Tripp Lite SU20KRTHW User Manual

Tripp Lite
1111 West 35th Street
Chicago, IL 60609 USA
Telephone: +(773) 869 1234
E-mail: saleshelp@tripplite.com
Model Number: SU20KRTHW
Highlights
20kVA / 20,000VA / 18,000W on-line double-conversion UPS; 0.9 power factor
200/208/220/230/240V 50/60Hz output; Economy mode option
Hot-swap power and battery modules, N+1 fault tolerance at loads up to 10kVA
USB, RS232 & EPO ports; support for SNMP/WEB and contact-closure card
options
Front panel LEDs with detailed LCD monitoring and control screen
Expandable runtime with optional external battery packs
Hardwire input (3 wire); Hardwire output
Description
Tripp Lite SU20KRTHW 20,000VA / 20kVA / 18,000 watt online, double-conversion UPS system offers complete power protection for critical server,
network and telecommunications equipment in a 12U rack/tower configuration. This system delivers complete N+1 redundancy when used at loads
up to 10kVA, and non-redundant operation at loads between 10 and 20kVA. Fault-tolerant auto-bypass prevents unexpected service interruptions
during UPS overload or internal fault conditions. Included parallel PDU with manual bypass switching enables hot-swappable replacement of all major
UPS system components in both N+1 and combined operating modes. Enhanced availability, fault tolerance and simple hot-swap replacement
options make this UPS ideal for advanced networking applications in data centers, computer rooms, network closets and rugged industrial locations.
Package Includes
Two SU10000RT3UPM UPS power modules
Two BP240V10RT3U battery packs
SUPDMB20KHW PDU with Bypass switch
4-post rackmount installation rails
PowerAlert software and cabling
Features
Tripp Lite SU20KRTHW 20kVA, 20,000VA / 18,000 watt on-line, double-conversion UPS system in 12U total rack/tower configuration
Unique configuration offers 20kVA non-redundant operation and automatic N+1 redundancy at load levels of 10kVA and under
Included Parallel PDU with manual bypass switch enables hot-swap replacement power modules at any supported load level
Hardwire input and output connections
Maintains full-time sine wave output within 2% of selectable 200/208/220/230/240V nominal
Supports 50/60Hz operation for worldwide frequency compatibility
Expandable runtime with optional external battery packs
Some external battery configurations require the use of Tripp Lite's External Battery Configuration Software (see manual)
Battery independent restart
Highly efficient economy mode option
Optional SNMPWEBCARD, RELAYIOCARD and RELAYIOMINI interface modules available (RELAYIOMINI requires removal of USB
interface module)
HID-compliant USB interface
Includes Free PowerAlert monitoring software; PowerAlert LOCAL, PowerAlert NSA and PowerAlert NMS for monitoring up to 250
SNMP-enabled UPS, PDU and other networking devices
Optional 2POSTRMKITHD supports installation in 2 post 19 inch racks (4 required)
Optional 2-9USTAND supports upright tower placement (2 required)
Supports Emergency Power Off (EPO) via built-in interface
Front panel LEDs and LCD readout with scroll controls
LED / LCD display panel rotates for viewing in rackmount or tower configurations
External battery packs are field replaceable and hot swappable
Frequency conversion mode enables conversion of 60Hz to 50Hz or 50Hz to 60Hz (no de-rating)
Specifications
OUTPUT
Output Volt Amp Capacity (VA)
20000
Output kVA capacity (kVA)
20
Output Watt Capacity (watts)
18000
Output kW capacity 18
Output power factor 0.9
Output Capacity Details
Supports up to 105% load continuously in double conversion mode, 106 to 125% for 1 minute, 126% to 150% for 30 seconds; Loads over 150% trigger immediate bypass mode operation to support loads directly from mains power; Double conversion mode is automatically restored as load levels are reduced to 95% or less
Nominal Output Voltage(s) Supported
200V; 208V; 220V; 230V; 240V
Nominal Voltage details
Voltage selection via front panel LCD interface
Frequency compatibility
50 / 60 Hz; Supports 50 to 60 Hz and 60 to 50 Hz conversion
Frequency compatibility details
Output frequency matches input nominal on startup; Frequency conversion mode enables conversion of 60Hz to 50Hz or 50Hz to 60Hz (no de-rating)
Output voltage regulation (line mode)
+/- 2%
Output voltage regulation (Economy line mode)
+/- 10%
Output voltage regulation (Battery mode)
+/- 2%
Built-in UPS output receptacles
Hardwire
Output AC waveform (AC mode)
Sine wave
Output AC waveform (battery mode)
Pure Sine wave
INPUT
Rated input current (at maximum load)
112.2A (200V), 108A (208V), 102A (220V), 97.6A (230V), 93.6A (240V)
Nominal Input Voltage(s) Supported
200V AC; 208V AC; 220V AC; 230V AC; 240V AC
UPS input connection type
Hardwire
UPS input connection description
3 wire single phase input (L1, L2, G)
Recommended Electrical Service
120A @ 200V-240V (L, N, PE), or 125A @ 200V, 208V, or 240V (L1, L2, G)
Phase Single-Phase
BATTERY
Full load runtime (minutes)
4.3 minutes (18,000 watts)
Half load runtime (minutes)
12.5 minutes (9000 watts)
Expandable battery runtime
Runtime is expandable with external battery packs
External battery pack compatibility
BP240V10RT3U; BP240V557C-1PH; BP240V787C-1PH; BP240V1037C-1PH; BP240V1407C-1PH
Expandable runtime description
For best results, add external batteries in multiples of two so that both included 10kVA power modules have an equal number and type of connected battery packs
DC system voltage (VDC)
240
Battery recharge rate (included batteries)
Less than 8 hours from 10% to 90%
Battery replacement description
Hot-swappable, user replaceable external battery packs
VOLTAGE REGULATION
Voltage regulation description
2% output voltage regulation in standard online, double-conversion mode
Overvoltage correction
Corrects overvoltages up to 300V
Undervoltage correction
Corrects undervoltages as low as 100V
LEDS ALARMS & SWITCHES
LED Indicators 6 LEDs indicate line power, online mode, economy/bypass mode, on-battery, charger and AC output status; LCD
screen offers additional information and control options
Front panel LCD display
Selectable LCD display with scroll and selection buttons enables UPS control and detailed monitoring options; LED/LCD panel rotates for viewing in rack/tower formats; LCD Display supports ENGLISH, FRENCH, GERMAN, ITALIAN, SPANISH and PORTUGUESE (see manual)
Alarms Unique audible alarms for all major UPS, environmental and power conditions (see manual)
Alarm cancel operation
Alarm cancel switch
Switches 2 Switches control off/on power status and alarm-cancel/self-test operation; 2 additional switches support set and
execute scrolling LCD functions; bundled PDU includes bypass switch to enable hot-swap UPS power module replacement
SURGE / NOISE SUPPRESSION
UPS AC suppression response time
Instantaneous