User’s Guide
0
I
+
CPSMP-130
48-VDC Power Supply Module
CPSMP-140
24-VDC Power Supply Module
13-Slot PointSystem™ Accessory
The Transition Networks CPSMP-130 power supply is a 48-VDC slide-in-module
that provides optional, redundant power to the CPSMC1310-100 13-slot
PointSystem™ chassis and any installed media converter slide-in-modules and
management modules.
The Transition Networks CPSMP-140 power supply is a 24-VDC slide-in-module
that provides optional, redundant power to the CPSMC1320-100 13-slot
PointSystem™ chassis and any installed media converter slide-in-modules and
management modules.
The figure below illustrates the components of both types of power supplies:
• An On/Off switch that, when set to “I”, allows the power supply module
to supply power to the chassis, and any installed modules.
•A panel fastener screw that secures the power supply module to the
chassis.
•A power LED indicator.
•A handle for installing and removing the power supply module to/from
the chassis.
•A fuse installed on the circuit board inside the power supply module’s
housing.
• A set of three (3) external power connectors that distribute power from an
external DC outlet to a chassis ground connector, a positive (+)
connector, and a negative (-) connector on the power supply module.
On/Off Switch
I
0
+
Panel Fastener Scre
Power LED
Handle
Fuse
(on the circuit boar
External Power Connector
Install the Power Supply Module . . . . .3
Connect to External Power . . . . . . . . .4
Replace the Power Supply Module . . .6
Replace the Fuse . . . . . . . . . . . . . . . . .8
Technical Specifications . . . . . . . . . .10
Troubleshooting . . . . . . . . . . . . . . . .11
Contact Us . . . . . . . . . . . . . . . . . . . .11
Compliance Information . . . . . . . . . .12
CPSMP-130 & CPSMP-140
READ AND FOLLOW ALL WARNING NOTICES & INSTRUCTIONS MARKED ON
THE PRODUCT OR INCLUDED IN THE MANUAL.
CAUTION: All installation and service must be performed by qualified service
personnel.
CAUTION: Wear a grounding device and observe electrostatic discharge
precautions when installing or servicing the power supply module. Failure to
observe this caution could result in damage to, and subsequent failure of, the
power supply module.
The Power Supply Module in the 13-Slot Chassis
CPSMP-130 Power Supply (48-VDC)
The CPSMP-130 power supply module may replace an existing 48-VDC power
supply or be installed in the second installation slot (see drawing below) of the
PointSystem™ 13-slot chassis to become the optional, redundant power
supply.
WARNING: Do NOT connect the power supply module to the external power
source before installing it into the chassis. Failure to observe this caution could
result in equipment damage and/or personal injury or death.
Install the Power Supply Module
CAUTION: Ensure that the power supply module has been disconnected
from the external power source and the module’s On/Off switch has been
set to “0”. Failure to observe this caution could result in damage to, and
subsequent failure of, the power supply module.
NOTE: The power supply module may be “hot swapped” (i.e., installed in the
chassis while the chassis is in operation) provided the module to be installed
has been disconnected from its external power source and the module’s
On/Off switch has been set to “0”.
DC Power
Supply
I
0
+
Second
Installation Slot
CPSMP-140 Power Supply (24-Volt)
The CPSMP-140 power supply module may replace an existing 24-VDC power
supply or be installed in the second installation slot (see drawing above) of the
PointSystem™ 13-slot chassis to become the optional, redundant power
supply.
NOTE: Both the CPSMP-130 and the CPSMP-140 DC power supply modules
may be installed as the redundant power supply in any of the three
PointSystem™ 13-slot chassis:
• CPSMC1300-100 (AC chassis)
• CPSMC1310-100 (48-VDC chassis)
• CPSMC1320-100 (24-VDC chassis)
For more information, see the user’s guide for the CPSMC13xx-100 13-slot
chassis on-line at: www.transition.com.
To install the power supply module into the PointSystem™ chassis:
1. Loosen the screw that secures the protective plate to the chassis and pull
the plate away from the chassis.
0
I
+
2. Set the On/Off switch on the power supply module to “0”.
3. Carefully slide the power supply module into the installation slot,
aligning the module with the installation guides.
0
I
+
0
I
+
4. Ensure that the power supply module is firmly seated inside the chassis.
5. Rotate the attached panel fastener screw clockwise to secure the power
supply module to the chassis.
2
24-hour Technical Support: 1-800-260-1312 -- International: 00-1-952-941-7600
techsupport@transition.com -- Click the “Transition Now” link for a live Web chat.
3
CPSMP-130 & CPSMP-140
Connect to External Power
CAUTION: Ensure that external power source is NOT powered and that the
On/Off switch on the power supply module is set to “0” when connecting to
the external power source. Failure to observe this caution could result in
damage to, and subsequent failure of, the power supply module.
48-VDC power supply
• This product is intended to be used in a restricted access location. Proper
earthing (grounding) is required to ensure safe operation and to comply
with customer installation requirements and local electrical codes. Prior
to installation, use a voltmeter/ohmmeter to check the wiring for the
presence of earth ground.
• A readily accessible disconnect device as part of the building installation
shall be incorporated into the fixed wiring. The disconnect device (a 48
VDC, 15 or 20A circuit breaker or switch) must be included in the
ungrounded supply conductor. Overcurrent protection must be a 48
VDC, 15 or 20A fuse or circuit breaker.
24-VDC Power Supply
• This product is intended to be used in a restricted access location. Proper
earthing (grounding) is required to ensure safe operation and to comply
with customer installation requirements and local electrical codes. Prior
to installation, use a voltmeter/ohmmeter to check the wiring for the
presence of earth ground.
• A readily accessible disconnect device as part of the building installation
shall be incorporated into the fixed wiring. The disconnect device (a 24
VDC, 15 or 20A circuit breaker or switch) must be included in the
ungrounded supply conductor. Overcurrent protection must be a 24
VDC, 15 or 20A fuse or circuit breaker.
Connect to External Power -- Continued
To power the CPSMP-130 or the CPSMP-140 power supply module:
1. Set the On/Off switch on the power supply module to “0”.
2. Verify that the external power source is NOT powered.
3. Connect the positive (+) terminal to the external power connector marked
“+”. Turn the terminal screw clockwise to secure.
4. Connect the negative (-) terminal to the external power connector marked
“-”. Turn the terminal screw clockwise to secure.
5. Connect the ground terminal to the external power connector marked
“chassis ground”. Turn the terminal screw clockwise to secure.
6. Set the power supply module power switch to “I”.
7. Verify that the power supply module is powered by observing the
illuminated power LED.
On/Off
GND
–
+
Switch
0
I
+
External Power Connectors
0
I
+
Panel Fastener Screw
Power LED
4
24-hour Technical Support: 1-800-260-1312 -- International: 00-1-952-941-7600
techsupport@transition.com -- Click the “Transition Now” link for a live Web chat.
5