Trane Voyager TC*, Voyager YC*, Voyager TC Series, Voyager YC Series User Manual

Packaged Cooling & Gas/Electric Rooftops
Voyager™
12½-25 Tons — 60 Hz
Packaged Cooling (TC*)
Packaged Gas/Electric (YC*)
May 2007 RT-PRC024-EN
Introduction
Packaged Rooftop Air Conditioners
Through the years, Trane has designed and developed the most complete line of Packaged Rooftop products available in the market today. Trane was the first to introduce the Micro—microelectronic unit controls—and has continued to improve and revolutionize this design concept.
The ReliaTel control platform offers the same great features and functionality as the original Micro, with additional benefits for greater application flexibility.
Voyager continues to provide the highest standards in quality and reliability, comfort, ease of service, and the performance of Trane light commercial products.
Trane customers demand products that provide exceptional reliability, meet stringent performance requirements, and are competitively priced. Trane delivers with Voyager.
Voyager features cutting edge technologies: reliable compressors, Trane engineered ReliaTel controls, computer-aided run testing, and Integrated Comfort™ Systems. So, whether you’re the contractor, the engineer, or the owner you can be certain Voyager Products are built to meet your needs.
It’s Hard To Stop A Trane.
®
Packaged Gas/Electric
Packaged Cooling
Contents
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Features and Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Application Considerations . . . . . . . . . . . . . . . . . . . . . 11
Selection Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Model Number Description . . . . . . . . . . . . . . . . . . . . . 14
General Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Performance Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Controls. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Electrical Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Jobsite Connections . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Typical Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
Dimensional Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
Mechanical Specifications . . . . . . . . . . . . . . . . . . . . . 102
RT-PRC024-EN 3
Features and Benefits
Standard Features
2” throwaway filters provided on 12½-25 ton units
5-year Limited Compressor Warranty (12½-17½ tons); 1 year on 20 & 25 tons
5 year Limited Heat Exchanger (12½ - 17½ tons) 1 year on 20 & 25 tons
1-year Limited Parts Warranty
Anti-Short Cycle Timer
Belt Drive Motors
Colored and Numbered Wiring
Crankcase Heaters
Dedicated Airflow
Easy Access Low Voltage Terminal Board (LTB)
Foil-Faced and Edge Captured Insulation
High Efficiency Drum and Tube Heat Exchanger
High Efficiency Gas Heat with Hot Surface Ignition
High Pressure Cutout
IAQ Sloped Condensate Drain Pan
Liquid Line Refrigerant Drier
Low Ambient Cooling to 0°F
Operating Charge of R-22
Patented Hybrid Condenser Coil for easy cleaning
Provisions for Through-the-Base Gas and Condensate Drain Connections
Quick Access Panels
Quick Adjust Idler Arm Pulley
ReliaTel Microprocessor Controls
Single Point Power
Single Side Service
Standardized Components
Trane built Scroll Compressors
U-shaped Airflow Pattern
Options
Factory Installed Options17*
2” Pleated Filters
Black Epoxy Pre-Coated Coils
Dehumidification Option
Differential Pressure Switches
High Efficiency Motors
Hinged Access Doors
Novar Return Air Sensor
Novar Unit Controls
Powered or Unpowered Convenience Outlet
Stainless Steel Heat Exchanger with 10 year warranty
Supply and/or Return Air Smoke Detector
4,13
Thermal Expansion Valve
Through the Base Electrical Access
Through the Base Electrical with Circuit Breaker
Through the Base Electrical with Disconnect Switch
Factory* or Field Installed Options
Barometric Relief
Clogged Filter/Fan Failure Switch
4,7
Discharge Air Sensing Kit
Economizer (Downflow)
Electric Heaters
•Frostat
3,4,7
LonTalk® Communications Interface (LCI)
Oversized Motors
Reference or Comparative Enthalpy
5,7
Tool-less Hail Guards
Trane Communications Interface (TCI)
2,7
*Some Factory Installed Options (FIOPS) available for Downflow Air Discharge units only. Please verify with ordering system for availability.
7,3
7
3,4,16
7
9
8
6
7
16
14,15
10,14,15
17
4,7
1
7,11 ,15
7
7
7
Explanation of Notes 1-17 located on page following Model Number Description.
Field Installed Options
•CO
Sensing
2
Digital Display Zone Sensor
Dual Thermistor Remote Zone Sensor
Economizer (Horizontal)
High Altitude Kit
High and Low Static Drive Kits
Humidity Sensor
Low Static Drive
LP Conversion Kit
Manual Outside Air Damper
Motorized Outside Air Dampers
Powered Exhaust
Quick Start Kit
ReliaTel Options Module
12
Remote Potentiometer
Roof Curb (Downflow Only)
•Thermostat
Ventilation Override Accessory
4
Zone Sensors and Remote Zone Sensors
Other Benefits
Cabinet design ensures water integrity
Ease of Service, Installation and Maintenance
Mixed model build enables “fastest in the industry” ship cycle times
Outstanding Airflow Distribution
ReliaTel Controls benefits
Unmatched Product Support
4 RT-PRC024-EN
Features and Benefits
Unmatched Support
Trane Sales Representatives are a Support Group that can assist you with:
–Product
– Application
– Service
– Training
– Special Applications
– Specifications
– Computer Programs and
much more
Standard Features
Anti-Short Cycle Timer (Standard with ReliaTel)
Provides a 3 minute minimum “ON” time and 3 minute “OFF” time for compressors to enhance compressor reliability by assuring proper oil return.
Colored And Numbered Wiring
Save time and money tracing wires and diagnosing the unit.
Compressors
Voy ager contains the best compressor technology available to achieve the highest possible performance. Dual compressors are outstanding for humidity control, light load cooling conditions and system back-up applications. Dual compressors are available on all models.
Condenser Coil
Voyager boasts a patent-pending 1+1+1 condenser coil, permanently gapped for easy cleaning.
Controls – ReliaTel
ReliaTel microprocessor controls provide unit control for heating, cooling and ventilating utilizing input from sensors that measure indoor and outdoor temperature and other zone sensors. ReliaTel also provides outputs for building automation systems and expanded diagnostics. For a complete list of ReliaTel offerings, refer to the “Other Benefits” section within the Features and Benefits section of this catalog.
Conversionless Units
The dedicated design units (either downflow or horizontal) require no panel removal or alteration time to convert in the field — a major cost savings during installation.
Horizontal units come complete with duct flanges so the contractor doesn’t have to field fabricate them. These duct flanges are a time and cost saver.
Crankcase Heaters
These band or insertion heaters provide improved compressor reliability by warming the oil to prevent migration during off-cycles or low ambient conditions. These are standard on all Voyager models.
Efficiencies
Standard or High Efficiency Cooling available.
Easy Access Low Voltage Terminal Board
Voy a g e r ’s Low Voltage Terminal Board is external to the electrical control cabinet. It is extremely easy to locate and attach the thermostat wire and test operation of all unit functions. This is another cost and time saving installation feature.
Foil Faced Insulation
All panels in the evaporator section of the unit have cleanable foil­faced insulation. All edges are either captured or sealed to ensure no insulation fibers get into the airstream.
Heat Exchanger - Drum and Tube
The cabinet features a drum and tube heat exchanger that is manufactured using aluminized steel with stainless steel components for maximum durability. The requirement for cycle testing of heat exchangers is 10,000 cycles by ANSI Z21.47. This is the standard required by both UL and AGA for cycle test requirements. Trane requires the design to be tested to 2½ times this current standard. The drum and tube design has been tested and passed over 150,000 cycles, which is over 15 times the current ANSI cycling requirements.
Forced Combustion Blower
Negative Pressure Gas Valve
Hot Surface Ignitor
Heat Exchanger
The negative pressure gas valve will not allow gas flow unless the combustion blower is operating. This is one of our unique safety features.
The forced combustion blower supplies pre-mixed fuel through a single stainless steel burner screen into a sealed drum where ignition takes place. It is more reliable to operate and maintain than a multiple burner system.
The hot surface ignitor is a gas ignition device which doubles as a safety device utilizing a continuous test to prove the flame. The design is cycle tested at the factory for quality and reliability.
RT-PRC024-EN 5
Features and Benefits
Our gas/electric rooftops exceed all California seasonal efficiency requirements and perform even better than the California NOx emission requirements.
Low Ambient Cooling
All Voyager microprocessor units have cooling capabilities down to 0°F as standard.
Low Voltage Connections
The wiring of the low voltage connections to the unit and the zone sensors is as simple as 1-1, 2-2, and 3-3. This simplified system makes it easy for the installer to wire.
Single Side Service
Single side service is standard on all units.
Sloped Drain Pans
Every Voyager unit has a non­corrosive, sloped drain pan made of pre-painted steel and standard on all units.
Standardized Components
Components are placed in the same location on all Voyager units. Familiarize yourself with one Voyager and you are familiar with every Voy ager.
Due to standardized components throughout the Voyager line, contractors/owners can stock fewer parts.
Through the Base Condensate
Every unit includes provisions for through the base condensate drain connections. This allows the drain to
Motors
All indoor fan motors are belt drive as standard.
be connected through the roof curb instead of a roof penetration.
Variety of Options*
Pressure Cutouts
Low and high pressure cutouts are standard on all Voyager models.
Quick-Access Panels
Remove three or more screws for access to the standardized internal components and wiring.
Quick­Adjust Slider Plate
With the Quick-Adjust Slider Plate, the belt and sheaves can be quickly adjusted without moving the mounted fan motor. The result is a major savings in time and money.
Single Point Power
A single electrical connection powers the unit.
Factory Installed Options
Black Epoxy Pre-Coated Coils
The pre-coated coils are an economical option for protection in mildly corrosive environments.
Circuit Breaker (Required with Through- the-Base Electrical)
This option is a factory installed thermal magnetic, molded case, HACR Circuit Breaker with provisions for through the base electrical connections. Available on all downflow models.
Disconnect Switch (Required with Through-the-Base Electrical)
Factory installed 3-pole, molded case, disconnect switch with provisions for through the base electrical connections are available. Available on all downflow models.
Codes require a method of assured unit shutdown for servicing. Field­installed disconnects sometimes interfere with service access. Factory installation of unit disconnects reduces costs, assures proper mounting and provides the opportunity to upgrade to unit circuit breaker protection.
Dehumidification (Hot Gas Reheat) Option
This option allows for increased outdoor air ventilation. It reduces humidity levels while increasing comfort level in the air space. Cooling can operate without a demand for dehumidification. The hot gas reheat coil is designed to deliver maximum reheat temperatures.
Hinged Access Doors
These doors permit easy access to the filter, fan/ heat, and compressor/ control sections. They reduce the potential roof damage from screws or sharp access door corners.
Motors
Factory or field installed oversized motors available for high static applications are available.
High Efficiency motors are also available with efficiency ratings from
86.5 up to 91.0. It is not available for all models.
Novar Unit Controls
Novar 3051 and 2024 are available for Voyager Cooling and Gas/Electric models.
Powered or Unpowered Convenience Outlet
This option is a GFCI, 120v/15amp, 2 plug, convenience outlet, either powered or unpowered.
Features and Benefits
This option can only be ordered when Through the Base Electrical with either the Disconnect Switch or Circuit Breaker option is ordered. This option is available on all downflow models.
Stainless Steel Heat Exchanger
The optional stainless steel heat exchanger is constructed of 304 stainless steel. It is resistant to corrosion and oxidation and easy to clean.
The high strength to weight ratio allows for high ventilation rates with gas units. It is an excellent option to compliment the dehumidification option as a high outside air ventilation unit.
With this option, a 10-year stainless steel heat exchanger warranty is standard.
Supply and/or Return Air Smoke Detector
With this option installed, if smoke is detected, all unit operation will be shut down. Reset will be manual at the unit. Return Air Smoke Detectors require minimum allowable airflow when used with certain models.
Thermal Expansion Valve
Available for a wider range of applications. This is available on high efficiency models.
Through-the-Base Electrical Utility Access
An electrical service entrance shall be provided allowing electrical access for both control and main power connections inside the curb and through the base of downflow units, and through the front of horizontal units. Option will allow for field installation of liquid-
tight conduit and an external field installed disconnect switch.
Factory provided through the base openings simplify wiring and piping. Because these utility openings frequently minimize the number of roof penetrations, the integrity of roofing materials is enhanced.
Two-Inch Pleated Filters
2” pleated media filters are offered as an option on all Voyager units for jobs with enhanced Indoor Air Quality (IAQ) requirements.
*Refer to Model Number Description for option availability.
Factory or Field Installed Options*
Barometric Relief
Designed to be used on downflow units, barometric relief is an unpowered means of relieving excess building pressure.
Clogged Filter/Fan Failure Switch
A dedicated differential pressure switch is available to achieve active fan failure indication and/or clogged filter indication.
These sensors allow a zone sensor service light or Integrated Comfort System to indicate a dirty filter or a fan that’s not working. The field installation charges for these valuable feedback devices often eliminate them from consideration. Factory installation can make such features a good investment.
Discharge Air Sensing Kit
Provides true discharge air sensing in heating models. The kit is functional only with the ReliaTel Options Module.
Electric Heaters
Electric heat modules are available within the basic unit. If ordering the Through the Base Electrical option with an Electrical Heater, the heater must be factory installed.
Fresh Air Options – Dampers and Economizer
0 - 25% manual or 0 - 50% motorized outside air hoods are available.
Economizers are equipped with either dry bulb or reference or comparative enthalpy sensing. These economizers provide free cooling as the outdoor temperature and/or humidity decreases. Correctly installed, they offer a valuable energy savings. Factory-installed economizers save time and ensure proper installation.
Frostat
This capillary bulb embedded in the face of the evaporator coil monitors coil temperature to prevent evaporator icing and protect the compressor. Recommended for applications with low leaving air temperatures, low airflow and or high latent load applications.
LonTalk® Communications Interface
The LonTalk communications interface allows the unit to communicate as a Tracer™LCI-V device or directly with generic LonTalkNetwork Building Automation System Controls.
Oversized Motors
Factory or field installed oversized motors available for high static applications.
Reference or Comparative Enthalpy
Measures and communicates humidity while maximizing comfort control.
Tool-less Hail Guards
Tool-less, hail protection quality coil guards shall be either factory or field­installed for condenser coil protection. This option protects the condenser coil from vandalism and/ or hail damage.
RT-PRC024-EN 7
Features and Benefits
Trane Communication Interface (TCI)
Available factory or field installed. This module when applied with the ReliaTel™ easily interfaces with Trane’s Integrated Comfort™ System.
*Refer to Model Number Description for option availability.
Field Installed Options*
CO2 Sensing
The CO2 sensor has the ability to monitor space occupancy levels within the building by measuring the parts per million of CO Dioxide) in the air. As the CO increase, the outside air damper modulates to meet the CO2 space ventilation requirements. The CO sensor kit is available as a field installed accessory.
Digital Display Zone Sensor
The Digital LCD (Liquid Crystal Display) zone sensor has the look and functionality of standard zone sensors. This sensor should be utilized with ReliaTel™ controls.
Dual Thermistor Remote Zone Sensor
This sensor will reduce the total number of remote sensors to obtain space temperature averaging. This sensor should be utilized with ReliaTel controls.
High Altitude Kit
Previously a Canadian Agency requirement for units applied about 2000 feet, it is not required by the U.S. Domestic contractors should consult with local authority on best practice. Devates gas orifices by 10%.
High Static Drive
Available on many models, this high static drive accessory extends the capability of the standard motor. Avoid expensive motors and operating costs by installing this optimized sheave accessory.
(Carbon
2
2
levels
2
Humidity Sensor/Humidistat
Used in conjunction with our Dehumidification (Hot Gas Reheat) units to provide outstanding humidity control and comfort. Humidity sensors can be wall or duct mounted and set for levels between 40% and 60%.
LP Conversion Kit
Provided for field conversion of gas/ electric units from Natural gas to Propane.
Powered Exhaust Option
This option is available on downflow units and provides exhaust of the return air, when using a downflow economizer, to maintain proper building pressurization. Great for relieving most building overpressurization problems.
Remote Potentiometer
When properly installed in the economizer control circuitry, this accessory provides a remote variable resistance to enable the operator to adjust the minimum damper position.
Roof Curbs
Available for downflow units. Only two roof curbs for the entire Voyager line simplifies curb selection.
Static Drive Accessories
Available on many models, this high and low static drive accessories extend the capability of the standard motor. Avoid expensive motors and operating costs by installing this optimized sheave accessory.
Ventilation Override Accessory
With the Ventilation Override Accessory installed, the unit can be set to transition to up to 3 different pre-programmed sequences for Smoke Purge, Pressurization, and Exhaust. The transition occurs when a binary input on the RTOM is closed (shorted). This would typically be a hard wired relay output from a smoke detector or fire control panel. The ventilation override kit is available as a field installed accessory.
Zone Sensors/Thermostats
Available in programmable, automatic and manual styles.
*Refer to Model Number Description for option availability.
Other Benefits
Airflow Distribution
Airflow is outstanding. The Voyager can replace an older machine with old ductwork and, in many cases, improve the comfort through better air distribution. The U-shaped airflow allows for improved static capabilities.
Cabinet Integrity
For added water integrity, Voyager has a raised 1 1/8" lip around the supply and return of the downflow units to prevent water from blowing into the ductwork.
Easy to Install, Service and Maintain
Because today’s owners are very cost-conscious when it comes to service and maintenance, the Trane Voyager was designed with direct input from service contractors. This valuable information helped to design a product that would get the serviceman off the job quicker and save the owner money. Voyager does this by offering outstanding standard features enhanced by a variety of factory and field installed options, multiple control options, rigorously tested proven designs and superior product and technical support.
ReliaTel™ Controls
ReliaTel controls provide unit control for heating, cooling and ventilating utilizing input from sensors that measure outdoor and indoor temperature.
Features and Benefits
ReliaTel Control Logic Enhances Quality and Reliability
—prevents the unit from short cycling, considerably improving compressor life.
—ensures that the compressor will run for a specific amount of time which allows oil to return for better lubrication, enhancing the reliability of the compressor.
Voyager with ReliaTel reduces the number of components required to operate the unit, thereby reducing possibilities for component failure.
ReliaTel Makes Installing and Servicing Easy
ReliaTel eliminates the need for field installed anti-shortcycle timer and time delay relays. ReliaTel controls provide these functions as an integral part of the unit. The contractor no longer has to purchase these controls as options and pay to install them.
ReliaTel™
The wiring of the low voltage connections to the unit and the zone sensors is as easy as 1-1, 2-2, and 3-3. This simplified system makes wiring easier for the installer.
ReliaTel Makes Testing Easy
ReliaTel requires no special tools to run the Voyager unit through its paces. Simply place a jumper between Test 1 and Test 2 terminals on the Low Voltage Terminal Board and the unit will walk through its operational steps automatically.
The unit automatically returns control to the zone sensor after stepping through the test mode a single time, even if the jumper is left on the unit.
As long as the unit has power and the “system on” LED is lit, ReliaTel is operational. The light indicates that the controls are functioning properly.
ReliaTel features expanded diagnostic capabilities when utilized with Trane Integrated Comfort™ Systems.
Some zone sensor options have central control panel lights which indicate the mode the unit is in and possible diagnostic information (dirty filters for example).
Other ReliaTel Benefits
The ReliaTel built-in anti-shortcycle timer, time delay relay and minimum “on” time control functions are factory tested to assure proper operation.
ReliaTel softens electrical “spikes” by staging on fans, compressors and heaters.
Intelligent Fallback is a benefit to the building occupant. If a component goes astray, the unit will continue to operate at predetermined temperature setpoint.
Intelligent Anticipation is a standard ReliaTel feature. It functions continuously as ReliaTel and zone sensor(s) work together in harmony to provide much tighter comfort control than conventional electro­mechanical thermostats.
The same ReliaTel Board fits all Voyager Packaged Gas/Electrics, Cooling, and Heat Pump models. This provides standardization of parts for contractors. Less money is tied up in inventory with ReliaTel.
VariTrac – Building Automation System
When Trane’s changeover VAV System for light commercial applications is coupled with Voyager, it provides the latest in technological advances for comfort management systems and can allow thermostat control in every zone served by Var iTra c.
TM
VariTr ac
Rigorous Testing
All of Voyager’s designs were rigorously rain tested at the factory to ensure water integrity.
Actual shipping tests were performed to determine packaging requirements. Units were test shipped around the country to determine the best packaging. Factory shake and drop tests were used as part of the package design process to help assure that the unit arrives at the job site in top condition.
Rigging tests include lifting a unit into the air and letting it drop one foot, assuring that the lifting lugs and rails hold up under stress.
We perform a 100% coil leak test at the factory. The evaporator and condenser coils are leak tested at 200 psig and pressure tested to 450 psig.
All parts are inspected at the point of final assembly. Sub-standard parts are identified and rejected immediately.
Every unit receives a 100% unit run test before leaving the production line to make sure it lives up to rigorous Trane requirements.
Voyager units incorporate either a one piece top or the Trane-Tite-Top
3
(T
). Each part of the top (either two or three pieces) overlaps in such a way that water cannot leak into the unit. These overlapped edges are gasketed and sealed to ensure superior water integrity.
RT-PRC024-EN 9
Features and Benefits
Factory Installed Options
Figure 1. Voyager Factory Installed Options
Application Considerations
Application of this product should be within the cataloged airflow and cooling considerations.
Barometric Relief
This product line offers an optional barometric relief damper for use in conjunction with economizer option. This accessory consists of gravity dampers which open with increased pressure. As the building air pressure increases, the pressure in the unit return air section also increases, opening the dampers and relieving the conditioned space.
Note: The effectiveness of
barometric relief damper during economizing operation is system related.
Note: Pressure drop of the return
air system should be considered to control building pressurization.
Black Epoxy Coil
The coils are manufactured with a thermoset, vinyl coating that is bonded to the aluminum fin stock prior to the fin stamping process. These coils are an economical option for protection in mildly corrosive environments.
Note: Not to be used where
seacoast applications exist.
Clearance Requirements
The recommended clearances identified with unit dimensions should be maintained to ensure adequate serviceability, maximum capacity and peak operating efficiency. Actual clearances which appear inadequate should be reviewed with the local Trane sales personnel.
Heating Operation
The heat exchanger is manufactured with aluminized steel. To prevent condensation within the heat exchanger, do not exceed 50% outside air or a minimum mixed air temperature of 40°F.
Optional Stainless Steel Heat Exchanger
The optional stainless steel heat exchanger is manufactured with 304 stainless steel. To prevent corrosion and prolong heat exchanger reliability, the minimum mixed air temperature allowed across the heat exchanger is 20°F.
The stainless steel heat exchanger option is an excellent option that compliments the dehumidification package. Whenever high outside air or outside applications exist, these options should be utilized.
Low Ambient Cooling
The Voyager™ line features, with ReliaTel™ microprocessor controls, low ambient cooling down to 0°F. The following options need to be included/considered when low ambient applications are required: continuous fan operation, crankcase heaters (standard), thermal expansion valves, frostat.
Contact your local Trane Representative for more assistance with low ambient cooling applications.
Unit Pitch
These units have sloped condensate drain pans. Units must be installed level. Any unit slope must be toward access side of the unit.
RT-PRC024-EN 11
Condensate Trap
The evaporator is a draw-thru configuration. A trap must be field provided prior to start-up on the cooling cycle.
Selection Procedure
Cooling Capacity
Note: Cooling Capacity Procedure
is the same for cooling (TC*) and gas/electric (YC*).
Step 1.
Calculate the building's total and sensible cooling loads at design conditions. Use the Trane calculation methods or any other standard accepted method.
Factors used in unit selection:
Total Cooling Load: 180 MBh Sensible Cooling Load: 129 MBh Airflow: 6000 cfm Electrical Characteristics: 460/60/3 Summer Design Conditions: Entering Evaporator Coil: 80 DB, 67 WB Outdoor Ambient: 95 DB External Static Pressure: 0.49 in. wg Rooftop - downflow configuration Accessories
•Roof curb
Economizer
Electric Heat
Step 2.
As a starting point, a rough determination must be made of the size of the unit. The final selection will be made after examining the performance at the given conditions. Divide the total cooling load by nominal BTUH per ton (12 MBh per ton); then round up to the nearest unit size.
180 MBh / 12 MBh = 15.0 tons
Step 3.
Ta bl e 7 shows that a TCD180B4 has a
gross cooling capacity of 184 MBh and 130 MBh sensible capacity at 6000 cfm and 95 DB outdoor ambient with 80 DB, 67 WB air entering the evaporator.
To Find Capacity at Intermediate Conditions Not in the Table.
When the design conditions are between two numbers that are in the capacity table, interpolation is required to approximate the capacity.
Note: Extrapolation outside of the
table conditions is not recommended.
Step 4.
In order to select the correct unit which meets the building's requirements, the fan motor heat must be deducted from the gross cooling capacity. The amount of heat that the fan motor generates is dependent on the effort by the motor
- cfm and static pressure. To determine the total unit static pressure you add the external static pressure to the additional static related by the added features:
External Static Duct System 0.49 wg Standard Filter 1 in. from
Tab le 5 4
Economizer from Table 56
Tab le 5 4 (100% Return Air)
Electric Heater Size 36 kW from Tab l e 5 4 (reference "Heating Capacity" section on this page for determination of heater size). No additional static add for gas/heat exchanger. Total Static Pressure 0.60 wg
0.10 wg
0.04 wg
0.07 wg
Note: The Evaporator Fan
Performance Ta bl e 2 4 has already accounted for the pressure drop for standard filters and wet coils (see note below Ta bl e 2 4 ). Therefore, the actual total static pressure is 0.60 -0.10 (from
Ta bl e 5 4 = 0.50 wg).
With 6000 cfm and 0.50 wg. Ta b le 2 4 shows 2.56 bhp for this unit. Note below the table gives a formula to calculate Fan Motor Heat,
3.15 x bhp = MBh.
3.15 x 2.56 = 8.06 MBh.
Now subtract the fan motor heat from the gross cooling capacity of the unit:
Net Total Cooling Capacity = 184 MBh - 8.06 = 175.9 MBh.
Net Sensible Cooling Capacity = 130 MBh - 8.06 = 121.9 MBh.
Step 5.
If the performance will not meet the required load of the building -total or sensible cooling load, try a selection at the next higher size unit.
Heating Capacity
Note: Heating capacity procedures
DIFFER for cooling (TC*) and gas/electric (YC*) units.
Step 1.
Calculate the building heating load using the Trane calculation form or other standard accepted method.
Step 2.
Size the system heating capacity to match the calculated building heating load. The following are building heating requirements:
TC* cooling units: 460 volt/3 phase Power Supply Total heating load of 115.0 MBH 6000 cfm
The electric heat accessory capacities are listed in Ta bl e 5 6. From the table, a 36 kw heater will deliver 122.94 MBh at 480 volts. In order to determine capacity at 460 volts, the heater voltage correction factor from Ta bl e 5 7 must be used. Therefore, 122.94 MBh x .94 (voltage correction factor) = 115.6 MBh.
YC* gas/electric: Fuel natural gas total heating load of 195 MBh. Table 24 shows 250 MBh and 350 MBh input models. The output capacities of these furnaces are 203 MBh and 284 MBh respectively. The low heat model with 203 MBh output best matches the building requirements.
Air Delivery Selection
Note: Air Delivery procedures is
the same for cooling (TC*) and gas/electric (YC*) units.
External static pressure drop through the air distribution system has been calculated to be 0.50 inches of water. From Ta bl e 5 4 static pressure drop through the economizer is 0.04 and the 36 kw heater is 0.07 inches of water (0.49 +
0.04 + 0.07). Enter Ta bl e 5 4 for a TCD180B4 at 6000 cfm and 0.50 static pressure. The standard motor at 777 rpm will give the desired airflow at a rated bhp of 2.71.
12 RT-PRC024-EN
Selection Procedure
Dehumidification Selection
Note: Dehumidification selection
procedure is the same for both cooling (TCD) and gas/ electric (YCD) models. Determine normal unit cooling and heating capacities as previously described in the selection procedures on prior page.
Typical 20 ton TFD241C 6400 cfm Total Supply airflow 2560 cfm Outside Air (40%) 3840 cfm Return Air
0.41" External Static Pressure
OA Conditions Part load day and raining 68°F db 67°F wb
66.5 dp 95% RH RA' conditions 75°F db 63°F wb 52% RH
55.9 dp
Step 1:
Determine the mixed/entering air condition (MA)
MA = (% outside air*outside air drybulb temperature) + (% return air*return air dry-bulb temperature) MA = (0.40*68°F) + (0.60*75°F) MA = 72.20°F db
Note: Repeat for wet-bulb
temperature (wb).
Plot on psychrometric chart.
MA
72.2°F db
64.7°F wb
Step 2:
Determine the additional static pressure drop for a reheat unit
Ta bl e 5 4 shows a static pressure drop
of 0.35" for the reheat coil and an additional .04 for the mandatory 2" pleated filters required when ordering the dehumidification option. Total static pressure=
1.0 + 0.035 + 0.04 = 1.075
(
1.1 for manual calculations)
Do not forget to also add any additional static from other accessories.
Ta bl e 4 5 (airflow table for 20 ton
dehumidification units) indicates that a standard motor and drive is needed for this airflow and static pressure range.
68°F DB,
OA
67°F WB
75°F DB,
RA
52% RH
MA
72.2°F DB 65°F WB
SA'
46.6°F DB
46.0°F WB
SA
72.2°F D B
57°F WB 38% RH
SA'
REHEAT
OA
MA
RA
SA
SA
Figure 2. Psychrometric Chart
Step 3a:
Determine leaving evaporator temperature (SA')
Leaving Evaporator Temperature = SA'
Utilizing the manual Cooling Capacity selection method as previously described, find the leaving evaporator temperatures with the formula:
Temp = gross sensible or
Δ
gross latent cooling capacity in Btuh ________________ (cfm) (1.085)
Subtract your sensible Δ temp from the entering db and latent Δ temp from the entering wb to determine the leaving evaporator db & wb (temperatures without the addition of fan heat).
51.7 db
51.03 wb
Connect MA and SA' on psychrometric chart with cooling curve.
Step 3b:
Determine leaving unit temperature in standard cooling mode
Repeat Step 3a substituting net sensible or latent capacity for gross sensible or latent capacity to find the leaving unit temperature including fan heat.
48.9 db 53.6 db
47.0 wb 51 wb
84% RH
49% dp
Step 4:
Determine reheat temperature rise Using the leaving evaporator temp, go to Ta bl e 5 9 and find the reheat temperature rise for that particular cfm: 17.55°F db
Note: Reheat temperature rise is
based on supply airflow and leaving evaporator coil temperature.
Step 5:
Determine leaving unit sensible temperature with reheat active (SA) Reheat temperature (obtained in step
3) + (SA' + fan heat) = SA
(SA’ + fan heat) = leaving unit temperature
in standard cooling mode from step 3b.
17.55°F db + 53.6°F = 71.2°F db
SA=71.2°F
Since reheat adds only sensible heat, the dewpoint temperature will remain constant so follow the dewpoint temperature line across the psychrometric chart to find the new wb temperature.
51 wb
29.4 dp
20.8 RH
Consider the Psychrometric Chart. If the space relative humidity is equal to or above the space relative humidity setpoint, the Dehumidification option will:
•Energize compressor or both
compressors (2 stage compressor units).
Hot gas reheat valve is energized
and hot gas is diverted to the reheat coil.
Dehumidification/reheat is
terminated when space humidity is reduced to 5% below relative humidity setpoint.
At MA, air enters the RTU. The RTU filters, cools, and dehumidifies the air as it moves through the evaporator coil. Air leaves the evaporator coil saturated at the preset dew point condition (SA') and is reheated by the hot gas reheat coil to deliver 71°F (SA) supply air to the space.
RT-PRC024-EN 13
Model Number Description
T C D 150 C 3 0 0 A A
1 2 3 456 7 8 9 10 11 12
DIGIT 1,2 — UNIT TYPE
TC Packaged Cooling, Electric
Heat
TF With Factory Installed
Options
YC Packaged Gas/Electric
YF With Factory Installed
Options
DIGIT 3 — AIRFLOW CONFIGURATION
DDownflow
H Horizontal
DIGIT 4,5,6 — NOMINAL GROSS COOLING CAPACITY (MBh)
150 12½ Tons Standard Efficiency
151 12½ Tons High Efficiency
180 15 Tons Standard Efficiency
181 15 Tons High Efficiency
210 17½ Tons Standard Efficiency
211 17½ Tons High Efficiency
240 20 Tons Standard Efficiency
241 20 Tons High Efficiency
300 25 Tons Standard Efficiency
301 25 Tons High Efficiency
DIGIT 7 — MAJOR DESIGN SEQUENCE
DIGIT 8 — VOLTAGE SELECTION
3 208-230/60/3
4 460/60/3
W 575/60/3
K 380/60/3
DIGIT 9,10 — FACTORY INSTALLED OPTIONS
Note: (Applicable to Digit 1, 2
T models only)
00 No Factory-installed Options
0A Factory-installed Economizer
0B Oversized Motor
0C Downflow Economizer and
Oversized Motor
0F Trane Communications
Interface (TCI)
0G Downflow Economizer and
TCI
0H TXV/Face-Split Evaporator
0J Oversized Motor and TXV
Face-Split Evaporator
0K Downflow Economizer,
Oversized Motor, and TXV Face-Split Evaporator
0L Downflow Economizer with
TXV/Face-Split Evaporator
0M Reheat Coil
0N Downflow Economizer and
Reheat Coil
0P Oversized Motor and Reheat
Coil
0R Downflow Economizer,
Oversized Motor and Reheat Coil
DIGIT 9 — HEATING CAPACITY
Note: (Applicable to Digit 1, 2
Y models only)
LLow Heat
M Medium Heat
H High Heat
DIGIT 10 — FACTORY INSTALLED OPTIONS
17
Note: (Applicable to Digit 1, 2
Y models only)
0 Packed Stock, No Options
A Downflow Economizer
B Oversized Motor
C Downflow Economizer and
Oversized Motor
F Trane Communications Interface
(TCI)
2,7
G Downflow Economizer and TCI
H TXV/Face-Split Evaporator
J Oversized Motor and TXV/Face
Split Evaporator
K Downflow Economizer,
Oversized Motor, and TXV/Face Split Evaporator
L Downflow Economizer with TXV
Face-Split Evaporator
M Reheat Coil
N Downflow Economizer and
Reheat Coil
P Oversized Motor and Reheat
Coil
1,3,16
3,16
1,3,16
R Downflow Economizer,
Oversized Motor and Reheat
1,3,16
Coil
DIGIT 11 — MINOR DESIGN SEQUENCE
DIGIT 12 — SERVICE SEQUENCE
Note: Explanation of Model
Number Notes located on the following page.
Note: Some Factory Installed
Options (FIOPS) available for Downflow Air Discharge units only. Please verify with ordering system for availability.
1
7
1
1,2
16
16
1,16
7,16
14 RT-PRC024-EN
Model Number Description
Options
7,3
10,14,15
7,11 ,15
17
7
3,14,16
7
9
8
6
7
16
17
4,7
1
5,7
7
*Factory Installed Options
2" Pleated Filters
Black Epoxy Pre-Coated Coils
Dehumidification Option
Differential Pressure Switches
High Efficiency Motors
Hinged Access Doors
Novar Return Air Sensor
Novar Unit Controls
Powered or Unpowered Convenience Outlet
Stainless Steel Heat Exchanger with 10-year warranty
Supply and/or Return Air Smoke Detector
4,13
Thermal Expansion Valve
Through the Base Electrical Access
Through the Base Electrical with Circuit Breaker
14,15
Through the Base Electrical with Disconnect Switch
Factory* or Field Installed Options
Barometric Relief
Clogged Filter/Fan Failure Switch
4,7
Discharge Air Sensing Kit
Economizer (Downflow)
Electric Heaters
•Frostat
LonTalk® Communications
3,4,7
Interface (LCI)
7
Oversized Motors7
Reference or Comparative Enthalpy
Tool-less Hail Guards
Trane Communications Interface (TCI)
2,7
Field Installed Options
•CO
Sensing
2
Digital Display Zone Sensor
Dual Thermistor Remote Zone Sensor
Economizer (Horizontal)
High Altitude Kit
High and Low Static Drive Kits
Humidity Sensor
•Low Static Drive
LP Conversion Kit
Manual Outside Air Damper
Motorized Outside Air Dampers
Powered Exhaust
Quick Start Kit
ReliaTel Options Module
12
Remote Potentiometer
Roof Curb (Downflow Only)
•Thermostat
Ventilation Override Accessory
4
Zone Sensors and Remote Zone Sensors
Model Number Notes
1. Some field set up required.
2. TCI is for use with non-VariTrac systems and VariTrac systems.
3. All 10th digit model numbers including reheat coil (M,N,P,R) require additional factory installed options; ReliaTel™options module, Frostat, and 2" pleated filters.
4. Requires ReliaTel options module.
5. Requires Economizer.
6. Must be ordered with Through­the-Base Electrical and either Unit Mounted Disconnect or Circuit Breaker.
7. Available factory installed on downflow AND horizontal units. Verify with ordering system.
8. The Novar control option includes the following factory installed and wired devices: Novar ETM-2024 or Novar 3051 rooftop controller, fan proving switch, clogged filter or unit shutdown switch, Cool 1, Cool 2, Heat switch and discharge air sensor (Novar 2024 is downflow only).
Note: Option cannot be
ordered in conjunction with FIOPS Smoke Detector option.
9. This option consists of the Novar return air sensor (Novar #WTS-
10) that is wired and shipped in the return air section of the unit. The sensor ships with approximately 15' of extra wire for dropping down the return air duct (downflow only).
10. Cannot be fused.
11. Must be factory installed when using Through-the-Base Options.
12. ReliaTel Options Module is required when ordering the following accessories: Clogged Filter Switch, Fan Fail Switch, Discharge Air Sensing Kit, Frostat, Ventilation Override, Smoke Detector and Dehumidification.
13. Option cannot be ordered in conjunction with field installed economizer on downflow units. Must be factory installed. The return air smoke detector may not fit up or work properly on the Voyager units when used in conjunction with 3rd party accessories (such as bolt on heat wheels, economizers, and power exhaust). Do not order the return air smoke detectors when using this type of accessory.
14. Unit mounted disconnect and circuit breakers are mutually exclusive of each other.
15. Through-the-base electrical option must be ordered with either unit mounted disconnect or circuit breaker. When adding heat, must order Trane Electric Heat.
16. Available on high efficiency, downflow units only.
17. All Factory Installed Options are Built-to-Order. Check order services for estimated production cycle.
Note: *Some Factory Installed
Options (FIOPS) available for Downflow Air Discharge units only. Please verify with ordering system for availability.
RT-PRC024-EN 15
General Data
Table 1. General Data — 12½-15 Tons
12½ Tons Downflow & Horizontal Units 15 Tons Downflow & Horizontal Units
TC*150D3,4,W,K YC*150D3,4,WL/H,K TC*180B3,4,W,K YC*180B3,4,WL/H,K
(vi)
(vii)
(i)
(iii)
(ii)
(iv)
(v)
150,000
9.8
5,000/4,400
142,000
10.5
14.49
9.2 9.2 9.2 9.2
Hi-Performance
0.375
24.18 2/16
Hi-Performance
0.375
17.50 2/15
Short Orifice
1/1.00 NPT
Propeller
2/26
Direct/1
10,600
2/.50 1,100
FC Centrifugal
1/15x15
Belt/1
1
3.0/5.0
1,740/3,450
145T/145T
Throwaway
(2)20x20x2,(4)20x25x2 (2)20x20x2,(4)20x25x2
9.3/9.4 Circuit 9.3/9.4 Circuit 17.5/9.5 Circuit 17.5/9.5 Circuit
150,000
9.6
5,000/4,000
142,000
10.3
14.79
Hi-Performance
0.375
24.18 2/16
Hi-Performance
0.375
17.50 2/15
Short Orifice
1/1.00 NPT
Propeller
2/26
Direct/1
10,600
2/.50 1,100
FC Centrifugal
1/15x15
Belt/1
1
3.0/5.0
1,740/3,450
145T/145T
Throwaway
(2)20x20x2,(4)20x25x2 (2)20x20x2,(4)20x25x2
182,000
9.9
6,000/5,300
174,000
10.2
17.57
Hi-Performance
0.375
27.12 3/16
Hi-Performance
0.375
17.50 2/15
Short Orifice
1/1.00 NPT
Propeller
2/26
Direct/1
10,200
2/.50
1,100
FC Centrifugal
1/15x15
Belt/1
1
3.0/5.0
1,740/3,450
145T/145T
Throwaway
(2)20x20x2,(4)20x25x2 (2)20x20x2,(4)20x25x2
6,000/5,300
Hi-Performance
Hi-Performance
Short Orifice
1/1.00 NPT
Propeller
FC Centrifugal
1/15x15
1,740/3,450
145T/145T
Throwaway
(2)20x20x2,(4)20x25x2 (2)20x20x2,(4)20x25x2
182.000
9.7
174,000
10.0
17.94
0.375
27.12 3/16
0.375
17.50 2/15
2/26
Direct/1
10,200
2/.50 1,100
Belt/1
1
3.0/5.0
Cooling Performance
Gross Cooling Capacity EER (Downflow/Horizontal) Nominal CFM / ARI Rated CFM ARI Net Cooling Capacity Integrated Part Load Value System Power (kW)
Compressor
Number/Type 2/Scrolls 2/Scrolls 2/Scrolls 2/Scrolls
Sound
Outdoor Sound Rating (BELS)
Outdoor Coil
Typ e Tube Size (in.) OD Face Area (sq. ft.) Rows/FPI
Indoor Coil
Typ e Tub e S i z e ( i n .) Face Area (sq. ft.) Rows/FPI Refrigerant Control Drain Connection Number/Size (in.)
Outdoor Fan
Typ e Number Used/Diameter (in.) Drive Type/No. Speeds CFM Number Motors/HP Motor RPM
Indoor Fan
Typ e Number Used/Diameter (in.) Drive Type/Number Speeds Number Motors Motor HP (Standard/Oversized) Motor RPM (Standard/Oversized) Motor Frame Size (Standard/ Oversized)
Filters
Typ e F u r n i s h e d Number Size Recommended Downflow Horizontal
Refrigerant Charge
Pounds of R-22
16 RT-PRC024-EN
General Data
(12½,15 Tons Standard Efficiency)
Table 1. (continued) General Data — 12½-15 Tons
12½ Tons Downflow & Horizontal Units 15 Tons Downflow & Horizontal Units
Heating Performance
(Gas/Electric Only)
Heating Models Low High Low High
Heating Input (Btuh) 150,000 250,000 250,000 350,000
1st Stage (Btu) 100,000 175,000 175,000 250,000
Heating Output (Btuh) 122,000 203,000 203,000 284,000
1st Stage (Btu) 81,000 142,000 142,000 203,000
AFUE (%)
(ix)
Downflow/Horizontal 81.0 80.7/79.9 80.7/79.9 80.1/79.1
Steady State Efficiency% 81.0 81.0 81.0 81.0
No. Burners 11
No. Stages 22
Gas Supply Line Pressure (in w.c.)
Natural or LP (minimum/maximum) 2.5/14.0 2.5/14.0
Gas Connection Pipe Size (in.) 1/2 1/2 3/4
(i)
Cooling Performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Certified in accordance with the Unitary Large Equipment Certification Program, which is based on ARI Standard 340/360-93.
(ii)
EER is rated at ARI conditions and in accordance with ARI Standard 210/240 or 360.
(iii)
Integrated Part Load Value is rated in accordance with ARI Standard 210/240 or 360. Units are rated at 80°F ambient, 80°F entering dry bulb, and 67°F entering wet bulb at ARI rated cfm.
(iv)
Outdoor Sound Rating shown is tested in accordance with ARI Standard 270 or 370.
(v)
For 380V/60Hz units, the oversized motor (Indoor Fan) is used as the standard motor. Refer to oversized motor data.
(vi)
An optional 2 inch pleated filter is also available.
(vii)
Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
(viii)
Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standards Institute standards. Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at th e rat e of 4% for each 1000 feet above sea level.
(ix)
AFUE is rated in accordance with DOE test procedures.
*Indicates both downflow/horizontal units.
(viii)
RT-PRC024-EN 17
General Data
(17½, 20 Tons Standard Efficiency)
Table 2. General Data — 17½-20 Tons
17½ Tons Downflow & Horizontal Units 20 Tons Downflow & Horizontal Units
TC*210C3,4,W,K YC*210C3,4,WL/H,K TC*240B3,4,W,K YC*240B3,4,WL/H,K
(vi)
(vii)
(i)
(iii)
(ii)
(iv)
(v)
210,000
9.8
7,000/5,800
196,000
10.0
20.0
9.4 9.4 9.4 9.4
Hi-Performance
0.375
27.12 3/16
Hi-Performance
0.375
17.50 4/15
Short Orifice
1/1.00 NPT
Propeller
2/26
Direct/1
13,400
2/1.0
1,125
FC Centrifugal
1/15x15
Belt/1
1
5.0/7.5
3,450/3,470
145T/184T
Throwaway
(2)20x20x2,(4)20x25x2 (2)20x20x2,(4)20x25x2
21.0/14.3 Circuit
21.5/14.5 Circuit
210,000
9.6
7,000/5,800
196,000
9.8
20.41
Hi-Performance
0.375
27.12 3/16
Hi-Performance
0.375
17.50 4/15
Short Orifice
1/1.00 NPT
Propeller
2/26
Direct/1
13,400
2/1.0
1,125
FC Centrifugal
1/15x15
Belt/1
1
5.0/7.5
3,450/3,470
145T/184T
Throwaway
(2)20x20x2,(4)20x25x2 (2)20x20x2,(4)20x25x2
21.0/14.3 Circuit
21.0/14.5 Circuit
242,000
9.7
8,000/7,000
232,000
10.0
23.91
Hi-Performance
0.375
35.30 3/16
Hi-Performance
0.375
26.00 2/15
Short Orifice
1/1.00 NPT
Propeller
2/26
Direct/1
14,600
2/1.0 1,125
FC Centrifugal
1/18x18
Belt/1
1
5.0/7.5
3,450/3,470
145T/184T
Throwaway
(4)20x20x2,(4)20x25x2
(8)20x25x2
18.9/21.0 Circuit 18.9/21.0 Circuit
242,000
9.5
8,000/7,000
232,000
9.8
24.42
Hi-Performance
0.375
35.30 3/16
Hi-Performance
0.375
26.00 2/15
Short Orifice
1/1.00 NPT
Propeller
2/26
Direct/1
14,600
2/1.0 1,125
FC Centrifugal
1/18x18
Belt/1
5.0/7.5
3,450/3,470
145T/184T
Throwaway
(4)20x20x2,(4)20x25x2
(8)20x25x2
1
Cooling Performance
Gross Cooling Capacity EER (Downflow/Horizontal) Nominal CFM / ARI Rated CFM ARI Net Cooling Capacity Integrated Part Load Value System Power (kW)
Compressor
Number/Type 2/Scrolls 2/Scrolls 2/Scrolls 2/Scrolls
Sound
Outdoor Sound Rating (BELS)
Outdoor Coil
Typ e Tube Size (in.) OD Face Area (sq. ft.) Rows/FPI
Indoor Coil
Typ e Tub e S i z e ( i n .) Face Area (sq. ft.) Rows/FPI Refrigerant Control Drain Connection Number/Size (in.)
Outdoor Fan
Typ e Number Used/Diameter (in.) Drive Type/No. Speeds CFM Number Motors/HP Motor RPM
Indoor Fan
Typ e Number Used/Diameter (in.) Drive Type/Number Speeds Number Motors Motor HP (Standard/Oversized) Motor RPM (Standard/Oversized) Motor Frame Size (Standard/ Oversized)
Filters
Typ e F u r n i s h e d Number Size Recommended Downflow Horizontal
Refrigerant Charge
Pounds of R-22 Downflow Horizontal
General Data
(17½, 20 Tons Standard Efficiency)
Table 2. (continued) General Data — 17½-20 Tons
17½ Tons Downflow & Horizontal Units 20 Tons Downflow & Horizontal Units
Heating Performance
(Gas/Electric Only)
Heating Models Low High Low High
Heating Input (Btuh) 250,000 350,000 250,000 400,000
1st Stage (Btu) 175,000 250,000 175,000 300,000
Heating Output (Btuh) 203,000 284,000 203,000 324,000
1st Stage (Btu) 142,000 203,000 142,000 243,000
AFUE (%)
(ix)
Downflow/Horizontal 80.7/79.9 80.1/79.1 80.2/81.0 79.8/79.7
Steady State Efficiency% 81.0 81.0 81.0 81.0
No. Burners 11
No. Stages 22
Gas Supply Line Pressure (in w.c.)
Natural or LP (minimum/maximum) 2.5/14.0 2.5/14.0
Gas Connection Pipe Size (in.) 1/2 3/4 1/2 3/4
(i)
Cooling Performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Certified in accordance with the Unitary Large Equipment Certification Program, which is based on ARI Standard 340/360-93.
(ii)
EER is rated at ARI conditions and in accordance with ARI Standard 210/240 or 360.
(iii)
Integrated Part Load Value is rated in accordance with ARI Standard 210/240 or 360. Units are rated at 80°F ambient, 80°F entering dry bulb, and 67°F entering wet bulb at ARI rated cfm.
(iv)
Outdoor Sound Rating shown is tested in accordance with ARI Standard 270 or 370.
(v)
For 380V/60Hz units, the oversized motor (Indoor Fan) is used as the standard motor. Refer to oversized motor data.
(vi)
An optional 2 inch pleated filter is also available.
(vii)
Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
(viii)
Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standards Institute standards. Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level.
(ix)
AFUE is rated in accordance with DOE test procedures.
*Indicates both downflow/horizontal units.
(viii)
RT-PRC024-EN 19
General Data
Table 3. General Data — 25 Tons
25 Tons Downflow & Horizontal Units
T/YC*300B3,4,W(L,H
(vii)
(viii)
(ii)
(iii)
(iv)
(v)
(vi)
290,000
9.7
10,000/8,750
272,000
9.8
28.05
9.4
Hi-Performance
0.375
36.43 2/16
Hi-Performance
0.375
26.00 3/15
Short Orifice
1/1.00 NPT
Propeller
2/28
Direct/1
16,700
2/1.0 1,125
FC Centrifugal
1/18x18
Belt/1
1
7.5/N/A
3,470/N/A
184T/N/A
Throwaway
(4)20x20x2,(4)20x25x2
(8)20x25x2
Cooling Performance
Gross Cooling Capacity EER (Downflow/Horizontal) Nominal CFM / ARI Rated CFM ARI Net Cooling Capacity Integrated Part Load Value System Power (kW)
Compressor
Number/Type 2/Scrolls
Sound
Outdoor Sound Rating (BELS)
Outdoor Coil
Typ e Tube Size (in.) OD Face Area (sq. ft.) Rows/FPI
Indoor Coil
Typ e Tub e S i z e ( i n .) Face Area (sq. ft.) Rows/FPI Refrigerant Control Drain Connection Number/Size (in.)
Outdoor Fan
Typ e Number Used/Diameter (in.) Drive Type/No. Speeds CFM Number Motors/HP Motor RPM
Indoor Fan
Typ e Number Used/Diameter (in.) Drive Type/Number Speeds Number Motors Motor HP (Standard/Oversized) Motor RPM (Standard/Oversized) Motor Frame Size (Standard/Oversized)
Filters
Typ e F u r n i s h e d Number Size Recommended Downflow Horizontal
Refrigerant Charge
Pounds of R-22 Downflow Horizontal 17.0/Circuit
(25 Tons Standard Efficiency)
(i)
),K
General Data
Table 3. (continued) General Data — 25 Tons
25 Tons Downflow & Horizontal Units
Heating Performance
(Gas/Electric Only)
Heating Models Low High
Heating Input (Btuh) 250,000 400,000
1st Stage (Btu) 175,000 300,000
Heating Output (Btuh) 203,000 324,000
1st Stage (Btu) 142,000 243,000
AFUE (%)
(x)
Downflow/Horizontal 80.2/81.0 79.8/79.7
Steady State Efficiency% 81.4/81.0 80.8/81.0
No. Burners 1
No. Stages 2
Gas Supply Line Pressure (in w.c.)
Natural or LP (minimum/maximum) 2.5/14.0
Gas Connection Pipe Size (in.) 1/2 3/4
(i)
Applies to Y* models only.
(ii)
Cooling Performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Certified in ac­cordance with the Unitary Large Equipment Certification Program, which is based on ARI Standard 340/360-93.
(iii)
EER is rated at ARI conditions and in accordance with ARI Standard 210/240 or 360.
(iv)
Integrated Part Load Value is rated in accordance with ARI Standard 210/240 or 360. Units are rated at 80°F ambient, 80°F entering dry bulb, and 67°F entering wet bulb at ARI rated cfm.
(v)
Outdoor Sound Rating shown is tested in accordance with ARI Standard 270 or 370.
(vi)
For 380V/60Hz units, the oversized motor (Indoor Fan) is used as the standard motor. Refer to oversized motor data.
(vii)
An optional 2 inch pleated filter is also available.
(viii)
Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and ser­vice instructions.
(ix)
Heating Performance limit settings and rating data were established and approved under labora­tory test conditions using American National Standards Institute standards. Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level.
(x)
AFUE is rated in accordance with DOE test procedures.
*Indicates both downflow/horizontal units.
(ix)
(25 Tons Standard Efficiency)
RT-PRC024-EN 21
General Data
(12½,15 Tons High Efficiency)
Table 4. General Data — 12½-15 Tons
12½ Tons Downflow & Horizontal Units 15 Tons Downflow & Horizontal Units
T/YC*151C3,4,W
(viii)
(iii)
(v)
(vi)
(vii)
(ix)
154,000
11.30
5,000/4,400
146,000
11.5
12.92
9.2 9.2
Hi-Performance
0.375
27.12 2/16
Hi-Performance
0.375
17.50 3/15
Short Orifice
1/1.00 NPT
Propeller
2/26
Direct/1
10,400
2/.50 1,100
FC Centrifugal
1/15x15
Belt/1
1
3.0/5.0
1,740/3,450
145T/145T
Throwaway
(2)20x20x2,(4)20x25x2 (2)20x20x2,(4)20x25x2
Hi-Performance
0.375
17.5 1/16
15.0/13.8
15.3/14.3
Cooling Performance
Gross Cooling Capacity
(iv)
EER Nominal CFM / ARI Rated CFM ARI Net Cooling Capacity Integrated Part Load Value System Power (kW)
Compressor
Number/Type 2/Scrolls 2/Scrolls
Sound
Outdoor Sound Rating (BELS)
Outdoor Coil
Typ e Tube Size (in.) OD Face Area (sq. ft.) Rows/FPI
Indoor Coil
Typ e Tub e S i z e ( i n .) Face Area (sq. ft.) Rows/FPI Refrigerant Control Drain Connection Number/Size (in.)
Outdoor Fan
Typ e Number Used/Diameter (in.) Drive Type/No. Speeds CFM Number Motors/HP Motor RPM
Indoor Fan
Typ e Number Used/Diameter (in.) Drive Type/Number Speeds Number Motors Motor HP (Standard/Oversized) Motor RPM (Standard/Oversized) Motor Frame Size (Standard/Oversized)
Filters
Typ e F u r n i s h e d Number Size Recommended Downflow Horizontal
Optional Hot Gas Reheat Coil
Typ e Tube Size (in.) OD Face Area (sq. ft) Rows/FPI
Refrigerant Charge Pounds of R-22
Standard Optional Hot Gas Reheat Coil
(i)
T/YC*181C3,4,W
189,000
11.50
6,000/5,300
180,000
13.3
15.65
Hi-Performance
0.375
35.30 3/16
Hi-Performance
0.375
26.00 3/15
Short Orifice
1/1.00 NPT
Propeller
2/26
Direct/1
11,000
2/.50 1,100
FC Centrifugal
1/18x18
Belt/1
1
3.0/5.0
1,740/3,450
145T/145T
Throwaway
(4)20x20x2,(4)20x25x2
(8)20x25x2
Hi-Performance
0.375
26
1/16
25.0/13.0
27.8/11.4
(ii)
General Data
(12½,15 Tons High Efficiency)
Table 4. (continued) General Data — 12½-15 Tons
12½ Tons Downflow & Horizontal Units 15 Tons Downflow & Horizontal Units
Heating Performance
(Gas/Electric Only)
Heating Models Low High Low High
Heating Input (Btuh) 150,000 250,000 250,000 350,000
1st Stage (Btu) 100,000 175,000 175,000 250,000
Heating Output (Btuh) 122,000 203,000 203,000 284,000
1st Stage (Btu) 81,000 142,000 142,000 203,000
(xi)
AFUE%
Downflow/Horizontal 81.0/81.0 80.7/79.9 80.7/79.9 80.1/79.1
Steady State Efficiency% 81.0 81.0 81.0 81.0
No. Burners 11 1 1
No. Stages 22 2 2
Gas Supply Line Pressure (in w.c.)
Natural or LP (minimum/maximum) 2.5/14.0 2.5/14.0
Gas Connection Pipe Size (in.) 1/2 1/2 1/2 3/4
(i)
TXV/Face-Split Option (Downflow Only) YCD151C3,4,W (EER):11.3; (System Power kW): 12.92; (Refrigerant Control): Expansion Valve; (Refrig­erant Charge): 13.4/12.0.
(ii)
TXV/Face-Split Option (Downflow Only) YCD181C3,4,W (EER):11.4; (System Power kW): 15.79; (Refrigerant Control): Expansion Valve; (Refrig­erant Charge): 26.0/12.0.
(iii)
Cooling Performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Certified in accordance with the Unitary Large Equipment Certification Program, which is based on ARI Standard 340/360-93.
(iv)
EER is rated at ARI conditions and in accordance with ARI Standard 210/240 or 360.
(v)
Integrated Part Load Value is rated in accordance with ARI Standard 210/240 or 360. Units are rated at 80°F ambient, 80°F entering dry bulb, and 67°F entering wet bulb at ARI rated cfm.
(vi)
Outdoor Sound Rating shown is tested in accordance with ARI Standard 270 or 370.
(vii)
For 380V/60Hz units, the oversized motor (Indoor Fan) is used as the standard motor. Refer to oversized motor data.
(viii)
An optional 2 inch pleated filter is also available.
(ix)
Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
(x)
Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Stan­dards Institute standards. Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level.
(xi)
AFUE is rated in accordance with DOE test procedures.
(x)
RT-PRC024-EN 23
General Data
(17½, 20, 25 Tons High Efficiency)
Table 5. General Data — 17½, 20, 25 Tons
17½ Tons Downflow &
Horizontal Units
T/YC*211C3,4,W T/YC*241C3,4,W
(vii)
(ii)
(iv)
(v)
(viii)
220,000
11.0
7,000/6,200
208,000
12.0
18.91
9.4 9.4 9.4
Hi-Performance
0.375
35.30 3/16
Hi-Performance
0.375
26.00 4/15
Short Orifice
1/1.0 NPT
Propeller
2/26
Direct/1
12,800
2/1.0 1,125
FC Centrifugal
1/18x18
Belt/1
1
5.0/7.5
3,450/3,470
145T/184T
Throwaway
(4)20x20x2,(4)20x25x2
(8)20x25x2
— — — —
25.7/12.5 —
Cooling Performance
Gross Cooling Capacity
(iii)
EER Nominal CFM / ARI Rated CFM ARI Net Cooling Capacity Integrated Part Load Value System Power (kW)
Compressor
Number/Type 2/Scrolls 2/Scrolls 2/Scrolls
Sound
Outdoor Sound Rating (BELS)
Outdoor Coil
Typ e Tube Size (in.) OD Face Area (sq. ft.) Rows/FPI
Indoor Coil
Typ e Tub e S i z e ( i n .) Face Area (sq. ft.) Rows/FPI Refrigerant Control Drain Connection Number/Size (in.)
Outdoor Fan
Typ e Number Used/Diameter (in.) Drive Type/No. Speeds CFM Number Motors/HP Motor RPM
Indoor Fan
Typ e Number Used/Diameter (in.) Drive Type/Number Speeds Number Motors Motor HP (Standard/Oversized) Motor RPM (Standard/Oversized) Motor Frame Size (Standard/Oversized)
Filters
Typ e F u r n i s h e d Number Size Recommended Downflow Horizontal
Optional Hot Gas Reheat Coil
Typ e Tube Size (in.) OD Face Area (sq. ft) Rows/FPI
Refrigerant Charge Pounds of R-22
Standard Optional Hot Gas Reheat Coil
20 Tons Downflow &
Horizontal Units
(i)
268,000
10.6
8,000/7,000
250,000
11.2
23.58
Hi-Performance
0.375
35.30 3/16
Hi-Performance
0.375
26.00
(vi)
/15
4
Short Orifice
1/1.0 NPT
Propeller
2/26
Direct/1
13,700
2/1.0 1,125
FC Centrifugal
1/18x18
Belt/1
1
5.0/7.5
3,450/3,470
145T/184T
Throwaway
(4)20x20x2,(4)20x25x2
(8)20x25x2
Hi-Performance
0.375
26
1/16
21.8/21.8
21.3/21.0
25 Tons Downflow &
Horizontal Units
T/YC*301C3,4,W
300,000
10.4
10,000/8,750
278,000
11.0
26.73
Hi-Performance
0.375
35.30 3/16
Hi-Performance
0.375
26.00 4/15
Short Orifice
1/1.0 NPT
Propeller
2/26
Direct/1
13,700
2/1.0 1,125
FC Centrifugal
1/18x18
Belt/1
1
7.5
3,470
184T
Throwaway
(4)20x20x2,(4)20x25x2
(8)20x25x2
— — — —
24.5/24.5 —
General Data
(17½, 20, 25 Tons High Efficiency)
Table 5. (continued) General Data — 17½, 20, 25 Tons
17½ Tons Downflow &
Horizontal Units
Heating Performance
(ix)
(Gas/Electric Only)
Heating Models Low High Low High Low High
Heating Input (Btuh) 250,000 350,000 250,000 400,000 250,000 400,000
1st Stage (Btu) 175,000 250,000 175,000 300,000 175,000 300,000
Heating Output (Btuh) 203,000 284,000 203,000 324,000 203,000 324.000
1st Stage (Btu) 142,000 203,000 142,000 243,000 142,000 243,000
(x)
AFUE%
Downflow/Horizontal 80.2/81.0 79.3/79.7 80.2/81.0 79.8/79.7 80.2/81.0 79.8/79.7
Steady State Efficiency% 81.0 81.0 81.0 81.0 81.0 81.0
No. Burners 111111
No. Stages 222222
Gas Supply Line Pressure (in w.c.)
Natural or LP (minimum/maximum) 2.5/14.0 2.5/14.0 2.5/14.0
Gas Connection Pipe Size (in.) 1/2 3/4 1/2 3/4 1/2 3/4
(i)
TXV/Face-Split Option (Downflow Only) YCD241C3,4,W (Gross Cooling Capacity):259,000; (ARI Net Cooling Capacity): 244,000; (System Power kW):
23.02; (Refrigerant Control): Expansion Valve; (Refrigerant Charge): 21.5/22.2
(ii)
Cooling Performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Certified in accordance with the Unitary Large Equipment Certification Program, which is based on ARI Standard 340/360-93.
(iii)
EER is rated at ARI conditions and in accordance with ARI Standard 210/240 or 360.
(iv)
Integrated Part Load Value is rated in accordance with ARI Standard 210/240 or 360. Units are rated at 80°F ambient, 80°F entering dry bulb, and 67°F entering wet bulb at ARI rated cfm.
(v)
Outdoor Sound Rating shown is tested in accordance with ARI Standard 270 or 370.
(vi)
On Hot Gas Reheat units, Indoor Coil = 3 rows.
(vii)
An optional 2 inch pleated filter is also available.
(viii)
Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
(ix)
Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standards Institute standards. Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level.
(x)
AFUE is rated in accordance with DOE test procedures.
*Indicates both downflow/horizontal units.
20 Tons Downflow &
Horizontal Units
25 Tons Downflow &
Horizontal Units
RT-PRC024-EN 25
Performance Data
Table 6. Gross Cooling Capacities 12½ Tons Three Phase Standard Efficiency T/YC*150D3,4,W,K
Ambient Temperature
85 95 105 115
Air Ent Entering Wet Bulb
Flow DB 61 67 73 61 67 73 61 67 73 61 67 73
CFM(F)MBHSHCMBHSHCMBHSHCMBHSHCMBHSHCMBHSHCMBHSHCMBHSHCMBHSHCMBHSHCMBHSHCMBHSHC
4500 75 135.0 108.0 153.0 86.0 162.0 59.3 126.0 103.0 146.0 82.0 158.0 56.7 116.0 98.2 138.0 77.7 152.0 53.8 106.0 93.1 127.0 80.0 145.0 50.5
80 136.0 128.0 154.0 105.0 163.0 79.5 127.0 123.0 147.0 101.0 159.0 76.5 117.0 117.0 138.0 97.0 153.0 73.2 110.0 110.0 128.0 92.2 145.0 69.6
85 142.0 142.0 154.0 123.0 164.0 95.9 135.0 135.0 147.0 120.0 159.0 94.2 127.0 127.0 138.0 116.0 153.0 91.7 120.0 120.0 128.0 111.0 146.0 88.5
90 150.0 150.0 155.0 142.0 166.0 112.0 144.0 144.0 148.0 139.0 161.0 111.0 137.0 137.0 139.0 136.0 154.0 109.0 130.0 130.0 130.0 130.0 146.0 107.0
5000 75 139.0 114.0 155.0 89.8 163.0 60.4 129.0 109.0 149.0 85.4 159.0 57.9 120.0 104.0 141.0 89.5 154.0 55.0 109.0 98.9 131.0 85.1 147.0 51.6
80 140.0 136.0 156.0 109.0 164.0 81.3 130.0 130.0 149.0 106.0 160.0 79.1 123.0 123.0 141.0 102.0 155.0 75.8 115.0 115.0 131.0 97.5 147.0 72.2
85 147.0 147.0 157.0 129.0 166.0 98.2 141.0 141.0 150.0 126.0 161.0 96.8 133.0 133.0 141.0 123.0 155.0 94.8 125.0 125.0 131.0 118.0 148.0 91.9
90 155.0 155.0 158.0 148.0 167.0 115.0 149.0 149.0 151.0 147.0 163.0 115.0 143.0 143.0 143.0 143.0 157.0 114.0 135.0 135.0 135.0 135.0 149.0 111.0
5500 75 142.0 120.0 157.0 91.3 164.0 61.5 132.0 115.0 151.0 88.8 160.0 59.0 122.0 110.0 143.0 84.2 155.0 56.1 112.0 104.0 133.0 89.9 148.0 52.9
80 143.0 143.0 158.0 112.0 165.0 82.0 135.0 135.0 152.0 110.0 161.0 80.4 127.0 127.0 143.0 107.0 156.0 78.3 119.0 119.0 134.0 102.0 149.0 74.7
85 152.0 152.0 159.0 133.0 167.0 99.9 145.0 145.0 152.0 132.0 163.0 99.1 138.0 138.0 144.0 129.0 157.0 97.4 130.0 130.0 134.0 125.0 150.0 95.0
90 159.0 159.0 160.0 154.0 169.0 118.0 153.0 153.0 153.0 153.0 164.0 118.0 147.0 147.0 147.0 147.0 158.0 117.0 140.0 140.0 140.0 140.0 151.0 116.0
6000 75 145.0 125.0 158.0 93.3 165.0 62.5 135.0 120.0 153.0 91.2 161.0 60.1 125.0 115.0 145.0 87.3 156.0 57.2 115.0 110.0 136.0 82.8 149.0 54.0
80 147.0 147.0 159.0 115.0 166.0 82.9 140.0 140.0 153.0 114.0 162.0 81.7 132.0 132.0 145.0 111.0 157.0 79.3 123.0 123.0 136.0 107.0 150.0 76.5
85 155.0 155.0 161.0 137.0 168.0 101.1 149.0 149.0 154.0 137.0 164.0 101.0 142.0 142.0 146.0 135.0 158.0 99.8 134.0 134.0 137.0 131.0 151.0 97.8
90 161.0 161.0 162.0 159.0 170.0 120.0 156.0 156.0 156.0 156.0 166.0 121.0 150.0 150.0 150.0 150.0 160.0 121.0 143.0 143.0 143.0 143.0 152.0 119.0
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula,
refer to appropriate airflow table notes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
*Indicates both downflow and horizontal units.
Table 7. Gross Cooling Capacities 15 Tons Three Phase Standard Efficiency T/YC*180B3,4,W,K
Ambient Temperature
85 95 105 115
Air Ent Entering Wet Bulb
Flow DB 61 67 73 61 67 73 61 67 73 61 67 73
CFM (F)MBHSHCMBHSHCMBHSHCMBHSHCMBHSHCMBHSHCMBHSHCMBHSHCMBHSHCMBHSHCMBHSHCMBHSHC
5400 75 168.0 133.0 188.0 106.0 198.0 73.0 157.0 128.0 181.0 101.0 194.0 70.4 147.0 122.0 172.0 97.0 187.0 67.3 137.0 117.0 162.0 92.1 179.0 63.2
80 168.0 156.0 188.0 128.0 199.0 97.3 155.0 155.0 181.0 125.0 195.0 94.3 149.0 143.0 172.0 120.0 188.0 90.8 140.0 137.0 162.0 115.0 179.0 86.7
85 174.0 174.0 189.0 150.0 200.0 117.0 166.0 166.0 182.0 147.0 196.0 115.0 158.0 158.0 172.0 143.0 189.0 113.0 150.0 150.0 162.0 138.0 180.0 110.0
90 184.0 184.0 190.0 172.0 202.0 136.0 177.0 177.0 183.0 170.0 197.0 135.0 170.0 170.0 170.0 170.0 190.0 133.0 162.0 162.0 165.0 157.0 181.0 131.0
6000 75 172.0 140.0 190.0 110.0 199.0 74.3 161.0 134.0 184.0 106.0 195.0 71.7 151.0 129.0 175.0 101.0 189.0 68.7 140.0 124.0 165.0 96.1 181.0 64.9
80 169.0 169.0 191.0 133.0 200.0 99.4 164.0 157.0 184.0 130.0 196.0 97.2 155.0 151.0 176.0 126.0 190.0 93.8 145.0 145.0 165.0 121.0 182.0 89.9
85 181.0 181.0 192.0 156.0 202.0 119.0 173.0 173.0 185.0 154.0 198.0 118.0 165.0 165.0 176.0 151.0 191.0 116.0 157.0 157.0 166.0 146.0 183.0 113.0
90 189.0 189.0 193.0 179.0 204.0 140.0 183.0 183.0 183.0 183.0 199.0 139.0 176.0 176.0 178.0 171.0 193.0 138.0 168.0 168.0 170.0 166.0 184.0 136.0
6600 75 176.0 147.0 192.0 112.0 200.0 75.5 165.0 141.0 186.0 110.0 196.0 73.0 154.0 136.0 178.0 105.0 190.0 69.8 144.0 130.0 168.0 99.8 182.0 66.1
80 178.0 171.0 193.0 136.0 201.0 101.0 169.0 165.0 187.0 135.0 197.0 98.8 160.0 159.0 178.0 131.0 191.0 96.1 150.0 150.0 168.0 127.0 183.0 92.6
85 185.0 185.0 194.0 161.0 203.0 122.0 179.0 179.0 188.0 160.0 199.0 121.0 171.0 171.0 179.0 158.0 193.0 119.0 163.0 163.0 169.0 153.0 185.0 116.0
90 193.0 193.0 193.0 193.0 205.0 143.0 188.0 188.0 188.0 188.0 201.0 143.0 181.0 181.0 182.0 178.0 195.0 142.0 173.0 173.0 174.0 174.0 186.0 140.0
7200 75 179.0 152.0 194.0 114.0 201.0 76.7 168.0 147.0 188.0 112.0 197.0 74.2 158.0 142.0 180.0 109.0 191.0 71.0 142.0 142.0 170.0 103.0 183.0 67.2
80 182.0 177.0 195.0 140.0 202.0 103.0 173.0 172.0 189.0 139.0 198.0 100.0 164.0 164.0 181.0 136.0 192.0 97.6 155.0 155.0 171.0 132.0 184.0 94.4
85 189.0 189.0 196.0 166.0 204.0 125.0 183.0 183.0 190.0 166.0 200.0 123.0 176.0 176.0 182.0 164.0 194.0 121.0 167.0 167.0 167.0 167.0 186.0 119.0
90 197.0 197.0 197.0 197.0 206.0 146.0 192.0 192.0 193.0 187.0 202.0 146.0 185.0 185.0 186.0 184.0 196.0 146.0 177.0 177.0 177.0 177.0 188.0 144.0
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula,
refer to appropriate airflow table notes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
*Indicates both downflow and horizontal units.
26 RT-PRC024-EN
Performance Data
(17½, 20 Tons Standard Efficiency)
Table 8. Gross Cooling Capacities 17½ Tons Three Phase Standard Efficiency T/YC*210C3,4,W,K
Ambient Temperature
85 95 105 115
Air Ent Entering Wet Bulb
Flow DB 61 67 73 61 67 73 61 67 73 61 67 73
CFM (F)MBHSHCMBHSHCMBHSHCMBHSHCMBHSHCMBHSHCMBHSHCMBHSHCMBHSHCMBHSHCMBHSHCMBHSHC
6300 75 195.0 171.0 213.0 127.0 224.0 83.3 182.0 164.0 206.0 124.0 219.0 80.1 169.0 158.0 195.0 119.0 213.0 76.1 155.0 151.0 181.0 113.0 204.0 71.8
80 200.0 200.0 214.0 157.0 226.0 114.0 191.0 191.0 207.0 156.0 221.0 112.0 180.0 180.0 196.0 153.0 214.0 110.0 168.0 168.0 183.0 147.0 205.0 106.0
85 211.0 211.0 217.0 188.0 229.0 140.0 204.0 204.0 209.0 188.0 223.0 139.0 195.0 195.0 199.0 186.0 216.0 139.0 184.0 184.0 187.0 182.0 206.0 137.0
90 219.0 219.0 220.0 217.0 230.0 164.0 214.0 214.0 214.0 214.0 225.0 167.0 207.0 207.0 207.0 207.0 218.0 169.0 198.0 198.0 198.0 198.0 208.0 168.0
7000 75 199.0 181.0 215.0 131.0 225.0 84.7 187.0 176.0 208.0 129.0 221.0 81.4 174.0 169.0 198.0 125.0 215.0 77.7 160.0 160.0 185.0 119.0 206.0 73.4
80 206.0 206.0 217.0 164.0 228.0 116.0 198.0 198.0 210.0 164.0 222.0 114.0 188.0 188.0 200.0 162.0 216.0 113.0 176.0 176.0 187.0 157.0 207.0 110.0
85 216.0 216.0 220.0 197.0 230.0 144.0 210.0 210.0 213.0 198.0 225.0 144.0 202.0 202.0 204.0 198.0 218.0 145.0 192.0 192.0 192.0 192.0 209.0 144.0
90 224.0 224.0 224.0 224.0 233.0 172.0 219.0 219.0 219.0 219.0 227.0 173.0 212.0 212.0 212.0 212.0 221.0 177.0 204.0 204.0 204.0 204.0 211.0 177.0
7700 75 203.0 191.0 217.0 135.0 226.0 86.1 192.0 187.0 211.0 138.0 222.0 82.9 178.0 178.0 201.0 131.0 216.0 79.2 165.0 165.0 188.0 126.0 208.0 75.0
80 211.0 211.0 219.0 169.0 229.0 118.0 204.0 204.0 212.0 171.0 224.0 117.0 194.0 194.0 203.0 170.0 218.0 116.0 183.0 183.0 191.0 167.0 209.0 114.0
85 220.0 220.0 222.0 203.0 232.0 147.0 214.0 214.0 216.0 207.0 226.0 148.0 207.0 207.0 207.0 207.0 220.0 150.0 197.0 197.0 197.0 197.0 211.0 150.0
90 226.0 226.0 226.0 226.0 235.0 176.0 223.0 223.0 222.0 222.0 229.0 179.0 216.0 216.0 216.0 216.0 223.0 184.0 208.0 208.0 208.0 208.0 214.0 186.0
8400 75 206.0 199.0 218.0 138.0 227.0 87.8 195.0 195.0 212.0 143.0 223.0 84.3 183.0 183.0 203.0 136.0 217.0 80.6 171.0 171.0 190.0 132.0 209.0 76.5
80 214.0 214.0 221.0 174.0 230.0 120.0 208.0 208.0 214.0 178.0 226.0 120.0 199.0 199.0 205.0 178.0 219.0 119.0 188.0 188.0 194.0 176.0 211.0 117.0
85 222.0 222.0 224.0 210.0 233.0 150.0 217.0 217.0 218.0 215.0 228.0 151.0 211.0 211.0 211.0 211.0 222.0 155.0 202.0 202.0 202.0 202.0 213.0 156.0
90 229.0 229.0 229.0 229.0 236.0 181.0 225.0 225.0 225.0 225.0 231.0 184.0 220.0 220.0 219.0 219.0 225.0 190.0 212.0 212.0 212.0 212.0 216.0 193.0
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula,
refer to appropriate airflow table notes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
*Indicates both downflow and horizontal units.
Table 9. Gross Cooling Capacities 20 Tons Three Phase Standard Efficiency T/YC*240B3,4,W,K
Ambient Temperature
85 95 105 115
Air Ent Entering Wet Bulb
Flow DB 61 67 73 61 67 73 61 67 73 61 67 73
CFM (F)MBHSHCMBHSHCMBHSHCMBHSHCMBHSHCMBHSHCMBHSHCMBHSHCMBHSHCMBHSHCMBHSHCMBHSHC
7200 75 223.0 180.0 251.0 143.0 265.0 97.7 209.0 173.0 242.0 137.0 260.0 94.3 195.0 165.0 228.0 130.0 252.0 90.3 180.0 158.0 212.0 135.0 241.0 85.5
80 226.0 214.0 252.0 173.0 267.0 131.0 208.0 208.0 242.0 169.0 261.0 127.0 197.0 197.0 228.0 162.0 253.0 122.0 186.0 186.0 213.0 155.0 242.0 117.0
85 235.0 235.0 253.0 204.0 268.0 158.0 224.0 224.0 242.0 200.0 262.0 156.0 213.0 213.0 229.0 194.0 253.0 153.0 201.0 201.0 214.0 188.0 242.0 149.0
90 248.0 248.0 255.0 234.0 271.0 185.0 239.0 239.0 245.0 232.0 264.0 185.0 228.0 228.0 228.0 228.0 255.0 183.0 217.0 217.0 217.0 217.0 243.0 179.0
8000 75 229.0 190.0 255.0 148.0 267.0 99.4 215.0 183.0 246.0 142.0 262.0 96.1 200.0 175.0 233.0 136.0 254.0 92.2 185.0 168.0 218.0 129.0 244.0 87.1
80 228.0 228.0 256.0 180.0 268.0 134.0 217.0 217.0 246.0 176.0 264.0 131.0 205.0 205.0 233.0 171.0 255.0 127.0 193.0 193.0 218.0 164.0 245.0 121.0
85 243.0 243.0 257.0 212.0 271.0 162.0 233.0 233.0 247.0 210.0 265.0 161.0 222.0 222.0 234.0 206.0 257.0 158.0 210.0 210.0 220.0 199.0 245.0 155.0
90 255.0 255.0 259.0 245.0 273.0 190.0 247.0 247.0 247.0 247.0 267.0 191.0 237.0 237.0 237.0 237.0 258.0 190.0 226.0 226.0 226.0 226.0 247.0 187.0
8800 75 234.0 199.0 257.0 151.0 268.0 101.0 220.0 192.0 249.0 147.0 263.0 97.9 205.0 184.0 237.0 141.0 256.0 93.7 190.0 177.0 222.0 134.0 246.0 88.6
80 236.0 236.0 259.0 185.0 270.0 136.0 224.0 224.0 249.0 183.0 265.0 134.0 212.0 212.0 237.0 178.0 257.0 130.0 200.0 200.0 222.0 172.0 247.0 126.0
85 250.0 250.0 260.0 220.0 273.0 165.0 240.0 240.0 251.0 219.0 267.0 165.0 229.0 229.0 239.0 216.0 259.0 163.0 217.0 217.0 225.0 210.0 248.0 160.0
90 260.0 260.0 263.0 254.0 275.0 194.0 253.0 253.0 253.0 253.0 270.0 196.0 244.0 244.0 244.0 244.0 261.0 196.0 233.0 233.0 233.0 233.0 250.0 194.0
9600 75 238.0 208.0 259.0 154.0 269.0 103.0 224.0 201.0 251.0 151.0 265.0 99.6 209.0 193.0 240.0 146.0 257.0 95.1 194.0 186.0 225.0 139.0 248.0 89.2
80 242.0 242.0 261.0 190.0 271.0 137.0 231.0 231.0 252.0 189.0 266.0 136.0 219.0 219.0 240.0 185.0 259.0 133.0 206.0 206.0 226.0 180.0 249.0 129.0
85 254.0 254.0 263.0 227.0 274.0 167.0 246.0 246.0 254.0 227.0 269.0 168.0 236.0 236.0 243.0 225.0 261.0 167.0 224.0 224.0 229.0 220.0 251.0 165.0
90 264.0 264.0 264.0 264.0 277.0 198.0 258.0 258.0 258.0 258.0 272.0 201.0 249.0 249.0 249.0 249.0 263.0 202.0 239.0 239.0 239.0 239.0 252.0 201.0
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula,
refer to appropriate airflow table notes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
*Indicates both downflow and horizontal units.
RT-PRC024-EN 27
Performance Data
(25 Tons Standard Efficiency)
Table 10. Gross Cooling Capacities 25 Tons Three Phase Standard Efficiency T/YC*300B3,4,W,K
Ambient Temperature
85 95 105 115
Air Ent Entering Wet Bulb
Flow DB 61 67 73 61 67 73 61 67 73 61 67 73
CFM (F)MBHSHCMBHSHCMBHSHCMBHSHCMBHSHCMBHSHCMBHSHCMBHSHCMBHSHCMBHSHCMBHSHCMBHSHC
9000 75 266 224 299 174 319 118 247 215 285 167 309 113 228 205 266 172 297 108 209 196 244 163 280 99.9
80 270 268 300 215 321 161 252 252 285 209 311 155 237 237 266 200 297 149 221 221 244 190 280 142
85 286 286 301 255 323 196 272 272 286 250 312 194 256 256 267 242 298 189 240 240 246 233 281 183
90 301 301 304 295 326 232 289 289 289 289 314 231 275 275 275 275 300 229 259 259 259 259 282 224
10000 75 272 237 303 180 322 120 253 227 290 174 312 115 234 218 271 165 300 109 214 208 249 156 284 102
80 277 277 304 223 324 171 262 262 290 219 314 161 246 246 271 211 301 155 229 229 249 201 284 147
85 294 294 306 266 327 208 282 282 291 263 316 200 266 266 273 257 302 197 249 249 253 248 285 192
90 308 308 310 309 329 239 297 297 297 297 318 240 284 284 284 284 304 239 268 268 268 268 286 235
10500 75 275 243 305 183 323 122 256 233 291 177 314 117 236 223 273 188 301 111 216 214 251 178 285 103
80 282 282 306 227 325 174 267 267 292 223 315 162 250 250 273 216 302 157 233 233 251 206 286 150
85 298 298 308 272 328 216 286 286 294 270 317 203 270 270 276 264 304 200 253 253 256 255 286 196
90 312 312 311 311 330 256 301 301 301 301 320 244 288 288 288 288 306 244 273 273 272 272 288 241
11000 75 278 248 306 185 324 123 258 239 293 181 315 118 239 229 275 172 302 113 217 217 253 184 286 104
80 286 286 308 231 325 160 271 271 294 228 316 163 254 254 276 221 304 160 237 237 253 212 287 153
85 301 301 310 277 327 224 289 289 296 276 319 205 274 274 278 271 305 204 257 257 257 257 288 200
90 314 314 314 314 330 266 304 304 304 304 321 248 291 291 291 291 307 249 276 276 276 276 289 246
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula,
refer to appropriate airflow table notes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
*Indicates both downflow and horizontal units.
Performance Data
(12½ Tons High Efficiency)
Table 11. Gross Cooling Capacities 12½ Tons Three Phase Standard Refrigeration System High Efficiency T/YC*151C3,4,W
Ambient Temperature
85 95 105 115
Air Ent Entering Wet Bulb
Flow DB 61 67 73 61 67 73 61 67 73 61 67 73
CFM (F)MBHSHCMBHSHCMBHSHCMBHSHCMBHSHCMBHSHCMBHSHCMBHSHCMBHSHCMBHSHCMBHSHCMBHSHC
4500 75 137.0 116.0 157.0 90.2 166.0 60.8 127.0 110.0 151.0 87.1 163.0 58.5 116.0 105.0 140.0 82.3 158.0 55.8 106.0 99.7 128.0 80.6 152.0 52.8
80 140.0 139.0 158.0 111.0 167.0 82.9 130.0 130.0 151.0 109.0 164.0 80.8 122.0 122.0 141.0 104.0 159.0 77.8 114.0 114.0 128.0 98.5 152.0 74.6
85 149.0 149.0 158.0 132.0 169.0 100.0 142.0 142.0 151.0 131.0 165.0 99.4 133.0 133.0 141.0 126.0 159.0 98.2 125.0 125.0 130.0 121.0 152.0 96.0
90 158.0 158.0 160.0 153.0 170.0 118.0 152.0 152.0 154.0 152.0 166.0 118.0 145.0 145.0 145.0 145.0 160.0 118.0 137.0 137.0 137.0 137.0 153.0 117.0
5000 75 141.0 123.0 159.0 93.4 167.0 61.6 131.0 117.0 154.0 90.9 164.0 59.4 120.0 112.0 144.0 86.6 159.0 56.8 109.0 107.0 132.0 81.0 153.0 53.7
80 145.0 145.0 160.0 116.0 168.0 84.1 136.0 136.0 154.0 114.0 165.0 82.4 128.0 128.0 144.0 110.0 161.0 80.9 119.0 119.0 132.0 105.0 154.0 77.5
85 155.0 155.0 161.0 138.0 170.0 103.0 148.0 148.0 155.0 138.0 166.0 102.0 140.0 140.0 145.0 135.0 161.0 102.0 131.0 131.0 134.0 129.0 154.0 100.0
90 162.0 162.0 163.0 160.0 172.0 121.0 157.0 157.0 157.0 157.0 168.0 122.0 151.0 151.0 151.0 151.0 163.0 123.0 143.0 143.0 143.0 143.0 155.0 122.0
5500 75 145.0 129.0 161.0 95.8 168.0 62.6 134.0 124.0 156.0 94.4 165.0 60.4 123.0 119.0 147.0 90.4 161.0 57.8 112.0 112.0 135.0 85.1 154.0 54.6
80 150.0 150.0 162.0 119.0 169.0 85.2 142.0 142.0 156.0 119.0 167.0 84.0 133.0 133.0 147.0 116.0 162.0 82.4 124.0 124.0 135.0 111.0 155.0 80.1
85 158.0 158.0 163.0 143.0 172.0 104.0 153.0 153.0 157.0 144.0 168.0 104.0 146.0 146.0 149.0 143.0 163.0 105.0 137.0 137.0 137.0 137.0 156.0 104.0
90 165.0 165.0 165.0 165.0 173.0 123.0 161.0 161.0 161.0 161.0 170.0 126.0 156.0 156.0 156.0 156.0 164.0 127.0 149.0 149.0 149.0 149.0 157.0 127.0
6000 75 148.0 136.0 162.0 97.9 168.0 63.5 137.0 131.0 157.0 97.1 166.0 61.4 126.0 125.0 150.0 94.3 162.0 58.9 116.0 116.0 138.0 89.0 155.0 55.6
80 154.0 154.0 163.0 123.0 170.0 86.2 147.0 147.0 158.0 124.0 168.0 85.8 138.0 138.0 150.0 122.0 162.0 83.3 128.0 128.0 138.0 117.0 156.0 82.2
85 161.0 161.0 165.0 147.0 172.0 106.0 157.0 157.0 160.0 150.0 169.0 106.0 151.0 151.0 152.0 150.0 164.0 107.0 142.0 142.0 142.0 142.0 158.0 107.0
90 167.0 167.0 167.0 167.0 174.0 126.0 164.0 164.0 164.0 164.0 171.0 128.0 159.0 159.0 159.0 159.0 166.0 131.0 153.0 153.0 153.0 153.0 159.0 132.0
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula,
refer to appropriate airflow table notes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
*Indicates both downflow and horizontal units.
RT-PRC024-EN 29
Performance Data
(12½ Tons High Efficiency)
Table 12. Gross Cooling Capacities 12½ Tons Three Phase Dehumidification (Hot Gas Reheat) or TXV Option High Efficiency T/Y*D151C3,4,W
Ambient Temperature
85 95 105 115
Air Ent Entering Wet Bulb
Flow DB 61 67 73 61 67 73 61 67 73 61 67 73
CFM (F)MBHSHCMBHSHCMBHSHCMBHSHCMBHSHCMBHSHCMBHSHCMBHSHCMBHSHCMBHSHCMBHSHCMBHSHC
2500* 75 123.8 88.0 138.9 73.4 155.2 55.8 118.2 84.4 132.8 70.1 148.6 52.6 112.1 80.7 126.2 66.6 141.5 49.2 105.6 76.8 119.1 62.8 133.8 45.6
80 123.9 100.8 139.0 85.5 155.2 69.8 118.3 97.3 132.9 82.0 148.7 66.4 112.1 93.3 126.3 78.3 141.5 62.8 105.7 89.6 119.2 74.4 133.9 59.0
85 124.0 113.6 139.1 98.3 155.3 82.5 118.5 110.1 133.0 94.7 148.8 79.1 112.5 106.3 126.4 91.0 141.6 75.4 104.3 104.3 119.3 87.1 134.0 71.6
90 126.0 124.6 139.0 110.8 155.4 95.2 120.6 120.6 133.0 107.2 148.8 91.7 115.5 115.5 126.4 103.5 141.7 88.0 110.3 110.3 119.4 99.5 134.1 84.2
3250* 75 133.0 99.5 148.7 80.0 165.5 59.1 126.7 95.9 141.9 76.4 158.2 55.7 120.0 91.9 134.7 72.5 150.4 52.2 112.8 87.8 126.9 68.5 142.0 48.5
80 133.1 115.7 148.8 96.0 165.6 76.1 126.9 112.0 142.1 92.4 158.3 72.5 120.2 108.1 134.8 88.6 150.5 68.8 113.2 104.1 127.0 84.5 142.1 64.9
85 132.7 132.7 148.8 111.9 165.7 92.0 128.6 126.0 142.1 108.2 158.4 88.4 122.5 121.6 134.8 104.3 150.6 84.7 116.2 116.2 127.1 100.4 142.3 80.7
90 139.8 139.8 148.9 127.6 165.7 107.7 134.5 134.5 142.2 124.0 158.4 104.1 128.9 128.9 135.0 120.1 150.7 100.5 122.8 122.8 127.5 116.3 142.4 96.5
4000 75 139.3 109.8 155.4 86.2 172.5 61.7 132.6 106.1 148.2 82.5 164.7 58.3 125.4 102.0 140.4 78.6 156.4 54.7 117.8 97.8 132.2 74.5 147.6 50.9
80 139.6 128.9 155.5 105.4 172.6 81.5 133.1 125.4 148.3 101.7 164.8 77.8 126.2 121.5 140.6 97.7 156.5 74.0 119.0 115.2 132.3 93.6 147.7 70.1
85 143.2 143.2 155.5 124.1 172.8 100.5 137.6 137.6 148.3 120.4 165.0 96.8 131.5 131.5 140.7 116.6 156.7 93.0 125.0 125.0 132.4 112.5 147.8 89.0
90 151.0 151.0 156.1 143.3 172.8 119.2 145.3 145.3 149.0 139.6 165.0 115.6 139.0 139.0 141.6 136.1 156.7 111.7 132.4 132.4 134.0 129.4 147.9 107.6
4500 75 142.5 116.0 158.8 90.2 176.0 63.3 135.6 112.2 151.3 86.4 168.0 59.8 128.2 108.3 143.3 82.4 159.5 56.2 120.4 104.1 134.9 78.2 150.4 52.4
80 143.3 137.5 158.8 111.1 176.2 84.8 135.1 135.1 151.4 107.3 168.1 81.1 130.0 127.1 143.5 103.5 159.6 77.3 122.7 122.1 135.0 99.3 150.5 73.3
85 149.0 149.0 159.0 131.9 176.3 105.6 143.1 143.1 151.6 128.2 168.2 101.9 136.7 136.7 143.6 124.2 159.8 98.2 129.9 129.9 135.2 120.1 150.7 94.2
90 157.2 157.2 160.1 153.3 176.4 126.4 151.1 151.1 151.1 151.1 168.3 122.6 144.6 144.6 145.9 142.5 159.7 118.6 137.6 137.6 138.2 137.5 150.8 114.8
5000 75 145.1 121.9 161.6 93.7 179.0 64.7 138.1 118.3 154.0 89.9 170.8 61.2 130.5 114.2 145.8 85.9 162.0 57.3 122.6 110.1 137.1 81.7 152.7 53.3
80 145.6 145.6 161.6 116.5 179.2 87.9 140.4 138.6 154.0 112.8 170.9 84.2 133.1 133.1 145.8 108.8 162.1 80.3 126.2 126.2 137.1 104.5 152.9 76.3
85 154.1 154.1 162.0 139.4 179.3 110.7 147.9 147.9 154.4 135.7 171.0 106.9 141.3 141.3 146.3 131.7 162.2 103.0 134.2 134.2 137.7 127.6 153.1 99.2
90 162.6 162.6 162.5 162.5 179.5 133.2 156.3 156.3 157.1 154.9 171.2 129.5 149.5 149.5 149.4 149.4 162.4 125.5 142.2 142.2 142.2 142.2 153.1 121.5
5500 75 147.5 127.8 164.0 97.2 181.5 66.0 140.3 124.0 156.2 93.3 173.1 62.2 132.6 119.9 147.8 89.3 164.1 58.4 124.6 116.0 138.9 85.1 154.7 54.3
80 150.2 149.4 164.1 121.8 181.7 90.9 143.5 143.5 156.2 117.9 173.2 87.1 136.8 136.8 147.9 114.0 164.3 83.2 129.7 129.7 139.0 109.8 154.8 79.2
85 158.5 158.5 164.6 146.7 181.8 115.5 152.1 152.1 156.8 142.9 173.4 111.8 145.3 145.3 148.6 139.0 164.4 107.8 138.0 138.0 140.0 134.9 154.9 103.7
90 167.4 167.4 167.9 167.1 182.1 139.9 160.8 160.8 160.7 160.7 173.6 136.1 153.8 153.8 153.7 153.7 164.6 132.2 146.3 146.3 146.2 146.2 155.1 128.2
6000 75 149.6 133.5 165.9 100.3 183.7 67.0 142.2 129.6 158.0 96.4 175.1 63.2 134.4 125.6 149.5 92.5 166.0 59.4 126.4 121.7 140.5 88.3 156.4 55.3
80 153.4 153.4 166.1 126.9 183.8 93.6 147.0 147.0 158.1 123.0 175.2 90.0 140.2 140.2 149.6 118.9 166.1 86.1 132.8 132.8 140.6 115.0 156.5 82.0
85 162.5 162.5 166.9 153.7 183.9 120.1 155.9 155.9 159.1 150.0 175.3 116.3 148.8 148.8 148.7 148.7 166.2 112.5 141.3 141.3 142.4 138.6 156.6 108.4
90 171.6 171.6 171.6 171.6 184.3 146.4 164.8 164.8 164.7 164.7 175.7 142.6 157.6 157.6 157.5 157.5 166.5 138.7 149.9 149.9 149.9 149.9 157.0 134.7
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula,
refer to appropriate airflow table notes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
*For 2500 and 3250 CFM - Unit applications below 320 CFM/Ton are only applicable to TCD models only (No Gas Heat). See below for restrictions:
• Electric heaters restricted on applications below 320 CFM/Ton.
• Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters are required on applications below 320 CFM/Ton.