Trane Installation, Operation And Maintenance Manual
Specifications and Main Features
Frequently Asked Questions
User Manual
Packaged Rooftop
Air Conditioners
27½ to 50 Ton - 60 Hz
23 to 42 Ton (81-148 kW) - 50 Hz
Voya ger™ Commercial with
™
ReliaTel
Controls
RT-PRC007-ENNovember 2006
Introduction
Packaged Rooftop
Air Conditioners
Through the years, Trane has designed
and developed the most complete line of
Packaged Rooftop products available in
the market today. Trane was the first to
introduce the Micro—microelectronic unit
controls—and has continued to improve
and revolutionalize this design concept.
The ReliaTel control platform offers the
same great features and functionality as
the original Micro, with additional benefits
for greater application flexibility.
The Voyager Commercial line offers 27½
to 50 ton 60 Hz and 23 to 42 ton 50 Hz
models. Both 50 and 60 Hz models come
in a choice of five sizes to meet the
changing demands of the commercial
rooftop market.
Trane customers demand products that
provide exceptional reliability, meet
stringent performance requirements, and
are competitively priced. Trane delivers
with Voyager Commercial.
Voyager Commercial features cutting
edge technologies: reliable 3-D
compressors, Trane engineered ReliaTel
controls, computer-aided run testing, and
Integrated Comfort™ Systems. So,
whether you’re the contractor, the
engineer, or the owner you can be certain
Voyager Commercial Products are built to
meet your needs.
Fewer parts than an equal capacity
reciprocating compressor means
significant reliability and efficiency
benefits. The single orbiting scroll
eliminates the need for pistons,
connecting rods, wrist pins and valves.
Fewer parts lead to increased reliability.
Fewer moving parts, less rotating mass
and less internal friction means greater
efficiency than reciprocating
compressors.
The Trane 3-D Scroll provides important
reliability and efficiency benefits. The 3-D
Scroll allows the orbiting scrolls to touch
in all three dimensions, forming a
completely enclosed compression
chamber which leads to increased
efficiency. In addition, the orbiting scrolls
only touch with enough force to create a
seal; there is no wear between the scroll
plates. The fixed and orbiting scrolls are
made of high strength cast iron which
results in less thermal distortion, less
leakage, and higher efficiencies. The
most outstanding feature of the 3-D
Scroll compressor is that slugging will
not cause failure. In a reciprocating
compressor, however, the liquid or dirt
can cause serious damage.
Low Torque Variation
The 3-D Scroll compressor has a very
smooth compression cycle; torque
variations are only 30 percent of that
produced by a reciprocating compressor.
This means that the scroll compressor
imposes very little stress on the motor
resulting in greater reliability. Low torque
variation reduces noise and vibration.
Suction Gas Cooled Motor
Compressor motor efficiency and
reliability is further optimized with the
latest scroll design. Cool suction gas
keeps the motor cooler for longer life and
better efficiency.
Proven Design Through Testing and
Research
With over twenty years of development
and testing, Trane 3-D Scroll
compressors have undergone more than
400,000 hours of laboratory testing and
field operation. This work combined with
over 25 patents makes Trane the
worldwide leader in air conditioning
scroll compressor technology.
One of two matched scroll plates —
the distinguishing feature of the scroll
compressor.
Chart illustrates low torque variation of
3-D Scroll compressor vs
reciprocating compressor.
5RT-PRC007-EN
Features and
Benefits
Quality and Reliability
Easy to Install, Service and
Maintain
Because today’s owners are very costconscious when it comes to service and
maintenance, the Trane Voyager was
designed with direct input from service
contractors. This valuable information
helped to design a product that would get
the serviceman off the job quicker and
save the owner money. Voyager does
this by offering:
ReliaTel™ Controls (LCI-R)
ReliaTel controls provide unit control for
heating, cooling and ventilating utilizing
input from sensors that measure outdoor
and indoor temperature.
Quality and Reliability are enhanced
through ReliaTel control and logic:
• prevents the unit from short cycling,
considerably improving
compressor life.
• ensures that the compressor will run
for a specific amount of time which
allows oil to return for better
lubrication, enhancing the reliability
of the commercial compressor.
Voyager with ReliaTel reduces the
number of components required to
operate the unit, thereby reducing
possibilities for component failure.
ReliaTel Makes Installing and
Servicing Easy
ReliaTel eliminates the need for field
installed anti-shortcycle timer and time
delay relays. ReliaTel controls provide
these functions as an integral part of the
unit. The contractor no longer has to
purchase these controls as options and
pay to install them.
The wiring of the low voltage connections
to the unit and the zone sensors is as
easy as 1-1, 2-2, and 3-3. This simplified
system makes it easier for the installer to
wire.
ReliaTel Makes Testing Easy
ReliaTel requires no special tools to run
the Voyager unit through its paces.
Simply place a jumper between Test 1
and Test 2 terminals on the Low Voltage
Terminal Board and the unit will walk
through its operational steps
automatically.
— The unit automatically returns
control to the zone sensor after
stepping through the test mode a
single time, even if the jumper is
left on the unit.
As long as the unit has power and the
“system on” LED is lit, ReliaTel is
operational. The light indicates that the
controls are functioning properly.
ReliaTel features expanded diagnostic
capabilities when utilized with Trane
Integrated Comfort™ Systems.
Some Zone Sensor options have central
control panel lights which indicate the
mode the unit is in and possible
diagnostic information (dirty filters for
example).
Other ReliaTel Benefits
The ReliaTel built-in anti-shortcycle timer,
time delay relay and minimum “on” time
control functions are factory tested to
assure proper operation.
ReliaTel softens electrical “spikes” by
staging on fans, compressors and
heaters.
Intelligent Fallback is a benefit to the
building occupant. If a component goes
astray, the unit will continue to operate at
predetermined temperature setpoint.
Intelligent Anticipation is a standard
ReliaTel feature. It functions continuously
as ReliaTel and zone sensor(s) work
together in harmony to provide much
tighter comfort control than conventional
electro-mechanical thermostats.
RT-PRC007-EN6
Features and
Benefits
Trane Communication Interface (TCI)
The TCI is available factory or field
installed. When applied with ReliaTel, this
module easily interfaces with the Trane
Integrated Comfort™ System.
Interoperability with LonTalk® (LCI-R)
The LonTalk Communication (LCI-R) for
Voyager Commercial offers a building
automation control system with
outstanding interoperability benefits.
LonTalk, which is an industry standard, is
an open, secure and reliable network
communication protocol for controls,
created by Echelon Corporation and
adopted by the LonMark Interoperability
Association. It has been adopted by
several standards, such as: EIA-709.1, the
Electronic Industries Alliance (EIA) Control
Network Protocol Specification and ANSI/
ASHRAE 135, part of the American
Society of Heating, Refrigeration, and AirConditioning Engineer’s BACnet control
standard for buildings.
Interoperability allows application or
project engineers to specifiy the best
products of a given type, rather than one
individual supplier’s entire system. It
reduces product training and installation
costs by standardizing communications
across products.
Interoperable systems allow building
managers to monitor and control
Voyager Commercial equipment with a
Trane Tracer Summit™ or a 3rd party
building automation system.
It enables integration with many different
building controls such as access/intrusion
monitoring, lighting, fire and smoke
devices, energy management, and a
wide variety of sensors for temperature,
pressure, humidity and occupancy CO
For additional information on LonMark,
visit www.lonmark.org or Echelon,
www.echelon.com.
Variable Frequency Drives (VFD)
Variable Frequency Drives are factory
installed and tested to provide supply fan
motor speed modulation. VFD’s, as
compared to inlet guide vanes or
discharge dampers, are quieter, more
efficient, and are eligible for utility
rebates. The VFD’s are available with or
.
2
without a bypass option. Bypass control
will simply provide full nominal airflow in
the event of drive failure.
VariTrac™ changeover-bypass VAV
For light commercial applications, Trane
offers constant volume (CV) Voyager
Commercial models with a changeoverbypass VAV system.
For the most advanced comfort
management systems, count on Trane.
Delivered VAV
Trane provides true pressure
independent variable air volume with
Voyager Commercial delivered VAV. The
system is auto-configured to reduce
programming and set-up time on the job.
Generally available only on sophisticated
larger models, this Voyager Commercial
system can economically handle comfort
requirements for any zone in the facility.
The system consists of:
• Voyager™ Commercial VAV packaged
rooftops
• Up to 32 VariTrane™ VAV boxes with
DDC (direct digital controls)
• VariTrac™ Central Control Panel (CCP)
with Operator Display (OD)
The VariTrac Central Control Panel acts as
a communications hub by coordinating
the actions of the VAV rooftop and the
VAV boxes. Single duct or fan powered
VAV boxes are available, along with an
option for factory-installed local heat. For
more details, see VAV-SLM003-EN.
Downflow and Horizontal Economizers
The economizers come with three control
options dry bulb, enthalpy and differential
enthalpy. (Photo below shows the three
fresh air hoods on the Horizontal
Discharge Configuration).
7RT-PRC007-EN
Features and
Benefits
Forced Combustion Blower
Negative Pressure Gas Valve
Hot Surface Ignitor
Drum and Tube Heat Exchanger
Outstanding Standard and Optional Components
Drum and Tube Heat Exchanger
The drum and tube heat exchanger is
designed for increased efficiency and
reliability and utilizes the same
technology that has been incorporated
into large commercial roof top units for
over 20 years.
The heat exchanger is manufactured
using optional stainless, or standard
aluminized, steel with stainless steel
components for maximum durability. The
requirement for cycle testing of heat
exchangers is 10,000 cycles by ANSI
Z21.47. This is the standard required by
both UL and AGA for cycle test
requirements. Trane requires the design
to be tested to 2½ times this current
standard. The drum and tube design has
been tested and passed over 150,000
cycles which is over 15 times the current
ANSI cycling requirements.
The negative pressure gas valve will not
allow gas flow unless the combustion
blower is operating. This is one of the
unique safety features of Voyager
Commercial.
The forced combustion blower supplies
pre-mixed fuel through a single stainless
steel burner screen into a sealed drum
where ignition takes place. It is more
reliable to operate and maintain than a
multiple burner system.
The hot surface ignitor is a gas ignition
device which doubles as a safety device
utilizing a continuous test to prove the
flame. The design is cycle tested at the
factory for quality and reliability.
All the gas/electric rooftops exceed all
California seasonal efficiency
requirements. They also perform better
than required to meet the California NOx
emission requirements.
High Efficiency Condenser Coil
Increased capacity and energy efficiency
with optional high capacity third row
condenser coil with or without black
epoxy pre-coating.
Excellent Part-Load Efficiency
The unique design of the scroll
compressor allows it to be applied in a
passive parallel manifolded piping
scheme, something that a “recip” just
doesn’t do very well.
When the unit begins stage back at part
load it still has the full area and circuitry of
its evaporator and condenser coils
available to transfer heat. In simple terms
this means superior part-load efficiencies
(IPLV) and lower unit operating costs.
Rigorous Testing
All of Voyager’s designs were rigorously
rain tested at the factory to ensure water
integrity.
Actual shipping tests are performed to
determine packaging requirements. Units
are test shipped around the country.
Factory shake and drop tested as part of
the package design process to help
assure that the unit will arrive at your job
site in top condition.
Rigging tests include lifting a unit into the
air and letting it drop one foot, assuring
that the lifting lugs and rails hold up under
stress.
We perform a 100% coil leak test at the
factory. The evaporator and condenser
coils are leak tested at 200 psig and
pressure tested to 450 psig.
All parts are inspected at the point of final
assembly. Sub-standard parts are
identified and rejected immediately.
Every unit receives a 100% unit run test
before leaving the production line to
make sure it lives up to rigorous Trane
requirements.
RT-PRC007-EN8
Features and
Benefits
Power Exhaust Option
Provides exhaust of the return air when
using an economizer to maintain proper
building pressurization. Great for relieving
most building overpressurization
problems.
Easy to Install
Contractors look for lower installation
(jobsite) costs. Voyager’s conversionless
units provide many time and money
saving features.
Conversionless Units
The dedicated design units (either
downflow or horizontal) require no panel
removal or alteration time to convert in
the field — a major cost savings during
installation.
Improved Airflow
U-shaped airflow allows for improved
static capabilities. The need for high static
motor conversion is minimized and saves
the time normally spent changing to high
static oversized motors.
Single Point Power
A single electrical connection powers the
unit.
Trane factory built roof curbs
Available for all units.
Added Efficiency
Low Ambient Cooling
All Voyager Commercial units have
cooling capabilities down to 0 F as
standard.
FC Fans with Inlet Guide Vanes
Trane’s forward-curved fans with inlet
guide vanes pre-rotate the air in the
direction of the fan wheel, decreasing
static pressure and horsepower,
essentially unloading the fan wheel. The
unloading characteristics of a Trane FC
fan with inlet guide vanes result in
superior part load performance.
Horizontal Discharge with
Power Exhaust Option
One of Our Finest Assets
Trane Commercial Sales Engineers are a
support group that can assist you with:
— Product
— Application
— Service
— Training
— Special Applications
— Specifications
— Computer Programs and more
9RT-PRC007-EN
Application
Exhaust Air Options
When is it necessary to provide building
exhaust?
Whenever an outdoor air economizer is
used, a building generally requires an
exhaust system. The purpose of the
exhaust system is to exhaust the proper
amount of air to prevent over or underpressurization of the building.
A building may have all or part of its
exhaust system in the rooftop unit. Often,
a building provides exhaust external to
the air conditioning equipment. This
external exhaust must be considered
when selecting the rooftop exhaust
system.
Voyager Commercial rooftop units offer
two types of exhaust systems:
1
Power exhaust fan.
2
Barometric relief dampers.
Application Recommendations
Power Exhaust Fan
The exhaust fan option is a dual,
nonmodulating exhaust fan with
approximately half the air-moving
capabilities of the supply fan system. It is
Trane’s experience that a non-modulating
exhaust fan selected for 40 to 50 percent
of nominal supply cfm can be applied
successfully.
The power exhaust fan generally should
not be selected for more than 40 to 50
percent of design supply airflow. Since it
is an on/off nonmodulating fan, it does
not vary exhaust cfm with the amount of
outside air entering the building.
Therefore, if selected for more than 40 to
50 percent of supply airflow, the building
may become underpressurized when
economizer operation is allowing lesser
Considerations
amounts of outdoor air into the building. If,
however, building pressure is not of a
critical nature, the non-modulating
exhaust fan may be sized for more than
50 percent of design supply airflow.
Consult Table PD-16 for specific exhaust
fan capabilities with Voyager Commercial
units.
Barometric Relief Dampers
Barometric relief dampers consist of
gravity dampers which open with
increased building pressure. As the
building pressure increases, the pressure
in the unit return section also increases,
opening the dampers and relieving air.
Barometric relief may be used to provide
relief for single story buildings with no
return ductwork and exhaust
requirements less than 25 percent.
Altitude Corrections
The rooftop performance tables and
curves of this catalog are based on
standard air (.075 lbs/ft). If the rooftop
airflow requirements are at other than
standard conditions (sea level), an air
density correction is needed to project
accurate unit performance.
Figure PD-1 shows the air density ratio at
various temperatures and elevations.
Trane rooftops are designed to operate
between 40 and 90 degrees Fahrenheit
leaving air temperature.
The procedure to use when selecting a
supply or exhaust fan on a rooftop for
elevations and temperatures other than
standard is as follows:
1
First, determine the air density ratio
using Figure PD-1.
2
Divide the static pressure at the
nonstandard condition by the air density
ratio to obtain the corrected static
pressure.
60 Hz
3
Use the actual cfm and the corrected
static pressure to determine the fan rpm
and bhp from the rooftop performance
tables or curves.
4
The fan rpm is correct as selected.
5
Bhp must be multiplied by the air density
ratio to obtain the actual operating bhp.
In order to better illustrate this procedure,
the following example is used:
Consider a 30 ton rooftop unit that is to
deliver 11,000 actual cfm at 1.50 inches
total static pressure (tsp), 55 F leaving air
temperature, at an elevation of 5,000 ft.
1
From Figure PD-1, the air density ratio is
0.86.
2
Tsp=1.50 inches/0.86=1.74 inches tsp.
3
From the performance tables: a 30 ton
rooftop will deliver 11,000 cfm at 1.74
inches tsp at 668 rpm and 6.93 bhp.
4
The rpm is correct as selected — 668
rpm.
5
Bhp = 6.93 x 0.86 = 5.96 .
Compressor MBh, SHR, and kw should
be calculated at standard and then
converted to actual using the correction
factors in Table PD-2. Apply these factors
to the capacities selected at standard cfm
so as to correct for the reduced mass
flow rate across the condenser.
Heat selections other than gas heat will
not be affected by altitude. Nominal gas
capacity (output) should be multiplied by
the factors given in Table PD-3 before
calculating the heating supply air
temperature.
RT-PRC007-EN10
Application
Exhaust Air Options
When is it necessary to provide building
exhaust?
Whenever an outdoor air economizer is
used, a building generally requires an
exhaust system. The purpose of the
exhaust system is to exhaust the proper
amount of air to prevent over or underpressurization of the building.
A building may have all or part of its
exhaust system in the rooftop unit. Often,
a building provides exhaust external to
the air conditioning equipment. This
external exhaust must be considered
when selecting the rooftop exhaust
system.
™
Voyager
two types of exhaust systems:
1
Power exhaust fan
2
Barometric relief dampers
Application Recommendations
Power Exhaust Fan
The exhaust fan option is a dual, nonmodulating exhaust fan with
approximately half the air-moving
capabilities of the supply fan system. The
experience of Trane is that a nonmodulating exhaust fan selected for 40 to
50 percent of nominal supply cfm can be
applied successfully.
The power exhaust fan generally should
not be selected for more than 40 to 50
percent of design supply airflow. Since it
is an on/off non-modulating fan, it does
not vary exhaust cfm with the amount of
outside air entering the building.
Therefore, if selected for more than
40 to 50 percent of supply airflow, the
building may become under-pressurized
when economizer operation is allowing
lesser amounts of outdoor air into the
building. If, however, building pressure is
Commercial rooftop units offer
Considerations
not of a critical nature, the non-modulating
exhaust fan may be sized for more than
50 percent of design supply airflow.
Barometric Relief Dampers
Barometric relief dampers consist of
gravity dampers which open with
increased building pressure. As the
building pressure increases, the pressure
in the unit return section also increases,
opening the dampers and relieving air.
Barometric relief may be used to provide
relief for single story buildings with no
return ductwork and exhaust
requirements less than
25 percent.
Altitude Corrections
The rooftop performance tables and
curves of this catalog are based on
standard air (.075 lb/ft) (.034 kg/cm). If the
rooftop airflow requirements are at other
than standard conditions (sea level), an air
density correction is needed to project
accurate unit performance.
Figure PD-1 shows the air density ratio at
various temperatures and elevations.
Trane rooftops are designed to operate
between 40 and 90°F (4.4 and 32.2°C)
leaving air temperature.
The procedure to use when selecting a
supply or exhaust fan on a rooftop for
elevations and temperatures other than
standard is as follows:
1
First, determine the air density ratio using
Figure PD-1.
2
Divide the static pressure at the
nonstandard condition by the air density
ratio to obtain the corrected static
pressure.
3
Use the actual cfm and the corrected
static pressure to determine the fan rpm
and bhp from the rooftop performance
tables or curves.
50 Hz
4
The fan rpm is correct as selected.
5
Bhp must be multiplied by the air density
ratio to obtain the actual operating bhp.
In order to better illustrate this procedure,
the following example is used:
Consider a 29-ton (105 kW) rooftop unit
that is to deliver 9,160 actual cfm (4323 L/
s) at 1.50 inches total static pressure (tsp)
(38 mm, 373 Pa), 55°F (12.8°C) leaving air
temperature, at an elevation of 5,000 ft
(1524 m).
From the performance tables: a 29-ton
(105 kW) rooftop will deliver 9,160 cfm at
1.74 inches tsp 4323 L/s at 434 Pa) at 651
rpm and 5.51 bhp (4.11 kW).
4
The rpm is correct as selected –
651 rpm.
5
Bhp = 5.51 x 0.86 = 4.74 bhp actual.
kW = 4.11 x 0.86 = 3.5 kW
Compressor MBh, SHR, and kW should
be calculated at standard and then
converted to actual using the correction
factors in Table PD-2. Apply these factors
to the capacities selected at standard cfm
so as to correct for the reduced mass flow
rate across the condenser.
Heat selections other than gas heat will
not be affected by altitude. Nominal gas
capacity (output) should be multiplied by
the factors given in Table PD-3 before
calculating the heating supply air
temperature.
11RT-PRC007-EN
Application
Considerations50/60 Hz
Acoustical Considerations
Proper placement of rooftops is critical to
reducing transmitted sound levels to the
building. The ideal time to make
provisions to reduce sound
transmissions is during the design
phase. And the most economical means
of avoiding an acoustical problem is to
place the rooftop(s) away from
acoustically critical areas. If possible,
rooftops should not be located directly
above areas such as: offices, conference
rooms, executive office areas and
classrooms. Instead, ideal locations
might be over corridors, utility rooms,
toilets or other areas where higher
sound levels directly below the unit(s)
are acceptable.
Several basic guidelines for unit
placement should be followed to
minimize sound transmission through
the building structure:
1
Never cantilever the compressor end of
the unit. A structural cross member must
support this end of the unit.
2
Locate the unit center of gravity which is
close to, or over, a column or main
support beam.
3
If the roof structure is very light, roof
joists must be replaced by a structural
shape in the critical areas described
above.
4
If several units are to be placed on one
span, they should be staggered to
reduce deflection over that span.
It is impossible to totally quantify the
effect of building structure on sound
transmission, since this depends on the
response of the roof and building
members to the sound and vibration of
the unit components. However, the
guidelines listed above are experienceproven guidelines which will help reduce
sound transmissions.
Clearance Requirements
The recommended clearances identified
with unit dimensions should be
maintained to assure adequate
serviceability, maximum capacity and
peak operating efficiency. A reduction in
unit clearance could result in condenser
coil starvation or warm condenser air
recirculation. If the clearances shown are
not possible on a particular job, consider
the following:
Do the clearances available allow for
major service work such as changing
compressors or coils?
Do the clearances available allow for
proper outside air intake, exhaust air
removal and condenser airflow?
If screening around the unit is being
used, is there a possibility of air
recirculation from the exhaust to the
outside air intake or from condenser
exhaust to condenser intake?
Actual clearances which appear
inadequate should be reviewed with a
local Trane sales engineer.
When two or more units are to be placed
side by side, the distance between the
units should be increased to 150 percent
of the recommended single unit
clearance. The units should also be
staggered for two reasons:
1
To reduce span deflection if more than
one unit is placed on a single span.
Reducing deflection discourages sound
transmission.
2
To assure proper diffusion of exhaust air
before contact with the outside air intake
of adjacent unit.
Duct Design
It is important to note that the rated
capacities of the rooftop can be met only
if the rooftop is properly installed in the
field. A well designed duct system is
essential in meeting these capacities.
The satisfactory distribution of air
throughout the system requires that
there be an unrestricted and uniform
airflow from the rooftop discharge duct.
This discharge section should be straight
for at least several duct diameters to
allow the conversion of fan energy from
velocity pressure to static pressure.
However, when job conditions dictate
elbows be installed near the rooftop
outlet, the loss of capacity and static
pressure may be reduced through the
use of guide vanes and proper direction
of the bend in the elbow. The high
velocity side of the rooftop outlet should
be directed at the outside radius of the
elbow rather than the inside.
RT-PRC007-EN12
Selection
Selection of Trane commercial air
conditioners is divided into five basic
areas:
1
Cooling capacity
2
Heating capacity
3
Air delivery
4
Unit electrical requirements
5
Unit designation
Factors Used In Unit Cooling Selection:
1
Summer design conditions — 95 DB/
76 WB, 95 F entering air to condenser.
2
Summer room design conditions —
76 DB/66 WB.
3
Total peak cooling load — 321 MBh
(27.75 tons).
4
Total peak supply cfm — 12,000 cfm.
5
External static pressure — 1.0 inches.
6
Return air temperatures — 80 DB/66 WB.
7
Return air cfm — 4250 cfm.
8
Outside air ventilation cfm and load —
1200 cfm and 18.23 MBh (1.52 tons).
9
Unit accessories include:
a
Aluminized heat exchanger — high heat
module.
Procedure
b
2” Hi-efficiency throwaway filters.
c
Exhaust fan.
d
Economizer cycle.
Step 1 — A summation of the peak
cooling load and the outside air
ventilation load shows: 27.75 tons + 1.52
tons = 29.27 required unit capacity. From
Table 18-2, 30-ton unit capacity at 80 DB/
67 WB, 95 F entering the condenser and
12,000 total peak supply cfm, is 30.0 tons.
Thus, a nominal 30-ton unit is selected.
Step 2 — Having selected a nominal 30ton unit, the supply fan and exhaust fan
motor bhp must be determined.
Supply Air Fan:
Determine unit static pressure at design
supply cfm:
External static pressure1.20 inches
Heat exchanger.14 inches
(Table PD-14)
High efficiency filter 2”.09 inches
(Table PD-14)
Economizer.076 inches
(Table PD-14)
Unit total static pressure1.50 inches
Using total cfm of 12,000 and total
static pressure of 1.50 inches, enter Table
PD-12. Table PD-12 shows 7.27 bhp with
652 rpm.
Step 3 — Determine evaporator coil
entering air conditions. Mixed air dry
bulb temperature determination.
Using the minimum percent of OA (1,200
cfm ÷ 12,000 cfm = 10 percent),
determine the mixture dry bulb to the
evaporator. RADB + %OA (OADB RADB) = 80 + (0.10) (95 - 80) = 80 + 1.5 =
81.5F
Approximate wet bulb mixture
temperature:
RAWB + OA (OAWB - RAWB) = 66 +
(0.10) (76-66) = 68 + 1 = 67 F.
60 Hz
A psychrometric chart can be used to
more accurately determine the mixture
temperature to the evaporator coil.
Step 4 — Determine total required unit
cooling capacity:
Required capacity = total peak load +
O.A. load + supply air fan motor heat.
From Figure SP-1, the supply air fan
motor heat for 7.27 bhp = 20.6 MBh.
Capacity = 321 + 18.23 + 20.6 =
359.8 MBh (30 tons)
Step 5 — Determine unit capacity:
From Table PD-4 unit capacity at 81.5 DB.
67 WB entering the evaporator, 12000
supply air cfm, 95 F entering the
condenser is 361 MBh (30.1 tons) 279
sensible MBh.
Step 6 — Determine leaving air
temperature:
Unit sensible heat capacity, corrected for
supply air fan motor heat 279 - 20.6 =
258.4 MBh.
Supply air dry bulb temperature
difference = 258.4 MBh ÷ (1.085 x 12,000
cfm) = 19.8 F.
Supply air dry bulb: 81.5 - 19.8 = 61.7.
Unit enthalpy difference = 361 ÷ (4.5 x
12,000) = 6.7
Btu/lb leaving enthalpy = h (ent WB) =
31.62
Leaving enthalpy = 31.62 Btu/lb -
6.7 Btu/lb = 24.9 Btu/lb.
From Table PD-1, the leaving air wet bulb
temperature corresponding to an
enthalpy of 24.9 Btu/lb = 57.5.
Leaving air temperatures =
61.7 DB/57.5 WB
13RT-PRC007-EN
Selection
Heating capacity selection:
1
Winter outdoor design conditions—5 F.
2
Total return air temperature — 72 F.
3
Winter outside air minimum ventilation
load and cfm — 1,200 cfm and 87.2 MBh.
4
Peak heating load 225 MBh.
Utilizing unit selection in the cooling
capacity procedure.
Mixed air temperature = RADB + %O.A.
(OADB - RADB) = 72
+ (0.10) (0-72) = 64.8 F.
Supply air fan motor heat temperature
rise = 20,600 BTU ÷ (1.085 x 12,000) cfm
= 1.6 F.
Mixed air temperature entering heat
module = 64.8 + 1.6 = 66.4 F.
Total winter heating load = peak heating
+ ventilation load - total fan motor heat =
225 + 87.2 - 20.6 = 291.6 MBh.
Electric Heating System
Unit operating on 480/60/3 power supply.
From Table PD-9, kw may be selected for
a nominal 30-ton unit operating on 480volt power. The high heat module — 90
KW or 307 MBh will satisfy the winter
heating load of 291.6 MBh.
Procedure
Table PD-9 also shows an air
temperature rise of 23.6 F for 12,000 cfm
through the 90 kw heat module.
Unit supply temperature at design
heating conditions = mixed air
temperature + air temperature rise = 66.4
+ 23.6 = 90 F.
Natural Gas Heating System
Assume natural gas supply — 1000 Btu/
3
. From Table PD-11, select the high
ft
heat module (486 MBh output) to satisfy
291.6 at unit cfm.
Table PD-11 also shows air temperature
rise of 37.3 F for 12,000 cfm through
heating module.
Unit supply temperature design heating
conditions = mixed air temperature + air
temperature rise = 66.4 + 37.3 = 103.7 F.
Air Delivery Procedure
Supply air fan bhp and rpm selection.
Unit supply air fan performance shown
in Table PD-12 includes pressure drops
for dampers and casing losses. Static
pressure drops of accessory
components such as heating systems,
and filters if used, must be added to
external unit static pressure for total
static pressure determination.
Figure SP-1 — Fan Motor Heat
120
110
100
90
80
70
60
50
40
FAN MOTOR HEAT - MBH
30
20
10
0
0510152025303540
MOTOR BRAKE HORSE POWER
60 Hz
The supply air fan motor selected in the
previous cooling capacity determination
example was 7.27 bhp with 652 rpm.
Thus, the supply fan motor selected is
7.5 hp.
To select the drive, enter Table PD-15 for a
30-ton unit. Select the appropriate drive
for the applicable rpm range. Drive
selection letter C with a range of 650
rpm, is required for 652 rpm. Where
altitude is significantly above sea level,
use Table PD-2 and PD-3, and Figure PD1 for applicable correction factors.
Unit Electrical Requirements
Selection procedures for electrical
requirements for wire sizing amps,
maximum fuse sizing and dual element
fuses are given in the electrical service
selection of this catalog.
Unit Designation
After determining specific unit
characteristics utilizing the selection
procedure and additional job
information, the complete unit model
number can be developed using the
model number nomenclature page.
B
STANDARD MOTOR
C
HIGH EFFICIENCY MOTOR
RT-PRC007-EN14
Selection
Procedure50 Hz
Selection of Trane commercial air
conditioners is divided into five basic
areas:
1
Cooling capacity
2
Heating capacity
3
Air delivery
4
Unit electrical requirements
5
Unit designation
Factors Used In Unit Cooling Selection:
1
Summer design conditions – 95 DB/
76 WB (35/24.4°C), 95°F (35°C) entering
air to condenser.
Return air temperatures – 80 DB/66°F WB
(26.7/18.9°C).
7
Return air cfm – 3540 cfm (1671 L/s).
8
Outside air ventilation cfm and load –
1000 cfm and 15.19 MBh (1.27 tons or
4.45 kW) 472 L/s.
9
Unit accessories include:
a
Aluminized heat exchanger – high heat
module.
b
2” Hi-efficiency throwaway filters.
c
Exhaust fan.
d
Economizer cycle.
Step 1 – A summation of the peak cooling
load and the outside air ventilation load
shows: 22.5 tons + 1.27 tons = 23.77 (79
kW + 4.45 kW = 83.45) required unit
capacity. From Table PD-18, 25 ton (89
kW) unit capacity at 80 DB/67 WB (27/
19°C), 95°F entering the condenser and
10,000 total peak supply cfm (4720 L/s), is
YC/TC/TE*305.
Step 2 – Having selected the correct unit,
the supply fan and exhaust fan motor
bhp must be determined.
Supply Air Fan:
Determine unit static pressure at design
supply cfm:
External static pressure1.24 inches
Using total cfm of 10,000 (4720 L/s) and
total static pressure of 1.50 inches
(38 mm), enter Table PD-25. Table PD-25
shows 5.35 bhp (4 kW) with 616 rpm.
Step 3 – Determine evaporator coil
entering air conditions. Mixed air dry
bulb temperature determination.
Using the minimum percent of OA (1,000
cfm ÷ 10,000 cfm = 10 percent),
determine the mixture dry bulb to the
evaporator. RADB + % OA
(OADB - RADB) = 80 + (0.10) (95 - 80) = 80
+ 1.5 = 81.5°F [26.7 + 1.5 = 28°C).
A psychrometric chart can be used to
more accurately determine the mixture
temperature to the evaporator coil.
Step 4 – Determine total required unit
cooling capacity:
Required capacity = total peak load +
O.A. load + supply air fan motor heat.
From Chart SP-1, the supply air fan
motor heat for 5.35 bhp = 15 MBh.
Capacity = 270 + 15 + 15 =
300 MBh (89 kW)
Step 5 – Determine unit capacity:
From Table PD-18 unit capacity at 81.5
DB/67 WB entering the evaporator,
10,000 supply air cfm, 95°F (35°C)
entering the condenser about 304 MBh
(89 kW) with 235 MBh (68.8 kW)
sensible.
Step 6 – Determine leaving air
temperature:
Unit sensible heat capacity, corrected for
supply air fan motor heat 235 - 15 = 220
MBh (64.4 kW).
Supply air dry bulb temperature
difference = 220 MBh ÷ (1.085 x
10,000 cfm) = 20.2°F (-6.6°C)
Supply air dry bulb: 81.5-20.2 = 61.3
(16.3°C)
Unit enthalpy difference = 305.6 ÷
(4.5 x 10,000) = 6.76
Btu/lb leaving enthalpy = h (ent WB)
= 31.62
Leaving enthalpy = 31.62 Btu/lb -
6.76 Btu/lb = 24.86 Btu/lb.
From Table PD-1, the leaving air wet bulb
temperature corresponding to an
enthalpy of 24.8 Btu/lb = 57.5.
Leaving air temperatures = 61.3 DB/57.5
WB (16.3/14.2°C).
15RT-PRC007-EN
Selection
Procedure50 Hz
1
Winter outdoor design conditions –
0°F (17.7°C).
2
Total return air temperature – 72°F
(22.2°C).
3
Winter outside air minimum ventilation
load and cfm – 1,000 cfm and
87.2 MBh.
4
Peak heating load 150 MBh.
Utilizing unit selection in the cooling
capacity procedure.
Mixed air temperature = RADB +
% O.A. (OADB - RADB) = 72
+ (0.10) (0-72) = 64.8°F.
Supply air fan motor heat temperature
rise = 20,600 Btu ÷ (1.085 x 10,000) cfm
= 1.9°F.
Mixed air temperature entering heat
module = 64.8 + 1.9 = 66.7°F.
Total winter heating load = peak heating
+ ventilation load - total fan motor heat =
150 + 87.2 - 15 =
222.2 MBh.
Electric Heating System
Unit operating on 415 power supply.
From Table PD-22, kW may be selected
for TC*305 unit to satisfy the winter
heating load. The 67 kW module will do
the job.
Table PD-22 also shows an air
temperature rise of 21.2°F for 10,000 cfm
through the 67 kW heat module.
Unit supply temperature at design
heating conditions = mixed air
temperature + air temperature rise = 66.7
+ 21.2 = 87.9°F.
Natural Gas Heating System
Assume natural gas supply – 1000
3
. From Table PD-24, select the low
Btu/ft
heat module (243 MBh output) to satisfy
222 at unit cfm.
Table PD-25 also shows air temperature
rise of 37.3°F for 10,000 cfm through
heating module.
Unit supply temperature design heating
conditions = mixed air temperature + air
temperature rise = 66.7 + 37.3 = 104.0°F.
Air Delivery Procedure
Supply air fan bhp and rpm selection.
Unit supply air fan performance shown
in Table PD-25 includes pressure drops for
dampers and casing losses. Static
pressure drops of accessory
components such as heating systems,
and filters if used, must be added to
external unit static pressure for total
static pressure determination.
The supply air fan motor selected in the
previous cooling capacity determination
example was 5.35 bhp with 616 rpm.
Thus, the supply fan motor selected is
7.5 hp.
To select the drive, enter Table PD-28 for a
305 unit. Select the appropriate drive for
the applicable rpm range. Drive selection
letter E with a range of 625 rpm, is
required for 616 rpm. Where altitude is
significantly above sea level, use Table
PD-2 and PD-3, and Figure
PD-1 for applicable correction factors.
Unit Electrical Requirements
Selection procedures for electrical
requirements for wire sizing amps,
maximum fuse sizing and dual element
fuses are given in the electrical service
selection of this catalog.
Unit Designation
After determining specific unit
characteristics utilizing the selection
procedure and additional job
information, the complete unit model
number can be developed using the
model number nomenclature page.
E = 208/60/3
F = 230/60/3
4 = 460/60/3
5 = 575/60/3
Digit 9 — Heating Capacity (See Note 4)
0 = No Heat (TC only)
L = Low Heat (YC only)
H = High Heat (YC only)
J = Low Heat-Stainless Steel Gas Heat
Exchangers (YC only)
K = High Heat-Stainless Steel Gas Heat
Exchanger (YC only)
Note: When second digit is “E” for Electric
Heat, the following values apply in the ninth
digit.
A = 36 KW
B = 54 KW
C = 72 KW
D = 90 KW
E = 108 KW
Digit 10 Design Sequence
A = First
Digit 11 — Exhaust
0 = None
1 = Barometric Relief
(Available w/Economizer only)
2 = Power Exhaust Fan
(Available w/Economizer only)
Digit 12 — Filter
A = Standard 2” Throwaway Filters
B = High Efficiency 2” Throwaway Filters
C = High Efficiency 4” Throwaway Filters
Digit 13 — Supply Fan Motor, HP
1 = 7.5 Hp Std. Eff.
2 = 10 Hp Std. Eff.
3 = 15 Hp Std. Eff.
4 = 20 Hp Std. Eff.
5 = 7.5 Hp Hi. Eff.
6 = 10 Hp Hi. Eff.
7 = 15 Hp Hi. Eff.
8 = 20 Hp Hi. Eff.
Digit 14 — Supply Air Fan Drive
Selections (See Note 3)
A = 550 RPMH = 500 RPM
B = 600 RPMJ = 525 RPM
C = 650 RPMK = 575 RPM
D = 700 RPML = 625 RPM
E = 750 RPMM = 675 RPM
F = 790 RPMN = 725 RPM
G = 800 RPM
Digit 15 — Fresh Air Selection
A = No Fresh Air
B = 0-25% Manual Damper
C = 0-100% Economizer, Dry Bulb Control
D = 0-100% Economizer, Reference
Enthalpy Control
E = 0-100% Economizer, Differential
Enthalpy Control
F = “C” Option and Low Leak Fresh
Air Damper
G = “D” Option and Low Leak Fresh
Air Damper
H = “E” Option and Low Leak Fresh
Air Damper
Notes:
1. All voltages are across the line starting only.
2. Option includes Liquid, Discharge, Suction Valves.
3. Supply air fan drives A thru G are used with 27½-35 ton units only and drives H thru N are used with 40 & 50
ton units only.
4. Electric Heat KW ratings are based upon voltage ratings of 240/480/600 V. Voltage offerings are as follows (see
table PD-9 for additional information):
TonsV oltage36547290108
27½ to 35240xx
40 and 50240x
5. The service digit for each model number contains 31 digits; all 31 digits must be referenced.
480xxxx
600xxx
480xxxx
600xxxx
60 Hz
5
Digit 16 — System Control
1 = Constant Volume
2 = VAV Supply Air Temperature Control
w/o Inlet Guide Vanes
3 = VAV Supply Air Temperature Control
w/Inlet Guide Vanes
4 = VAV Supply Air Temperature Control
w/Variable Frequency Drive w/o Bypass
5 = VAV Supply Air Temperature Control
w/Variable Frequency Drive and Bypass
Note: Zone sensors are not included with
option and must be ordered as a separate
accessory.
Digit 17 - 28 — Miscellaneous Options
A = Service Valves (See Note 2)
B = Through the Base Electrical Provision
C = Non-Fused Disconnect Switch with
External Handle
D = Factory-Powered 15A GFI
Convenience Outlet and Non-Fused
Disconnect Switch with
External Handle
E = Field-Powered 15A GFI
Convenience Outlet
F = Trane Communication Interface (TCI)
G = Ventilation Override
H = Hinged Service Access
J = Condenser Coil Guards
K = LCI (LonTalk)
L = Unused digit
M = Stainless Steel Drain Pans
Digit 29 — Condenser Coil Options
0 = Standard Efficiency Condenser
Coil
N = Standard Efficiency Condenser
Coil with Black Epoxy Pre-Coating
3 = High Efficiency Condenser Coil
Q = High Efficiency Condenser Coil with
Black Epoxy Pre-Coating
Digit 30-31 — Miscellaneous Options
P = Discharge Temperature Sensor
R = Clogged Filter Switch
0 = No Heat (TC only)
L = Low Heat (YC only)
H = High Heat (YC only)
Note: When second digit is “E” for Electric
Heat, the following values apply in the
ninth digit.
380V / 415V
A = 2327 kW
B = 3440 kW
C = 4554 kW
D = 5667 kW
E = 6881 kW
Digit 10 – Design Sequence
A = First
Digit 11 – Exhaust
0 = None
1 = Barometric Relief
(Available w/Economizer only)
2 = Power Exhaust Fan
(Available w/Economizer only)
Digit 12 – Filter
A = Standard 2” (51 mm) Throwaway Filters
B = High Efficiency 2” (51 mm) Throwaway
Filters
C = High Efficiency 4” (102 mm) Throwaway
Filters
Digit 13 – Supply Fan Motor, HP
1 = 7.5 Hp Std. Eff. (5.6 kW)
2 = 10 Hp Std. Eff. (7.5 kW)
3 = 15 Hp Std. Eff. (11.2 kW)
4 = 20 Hp Std. Eff. (14.9 kW)
Digit 14 – Supply Air Fan Drive Selections
(See Note 3)
A = 458H = 417
B = 500J = 437
C = 541K = 479
D = 583L = 521
E = 625M = 562
F = 658N = 604
G = 664
Digit 15 – Fresh Air Selection
A = No Fresh Air
B = 0-25% Manual Damper
C = 0-100% Economizer, Dry Bulb Control
D = 0-100% Economizer, Reference
Enthalpy Control
E = 0-100% Economizer, Differential
Enthalpy Control
F = “C” Option and Low Leak Fresh
Air Damper
G = “D” Option and Low Leak Fresh
Air Damper
H = “E” Option and Low Leak Fresh
Air Damper
Digit 16 – System Control
1 = Constant Volume
2 = VAV Supply Air Temperature Control
w/o Inlet Guide Vanes
3 = VAV Supply Air Temperature Control
w/Inlet Guide Vanes
50 Hz
Note: Zone sensors are not included with
option and must be ordered as a separate
accessory.
Digit 17 - 28 — Miscellaneous Options
A = Service Valves (See Note 2)
B = Through the Base Electrical Provision
C = Non-Fused Disconnect Switch with
External Handle
D = Factory-Powered 15A GFI
Convenience Outlet and Non-Fused
Disconnect Switch with
External Handle
E = Field-Powered 15A GFI
Convenience Outlet
F = Trane Communication Interface (TCI)
G = Ventilation Override
H = Hinged Service Access
J = Condenser Coil Guards
K = LCI (LonTalk)
L = Unused digit
M = Stainless Steel Drain Pans
Digit 29 — Condenser Coil Options
0 = Standard Efficiency Condenser
Coil
N = Standard Efficiency Condenser
Coil with Black Epoxy Pre-Coating
3 = High Efficiency Condenser Coil
Q = High Efficiency Condenser Coil with
Black Epoxy Pre-Coating
Digit 30-31 — Miscellaneous Options
P = Discharge Temperature Sensor
R = Clogged Filter Switch
5
Notes:
1. All voltages are across-the-line starting only.
2. Option includes Liquid, Discharge, Suction Valves.
3. Supply air fan drives A thru G are used with 22.9-29.2 ton (82-105 kW) units only and drives H thru N are used with 33.3
and 41.7 ton (120-148 kW) units only.
4. Electric Heat kW ratings are based upon voltage ratings of 380/415 V. Heaters A, B, C, D are used with 22.9-29.2 ton (82105 kW) units only and heaters B, C, D, E are used with 33.3-41.7 ton (120-148 kW) units only.
5. The service digit for each model number contains 31 digits; all 31 digits must be referenced.
RT-PRC007-EN18
General Data
60 Hz
Table GD-1 — General Data — 27½ - 30 Tons
Cooling Performance
Nominal Gross Capacity329,000363,000
Natural Gas Heat
1
2
LowHighLowHigh
Heating Input (BTUH)350,000600,000350,000600,000
First Stage250,000425,000250,000425,000
Heating Output (BTUH)283,500486,000283,500486,000
First Stage202,500344,500202,500344,500
Steady State Efficiency (%)
Face Area (sq. ft.)51.3351.3351.3351.33
Rows/Fins Per Inch2/163/162/163/16
Indoor Coil — TypeHi-PerformanceHi-Performance
Tube Size (in.) OD
Face Area (sq. ft.)31.6731.67
Rows/Fins Per Foot2/1802/180
Refrigerant ControlTXVTXV
No. of Circuits11
Drain Connection No./Size (in)1/1.251/1.25
TypePVCPVC
Outdoor Fan TypePropellerPropeller
No. Used/Diameter3/28.003/28.00
Drive Type/No. SpeedsDirect/1Direct/1
CFM24,80024,800
No. Motors/HP/RPM3/1.10/11253/1.10/1125
Indoor Fan TypeFCFC
No. Used11
Diameter/Width (in)22.38/22.0022.38/22.00
Drive Type/No. SpeedsBelt/1Belt/1
No. Motors/HP1/7.50/10.001/7.50/10.00
Motor RPM17601760
Motor Frame Size213/215T213/215T
Exhaust Fan TypePropellerPropeller
No. Used/Diameter (in)2/26.002/26.00
Drive Type/No. Speeds/MotorsDirect/2/2Direct/2/2
Motor HP/RPM1.0/10751.0/1075
Motor Frame Size4848
Filters — Type FurnishedThrowawayThrowaway
No./ Recommended Size (in)
6
Refrigerant Charge (Std./Hi Eff Cond Coil) (Lbs of R-22)4(Std) 46.0/(High) 58.0(Std.) 46.6/(High) 58.0
Minimum Outside Air Temperature
For Mechanical Cooling0 F0 F
Notes:
1. Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. Rated and tested in
accordance with the Unitary Large Equipment certification program, which is based on ARI Standard 340/360-93.
2. Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standards Institute standards.
Ratings shown are for elevations up to 4,500 feet.
3. Steady State Efficiency is rated in accordance with DOE test procedures.
4. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
5. Maximum KW @ 208V = 41, @ 240V = 54. For Electric heat KW range per specific voltage, see table PD-10.
6. Filter dimensions listed are nominal. For actual filter and rack sizes see the Unit Installation, Operation, Maintenance Guide.
27½ Ton30 To n
3
/
4
5
27-90
3
/
8
1
/
2
27-90
1
1
5
3
8
/
/
2
16/16 x 20 x 216/16 x 20 x 2
1
3
8
/
19RT-PRC007-EN
General Data60 Hz
Table GD-2— General Data — 35-40 Ton
Cooling Performance
Nominal Gross Capacity417,000513,000
Natural Gas Heat
1
2
LowHighLowHigh
Heating Input (BTUH)350,000600,000400,000800,000
First Stage250,000425,000300,000600,000
Heating Output (BTUH)283,500486,000324,000648,000
First Stage202,500344,500243,000486,000
Steady State Efficiency (%)
3
81.0081.0081.0081.00
No. Burners1212
No. Stages2222
Gas Supply Pressure (in. w.c.)
Natural or LP (minimum/maximum)2.5/14.02.5/14.02.5/14.02.5/14.0
Gas Connection Pipe Size (in.)
Electric Heat
KW Range
5
3
/
4
Capacity Steps:22
Compressor
Number/Type2/Scroll3/Scroll
Size (nominal)1515/15/10
Unit Capacity Steps (%)100/50100/60/40
Motor RPM34503450
Outdoor CoilStandard EfficiencyHigh EfficiencyStandard EfficiencyHigh Efficiency
TypeLancedLancedLancedLanced
Tube Size (in.) OD
3
/
8
Face Area51.3351.3369.7975.00
Rows/Fins Per Inch2/163/162/163/16
Indoor Coil — TypeHi-PerformanceHi-Performance
Tube Size (in.) OD
Face Area (sq. ft.)31.6737.50
Rows/Fins Per Foot3/1803/180
Refrigerant ControlTXVTXV
No. of Circuits12
Drain Connection No./Size (in)1/1.251/1.25
TypePVCPVC
Outdoor Fan TypePropellerPropeller
No. Used/Diameter3/28.004/28.00
Drive Type/No. SpeedsDirect/1Direct/1
CFM24,80031,700
No. Motors/HP/RPM3/1.10/11254/1.10/1125
Indoor Fan TypeFCFC
No. Used11
Diameter/Width (in)22.38/22.0025.00/25.00
Drive Type/No. SpeedsBelt/1Belt/1
No. Motors/HP1/7.50/10.00/15.001/10.00/15.00
Motor RPM17601760
Motor Frame Size213/215/254T215/254T
Exhaust Fan TypePropellerPropeller
No. Used/Diameter (in)2/26.002/26.00
Drive Type/No. Speeds/MotorsDirect/2/2Direct/2/2
Motor HP/RPM1.0/10751.0/1075
Motor Frame Size4848
Filters — Type FurnishedThrowawayThrowaway
No./Recommended Size (in)
6
Refrigerant Charge (Std./Hi Eff Cond Coil) (Lbs of R-22)4(Std.) 51.5/(High) 63.0(Std.) 31.0/47.1 per circuit/(High) 36.0/65.0 per circuit
Minimum Outside Air Temperature
For Mechanical Cooling0 F0 F
Notes:
1. Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. Rated and tested in
accordance with the Unitary Large Equipment certification program, which is based on ARI Standard 340/360-93.
2. Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standards Institute standards.
Ratings shown are for elevations up to 4,500 feet.
3. Steady State Efficiency is rated in accordance with DOE test procedures.
4. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
5. Maximum KW @ 208V = 41, @ 240V = 54. For Electric heat KW range per specific voltage, see table PD-10.
6. Filter dimensions listed are nominal. For actual filter and rack sizes see the Unit Installation, Operation, Maintenance Guide.
35 Ton40 To n
3
/
4
5
41-108
3
/
8
1
/
2
27-90
1
/
1
5
3
/
8
2
16/16 x 20 x 217/16 x 20 x 2
1
3
/
8
RT-PRC007-EN20
General Data
60 Hz
Table GD-3— General Data — 50 Ton
Cooling Performance
Nominal Gross Capacity616,000
Natural Gas Heat
1
2
LowHigh
Heating Input (BTUH)400,000800,000
First Stage300,000600,000
Heating Output (BTUH)324,000648,000
First Stage243,000486,000
Steady State Efficiency (%)
3
81.0081.00
No. Burners12
No. Stages22
Gas Supply Pressure (in. w.c.)
Natural or LP (minimum/maximum)2.5/14.02.5/14.0
Gas Connection Pipe Size (in.)
Electric Heat
KW Range
5
3
/
4
Capacity Steps:2
Compressor
Number/Type3/Scroll
Size (nominal)14
Unit Capacity Steps (%)100/67/33
Motor RPM3450
Outdoor CoilStandard EfficiencyHigh Efficiency
TypeLancedLanced
Tube Size (in.) OD
3
/
8
Face Area (sq. ft.)69.7975.00
Rows/Fins Per Inch2/163/16
Indoor Coil — TypeHi-Performance
Tube Size (in.) OD
Face Area (sq. ft.)37.50
Rows/Fins Per Foot4/164
Refrigerant ControlTXV
No. of Circuits2
Drain Connection No./Size (in)1/1.25
TypePVC
Outdoor Fan — TypePropeller
No. Used/Diameter4/28.00
Drive Type/No. SpeedsDirect/1
CFM31,700
No. Motors/HP/RPM4/1.10/1125
Indoor Fan TypeFC
No. Used1
Diameter/Width (in)25.00/25.00
Drive Type/No. SpeedsBelt/1
No. Motors/HP1/10.00/15.00/20.00
Motor RPM1760
Motor Frame Size215/254/256T
Exhaust Fan TypePropeller
No. Used/Diameter (in)2/26.00
Drive Type/No. Speeds/MotorsDirect/2/2
Motor HP/RPM1.0/1075
Motor Frame Size48
Filters — Type FurnishedThrowaway
No./Recommended Size (in)
Refrigerant Charge (Std./Hi Eff Cond Coil) (Lbs of R-22)
6
4
(High) 36.0/72.0 per circuit
Minimum Outside Air Temperature
For Mechanical Cooling0 F
Note: Above data based on tests completed in
accordance with AMCA Standard 500.
Notes:
1. Cooling Performance is rated at 95 F ambient, 80 F
entering dry bulb, 67 F entering wet bulb. Gross
capacity does not include the effect of fan motor heat.
Rated and tested in accordance with the Unitary
Large Equipment certification program, which is
based on ARI Standard 340/360-93.
2. Heating Performance limit settings and rating data
were established and approved under laboratory test
conditions using American National Standards
Institute standards. Ratings shown are for elevations
up to 4,500 feet.
3. Steady State Efficiency is rated in accordance with
DOE test procedures.
4. Refrigerant charge is an approximate value. For a
more precise value, see unit nameplate and service
instructions.
5. Maximum KW @ 208V = 41, @ 240V = 54. For Electric
heat KW range per specific voltage, see table PD-10.
6. Filter dimensions listed are nominal. For actual filter
and rack sizes see the Unit Installation, Operation,
Maintenance Guide.
0.5 (In.)1.0 (In.)
21RT-PRC007-EN
General Data50 Hz
Table GD-5 – General Data – 23-25 Tons
Cooling Performance
1
Nominal Gross Capacity - Btu (kW)277,000 (81.1)303,000 (88.7)
System Power - kW24.928.6 kW
Compressor
Number/Type2/Scroll2/Scroll
Size (Nominal Tons)10/1515/15
Unit Capacity Steps (%)100/40100/50
Motor rpm28752875
Tube Size OD - in. (mm)0.375 (10)0.375 (10)0.375 (10)0.375 (10)
Face Area - sq ft (sq m)51.3 (4.8)51.3 (4.8)51.3 (4.8)51.3 (4.8)
Rows/Fins Per Inch2/163/162/163/16
Indoor Coil - TypeHi PerformanceHi Performance
Tube Size OD - in. (mm)0.500 (13)0.500 (13)
Face Area - sq ft (sq m)31.7 (2.9)31.7 (2.9)
Rows/Fins Per Foot2/1802/180
Refrigerant ControlTXVTXV
PVC Drain Connect No./Size - in. (mm)1/1.25 (1/32)1/1.25 (1/32)
Outdoor Fan TypePropellerPropeller
No. Used33
Diameter - in. (mm)28.0 (711)28.0 (711)
Drive Type/No. SpeedsDirect/1Direct/1
cfm ( L/s)20,450 (9650)20,450 (9650)
No. Motors (rpm)3 (940)3 (940)
Motor- hp (kW)0.75 (0.56)0.75 (0.56)
Indoor Fan Type/No. UsedFC/1FC/1
Diameter - in. (mm)22.4 (568)22.4 (568)
Width - in. (mm)22.0 (559)22.0 (559)
Drive TypeBeltBelt
No. Speeds/No. Motors1/11/1
Motor - hp (kW)7.5 (5.6)7.5 (5.6)
Motor rpm/Frame Size1460/213T1460/213T
Filters - TypeThrowawayThrowaway
Furnished/No.Yes/16Yes/16
Recommended Size - in. (mm)16X 20 X2 (406X 508 X51)16x20x2 (406X 508x51)
Refrigerant Charge(Std./Hi Eff Cond Coil)
(Lbs of R-22)
Notes:
1. Cooling Performance is rated at 95°F (35°C) ambient, 80°F (27°C) entering dry bulb, 67°F (19°C) entering wet bulb. Gross capacity does not include the effect of fan motor heat.
2. Heating Performance Limit settings and ratings data were established and approved under laboratory test conditions using American National Standards.
3. Steady State Efficiency is rated in accordance with DOE test procedures.
4. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
1. Cooling Performance is rated at 95°F (35°C) ambient, 80°F (27°C) entering dry bulb, 67°F (19°C) entering wet bulb. Gross capacity does not include the effect of fan motor heat.
2. Heating Performance Limit settings and ratings data were established and approved under laboratory test conditions using American National Standards.
3. Steady State Efficiency is rated in accordance with DOE test procedures.
4. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
Nominal Gross Capacity - Btu (kW)520,000 (152)
System Power - kW50.9
Compressor
Number/Type3/Scroll
Size (Nominal Tons)14/14/14
Unit Capacity Steps (%)100/67/33
Motor rpm2875
Natural Gas Heat
2
Heating Input - Btu (kW)335,000 (98.2)670,000 (196)
First Stage300,000 (87.9 kW)600,000 (176 kW)
Heating Output - Btu (kW)271,350 (79.5)542,700 (159)
First Stage243,500 (71.4 kW)486,000 (166 kW)
Steady State Efficiency(%)
3
No. Burners/No. Stages1/2
Gas Connect Pipe Size - in. (mm)0.75 (19)
Outdoor CoilStandard Efficiency High Efficiency
TypeLancedLanced
Tube Size OD - in. (mm)0.375 (10)0.375 (10)
Face Area - sq ft (sq m)69.8 (6.5)75.0 (7.0)
Rows/Fins Per Inch2/163/16
Indoor Coil - TypeHi-Performance
Tube Size OD - in. (mm)0.500 (13)
Face Area - sq ft (sq m)37.5 (3.5)
Rows/Fins Per Foot4/164
Refrigerant ControlTXV
PVC Drain Connect No./Size - in. (mm)1/1.25 (1/32)
Outdoor Fan TypePropeller
No. Used4
Diameter - in. (mm)28.0 (711)
Drive Type/No. SpeedsDirect/1
cfm (L/s)26,200 (12,400)
No. Motors (rpm)4 (940)
Motor - hp (kW)0.75 (0.56)
Indoor Fan Type/No. UsedFC/1
Diameter - in. (mm)25.0 (635)
Width - in. (mm)25.0 (635)
Drive TypeBelt
No. Speeds/No. Motors1/1
Motor hp10.0 (7.5 kW)
Motor rpm/Frame Size1460/215T
Filters - TypeThrowaway
Furnished/No.Yes/17
Recommended Size - in. (mm)16x20x2 (406x508x51)
1. Cooling Performance is rated at 95°F (35°C) ambient, 80°F (27°C) entering dry bulb, 67°F (19°C) entering wet bulb. Gross
capacity does not include the effect of fan motor heat.
2. Heating Performance Limit settings and ratings data were established and approved under laboratory test conditions
using American National Standards.
3. Steady State Efficiency is rated in accordance with DOE test procedures.
4. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.