Document Attached:
ABB ODIN Meter Technical Documentation
Data Sheet
EM3/../ODIN
EM3/../ODIN Three Phase Electricity Meter Data Sheet TA200706 Issue 1/A 14/7/031
Page 2
EM3/CT/NData Sheet
TrendControl Systems Ltd reserves the right to revise this publication from time to time and make changes to the content hereof
without obligation to notify any person of such revisions or changes.
Trend Control Systems Ltd. P.O. Box 34 Horsham Sussex RH12 2YF England Tel:+44 (0)1403 211888 Fax:+44 (0)1403 241608 www.trend-controls.com
2
EM3/../ODIN Three Phase Electricity Meter Data Sheet TA200706 Issue 1/A 14/7/03
Page 3
ODIN Meter
An electricity energy meter from ABB
Technical documentation
Page 4
ODIN Meter
Contents
General description .............................................................................................................. 2
OD4165 direct connection, 3 phase meter up to and including 65 A ............................... 3
OD4110 transformer connection, 3 phase meter ............................................................... 4
Example of connections ....................................................................................................... 8
Page 5
ODIN Meter
General Description
ODIN Meter is a compact electricity energy meter made for measuring active
electrical energy and designed to be mounted on a DIN rail in distribution boards
or in standard cabinets.
During the development process creating SIMPLICITY was the number one priority.
The ODIN Meter shall be perceived as easy to install, use and distribute.
St375010
Examples of this can already be seen on the front of the electricity energy meter,
clear marking, strong screws in the connecting terminal and an easy to read display.
Enclosed in the carton are easy to understand instructions, which use text and
diagrams to describe in detail how the installation should be carried out.
The ODIN Meter is certified according to the international standard IEC 61036. The
standard covers several technical requirements including climate, mechanics,
electronics, EMC and accuracy. Furthermore the ODIN Meter has a national
approval from Sweden’s Test and Research Institute (SP) as a revenue meter. This
guarantees the ODIN Meter is highly reliable, has a long life expectancy and
maintains its measuring accuracy.
3ABB
Page 6
ODIN Meter
OD4165 direct connection, 3 phase meter up to
and including 65 A
Article numberTypeVoltage (V)Pulse output frequency
2CMA131024R1000OD4165230/400V100 imp./kWh
Technical Data
St375010
Voltage:
Voltage range-20% to +15%
Max current65 A
Start current25 mA
Power consumption of current circuits< 3 VA/phase
Frequency50/60 Hz
Accuracy of measurementClass 2 (±2%)
StandardIEC 61036
Temperature range-25 to +55oC
Material of front coverPolycarbonate
Material of back coverPolycarbonate/glass fibre
Resistance to heat and fireEquivalent to IEC 695-2-1
Protection against penetration of dust and waterIP 20
Connection area in the current connecting terminals1 – 16 mm
Pulse output
Connection area in the connecting terminal0.5 – 2.5 mm
External pulse voltage5 – 40 V DC
Max. current100 mA
Pulse length100 ms ±2.5 ms
Pulse frequency100 imp/kWh
StandardIEC 62053-1 (S0)
LED
Pulse frequency100 imp/kWh
Pulse length40 ms
DisplayLCD with 7 digits
3x230/400 V AC
2
2
without a
decimal place, 6 mm
Front view
Type description
St375004
Load indicator
OD4165
Drestromzahler 5(65)A Kl.2
Electricity meter 5(65)A Cl.2
Phase indicator
Direct connection
Identification No.
Wiring diagram
National approval
symbol (SP)
LED
frequency
Pulse output
frequency
4ABB
Page 7
St375010
ODIN Meter
OD4110 connection via external current transformers,
3 phase meter
Article numberTypeVoltage (V)Pulse output frequency
2CMA1310251000OD4110230/400V1 imp./kWh
Technical Data
Voltage:3x230/400 V AC
Voltage range-20% to +15%
Max. current10 A
Starting current15 mA
Power consumption of current circuits< 0.02 VA/phase
Power consumption of voltage circuits< 2 VA/phase
Frequency50/60 Hz
Accuracy of measurementClass 2 (±2 %)
StandardIEC 61036
Temperature range-25 to +55oC
Programmable transformer ratios5/5, 75/5, 100/5
Material of front coverPolycarbonate
Material of back coverPolycarbonate/glass fibre
Resistance to heat and fireEquivalent to IEC 695-2-1
Protection against penetration of dust and waterIP 20
Connection area in the current connection terminal1 – 16 mm