Transition Networks CPSMP-140, CPSMP-130 User Manual

User’s Guide
+
+
+
+
s
d
w
0 I
­+
CPSMP-130
48-VDC Power Supply Module
CPSMP-140
24-VDC Power Supply Module
13-Slot PointSystem™ Accessory
The Transition Networks CPSMP-130 power supply is a 48-VDC slide-in-module that provides optional, redundant power to the CPSMC1310-100 13-slot PointSystem™ chassis and any installed media converter slide-in-modules and management modules.
The Transition Networks CPSMP-140 power supply is a 24-VDC slide-in-module that provides optional, redundant power to the CPSMC1320-100 13-slot PointSystem™ chassis and any installed media converter slide-in-modules and management modules.
An On/Off switch that, when set to “I”, allows the power supply module to supply power to the chassis, and any installed modules.
•A panel fastener screw that secures the power supply module to the chassis.
•A power LED indicator.
•A handle for installing and removing the power supply module to/from the chassis.
•A fuse installed on the circuit board inside the power supply module’s housing.
A set of three (3) external power connectors that distribute power from an external DC outlet to a chassis ground connector, a positive (+) connector, and a negative (-) connector on the power supply module.
On/Off Switch
I 0
­+
Panel Fastener Scre Power LED
Handle
Fuse (on the circuit boar
External Power Connector
Install the Power Supply Module . . . . .3
Connect to External Power . . . . . . . . .4
Replace the Power Supply Module . . .6
Replace the Fuse . . . . . . . . . . . . . . . . .8
Technical Specifications . . . . . . . . . .10
Troubleshooting . . . . . . . . . . . . . . . .11
Contact Us . . . . . . . . . . . . . . . . . . . .11
Compliance Information . . . . . . . . . .12
CPSMP-130 & CPSMP-140
READ AND FOLLOW ALL WARNING NOTICES & INSTRUCTIONS MARKED ON THE PRODUCT OR INCLUDED IN THE MANUAL.
CAUTION: All installation and service must be performed by qualified service personnel.
CAUTION: Wear a grounding device and observe electrostatic discharge precautions when installing or servicing the power supply module. Failure to observe this caution could result in damage to, and subsequent failure of, the power supply module.
The Power Supply Module in the 13-Slot Chassis
CPSMP-130 Power Supply (48-VDC)
The CPSMP-130 power supply module may replace an existing 48-VDC power supply or be installed in the second installation slot (see drawing below) of the PointSystem™ 13-slot chassis to become the optional, redundant power supply.
WARNING: Do NOT connect the power supply module to the external power source before installing it into the chassis. Failure to observe this caution could result in equipment damage and/or personal injury or death.
Install the Power Supply Module
CAUTION: Ensure that the power supply module has been disconnected from the external power source and the module’s On/Off switch has been set to “0”. Failure to observe this caution could result in damage to, and subsequent failure of, the power supply module.
NOTE: The power supply module may be “hot swapped” (i.e., installed in the chassis while the chassis is in operation) provided the module to be installed has been disconnected from its external power source and the module’s On/Off switch has been set to “0”.
DC Power
Supply
I 0
­+
Second
Installation Slot
CPSMP-140 Power Supply (24-Volt)
The CPSMP-140 power supply module may replace an existing 24-VDC power supply or be installed in the second installation slot (see drawing above) of the PointSystem™ 13-slot chassis to become the optional, redundant power supply.
NOTE: Both the CPSMP-130 and the CPSMP-140 DC power supply modules may be installed as the redundant power supply in any of the three PointSystem™ 13-slot chassis:
CPSMC1300-100 (AC chassis)
CPSMC1310-100 (48-VDC chassis)
CPSMC1320-100 (24-VDC chassis)
For more information, see the user’s guide for the CPSMC13xx-100 13-slot chassis on-line at: www.transition.com.
To install the power supply module into the PointSystem™ chassis:
1. Loosen the screw that secures the protective plate to the chassis and pull the plate away from the chassis.
0 I
­+
2. Set the On/Off switch on the power supply module to “0”.
3. Carefully slide the power supply module into the installation slot, aligning the module with the installation guides.
0 I
­+
0 I
­+
4. Ensure that the power supply module is firmly seated inside the chassis.
5. Rotate the attached panel fastener screw clockwise to secure the power supply module to the chassis.
2
24-hour Technical Support: 1-800-260-1312 -- International: 00-1-952-941-7600
techsupport@transition.com -- Click the “Transition Now” link for a live Web chat.
3
CPSMP-130 & CPSMP-140
Connect to External Power
CAUTION: Ensure that external power source is NOT powered and that the On/Off switch on the power supply module is set to “0” when connecting to the external power source. Failure to observe this caution could result in damage to, and subsequent failure of, the power supply module.
48-VDC power supply
This product is intended to be used in a restricted access location. Proper earthing (grounding) is required to ensure safe operation and to comply with customer installation requirements and local electrical codes. Prior to installation, use a voltmeter/ohmmeter to check the wiring for the presence of earth ground.
A readily accessible disconnect device as part of the building installation shall be incorporated into the fixed wiring. The disconnect device (a 48 VDC, 15 or 20A circuit breaker or switch) must be included in the ungrounded supply conductor. Overcurrent protection must be a 48 VDC, 15 or 20A fuse or circuit breaker.
24-VDC Power Supply
This product is intended to be used in a restricted access location. Proper earthing (grounding) is required to ensure safe operation and to comply with customer installation requirements and local electrical codes. Prior to installation, use a voltmeter/ohmmeter to check the wiring for the presence of earth ground.
A readily accessible disconnect device as part of the building installation shall be incorporated into the fixed wiring. The disconnect device (a 24 VDC, 15 or 20A circuit breaker or switch) must be included in the ungrounded supply conductor. Overcurrent protection must be a 24 VDC, 15 or 20A fuse or circuit breaker.
Connect to External Power -- Continued
To power the CPSMP-130 or the CPSMP-140 power supply module:
1. Set the On/Off switch on the power supply module to “0”.
2. Verify that the external power source is NOT powered.
3. Connect the positive (+) terminal to the external power connector marked “+”. Turn the terminal screw clockwise to secure.
4. Connect the negative (-) terminal to the external power connector marked “-”. Turn the terminal screw clockwise to secure.
5. Connect the ground terminal to the external power connector marked “chassis ground”. Turn the terminal screw clockwise to secure.
6. Set the power supply module power switch to “I”.
7. Verify that the power supply module is powered by observing the illuminated power LED.
On/Off
GND
– +
Switch
0 I
­+
External Power Connectors
0 I
­+
Panel Fastener Screw
Power LED
4
24-hour Technical Support: 1-800-260-1312 -- International: 00-1-952-941-7600
techsupport@transition.com -- Click the “Transition Now” link for a live Web chat.