Trane Voyager III, IntelliPak II, IntelliPak I Installation Manual

Installation
Variable Frequency Drive Conversion TR1 to TR200
IntelliPak™ I and II and Voyager™ III only
Models: Only Clarksville built units with factory installed VFDs. This includes the following Voyager III commercial units with the VAV option and IntelliPak I and II units with the VAV and/or Statitrac™ option built prior to Trane TR200 drive unit installation.
S*HF 20 to 75 ton (IntelliPak I) TC, YC and TE 27½ to 50 ton (VIII) S*HG 90 to 130 ton (IntelliPak I) S*HJ 90 to 150 ton (IntelliPak II)
July 2009
PART-SVN121A-EN
Warnings, Cautions and Notices
Warnings, Cautions and Notices. Note that warnings, cautions and notices appear at
appropriate intervals throughout this manual. Warnings are provided to alert installing contractors to potential hazards that could result in personal injury or death. Cautions are designed to alert personnel to hazardous situations that could result in personal injury, while notices indicate a situation that could result in equipment or property-damage-only accidents.
Your personal safety and the proper operation of this machine depend upon the strict observance of these precautions.
ATTENTION: Warnings, Cautions and Notices appear at appropriate sections throughout this
literature. Read these carefully.
WARNIN G: Indicates a potentially hazardous situation which, if not avoided, could result in
death or serious injury.
CAUTION: Indicates a potentially hazardous situation which, if not avoided, could result in
minor or moderate injury. It could also be used to alert against unsafe practices.
NOTICE: Indicates a situation that could result in equipment or property-damage only accidents.
Note: This document is customer property and must be retained by the unit's owner for use by
maintenance personnel.
WARNING
Personal Protective Equipment (PPE) Required!
Installing/servicing this unit could result in exposure to electrical, mechanical and chemical hazards.
Before installing/servicing this unit, technicians MUST put on all Personal Protective Equipment (PPE) recommended for the work being undertaken. ALWAYS refer to appropriate MSDS sheets and OSHA guidelines for proper PPE.
When working with or around hazardous chemicals, ALWAYS refer to the appropriate MSDS sheets and OSHA guidelines for information on allowable personal exposure levels, proper respiratory protection and handling recommendations.
If there is a risk of arc or flash, technicians MUST put on all necessary Personal Protective Equipment (PPE) in accordance with NFPA70E for arc/flash protection PRIOR to servicing the unit.
Failure to follow recommendations could result in death or serious injury.Introduction
This manual describes the installation procedures required to retrofit TR1 Variable Frequency Drives (VFD).
Trademarks
Trane, the Trane logo, IntelliPak, Statitrac, and Voyager are trademarks of Trane in the United States and other countries. All trademarks referenced in this document are the trademarks of their respective owners.
© 2009 Trane All rights reserved PART-SVN121A-EN
Table of Contents
General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
About This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Tools Required . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Removing the Existing VFD and Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Installation of TR200 VFD and Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
VFD and Back Panel Assembly for TR200 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Miscellaneous . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
TR200 VFD Programming Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
VFD Programming Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
VFD Removal from Back Panel Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Power Supply Wiring Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Control Wiring Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
TR1 Keypad Assembly Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
TR200 Drive Installation instruction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Power Supply Wiring to TR200 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Control Wiring to TR200 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Keypad and Cable Adapter Assembly Installation for TR200 . . . . . . . . . 16
Wiring Diagram Matrix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
PART-SVN121A-EN 3
General Information
About This Manual
The step-by-step instructions outlined in this manual describe the procedures required to successfully retrofit a TR1 on 20 ton to 150 ton IntelliPak™ I and II rooftop air conditioning and 27½ to 50 ton Voyager™ III rooftop air conditioning units to a Trane TR200 VFD drive. For help selecting the proper parts for this work, refer to general service bulletin PART-SVB24A-EN or the most current version of that same literature.
The installation instructions in this manual are divided into three general topic areas:
Removal of existing TR1 VFD and components.
Installation of replacement TR200 VFD and components.
TR200 programming of parameters.
Follow start-up and trouble shooting procedures outlined in the service manuals of the unit and/ or the literature that is included with this TR200 control.
Tools Required
Very few tools are required to perform this installation. A service technician with a well-stocked tool chest should have the right tools to perform the job; However, a large-frame VFD will require a crimping tool for ring lugs and a drill with a #21 (4mm) drill bit sized to allow a #10-32 screw to thread into sheet metal.
4 PART-SVN121A-EN
Removing the Existing VFD and Components
SUPPLY FAN VFDSUPPLY FAN VFD
VARIABLE FREQUENCY DRIVEVARIABLE FREQUENCY DRIVE ENCLOSUREENCLOSURE
EXHAUSTEXHAUST
FANFAN VFDVFD
RETURN & EXHAUST SECTIONRETURN & EXHAUST SECTION
FILTER
SECTION
EVAP COIL
SUPPLY FAN SECTIONSUPPLY FAN SECTION
CONDENSER FANSCONDENSER FANS
COMPRESSOR SECTIONCOMPRESSOR SECTION
HEAT SECTIONHEAT SECTION
HTG ACCESS
PANEL
HEAT SECTION
ELEC CONTROL
ELEC CONTROL
PANELPANEL
SUPPLY FAN SECTION
EVAP COIL
EVAP COIL
FILTER
SECTION
O/A DAMPERSR/A DAMPERS
RETURN & EXHAUST
EXHAUSTEXHAUST
FAN
FAN
VFDVFD
VARIABLE FREQUENCY DRIVEVARIABLE FREQUENCY DRIVE ENCLOSUREENCLOSURE
SUPPLY FAN VFDSUPPLY FAN VFD
CONDENSER FANS
COMPRESSOR SECTION
The section that follows will give the procedure to remove a TR1 VFD from its panel assembly and remove the remote keypad in the IntelliPak I, IntelliPak II, and Voyager III main control panels.
Programming parameters are supplied with the VFD and a minimum of five must be set based on unit specifications, see Table 4, p. 17.
VFD Removal from Back Panel Assembly
Locate the existing TR1 VFD unit enclosure near the return and exhaust section as shown in
Figure 1 and Figure 2, p. 5 for IntelliPak I units, adjacent to the supply/exhaust sections of IntelliPak
II Figure 3, p. 6 and opposite supply fans on the Voyager III units as shown in Figure 4, p. 6.
Identify the correct VFD for replacement. The IntelliPak I and II rooftops can have both supply and exhaust/return VFDs. The IntelliPak I supply VFD is located on the back panel of the unit enclosure and the exhaust/return VFD is located on the inner door of the unit enclosure which must be turned to the open position for the VFD to be removed. The IntelliPak II supply VFD is adjacent to the supply fan section, and the exhaust/return VFD is adjacent to the exhaust/return fan section. Voyager III units only have supply VFDs and are located by the supply fan on the opposite side of the unit from the control panel.
Figure 1. Typical IntelliPak I 20 to 75 ton configuration
Figure 2. Typical IntelliPak I 90 to 130 ton configuration
PART-SVN121A-EN 5
Removing the Existing VFD and Components
Return/
Exhaust
Fan
Fresh Air Dampers
Supply Fan
Condenser
Fans
Compressor
Section
Heating Section
Exhaust Damper
Hood
Evap Coil
Evap Coil
Controls
Variable
Frequency
Drive (VFD)
Filter Section
Reheat Coil Option
Fresh Air Dampers
Return Air Dampers
Variable
Frquency
Drive (VFD)
Variable
Frequency
Drive
Baysens set 2-Pc connection
tubings
Variable
Frequency
Drive
VFD ACCESS
Figure 3. Typical IntelliPak II 90 to 150 ton configuration
Figure 4. Typical Voyager III 27.5 to 50 ton configuration
6 PART-SVN121A-EN
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects and discharge all motor start/run capacitors before servicing. Follow proper lockout/tagout procedures to ensure the power cannot be inadvertently energized. For variable frequency drives or other energy storing components provided by Trane or others, refer to the appropriate manufacturer’s literature for allowable waiting periods for discharge of capacitors. Verify with an appropriate voltmeter that all capacitors have discharged. Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury.
Note: For additional information regarding the safe discharge of capacitors, see
PROD-SVB06A-EN or PROD-SVB06A-FR
Disconnect the following power supply and control wires from each VFD.
Power Supply Wiring Removal
The following instructions relate to either the IntelliPak I, II or Voyager III.
VFD with bypass
– Disconnect power supply wires 1A, 2A, 3A from VFD connection points 91, 92, 93 (L1, L2, L3
respectively) and wires 10A, 11A, 12A, 13A from VFD connection points 96, 97, 98, 95 (T1, T2, T3, GND respectively).
VFD without bypass
– Disconnect power supply wire 1A, 2A, 3A from VFD connection points 91, 92, 93 (L1, L2, L3
respectively) and wires T1, T2, T3, 13A from VFD connection points 96, 97, 98, 95 (T1, T2, T3, GND respectively).
Removing the Existing VFD and Components
PART-SVN121A-EN 7
Removing the Existing VFD and Components
Control Wiring Removal
Disconnect all control wires from the TR1 VFD itself and note the connection point numbers. The TR1 and TR200 have the same connection point numbers. See Tab l e 1, p. 8 for common control wires and their connection point numbers. See Tab l e 2 , p. 8 for VFD keypad cables listed according to product line and function.
Table 1. Listed are typical control wires to remove from the TR1 and reinstall on the TR200. This
applies to IntelliPak I, IntelliPak II, and Voyager III drives except as noted. Extra spaces are included in the table so that any other control wires may be recorded
Control Wire
18B 12
28A 27
30A 53
31A 55
32A 18
34A*** 05
Jumper wire*** 39 and 04
VFD keypad cable*
45A** 02*
46A** 01*
Notes
1. * See Table 2, p. 8 for cable names.
2. ** IntelliPak I 90-130 ton units only.
3. ***VFD with bypass only.
VFD Connection Point
Sub D Connector (front of VFD)
Table 2. Listed are VFD keypad cables according to product line and VFD function
Product/Function Keypad Cable
IntelliPak I/ Supply Fan CBL3U72-6
IntelliPak I/ Exh/Rtn Fan CBL3U74-6
IntelliPak I/ Supply Fan #1* CBL3U72-6
IntelliPakI/ Supply Fan #2* CBL3U73-6
IntelliPak II/ Supply Fan CBL5U16-6
IntelliPak II/ Exh/Rtn Fan CBL8U17-6
Voyager III/ Supply Fan CBLVFD-6
Note: * IntelliPak I 90-130 ton units only.
8 PART-SVN121A-EN
Loading...
+ 16 hidden pages