TREND 963 User Manual

4 (1)
TREND 963 User Manual

Information Sheet

963 and TOPS

BACnet Protocol Implementation Conformance Statement

BACnet Protocol Implementation Conformance Statement

This statement describes the BACnet capabilities of the 963 Supervisor v3.10 when it is used in conjunction with the Trend Open

Protocol Server v1.1 and its BACnet driver.

Date:

19/01/2009

 

Vendor Name:

Trend Control Systems Ltd.

 

Product Name:

963 Supervisor

 

Product Model Number:

963, TOPS

 

Applications Software Version: TOPS Iss 2.00

Firmware Revision: Detailed firmware revision can be read from

the TOPS Device object

BACnet Protocol Revision:

4

Product Description

963 is a graphical, real-time, user interface for the building control system. It enables the user to monitor plant or building services, and make changes to the way the building is controlled from a graphical display. TOPS provides communications facilities to other applications when used with 963, it enables 963 to communicate with BACnet devices enabling the 963 to read values from, or write values to those devices, and receive alarms from the BACnet devices.

List all BACnet Interoperability Building Blocks Supported (Annex K):

ID

BIBB

Title

1.1

DS-RP-A

Data Sharing-ReadProperty-A

1.3

DS-RPM-A

Data Sharing-ReadProperty Multiple-A

1.7

DS-WP-A

Data Sharing-WriteProperty-A

1.9

DS-WPM-A

Data Sharing-WritePropertyMultiple-A

2.1

AE-N-A

Alarm and Event-Notification-A

3.1

SCHED-A

Scheduling-A

4.4

T_ATR_A

Trending-Automated Trend Retrieval-A

5.1

DM-DDB-A

Device Management-Dynamic Device Building-A

Segmentation Capability

  Segmented requests supported

Window Size

Segmented responses supported

Window Size

Standard Object Types Supported

An object type is supported if it may be present in the device. For each standard Object Type supported provide the following data:

1)Whether objects of this type are dynamically creatable using the CreateObject service.

2)Whether objects of this type are dynamically deletable using the DeleteObject service.

3)List of the optional properties supported.

4)List of all properties that are writable where not otherwise required by this standard.

5)List of proprietary properties and for each its property identifier, datatype, and meaning.

6)List of any property range restrictions.

Device Object Type

1.Creatable: No

2.Deletable: No

3.Optional Properties Supported: Location

Description Max_Segments_Accepted

APDU_Segment_Timeout

Configuration_Files

Last_Restore_Time

Backup_Failure_Timeout Active_COV_Subscriptions

4.Writeable Properties: None

5.Proprietary Properties: None

6.Property Range Restrictions: None

963 and TOPS BACnet PICS TP201011 Issue 2 19/01/2009

1

963 and TOPS

Information Sheet

 

 

Available BACnet Properties

The tables below list the BACnet objects, and properties that the 963 can read from, or write to when used in conjunction with

TOPS.

BACnet Analogue Input Object

The BACnet analogue input object maps to the Trend sensor module.

BACnet Property

Read/Write

Trend Parameter

Object_Name

Read

Label ($)

Present_Value

Read

Value (V)

Units

Read

Units (%)

BACnet Binary Input Object

The BACnet binary input object maps to the Trend digital input module.

BACnet Property

Read/Write

Trend Parameter

Object_Name

Read

Label ($)

Present_Value

Read

Value (V)

BACnet Analogue Output Object

The BACnet analogue output object maps to the Trend analogue driver module.

BACnet Property

Read/Write

Trend Parameter

Object_Name

Read

Label ($)

Present_Value

Read

Value (V)

Units

Read

Units (%)

BACnet Schedule Object

The BACnet schedule object maps to the Trend time zone module.

BACnet Property

Read/Write

Trend Parameter

Object_Name

Read

Label ($)

Exception_Schedule

Read/Write

Exceptions (Cn)

Weekly_Schedule

Read/Write

Normal Week Wn).

BACnet Analogue Value Object

The BACnet analogue value object maps to the Trend knob module.

BACnet Property

Read/Write

Trend Parameter

Object_Name

Read

Label ($)

Present_Value

Read/Write

Value (V)

Units

Read

Units (%)

Low_Limit

Read

Bottom Range (B)

High_Limit

Read

Top Range (T)

BACnet Binary Value Object

The BACnet binary value object maps to the Trend switch module.

BACnet Property

Read/Write

Trend Parameter

Object_Name

Read

Label ($)

Present_Value

Read/Write

Value (V)

BACnet Binary Output Object

The BACnet binary output object maps to the Trend digital driver module.

BACnet Property

Read/Write

Trend Parameter

Object_Name

Read

Label ($)

Present_Value

Read

Value (V)

Units

Read

Units (%)

BACnet Device Object

The BACnet device object maps to the Trend time module, and address module.

BACnet Property

Read/Write

Trend Parameter

 

 

Time Module

Local_Time

Read

Hour (H)

Local_Time

Read

Minute (N)

Local_Date

Read

Day (D)

Local_Date

Read

Month (M)

Local_Date

Read

Year (Y)

Local_Date

Read

Day of Week (W)

 

 

Address Module

Object_Name

Read

Identifier (D)

Firmware_Version

Read

Version (C)

BACnet Trend Log Object

BACnet Trend Log Object maps to the Trend plot module.

BACnet Property

Read/Write

Trend Parameter

Buffer_Size

Read

Number

of

 

 

Records (N)

Record_Count

Read

Record Count (R)

Total_Record_Count

Read

Total

Record

 

 

Count (C)

 

Log_Buffer

Read

Log Values (Bn)

Log_Interval

Read

Interval (I)

 

Object_Name

Read

Label ($)

 

Notification_Threshold

Read

N o t i f i c a t i o n

 

 

Threshold (n)

R e c o r d s _ S i n c e _

Read

Records

Since

Notification

 

Last Notification

 

 

(r)

 

Last_Notify_Record

Read

Last notify Record

 

 

(l)

 

2

963 and TOPS BACnet PICS TP201011 Issue 2 19/01/2009