SmartOnline 208/240V 20kVA 18kW
Highlights
20kVA / 20,000VA / 18,000W
on-line double-conversion UPS;
0.9 power factor
200/208/220/230/240V 50/60Hz
output; 96% Efficient
Economy-mode option
Hot-swap power and battery
modules, N+1 fault tolerance at
loads up to 10kVA
USB, RS232 & EPO ports; slot
for network management card
options
Front panel LEDs with detailed
LCD monitoring and control
screen
Expandable runtime with optional
external battery packs
Hardwire input (3 wire); L6-20R
and L6-30R outlets
Package Includes
Two SU10000RT3UPM UPS
power modules
Two BP240V10RT3U battery
packs
SUPDMB20K8 PDU with Bypass
switch
4-post rackmount installation kit
PowerAlert software and
complete cabling
Double-Conversion UPS, N+1, 12U, Network Card
Slot, USB, DB9, Bypass Switch, L6-20R
MODEL NUMBER: SU20KRT8
Description
Tripp Lite SU20KRT8 20,000VA / 20kVA / 18,000 watt online, double-conversion UPS system offers complete
power protection for critical server, network and telecommunications equipment in a 12U rack/tower
configuration. This system delivers complete N+1 redundancy when used at loads up to 10kVA, and
non-redundant operation at loads between 10 and 20kVA. Fault-tolerant auto-bypass prevents unexpected
service interruptions during UPS overload or internal fault conditions. Included parallel PDU with manual bypass
switching enables hot-swappable replacement of all major UPS system components in both N+1 and combined
operating modes. Enhanced availability, fault tolerance and simple hot-swap replacement options make this UPS
ideal for advanced networking applications in data centers, computer rooms, network closets and rugged
industrial locations.
Features
Tripp Lite SU20KRT8 20kVA, 20,000VA / 18,000 watt on-line, double-conversion UPS system in 12U total
rack/tower configuration
Unique configuration offers 20kVA non-redundant operation and automatic N+1 redundancy at load levels of 10kVA and under
Included Parallel PDU with manual bypass switch enables hot-swap replacement of power modules at any supported load level
Hardwire input; 8 L6-20R & 2 L6-30R outlets
Maintains full-time sine wave output within 2% of selectable 200/208/220/230/240V nominal
Supports 50/60Hz operation for worldwide frequency compatibility
Expandable runtime with optional external battery packs
Some external battery configurations require the use of Tripp Lite's External Battery Configuration Software(see manual)
Battery independent restart
Intelligent battery management system with temperature-compensated charging extends battery life
Highly efficient economy mode option
Slot for optional network management cards, such as Tripp Lite's SNMPWEBCARD, RELAYIOCARD and RELAYIOMINI modules
available(RELAYIOMINI requires removal of USB interface module)
Applications utilizing the optional network communications card require two SNMPWEBCARD accessories(install one per included power module)
HID-compliant USB interface
Includes Free PowerAlert monitoring software; PowerAlert LOCAL, PowerAlert NSA and PowerAlert NMS for monitoring up to 250 SNMP-enabled UPS,
PDU and other networking devices
Optional 2POSTRMKITHD supports installation in 2 post 19 inch racks(4 required)
Optional 2-9USTAND supports upright tower placement(2 required)
Supports Emergency Power Off(EPO) via built-in interface
Front panel LEDs and LCD readout with scroll controls
LED / LCD display panel rotates for viewing in rackmount or tower configurations
External battery packs are field replaceable and hot swappable
Frequency conversion mode enables conversion of 60Hz to 50Hz or 50Hz to 60Hz(no de-rating)
Specifications
OUTPUT
Output Volt Amp Capacity (VA) 20000
Output kVA Capacity (kVA) 20
Output Watt Capacity (Watts) 18000
Output kW Capacity (kW) 18
Output Capacity Details
Power Factor 0.9
Crest Factor 3:1
Nominal Output Voltage(s)
Supported
Nominal Voltage Details Voltage selection via front panel LCD interface
Frequency Compatibility 50 / 60 Hz; Supports 50 to 60 Hz and 60 to 50 Hz conversion
Frequency Compatibility Details
Output Voltage Regulation (Line
Mode)
Output Voltage Regulation
(Economy Line Mode)
Output Voltage Regulation (Battery
Mode)
Output Receptacles (8) L6-20R; (2) L6-30R
Output Circuit Breakers 8 20A breakers protect one L6-20R outlet each, 2 30A breakers protect one L6-30R outlet each
Supports up to 105% load continuously in double conversion mode, 106 to 125% for 1 minute, 126% to 150% for 30
seconds; Loads over 150% trigger immediate bypass mode operation to support loads directly from mains power;
Double conversion mode is automatically restored as load levels are reduced to 95% or less
200V; 208V; 240V
Output frequency matches input nominal on startup; Frequency conversion mode enables conversion of 60Hz to
50Hz or 50Hz to 60Hz (no de-rating)
+/- 2%
+/- 10%
+/- 2%
Output AC Waveform (AC Mode) Pure Sine wave
Output AC Waveform (Battery Mode) Pure Sine wave