply voltage is below 240V.
12
Page 15
Spellbind
REPLACING THE COVER
Valve
spindle
Replacing the cover
IMPORTANT: Before finally fitting the cover,
the following steps must be taken:
a. Check all plumbing connections are
watertight.
b. Check terminal block screws are fully
tightened.
c. Make sure the pipe and cable entering
the unit do not prevent the cover locating
correctly to the backplate.
d. Make sure the valve spindle has the ‘flat’
and keyway slot uppermost, the 12 o’clock
position (fig.15).
e. Make sure the temperature control knob
on the cover is rotated to 12 o’clock, the
knob ‘flat’ inside the cover should be
uppermost (fig.16).
Offer the cover to the unit. Carefully locate
the cover tags into the guide pockets on the
backplate and check the wires are not trapped.
Guide into position so that the control spindle
locates correctly (the ‘flats’ ensure the spindle
and knob will only fit one way). While applying
slight pressure to the front cover, secure in
position with the three retaining screws.
The flexible hose can be left attached to the
shower outlet. Make sure the supplied sealing
washer is fitted.
Once the riser rail kit is installed, the shower is
ready for normal operation.
WARNING!
The outlet of the shower acts as a
vent and MUST NOT be connected to
anything other than the hose and
This appliance is not intended for use
by young children or infirm persons
unless they have been adequately
supervised by a responsible person to
ensure that they can use the appliance
Young children should be supervised to
ensure that they do not play with the
W-004-A
showerhead supplied.
Fig.15
Fig.16
WARNING!
W-020-A
safely.
appliance.
13
Page 16
Spellbind
COMMISSIONING
Valve
spindle
Fig.17
Fig.18
Commissioning
WARNING!
Before normal operation of the
shower, it is essential the following
commissioning procedure is completed
The first operation of the shower is intended to
flush out any remaining system debris and to
make sure water is purged through the unit so
that the heater unit contains water before the
elements are switched on.
Refit the trimplate by carefully guiding into the
locating slots in the backplate.
At this stage, the cover is temporarily fitted in
order to carry out the commissioning procedure.
a. Offer the cover to the unit. DO NOT connect
the 14-way ribbon cable at this stage.
b. Make sure the valve spindle has the ‘flat’
and keyway slot uppermost at the 12 o’clock
position (fig.17).
c. Make sure the temperature control knob on
the cover is rotated to 12 o’clock – the knob
‘flat’ inside the cover should be uppermost
(fig.18).
d. Carefully locate the cover tags into the guide
pockets on the backplate and check the wires
are not trapped.
e. Guide into position so that the control
spindle locates correctly (the ‘flats’ ensure the
spindle and knob only fit one way).
Should any difficulty arise, recheck the points
above.
While applying slight pressure to the front
cover, secure in position with the three retaining
screws.
Fit the flexible hose (but without the
showerhead) to the shower outlet, with the
outlet of the hose directed to waste. Check the
supplied sealing washer is in place.
Turn on the water supply to the shower at the
isolating stopvalve. Switch on the electricity
supply to the shower at the isolating switch.
Water will start to flow through the unit and
discharge from the flexible hose.
W-001-A
correctly.
14
Page 17
Spellbind
It will take about thirty seconds for a smooth
flow of water to be obtained while air and any
debris is being dispersed from the shower. When
a smooth flow of water is obtained, disconnect
the electricity supply to the shower at the
isolating switch. This will stop the water flow.
Unscrew the cover retaining screws again and lift
the cover from the backplate.
Attached to the control PCB, inside the cover,
is a 14-way ribbon cable. The ribbon cable
connector must be plugged into the socket
located on the power PCB situated inside the
unit (fig.19). The connector can only be
correctly plugged in one way by virtue of a
location lug on the plug. The ribbon cable also
has a coloured edge which is on the right-hand
side when correctly fitted to the socket.
Fig.19
15
Page 18
Spellbind
OPERATING THE SHOWER
Power button
Cold button
Display
Temperature
control
Start/stop
button
Fig.20
Fig.21
Fig.22
Operating the shower
WARNING!
Before normal operation of the
shower, it is essential the following
commissioning procedure is completed
The shower controls are shown in fig.20.
CAUTION: It is recommended that persons
who may have difficulty understanding or
operating the shower controls should not
be left unattended while using the shower.
Special consideration should be given to
young children and the less able bodied.
Make sure the water supply is turned fully on.
Switch the electric supply back on at the
isolating switch.
Immediately, the start up routine commences
and the display flashes all information for three
seconds (fig.21).
The display then shows ‘OK’ in a blue backlight
(fig.22). It will remain in this standby mode
until the shower is started.
W-001-A
correctly.
To start the shower
Press the START/STOP button and water will
flow.
The display shows ‘FUL’ (fig.23) indicating full
power is being used.
After about five seconds, two ‘UP ARROWS’ start
flashing indicating the unit is working towards
its preset showering temperature (fig.24). This
is achieved shortly when the display shows the
temperature as °C.
Fig.23
To stop the shower
Press the START/STOP button and the phased
shutdown will commence. The current
temperature and segments are replaced with a
flashing ‘SD’ and ‘SHUTTING DOWN’ alternating
on the display (fig.25). Water stops flowing
after about five seconds after which the display
returns to ‘OK’.
The shower can be left in this standby mode
ready for the next immediate user, otherwise,
switch off at the isolating switch.
16
Page 19
Spellbind
Control buttons
Apart from the START/STOP button, there are
two other control buttons — POWER and COLD.
The button marked is for COLD water only.
When pressed the current display is replaced by
‘CLD’ (fig.26). It remains in this state until the
POWER button is pressed. (Adjustment of the
temperature control at this setting has no effect
on the force of the water from the showerhead).
The button marked is the POWER button
which is a toggle switch between full power and
economy power.
Economy is for using less power when the
ambient mains water temperature is high during
hot months.
If the shower is on full power and the POWER
button is pressed, the current display is replaced
by ‘ECO’ for five seconds (fig.27). During this
time, the flow rate decreases to try to achieve
the same temperature as before.
Note: if the setting was high at full power,
then it will not be possible to obtain the same
temperature on economy power. The shower
will try to provide the highest temperature at the
best flow rate.
Note: If the stated flow rate required for the unit
cannot be met due to low water pressure, it will
be necessary to operate the shower on economy
power during hot months because of flow rate
limitations entering the unit.
Full is the maximum power setting which allows
the highest flow achievable for your preferred
temperature.
If the shower is on economy power or the
cold setting and the power button is pressed,
the current display is replaced by ‘FUL’ for five
seconds (fig.28). During this time, the flow
rate increases to achieve the same temperature
as before or to correspond to the current
temperature control position.
It is advisable to leave the power setting at full at
all times, except during periods of hot weather.
Fig.24
Fig.25
Fig.26
Fig.27
Fig.28
17
Page 20
Spellbind
Fig.29
Fig.30
Fig.31
Fig.32
To adjust the shower temperature
The showering temperature is varied by turning
the temperature control which changes the
mix of hot water coming from the heater can
and the incoming cold water. On the display
circumference are eleven outer segments
which represent the range of the temperature
control. Rotating the temperature control causes
segments to light up, indicating the actual
position of the control relative to its minimum
and maximum temperatures.
Fig.29 shows minimum temperature position
(one segment alight that corresponds to the
temperature control).
Fig.30 shows maximum temperature position
(all segments alight that corresponds to the
temperature control).
To decrease the shower temperature
Turn the temperature control anti-clockwise;
the current temperature display is replaced
by two flashing ‘DOWN ARROWS’ (fig.31).
Five seconds later the display shows the new
temperature.
To increase the shower temperature
Turn the temperature control clockwise; the
current temperature display is replaced by two
flashing ‘UP ARROWS’ (fig.32). Five seconds
later the display shows the new temperature.
Note: It is advisable to be certain that the
showering temperature is satisfactory by testing
with your hand before stepping under the
showerhead.
There will always be a time delay of a few
seconds between selecting a temperature
and the water reaching the stable selected
temperature.
18
Page 21
Spellbind
OPERATING FUNCTIONS
Operating functions
Clean showerhead
After a preset number of START/STOP button
operations (nominally 75), the start up routine
acts as normal but instead of a blue ‘OK’ the
display backlight turns red and a flashing ‘CS’
alternating with a flashing ‘showerhead symbol’
and ‘CLEAN’ appear (fig.33).
This is a reminder to clean the showerhead. It
does NOT indicate a defect to the shower.
To remove the red ‘CS’ from the display, press
the POWER and COLD buttons together for
three seconds. Alternatively you can continue
as normal by pressing the START/STOP button
but the ‘symbol’ and ‘CLEAN’ will continue to
flash at the side of the °C figure for a further five
shower operations. After this it will stop (whether
you clean the showerhead or not). The shower
will then reset automatically for a further preset
number of shower operations before flashing the
reminder again.
Low pressure
When the display backlight turns red and
‘LP’ and ’LOW PRESSURE’ flash alternately, it
means the water pressure has fallen below the
minimum required for correct operation of the
shower (fig.34). This causes the low pressure
switch to operate turning off power to the
heating elements preventing any maintained
temperature rises. Water will stop flowing until
the unit has been reset.
Press the ‘START/STOP’ button once to reset the
shower. The shower will shut down and then
begin its start up routine.
If the low water pressure continues, the ‘LOW
PRESSURE’ display will flash once more and the
shower will require resetting again.
If the pressure is acceptable the display will
change to show ‘OK’ in a blue backlight and the
shower will run as normal.
Fig.33
Fig.34
19
Page 22
Spellbind
ADJUSTING THE SHOWERHEAD
Fig.35
Phased shutdown
During use, when the START/STOP button is
pressed, power is switched off to the elements
and the power indicator will extinguish. The
display will change to a flashing ‘SD’. Water
continues to flow for a few seconds, flushing
out any remaining hot water. This makes sure
the next immediate user will not receive a slug
of hot water if standing under the showerhead
when starting the shower.
Safety cut-out
The shower is fitted with a thermal cut-out safety
device. In the event of abnormal operation
which could cause unsafe temperatures within
the unit, the device will disconnect the heating
elements.
It will require a visit from a qualified engineer to
determine the nature of the fault and replace the
safety device, once the unit has been repaired.
WARNING!
After any servicing of mains water
supply, always flush out the pipework
to remove any debris.
Always make sure the unit is started
on COLD in order to purge any air in
W-002-A
the pipework.
Adjusting the showerhead
Five showerhead patterns are available (fig.35).
Adjust the spray pattern by turning the bezel
on the showerhead in either direction until the
desired pattern is obtained.
20
Page 23
Spellbind
Sprayplate
key
Sprayplate
CLEANING THE SHOWERHEAD
Cleaning the showerhead
Before cleaning, turn off the unit at the isolation
switch to avoid the shower being accidentally
switched on.
IT IS IMPORTANT TO KEEP THE SHOWERHEAD
CLEAN TO MAINTAIN THE PERFORMANCE
OF THE SHOWER. The hardness of the water
will determine the frequency of cleaning. For
example, if the shower is used every day in a
very hard water area, it may be necessary to
clean the showerhead on a weekly basis.
Sprayplate removal
There is no need to remove the showerhead
from the hose.
Using the removal tool supplied (fig.36),
locate the raised ’bosses’ into the recesses in the
sprayplate. Hold in firmly and twist anti-clockwise
(fig.37). This movement may turn the cartridge
assembly as well until it reaches a ‘stop’.
Hold the cartridge firmly and continue to twist
anti-clockwise. Having loosened the sprayplate, it
can be unscrewed and removed completely.
Clean the sprayplate with a suitable brush or
preferably leave it to soak overnight in a mild
proprietary descalent. Make sure all traces of
scale are removed and thoroughly rinse in clean
water afterwards.
Before replacing the sprayplate, switch the
power back on at the isolating switch and direct
the hose and showerhead to waste.
Turn the temperature control fully anti-clockwise.
Press the start/stop button.
This operation will flush out any loose scale
deposits in the unit and showerhead. Stop after
about thirty seconds.
Refit the sprayplate by screwing clockwise. Use
the tool to screw the sprayplate tight.
Fig.36
Fig.37
21
Page 24
Spellbind
Inlet
filte
r
Instructions for installers and service engineers only
INSTRUCTIONS FOR INSTALLERS AND SERVICE ENGINEERS ONLY
Fig.38
CLEANING THE INLET FILTER
It is recommended that the filter is periodically
cleaned in order to maintain the performance of
the shower. It is essential that this operation is
carried out by a competent person.
SWITCH OFF THE ELECTRICITY SUPPLY AT
THE MAINS.
Remove the cover. The inlet filter is situated in
the solenoid inlet (fig.38) and can be removed
to clean.
Remove the trimplate and disconnect and
remove the compression fitting to gain access
to the filter. Also, depending on the incoming
pipework arrangements, if there is not enough
slack in the pipework, it could mean the removal
of the unit from the wall.
When cleaning the plastic filter, DO NOT use
a sharp object, as it will cause damage. It is
preferable to use an old toothbrush or similar.
22
Page 25
Spellbind
INSTRUCTIONS FOR INSTALLERS AND SERVICE ENGINEERS ONLY
CLEANING THE SCALE TRAP
It is recommended in hard water areas, the
scale trap is periodically cleaned to maintain the
performance of the shower.
It is essential that this operation is carried out by
a competent person.
SWITCH OFF THE ELECTRICITY SUPPLY AT
THE MAINS.
Remove the cover and unplug the ribbon cable.
The scale trap is located at the lower left-hand
side of the unit. Unscrew the single central screw
(fig.39) then pull off the cap complete with ‘O’
rings.
Be aware of water discharging as the heater can
exhausts.
Clean out the trap and remove all sediment.
Flush the can through by leaving the cap off and
switching on the power at the isolating switch.
Note: Make sure the water that flows out of the
scale trap will safely flow to waste.
Switch off the power at the isolating switch.
Replace the cap making sure the ‘O’ rings are
in place and free from debris. Secure with the
central screw.
Switch the power back on again at the isolating
switch to enable the can to fill with water. Check
for water leakage at the scale trap. When water
flows smoothly from the showerhead stop the
flow by switching off the power at the isolating
switch.
Reconnect the ribbon cable and replace the
cover and secure with the three screws.
Fig.39
23
Page 26
Spare parts
SPARE PARTS
Ref. Description Part No.
Spellbind
2
1
3
4
6
8
9
11
12
15
5
7
10
13
14
1. Printed circuit board:
Power 9.5kW 7073034
Power 10.5kW 7073169
18. Flexible hoses are available in the following
sizes:
1.00 m in white, chrome and gold
1.25 m in white, chrome and gold
1.75 m in chrome only
16
17
18
25
Page 28
Spellbind
FAULT FINDING
IMPORTANT: Switch off the electricity at the mains supply and remove the circuit fuse before
attempting any fault finding inside the unit.
Fault finding
Problem/Symptom Cause Action/Cure
1 Shower inoperable.
2 Water flows when
isolating switch is
switched on.
3 Water too hot.
4 Unstable shower
temperature or flow.
5 Water too cool or
cold.
6 ‘LP’ flashing on
display.
1.1 Interrupted power
supply.
1.2 Unit malfunction.
2.1 Ribbon cable is
not connected.
2.2 Unit malfunction.
3.1 Temperature
control incorrect
setting.
3.2 Unit malfunction.
4.1 Blockages.
4.2 Loose ribbon
cable connection.
4.3 Unit malfunction.
5.1 Temperature
control incorrect
setting.
5.2 Unit malfunction.
5.3 Safety cut-out
operated.
6.1 Water pressure
has dropped below
minimum required.
6.2 Blockage in outlet.
6.3 Loose connection
on PCB.
6.4 Blocked
connecting tube to
pressure switch.
1.1.1 Blown fuse or circuit breaker. Check
supply. Renew or reset fuse or circuit breaker. If it
fails again, consult a qualified electrician.
1.1.2 Power cut? Check other appliances and if
necessary, contact local Electric Supply Co.
1.2.1 Have unit checked by suitably qualified
electrician or contact Customer Service.
2.1.1 Switch off the electric supply, remove the
shower cover and plug in ribbon cable.
2.2.1 Contact Customer Service.
3.1.1 Turn temperature control anti-clockwise.
3.2.1 Contact Customer Service.
4.1.1 Clean showerhead. Check inlet filter.
4.2.1 Check connections on PCB.
4.3.1 Contact Customer Service.
5.1.1 Turn temperature control clockwise.
5.2.1 Contact Customer Service.
5.3.1 The thermal safety cut-out device has
operated. Have unit checked by suitably qualified
electrician or contact Customer Service.
6.1.1 Wait until water pressure has returned to
normal.
6.2.1 Check and clean outlet and/or
showerhead.
6.3.1 Check connection on PCB from pressure
switch.
6.4.1 Make sure the tube from solenoid valve to
pressure switch is not kinked or blocked.
26
Page 29
Spellbind
FAULT FINDING
Problem/Symptom Cause Action/Cure
7 Water continues
to flow when unit is
isolated at isolating
switch.
8 Pressure relief device
has operated (water
ejected from PRD
tube).
7.1 Debris in solenoid.
8.1 Blocked
showerhead.
8.2 Twisted/blocked
flexible shower hose.
8.3 Showerhead
not removed whilst
commissioning.
7.1.1 Contact Customer Service for advice.
8.1.1 Clean or replace blocked showerhead
cartridge and then fit a new PRD.
8.2.1 Check for free passage through hose.
Replace the hose if necessary, then fit new PRD.
8.3.1 Fit new PRD. Commission unit with
showerhead removed.
27
Page 30
Entry Points
Diagram Key:
Water Entry Points
Cable Entry Points
Spellbind
28
Page 31
Spellbind
As a producer and a supplier of electric showers, Triton Showers is committed to the protection of the environment
WEEE Directive – Policy Statement
via our own environmental policy and the compliance with the WEEE directive.
Triton Showers is fully registered with the Environment Agency under the following schemes:
Repic: Producers take-back scheme (PTS), registration number WEE/EJ3466QV
Valpak: Distributor take-back scheme (DTS), registration number 9659
All our electric products are labelled accordingly with the crossed out wheeled bin symbol. This indicates, for
disposal purposes at end of life, that these products must be taken to a recognised collection points, such as
local authority sites/local recycling centres; this will be free of any charges. Do not return to Triton Showers.
29
Page 32
UK SERVICE POLICY
In the event of a product fault or complaint occurring, the following
procedure should be followed:
1. Telephone Customer Service on 0844 980 0750 having available,
your details including post code, the model number and power
rating of the product, together with the date of purchase and, where
applicable, details of the particular fault.
2. If required, the Customer Service Advisor will arrange
for a qualified engineer to call.
3. All products attended to by a Triton service engineer must be
installed in full accordance with the Triton installation guide
applicable to the product. (Every product pack contains an installation
guide, however, they can also be bought via our Customer Service Spares
Department).
4. Our engineer will require local parking and if a permit is required this
must be available to the engineer on arrival at the call.
5. It is essential that you or an appointed representative (who must
be over 18 years of age) is present for the duration of the service
engineer's visit. If the product is in guarantee you must produce
proof of purchase.
6. Where a call under the terms of guarantee has been booked and
the failure is not product related (i.e. scaling and furring, incorrect
water pressure, pressure relief device operation or electrical/plumbing
installation fault) a charge will be made. A charge will also be issued
if nobody is at home when the service engineer calls or adequate
parking/permit is not available.
7. If the product is no longer covered by the guarantee an up front
fixed fee will be charged before the site visit.
8. Should proof of purchase not be available on an “in-guarantee” call,
or should the service engineer find that the product is no longer
under guarantee, the engineer will charge the same fixed price and
the customer will be expected to pay the engineer before he leaves.
If payment is not made on the day an administration charge will be
added to the fixed charge.
9. If a debt is outstanding from a previous visit, or from any other Triton
purchase. Triton reserves the right to withhold service until the debt
has been settled.
10. Triton takes the health, safety and wellbeing of its employees very
seriously and expects customers to treat all staff members with respect.
Should any employee feel threatened or receive abuse, either verbally
or physically, Triton reserves the right to withhold service and will
support the employee with a legal prosecution.
Replacement Parts Policy
It is the policy of Triton Showers to maintain parts availability for the
duration of production and a period of 5 years thereafter in accordance
with industry standards. In the event of a spare part not being available a
substitute part will be supplied.
Spare parts can be ordered via our online spare parts store, or by
telephoning Triton Spares Department. Payment should be made by
credit/debit card (excluding American Express or Diners Card). Payment
can also be made by pre-payment of a pro-forma invoice, by cheque or
postal order.
Telephone orders are based on information given during of the call.
Before contacting Triton, please verify your requirements using the
information contained in the user guide. Triton cannot accept liability for
incorrect part identification.
TRITON STANDARD GUARANTEE
Triton guarantee this product against all mechanical and
electrical defects arising from faulty workmanship or
materials for a period of two years for domestic use only,
from the date of purchase, provided that it has been
installed by a competent person in full accordance with the
fitting instructions.
Any part found to be defective during this guarantee period
we undertake to repair or replace at our option without
charge so long as it has been properly maintained and
operated in accordance with the operating instructions, and
has not been subject to misuse or damage.
This product must not be taken apart, modified or repaired
except by a person authorised by Triton. This guarantee
applies only to products installed within the United Kingdom
and does not apply to products used commercially. This
guarantee does not affect your statutory rights.
What is not covered:
1. Breakdown due to: a) use other than domestic use by
you or your resident family; b) wilful act or neglect; c) any
malfunction resulting from the incorrect use or quality of
electricity, gas or water or incorrect setting of controls; d)
failure to install in accordance with this installation guide.
2. Claims for missing parts once the product has been
installed.
3. Repair costs for damage caused by foreign objects
or substances.
4. Total loss of the product due to non-availability
of parts.
5. Compensation for loss of use of the product or
consequential loss of any kind.
6. Call out charges where no fault has been found with the
appliance.
7. Call out charges where the water supply cannot be
isolated, this includes consequential losses arising from
unserviceable supply valves.
8. The cost of repair or replacement of pressure relief
devices, showerheads, hoses, riser rails and/or wall
brackets, isolating switches, electrical cable, fuses and/or
circuit breakers or any other accessories installed at the
same time.
9. The cost of routine maintenance, adjustments, overhaul
modifications or loss or damage arising therefrom,
including the cost of repairing damage, breakdown,
malfunction caused by corrosion, furring, pipe scaling,
limescale, system debris or frost.