Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and airconditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment
by an unqualified person could result in death or serious injury. When working on the equipment, observe all pr ecautions in the literature and
on the tags, stickers, and labels that are attached to the equipment.
June 2014
RT-SVX34H-EN
Proprietary and Confidential
Warnings, Cautions and Notices
Warnings, Cautions and Notices. Note that warnings,
cautions and notices appear at appropriate intervals
throughout this manual. Warnings are provided to alert
installing contractors to potential hazards that could result
in personal injury or death. Cautions are designed to alert
personnel to hazardous situations that could result in
personal injury, while notices indicate a situatio n that could
result in equipment or property-damage-only accidents.
Your personal safety and the proper operation of this
machine depend upon the strict observance of these
precautions.
ATTENTION: Warnings, Cautions and Notices appear at
appropriate sections throughout this literature. R ead these
carefully:
WARNING
CAUTIONs
NOTICE:
Indicates a potentially hazardous
situation which, if not avoided, could
result in death or serious injury.
Indicates a potentially hazardous
situation which, if not avoided, could
result in minor or moderate injury. It
could also be used to alert against
unsafe practices.
Indicates a situation that could result in
equipment or property-damage only
Personal Protective Equipment (PPE)
Required!
Installing/servicing this unit could result in exposure to
electrical, mechanical and chemical hazards.
•Before installing/servicing this unit, technicians
MUST put on all Personal Protective Equipment (PPE)
recommended for the work being undertaken.
AL W A Y S ref er to appropr iate MSDS sheets and OSHA
guidelines for proper PPE.
•When working with or around hazardous chemicals,
ALWAYS refer to the appropriate MSDS sheets and
OSHA guidelines for information on allowable
personal exposure levels, proper respiratory
protection and handling recommendations.
•If there is a risk of ar c or flash, tec hnicians MUST put
on all Personal Protective Equipment (PPE) in
accordance with NFPA 70E or other country-specific
requirements fo r arc flash protection, PRIOR to
servicing the unit.
Failure to follow instructions could result in death or
serious injury.
WARNING
Important
Environmental Concerns!
Scientific research has shown that certain man-made
chemicals can affect the earth’s naturally occurring
stratospheric ozone layer when released to the
atmosphere. In particular, several of the identified
chemicals that may affect the ozone layer are refrigerants
that contain Chlorine, Fluorine and Carbon (CFCs) and
those containing Hydrogen, Chlorine, Fluorine and Carbon
(HCFCs). Not all refrigerants containing these compounds
have the same potential impact to the environment. T rane
advocates the responsible handling of all refrigerantsincluding industry replacements for CFCs such as HCFCs
and HFCs.
Responsible Refrigerant Practices!
Trane believes that responsible refrigerant practices are
important to the environment, our customers, and the air
conditioning industry. All technicians who handle
refrigerants must be certified. The Federal Clean Air Act
(Section 608) sets forth the requirements for handling,
reclaiming, recovering and recycling of certain refrigerants
and the equipment that is used in these service procedures.
In addition, some states or municipalities may have
additional requirements that must also be adhered to for
responsible management of refrigerants. Know the
applicable laws and follow them.
WARNING
Proper Field Wiring and Grounding
Required!
All field wiring MUST be performed by qualified
personnel. Improperly installed and grounded field
wiring poses FIRE and ELECTROCUTION hazards. To
avoid these hazards, y ou MUST follow requirements f or
field wiring installation and grounding as described in
NEC and your local/state electrical codes. Failure to
follow code could result in death or serious injury.
Overview of Manual
One copy of the appropriate service literature ships inside
the control panel of each unit. The procedures discussed in
this manual should only be performed by qualified,
experienced HVAC technicians.
Note: Do not release refrigerant to the atmosphere! If
adding or removing refrigerant is required, the
service technician must comply with all federal,
state, and local laws.
This booklet describes the proper installation, startup,
operation, and maintenance procedures for TC_, TE_, and
YC_22.9 to 50 Ton CV (Constant Volume), V AV (Variable Air
V o lu me), and SZ VAV (Single Zone Variable Air Volu me)
applications. Refer to the table of contents for a listing of
specific topics. Refer to “Diagnostics,” p. 117 for
troubleshooting information.
By carefully reviewing the information within this manual
and following the instructions, the risk of improper
operation and/or component dama ge will be minimized.
It is important that periodic maintenance be performed to
help assure trouble free operation. A maintenance
schedule is provided at the end of this manual. Should
equipment failure occur, contact a qualified service
organization with qualified, experienced HVAC technicians
to properly diagnose and repair this equipment.
Revision History
RT-SVX34G-EN (3 June 2014)
•Added features: Low Leak Damper option, eStage,
Ultra Low Leak Power Exhaust, Touchscreen Human
Interface.
•Updated Model Number Description, Startup,
Sequence of Operation, Diagnostics, Unit Wiring
Diagrams.
Warnings, Cautions and Notices
60 Hz units with standard options are certified by
Underwriters Laboratory.
RT-SVX34H-EN3
Table of Contents
Model Number Description . . . . . . . . . . . . . . . 8
A = 2” MERV 4, Std Eff, Throwaway
B = 2” MERV 8, High Eff, Throwaway
C = 4” MERV 8, High Eff, Throwaway
D = 4” MERV 14, High Eff, Throwaway
Filters
Filters
Filters
Filters
Digit 13 — Supply F an Motor, HP
1= 7.5 Hp
2=10 Hp
3= 15 Hp
4= 20 Hp
Digit 14 — Supply Air Fan Drive
Selections3
A =550 RPMH = 500 RPM
B = 600 RPM J = 525 RPM
C = 650 RPMK = 575 RPM
D =700 RPML = 625 RPM
E =750 RPMM = 675 RPM
F=790 RPMN = 725 RPM
G =800 RPM
Digit 15 — Fresh Air Selection
A=No Fresh Air
B =0-25% Manual Damper
C =0-100% Economizer, Dry Bulb
Control
D = 0-100% Economizer,
Reference Enthalpy Control
E =0-100% Economizer,
Differential Enthalpy Control
F=“C” Option and Low Leak
Fresh Air Damper
G =“D” Option and Low Leak
Fresh Air Damper
H =“E” Option and Low Leak
Fresh Air Damper
J=“C” Option and Ultra Low Leak
Outside Air Damper
K =“D” Option and Ultra Low Leak
Outside Air Damper
L=E Option and Ultra Low Leak
Outside Air Damper
1=Option “C” with Traq
2=Option “D” with Traq
3=Option “E” with Traq
4=Option “F” with Traq
5=Option “G” with Traq
6=Option “H” with Traq
7=Option “C” with Traq w/ Ultra
Low Leak Outside Air Damper
8=Option “D” with Traq w/ Ultra
Low Leak Outside Air Damper
9=Option “E” with Traq w/ Ultra Low
Leak Outside Air Damper
Digit 16 — System Control
1=Constant Volume w/Zone
Temperature Control
2=Constant Volume w/ Discharge Air
Control
4=VAV Supply Air Temperature
Control w/Variable Frequency
Drive w/o Bypass
5=VAV Supply Air Temperature
Control w/Variable Frequency
Drive and Bypass
6=Single Zone VAV w/VFD w/o
Bypass
7=Single Zone VAV w/VFD w/
Bypass
8 RT-SVX34H-EN
Model Number Description
A =VAV Supply Air Temperature
Control w/VFD w/o Bypass w/
Motor Shaft Grounding Ring
B =VAV Supply Air Temperature
Control w/VFD w/Bypass w/Motor
Shaft Grounding Ring
C =Single Zone VAV w/VFD w/o
Bypass w/ Motor Shaft Grounding
Ring
D =Single Zone VAV w/VFD w/
Bypass w/Motor Shaft Grounding
Ring
Note: Zone sensors are not included
with option and must be ordered
as a separate accessory.
Miscellaneous Options
Digit 17
A =Service Valves
Note: Service valves cannot be selected
with High Efficiency units
(Digit 29 = K or L). Liquid and
discharge service valves are
included with High Efficiency
units.
2
Digit 18
B =Through the Base Electrical
Provision
Digit 19
C = Non-Fused Disconnect Switch
w/External Handle
Digit 20
D =Factory-Powered 15A GFI
Convenience Outlet and
Non-Fused Disconnect Switch
w/External Handle
Digit 21
E =Field-Powered 15A GFI
Convenience Outlet
Note: If convenience outlet needed w/
High Fault SCCR, option must be
ordered under digit 27.
Digit 22
F=Trane Communication
Interface (TCI)
Digit 23
G =Ventilation Override
Digit 24
H =Hinged Service Access
Digit 25
H =Tool-less Condenser Hail Guards
J=Condenser Coil Guards
Digit 26
K =LCI (LonTalk)
B =BACnet Communications
Interface (BCI)
Digit 27
0=5kA SCCR
D =High Fault SCCR w/ Disconnect
E =High Fault SCCR w/ Disconnect w/
Powered Convenience Outlet
7
7
Digit 28
0=Pre-Painted Steel Drain Pan
M =Stainless Steel Drain Pan
1=Pre-Painted Steel Drain Pan w/
0=Standard Efficiency
J=Corrosion Protected Condenser
K =High efficiency unit (eStage)
L=High efficiency unit (eStage) w/
Condenser Coil
Coil
Corrosion Protected Condenser
Coil
Digit 30-31 — Miscellaneous
Options
P =Discharge Temperature
R =Clogged Filter Switch
Sensor
Digit 32 — Dehumidification
Option
T =Modulating Hot Gas Reheat
Digit 33 — Human Interface
5=Touchscreen Human Interface, 5"
Model Number Notes
1. All voltages are across the line
starting only.
2. Option includes Liquid, Discharge,
Suction Valves.
3. Supply air fan drives A thru G are
used with 27½-35 ton units only and
drives H thru N are used with 40 & 50
ton units only.
4. Electric Heat KW ratings are based
upon voltage ratings of 208/240/480/
600 V. For a 240 V heater derated to
208 V, the resulting kW rating
decreases from 36 kW to 27 kW, and
from 54 kW to 41 kW. Voltage
offerings are as follows:
Electric
Heater
Rated
Tons
Voltage
27½
to 35
40
and
50
5. The service digit for each model
number contains 32 digits; all 32
digits must be referenced.
6. Ventilation override exhaust mode is
not available for the exhaust fan with
fresh air tracking power exhaust. V OM
is available for the exhaust fan
without fresh air tracking power
exhaust.
1= 7.5 Hp (5.6 kW)
2=10 Hp (7.5 kW)
3=15 Hp (10 kW)
4=20 Hp (15 kW)
Digit 14 – Supply Air Fan Drive
Selections
A =458 RPMH = 417 RPM
B = 500 RPM J = 437 RPM
C = 541 RPMK = 479 RPM
D =583 RPML = 521 RPM
E =625 RPMM = 562 RPM
F=658 RPMN = 604 RPM
G =664 RPM
3
Digit 15 – Fresh Air Selection
A=No Fresh Air
B =0-25% Manual Damper
C =0-100% Economizer, Dry Bulb
D =0-100% Economizer,
E =0-100% Economizer,
F=“C” Option and Low Leak
G =“D” Option and Low Leak
H =“E” Option and Low Leak
J=“C” Option and Ultra Low Leak
K =“D” Option and Ultra Low Leak
L=“E” Option and Ultra Low Leak
1=Option “C” with Traq
2=Option “D” with Traq
3=Option “E” with Traq
4=Option “F” with Traq
Control
Reference Enthalpy Control
Differential Enthalpy Control
Fresh Air Damper
Fresh Air Damper
Fresh Air Damper
Outside Air Damper
Outside Air Damper
Outside Air Damper
5=Option “G” with Traq
6=Option “H” with Traq
7=Option “C” with Traq w/ Ultra
8=Option “D” with Traq w/ Ultra
9=Option “E” with Traq w/ Ultra L ow
Low Leak Outside Air Damper
Low Leak Outside Air Damper
Leak Outside Air Damper
Digit 16 – System Control
1=Constant Volume w/ Zone
2=Constant V olume w/ Di scharge Air
4=VAV Supply Air Temperature
5=VAV Supply Air Temperature
6=Single Zone VAV w/VFD w/o
7=Single Zone VAV w/VFD w/
A =VAV Supply Air Temperature
B =VAV Supply Air Temperature
C =Single Zone VAV w/VFD w/o
D =Single Zone VAV w/VFD w/
Note: Zone sensors are not included
Temperature Control
Control
Control w/Variable Frequency
Drive w/o Bypass
Control w/Variable Frequency
Drive and Bypass
Bypass
Bypass
Control w/VFD w/o Bypass w/
Motor Shaft Grounding Ring
Control w/VFD w/Bypass w/Motor
Shaft Grounding Ring
Bypass w/ Motor Shaft Grounding
Ring
Bypass w/Motor Shaft Grounding
Ring
with option and must be ordered
as a separate accessory.
Miscellaneous Options
Digit 17
A =Service Valves
Note: Service valves cannot be selected
with High Efficiency units
(Digit 29 = K or L). Liquid and
discharge service valves are
included with High Efficiency
units.
2
Digit 18
B =Through the Base Electrical
Provision
Digit 19
C = Non-Fused Disconnect Switch
with External Handle
Digit 20
*=Unused Digit
Digit 21
*=Unused Digit
10 RT-SVX34H-EN
Model Number Description
Digit 22
F=Trane Communication Interface
(TCI)
Digit 23
G =Ventilation Override
Digit 24
H =Hinged Service Access
Digit 25
H =Tool-less Condenser Hail Guards
J=Condenser Coil Guards
Digit 26
K =LCI (LonTalk)
B =BACnet Communications
Interface (BCI)
Digit 27
0=5kA SCCR
D =High Fault SCCR w/ Disconnect
Digit 28
0=Pre-Painted Steel Drain Pan
M =Stainless Steel Drain Pan
1=Pre-Painted Steel Drain Pan w/
Condensate Overflow Switch
2=Stainless Steel Drain Pan w/
Condensate Overflow Switch
Digit 29 — Condenser Coil
Options
0=Standard Efficiency
Condenser Coil
J=Corrosion Protected Condenser
Coil
K =High efficiency unit (eStage)
L=High efficiency unit (eStage) w/
Corrosion Protected Condenser
Coil
Digit 30-31 — Miscellaneous
Options
P =Discharge Temperature Sensor
R =Clogged Filter Switch
Digit 32 — Dehumidification
Option
T =Modulating Hot Gas Reheat
Digit 33 — Human Interface
5=Touchscreen Human Interface, 5"
29.2 ton (82-105 kW) units only and
heaters B, C, D, E are used with 33.3-
41.7 ton (120-148 kW) units only.
5. The service digit for each model
number contains 32 digits; all 32
digits must be referenced.
6. Ventilation override exhaust mode is
not available for the exhaust fan with
fresh air tracking power exhaust. VOM
is available for the exhaust fan
without fresh air tracking power
exhaust.
Model Number Notes
1. All voltages are across-the-line
starting only.
2. Option includes Liquid, Discharge,
Suction Valves.
3. Supply air fan drives A thru G are
used with 22.9-29.2 ton (82-105 kW)
units only and drives H through N are
used with 33.3 and 41.7 ton (120-148
kW) units only.
4. Electric Heat kW ratings are based
upon voltage ratings of 380/415 V.
Heaters A, B, C, D are used with 22.9-
RT-SVX34H-EN11
General Information
Commonly Used Acronyms and
Abbreviations
BAS = Building Automation SystemPSIG = Pounds Per Square Inch Gauge pressure
CFM = Cubic Feet per MinutePHM= Phase monitor
CLV= Cooling Valve (Reheat only)R/A = Return Air
COMM = Module Designation for TCI/LCIRAH= Return Air Humidity
CV= Constant VolumeRAT= Return Air Temperature sensor
CW = ClockwiseRH = Right Hand
CCW = CounterclockwiseRHP = Reheat Pumpout Solenoid
DSP = Direct Space Pressure controlRHV= Reheat Valve
DTS = Discharge Air SensorRLP= Reheat Low Pressure Cutout
DWU = Daytime Warm-upRPM = Revolutions Per Minute
E/A = Exhaust AirRTAM = ReliaTel Air Handler Module
ECA= Economizer ActuatorRTDM = ReliaTel Dehumidification Module
EET= Entering Evaporator Temperature SensorRTVM = ReliaTel Ventilation Module
F/A= Fresh AirRTOM = ReliaTel Options Module
FDD = Fault Detection & DiagnosticsRTRM = ReliaTel Refrigeration Module
FFS= Fan Failure SwitchS/A = Supply Air
HI= Human InterfaceSCCR = Short Circuit Current Rating
ICS = Integrated Comfort System (See BAS)SPC= Space Pressure Calibration Solenoid
IDM = Indoor Fan MotorSPP= Space Pressure Transducer
I/O = Input/OutputSPT= Static Pressure Transducer
IOM =
LCI = LonTalk® Communication InterfaceTCI = Trane Communication Interface
LCI-R = LonTalk Communication Interface with ReliaTelTCO = Temperature Cutout
LH = Left HandTD5= 5" Touchscreen Display
MAS = Mixed Air SensorTDL= Temperature Discharge Limit
MAT = Mixed Air TemperatureVAV = Variable Air Volume
MCHE = MicrochannelVFD = Variable Frequency Drive
MWU = Morning Warm UpVHR= Ventilation Heat Relay (VAV box relay)
NSB = Night Setback (programmable ZSM BAYSENS119*)W.C. = Water Column
O/A = Outside AirWCI= Wireless Comm Interface
OAH = Outside Air HumidityXFSP= Exhaust Fan Setpoint
OAT = Outside Air TemperatureZSM = Sensor, Zone Sensor, Zone Sensor Module, Zone Panel
PGA = Power Exhaust Actuator
Installation, Operation and Maintenance manual (Ships
with each unit)
SZVAV = Single Zone Variable Air Volume
About the Unit
Overall unit dimensional data is illustrated in Figure 1,
p. 14 to Figure 9, p. 18. Each package rooftop unit ships
fully assembled and charged with the proper refrigerant
quantity from the factory. They are controlled by a
microelectronic unit control processor . Several solid state
modules are grouped to form the “Control System”. The
number of modules within any given control system will
be dependent upon the options and accessories ordered
Basic unit components include:
•Scroll compressors
•One (1) Intertwined Evaporator Coil
•One (1) Supply Fan
•Three (3) to Four (4) Condenser Fans
•Microchannel Condenser Coils
•Filters (type is dependent on opti on selection)
with the unit. Acronyms are used extensively throughout
this manual when referring to the “Control System”.
12 RT-SVX34H-EN
Precautionary Measur es
WARNING
Fiberglass Wool!
Product contains fiberglass wool. Disturbing the
insulation in this product during installation,
maintenance or rep air will expose you to airborne
particles of glass wool fibers and ceramic fibers known
to the state of California to cause cancer through
inhalation. You MUST wear all necessary Personal
Protective Equipment (PPE) including gloves, eye
protection, mask, long sleev es and pants when w orking
with products containing fiberglass wool. Exposition to
glass wool fibers without all necessary PPE equipment
could result in cancer, respiratory, skin or eye irritation,
which could result in death or serious injury.
- Avoid breathing fiberglass dust.
- Use a NIOSH approved dust/mist respirator.
- Avoid contact with the skin or eyes. Wear long-sleeved,
loose-fitting clothing, gloves, and eye protection.
- Wash clothes separately from other clothing: rinse
washer thoroughly.
- Operations such as sawing, blowi ng , tear-out, and
spraying may generate fiber concentrations requiring
additional respiratory protection. Use the appropriate
NIOSH approved respiration in these situations.
First Aid Measures
Eye Contact - Flush eyes with water to remove dust. If
symptoms persist, seek medical attention.
Skin Contact - Wash af fected areas gently with soap and
warm water after handling.
An optional roof curb, specifically designed for the V oyager
commercial rooftop units is available from T rane. The roof
curb kit must be field assembled and installed according to
the latest edition of the curb installation guide.
Unit Inspection
As soon as the unit arrives at the job site:
•V erify that the nameplate data corresponds to the sales
order and bill of lading (including electrical data).
•Visually inspect the exterior of the unit, including the
roof, for physical signs of shipping damage.
•Check for material shor tages. Figure 11, p. 19 illustrates
where “ship with” items are placed inside the unit.
If the job site inspection reveals damage or material
shortages, file a claim with the carrier immediately . Specify
the type and extent of the damage on the “bill of lading”
before signing. Do not install a damaged unit without the
Appropriate Trane sales representative's approval!
•Visually check the internal components for shipping
damage as soon as possible after delivery and before it
is stored. Do not walk on the sheet metal base pans.
General Information
WARNING
No Step Surface!
Do not walk on the sheet metal drain pan. Walking on
the drain pan could cause the supporting metal to
collapse, resulting in the operator/technician to fall.
Failure to follow this recommendation could result in
death or serious injury.
Bridging between the unit's main supports may consist of
multiple 2 by 12 boards or sheet metal grating.
•If concealed damage is discovered, notify the carrier's
terminal office immediately by phone and by mail.
Concealed damage must be reported within 15 days.
•Request an immediate joint inspection of the damage
by the carrier and the consignee. Do not remove the
damaged material from the receiving location. Take
photos of the damage, if possible. The owner must
provide reasonable evidence that the damage did not
occur after delivery.
Storage
Take precautions to prevent condensate formation inside
the unit electrical components and motors when:
a. The unit is stored before it is installed; or,
b. The unit is set on the roof curb and temporary
auxiliary heat is provided in the building.
Isolate all side panel service entrances and base pan
openings (e.g., conduit holes, S/A and R/A openings, and
flue openings) to minimize ambient air from entering the
unit until it is ready for startup.
Do not use the unit heater as temporary heat without
completing the startup procedures detailed under
“Startup,” p. 40.
Trane will not assume responsibility for equipment
damage resulting from accumulation of condensate on the
unit electrical components.
RT-SVX34H-EN13
Unit Dimensions and Weights
Recommended Clearances
Adequate clearance around and above each Voyager
Commercial unit is required to ensure proper operation
and to allow sufficient access for servicing.
If the unit installation is higher than the typical curb
elevation, a field constructed catwalk around the unit is
recommended to provide safe, easy access for
maintenance and servicing. Table 1, p. 20 lists the
recommended clearances for single and multiple unit
installation. These clearances are necessary to assure
adequate serviceability, cataloged capacities, and peak
operating efficiency.
If the clearances available on the job site appear to be
inadequate, review them with your Trane sales
representative.
Roof Curb and Ductwork
The curbs for the 27.5 to 50 Ton commercial rooftop units
enclose the entire unit base area. They are referred to as
“full perimeter” type curbs.
Step-by-step instructions for the curb assembly and
installation with curb dimensions and curb configuration
for “A”, “B”, and “C” cabinets ship with each Trane
accessory roof curb kit. (See the latest edition of the curb
installation guide) Follow the instructions carefully to
assure proper fit when the unit is set into place.
The S/A and R/A ductwork adjoining the roof curb must be
fabricated and installed by the installing contractor b efore
the unit is set into place. Trane curbs include flanges
around the openings to accommodate duct attachment.
Ductwork installation recommendations are included in
the instruction booklet that ships with each Trane
accessory roof curb kit.
Note: For sound consideration, cut on ly the holes in the
roof deck for the supply and return duct
penetration. Do Not remove the roof decking from
the inside perimeter of the curb.
the unit into the ductwork. Refer to figures beginning on
page 14 for the S/A and R/A opening dimensions.
All outdoor ductwork between the unit and the structure
should be weather proofed after installation is completed.
If optional power exhaust is selected, an access door must
be field-installed on the horizontal return ductwork to
provide access to exhaust fan motors.
a. The ductwork can be attached directly to the S/A
and R/A openings. Be sure to use a flexible duct
connector at the unit.
b. For “built-up” curbs supplied by others, gask ets
must be installed around the curb perimeter flange,
Supply Air opening, and Return Air openings.
c. Insulation must be installed on the bottom of the
condenser section of the unit.
Horizontal Ductwork
When attaching the ductwork to a horizontal supply or
horizontal return unit, provide a water tight flexible
connector at the unit to prevent noise transmission from
14 RT-SVX34H-EN
Unit Dimensions and Weights
1 1/4
(32)
3 1/4
(81)
NOTES:
1. SEE DETAIL HOOD DRAWING FOR HORIZONTAL /
DOWNFLOW UNITS FOR ADDITIONAL DIMENSION
AND LOCATION.
179 3/4"
4565.65mm
42"
1066.8mm
83 13/16"
2128.8mm
90 1/16"
2287.5mm
180 5/16"
4579.9mm
90 3/8"
2295.5mm
5 3/8"
136.5mm
7 9/16"
192.1mm
3.25 [82.55mm] TO TOP OF FAN GRILLE
70 7/16"
1789.1mm
31.39"
797.3mm
6.91"
175.6mm
1 1/4" [31.7mm]
FEMALE
PVC PIPE
3/4" [19.0mm] NPT
GAS INLET
SEE NOTE 2
CUSTOMER
CONNECTION POINT
Figure 2.Rear view showing duct openings for horizontal supply and return, 60 Hz 27½-35, 50 Hz 23-29 Tons (TCH,
TEH, YCH low heat)
Notes:
•For combination of horizontal and downflow openings
•On horizontal units, the VFD is located between the
supply and return ductwork, which makes access
limited.
Figure 3.60 Hz 27½-35 , 50 Hz 23-29 T o ns (TC, TE, YC low heat)
(digit 3 = F or R) see Figure 1, p. 14 for appropriate
downflow/upflow dimensions and Figure 2, p. 15 for
appropriate horizontal dimensions.
•On horizontal units, the VFD is located between the
supply and return ductwork, which makes access
limited.
•For combination of horizont al and downflow openings
(digit 3 = F or R) see Figure 4, p. 16 for appropriate
downflow/upflow dimensions and Figure 5, p. 16 for
appropriate horizontal dimensions.
1. SEE ROOFCURB DRAWING FOR DETAILS
ON FIELD DUCT FITUP AND CONNECTIONS
2. SEE DETAIL HOOD DRAWING FOR HORIZONTAL /
DOWNFLOW UNITS FOR ADDITIONAL DIMENSION
AND LOCATION.
SEE NOTE 2
CUSTOMER
CONNECTION POINT
1066.8mm
2287.5mm
136.5m
192.1m
3.25 [82.55mm] TO
TOP OF FAN GRILLE
1789.1mm
797.3mm
175mm
1 1/4" [31.7mm]
Unit Dimensions and Weights
Note: Dimensions in ( ) are mm, 1”= 25.4 mm.
Figure 7.60 Hz 40-50, 50 Hz 33-42 Tons (TD, TD, YD low and high heat)
RT-SVX34H-EN17
Unit Dimensions and Weights
1 1/4
(32)
3 1/4
(81)
7 9/16"
232 3/8"
5902.3mm
232 3/4"
5911.8mm
90 5/8"
49 9/16"
1258.8mm
93 3/8"
2371.7mm
5 5/16"
90 1/16"
77"
1955.8mm
32.84"
834.2mm
4.66"
118.4mm
NOTES:
1. SEE ROOFCURB DRAWING FOR DETAILS
ON FIELD DUCT FITUP AND CONNECTIONS
2. SEE DETAIL HOOD DRAWING FOR HORIZONTAL /
DOWNFLOW UNITS FOR ADDITIONAL DIMENSION
AND LOCATION.
SEE NOTE 2
CUSTOMER
CONNECTION POINT
2301.8mm
PVC PIPE FEMALE
1" [25.4MM] NPT
HIGH HEAT GAS INLET
2287.5mm
136.5m
192.1m
3.25 [82.55mm] TO
TOP OF FAN GRILLE
1 1/4" [31.7mm]
3/4" [19MM] NPT
LOW HEAT GAS INLET
Figure 8.Duct openings, 60 Hz 40-50, 50 Hz 33-42 Tons (TH, TH, YH low and high heat)
Notes:
•On horizontal units, the VFD is located between the
supply and return ductwork, which makes access
limited.
•For combination of horizontal and downflow openings
(digit 3 = F or R) see Figure 7, p. 17 for appropriate
downflow/upflow dimensions and Figure 8, p. 18 for
appropriate horizontal dimensions.
Figure 9.60 Hz 40-50, 50 Hz 33-42 Tons (TC, TE, Y C low and high heat)
Note: Dimensions in ( ) are mm, 1”= 25.4 mm.
18RT-SVX34H-EN
Figure 10. Fresh air and power exhaust dimensions for TC*, TE*, and YC* units
Figure 11. Location of “Ship With” items for TC*, TE*, and YC* units
Unit Dimensions and Weights
RT-SVX34H-EN19
Unit Dimensions and Weights
Unit Rigging and Placement
WARNING
Heavy Objects!
Ensure that all the lifting equipment used is properly
rated for the weight of the unit being lifted. Each of the
cables (chains or slings), hooks, and shackles used to
lift the unit must be capable of supporting the entire
weight of the unit. Lifting cables (chains or slings) may
not be of the same length. Adjust as necessary for even
unit lift. Other lifting arrangements could cause
equipment or property damage. Failure to follow
instructions above or properly lift unit could result in
unit dropping and possibly crushing operator/
technician which could result in death or serious injury.
Use spreader bars as shown in the diagram. Refer to the
Installation manual or nameplate for un it weight. Refer to
the Installation instructions located inside the control
panel for further rigging information.
1. Verify that the roof curb has the proper gaskets
installed and is level and square to assure an adequate
curb-to-unit seal.
The units must be as level as possible in order to
assure proper condensate flow out of the unit. The
maximum side-to-side and end-to-end slope allowable
in any application is listed in Table 2, p. 20.
Table 1.Minimum operating clearances installation
(horizontal, downflow, and mixed airflow
configurations)
Recommended Clearances
Condenser
(a)
Coil
Single Unit
TC*, TE*, YC*
27.5 to 50 Tons
Multiple Unit
TC*, TE*, YC*
27.5 to 50 Tons
(a) Condenser coil is located at the end and side of the unit.
Economizer/
Exhaust End
6 Feet8 Feet4 Feet
Distance Between Units
Economizer/
Exhaust EndEnd/Side
12 Feet16 Feet8 Feet
Orientation
End/Side
Service Side
Access
Service Side
Access
Table 2.Maximum slope
Cabinet
“A” (27.5 - 35 Ton Low Heat) 3 1/21 5/8
“B” (27.5 - 35 Ton High Heat)41 5/8
“C” (All 40 and 50 Ton Units)4 1/21 5/8
Note: Do not exceed these allowances. Correct the improper slope by
building up the curb base. The material used to raise the base must
be adequate to support both the curb and the unit weight.
1. Point loading is identified with corner A being the corner with the compressors.
As you move clockwise around the unit as viewed from the top, mid-point B,
corner C, corner D, mid-point E and corner F.
2. Point load calculations provided are based on the unit weight for YC high heat
gas models.
Note: Basic unit weight includes minimum horsepower supply fan motor.
HGRH
Coil
Hail
Guards
Ultra
Low
Leak
Econ
Low
Leak
50%
Exhaust
Ultra Low
Leak
100%
Exhaust
High
Efficiency
(eStage)
Non-
Factory
GFI
with
Discon.
Switch
Roof CurbW/OWith
22RT-SVX34H-EN
Installation General Requirements
Condensate Drain Connection
Each commercial rooftop unit is equipped with one (1) 11/4 inch Female PVC condensate drain connection.
Refer to Figure 11, p. 19 for the location of the connector. A
condensate trap must be installed due to the drain
connection being on the “negative pressure” side of the
fan. Install a P-Trap at the unit using the guidelines in
Figure 14, p. 23.
Pitch the drain line at least 1/2 inch for every 10 feet of
horizontal run to assure proper condensate flow.
Ensure that all condensate drain line installations comply
with applicable building and waste disposal codes.
Notes:
•For units with optional Condensate Overflow Switch
(COF), the switch will not work properly if unit is not
level or slightly sloped toward switch.
•To ensure proper condensate flow during operation
the unit and the curb must be level.
Figure 14. Condensate trap installation
O/A Sensor & Tubing Installation
An Outside Air Pressure Sensor is shipped with all units
designed to operate on traditional variable air volume
applications (non-SZ VAV) and units with Statitrac™.
A duct pressure transducer and the outside air sensor is
used to control the discharge duct static pressure to w ithin
a customer -specified controlband. Refer to the illustration
in Figure 16, p. 24 and the following steps to install the
sensor and the pneumatic tubing.
1 . Remove the O/A pressure sensor kit located inside the
fan section. The kit contains the following items;
• an O/A static pressure sensor
• a sensor mounting bracket
• 50’ of 3/16” O.D. pneumatic tubing
• mounting hardware
2. Using two #10-32 x 1-3/4” screws provided, install the
sensor's mounting bracket to the factory provided
bracket (near the fan section).
3. Using the #10-32 x 1/2” screws provided, install the O/
A static pressure sensor vertically to the sensor
bracket.
4. Remove the dust cap from the tubing connector
located below the sensor in the vertical support.
5. Attach one end of the 50' x 3/16” O.D. factory provided
pneumatic tubing to the sensor's top port, and the
other end of the tubing to the connector in the vertical
support. Discard any excess tubing.
Units with Statitrac™
1. Open the filter access door, and locate the Statitrac
Transducer Assembly illustrated in Figure 17, p. 24.
There are two tube connectors mounted on the left of
the solenoid and transducers. Connect one end of the
Condensate Overflow Switch
This switch protects building from condensate overflow
damage. It is factory-installed and tested.
Figure 15. Condensate overflow switch location
RT-SVX34H-EN23
field provided 1/4” (length 50-100 ft.) or 3/8” (length
greater than 100 ft.) O.D. pneumatic tubing for the
space pressurization control to the fitting indicated in
the illustration.
2. Route the opposite end of the tubing to a suitable
location inside the building. This location should be
the largest open area that will not be affected by
sudden static pressure changes.
Installation General Requirements
LO
HI
CNO
NC
Sensing Tube
to Traq LO Side
Pressure Port
Airow
Transducer
Sensing Tube
to Traq HI Side
Pressure Port
Figure 16. Pressure tubing
Figure 17.Transducer assembly
Note: Statitrac and Traq transducer assembly shown.
Units ordered with the factory mounted disconnect switch
come equipped with an externally mounted handle. This
allows the operator to disconnect power from the unit
without having to open the control panel door . The handle
location and its three positions are shown below;
ON - Indicates that the disconnect switch is closed,
allowing the main power supply to be applied at the unit.
OFF - Indicates that the disconnect switch is open,
interrupting the main power supply at the unit.
OPEN COVER/RESET - Turning the handle to this position
releases the handle from the disconnect sw itch, allowing
the control panel door to be opened.
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote
disconnects before servicing . Follow proper lock out/
tagout procedures to ensure the power can not be
inadvertently energized. Failure to disconnect power
before servicing could result in death or serious injury.
Once the door has been opened, it can be closed with the
handle in any one of the three positions outlined above,
provided it matches the disconnect switch position. The
handle can be loc ked in the “OFF” position . While holding
the handle in the “OFF” position, push the spring loaded
thumb key, attac hed to the handle, into the base slot. Place
the lock shackle between the handle and the thumb key.
This will prevent it from springing out of position.
Figure 18. Disconnect switch
An overall layout of the field required power wiring is
illustrated in Figure 19, p. 26. To insure that the unit supply
power wiring is properly sized and installed, follow the
guidelines outlined below.
Note: All field installed wiring must conform to NEC
guidelines as well as State and Local codes.
Ve rify that the power supply available is compatible with
the unit's name plate ratings for all components. The
available power supply must be within 10% of the rated
voltage stamped on the nameplate. Use only copper
conductors to connect the 3-phase power supply to the
unit.
NOTICE:
Use Copper Conductors Only!
Unit terminals ar e not designed t o accept other types of
conductors. Failure to use copper conductors could
result in equipment damage.
Main Power Wiring
WARNING
Proper Field Wiring and Grounding
Required!
All field wiring MUST be performed by qualified
personnel. Improperly installed and grounded field
wiring poses FIRE and ELECTROCUTION hazards. To
avoid these hazards, y ou MUST follo w requir ements for
field wiring installation and grounding as described in
NEC and your local/state electrical codes. Failure to
follow code could result in death or serious injury.
1. Table 7, p. 27 to T a bl e 12, p. 29 list the electrical service
sizing data. The electrical service must be protected
from over current and short circuit conditions in
accordance with NEC requirements. Protection
devices must be sized according to the electrical data
on the nameplate. Refer to “Electrical Wire Sizing and
Protection Device Equations” on page 29 for
determining:
a. The appropriate electrical service wire size based
on “Minimum Circuit Ampacity” (MCA),
b. The “Maximum Over current Protection” (MOP)
device.
c. The “Recommended Dual Element fuse size” (RDE).
2. If the unit is not equipped with an optional factory
installed Nonfused disconnect switc h, a field supplied
disconnect switch must be installed at or near the unit
in accordance with the National Electrical Code (NEC
latest edition). Refer to DSS calculations
Wire Sizing and Protection Device Equations” on
page 29 for determining correct size.
“Electrical
RT-SVX34H-EN25
Installation Electrical
Location for the electrical service entrance is shown in
the unit dimensional drawings beginning with
Figure 1, p. 14. Complete the unit's power wiring
connections onto either the main terminal bloc k HTB1,
or the factory mounted nonfused disconnect switch
inside the unit control panel.
Note: When the factory installed through-the-base
option is not used, the installing contractor is
required to seal any ho les made in the base o f the
unit to prevent water from leaking into the building.
3. Provide proper grounding for the unit in accordance
with local and national codes.
Figure 19. Typical field power wiring
Through-the-Base Electrical (Optional
Accessory)
Liquid-tight conduit couplings are secured to the base of
the unit for both power and control wiring. Liquid-tight
conduit must be field installed between the couplings and
the unit control box to prevent water leaks into the
building.
Note: If the unit is set on the roof curb and temporary
auxiliary heat is provided in the building, it is
recommended that the electrical and control wiring
conduit opening in the control box be temporarily
sealed to provide a vapor barrier.
26 RT-SVX34H-EN
Installation Electrical
Table 7.27½-50 ton electrical serv ice sizing data—60Hz
1
Fan Motors
Compressor - Std
Efficiency
Electrical
Characteri
Model
TC/TE/
YC*330
TC/TE/
YC*360
TC/TE/
YC*420
TC/TE/
YC*480
TC/TE/
YC*600
Notes:
1. All customer wiring and devices must be installed in accordance with local and national electrical codes.
2. 100% Power Exhaust is with or without Statitrac™.
stics
208/60/3187-229
230/60/3207-253
460/60/3414-506
575/60/3517-633
208/60/3187-2292/1350.5
230/60/3207-2532/1350.5
460/60/3414-5062/1323.0
575/60/3517-6332/1319.0
208/60/3187-229
230/60/3207-253
460/60/3414-506
575/60/3517-633
208/60/3187-229
230/60/3207-253
460/60/3414-506
575/60/3517-633
208/60/3187-229
230/60/3207-253
460/60/3414-506
575/60/3517-633
Allowable
Voltage
Range
No/
Ton
1/12,
1/13
1/12,
1/13
1/12,
1/13
1/12,
1/13
1/13,
1/15
1/13,
1/15
1/13,
1/15
1/13,
1/15
1/13,
1/20
1/13,
1/20
1/13,
1/20
1/13,
1/20
2/13,
1/15
2/13,
1/15
2/13,
1/15
2/13,
1/15
RLA
(Ea.)
44.0/
50.5
44.0/
50.5
21.0/
23.0
17.5/
19.0
50.5/
56.0
50.5/
56.0
23.0/
27.5
19.0/
23.0
50.5/
83.9
50.5/
83.9
23.0/
34.0
19.0/
27.3
50.5/
56.0
50.5/
56.0
23.0/
27.5
19.0/
23.0
(Ea.)
Compressor - High
Efficiency, eStageSupplyCondenserExhaust
LRA
No/
RLA
LRA
(Ea.) H P FLA No HP
203,
267
203,
267
203,
267
203,
267
203,
304
203,
304
98,
147
84,
122
203,
315
203,
315
98,
158
84,
136
267,
345
267,
345
142,
155
103,
126
7.5
10.0
7.5
10.0
7.5
10.0
7.5
10.0
7.5
10.0
7.5
10.0
7.5
10.0
7.5
10.0
7.5
10.0
15.0
7.5
10.0
15.0
7.5
10.0
15.0
7.5
10.0
15.0
10.0
15.0
10.0
15.0
10.0
15.0
10.0
15.0
10.0
15.0
20.0
10.0
15.0
20.0
10.0
15.0
20.0
10.0
15.0
20.0
28.0,
37.1
28.0,
37.1
14.1,
16.8
12.2,
14.7
28.0,
40.9
28.0,
40.9
14.1,
18.6
12.2,
15.4
28.0,
44.9
28.0,
44.9
14.1,
19.2
12.2,
16.6
31.1,
50.5
31.1,
50.5
14.1,
23.0
11.5,
19.0
40.9,
56.0
40.9,
56.0
18.6,
27.5
15.4,
23.0
98, 142
84, 103
98, 142
84, 103
22.2
29.5
18.8
25.2
9.4
12.6
7.8
10.1
22.2
29.5
18.8
25.2
9.4
12.6
7.8
10.1
22.2
29.5
40.7
18.8
25.2
35.4
9.4
12.6
17.7
7.8
10.1
15.1
29.5
40.7
25.2
35.4
12.6
17.7
10.1
15.1
29.5
40.7
56.1
25.2
35.4
49.4
12.6
17.7
24.7
10.1
15.1
19.6
304/
315
304/
315
147/
158
122/
136
315/
315
315/
315
158/
158
136/
136
315/
351
315/
351
158/
197
136/
146
315/
485
315/
485
158/
215
136/
175
315/
351
315/
351
158/
197
136/
146
Ton
1/6,
2/9
1/6,
2/9
1/6,
2/9
1/6,
2/9
1/6,
2/10
1/6,
2/10
1/6,
2/10
1/6,
2/10
1/6,
2/11
1/6,
2/11
1/6,
2/11
1/6,
2/11
1/8,
2/13
1/8,
2/13
1/8,
2/13
1/8,
2/13
1/10,
2/15
1/10,
2/15
1/10,
2/15
1/10,
2/15
(Ea.)
50%100
FLA
(Ea.)
31.17.0 12 1.0 4.1
31.17.0 12 1.0 4.1
31.13.5 12 1.0 1.8
31.12.8 12 1.0 1.4
31.17.0 12 1.0 4.1
31.17.0 12 1.0 4.1
31.13.5 12 1.0 1.8
31.12.8 12 1.0 1.4
31.17.0 12 1.0 4.1
31.17.0 12 1.0 4.1
31.13.5 12 1.0 1.8
31.12.8 12 1.0 1.4
41.17.0 12 1.5 5.4
41.17.0 12 1.5 5.4
41.13.5 12 1.5 2.7
41.12.8 12 1.5 2.2
41.17.0 12 1.5 5.4
41.17.0 12 1.5 5.4
41.13.5 12 1.5 2.7
41.12.8 12 1.5 2.2
%
HP
FLA
(Ea.)No.
RT-SVX34H-EN27
Installation Electrical
Table 8.Electrical service sizing data — electric heat
module (electric heat only) — 60 Hz
Models: TE(D,H,F,R) 330—600 Electric Heat FLA
KW Heater
Nominal
Unit Size
(Tons)
27½-35
40- 50
Note: All FLA in this table are based on heater operating at 208, 240, 480,
Table 12. Electrical service sizing data — crankcase
heaters (heating mode only) — 50Hz
FLA Add
Nominal Unit Size
(Tons)
23 - 2911
33 - 4211
Unit Voltage
380415
Electrical Wire Sizing and
Protection Device Equations
To correctly size the main power wiring based on MCA
(Minimum Circuit Ampacity), use the appropriate
equation listed below. Read the definitions that follow and
then use Calculation #1 for determining MCA (Minimum
Circuit Ampacity), MOP (Maximum Over current
Protection), and RDE (Recommended Dual Element fuse
size) for TC (Cooling Only) units and Y C (Cooling with Gas
Heat) units. Use Calculation #2 for TE (Cooling with Electric
Heat) units.
Load Definitions:
•LOAD 1 = CURRENT OF THE LARGEST MOTOR
(Compressor or Fan Motor)
•LOAD 2 = SUM OF THE CURRENTS OF ALL
REMAINING MOTORS
•LOAD 3 = FLA (Full Load Amps) OF THE ELECTRIC
HEATER
•LOAD 4 = ANY OTHER LOAD RATED AT 1 AMP OR
MORE
•CRANKCASE HEATERS FOR HEATING MODE ONLY:
• 208/230 VOLT
– 27.5 - 35 Ton Units, Add 1 Amp
– 40 - 50 Ton Units, Add 2 Amps
MCA = (1.25 x Load 1) + Load 2 + Load 4
MOP = (2.25 x Load 1) + Load 2 + Load 4 (See Note 1)
RDE = (1.5 x Load 1) + Load 2 + Load 4 (See Note 2)
Calculation # 2 - TE*-27.5 to 50 Ton Units
A. Single Source Power (all voltages)
T o calculate the correct MCA (Minimum Circuit Ampacity),
MOP (Maximum Over current Protection), and RDE
(Recommended Dual Element fuse size), two (2) sets of
calculations must be performed;
1 . Calculate the M CA, MOP and/or RDE values using th e
above equation as if the unit is operating in the cooling
mode.
2. Calculate the MCA, MOP and/or RDE values as if the
unit is operating in the heating mode, as follows:
Note: When determining loads, the compressors and
condenser fan motors do not operate during the
heating cycle.
Units with less than 50 KW Heaters
MCA = 1.25 x (Load 1 + Load 2 + Load 4) + (1.25 x Load 3)
Units with 50 KW or Larger Heaters
MCA = 1.25 x (Load 1 + Load 2 + Load 4) + Load 3
The MCA value stamped on the nameplate is the largest of
the two calculated values.
MOP = (2.25 x Load 1) + Load 2 + Load 3 + Load 4 (See Note
1)
The MOP value stamped on the nameplate is the largest of
the two calculated values.
RDE = (1 .5 x Load 1) + Load 2 + Load 3 + Load 4 (See Note 2)
Note: Select an over current protection device equal to
the MOP value. If the calculated MOP value does
not equal a standard size protection device listed in
NEC 240-6, select the next lower over current
protection device. If the calculated MOP value is
less than the MCA value, select the lowest over
current protection device whic h is equal to or larger
than the MCA, providing the selected over current
device does not exceed 800 amps.
Note: Select a Dual Element Fuse equal to the RDE value.
If the calculated RDE value does not equal a
standard dual element fuse size listed in NEC 2406, select the next higher fuse size. If the calculated
RDE value is greater than the MOP value, select a
Dual Element fuse equal to the calculated MOP
(Maximum Over current Protection) value
RT-SVX34H-EN29
Installation Electrical
Disconnect Switch Sizing (DSS)
Calculation A. - YC*, TC*, and TE* Units:
DSS = 1.15 X (LOAD1 + LOAD2 + LOAD4)
For TE* units, use calculations A and B.
Calculation B. - TE* Units:
DSS = 1 .15 X (LO AD3 + Supply Fan FLA + Exhaust
Fan FLA).
Use the larger value of calculations A or B to size the
electrical disconnect switch.
Low Voltage Wiring
An overall layout of the var ious c ont rol opti ons avai lable
for a Constant Volume application is illustrated in
Figure 20, p. 32andFigure 21, p. 33 illustrates the various
control options for a V ariable Air Volume application. The
required number of conductors for eac h control device are
listed in the illustration.
A typical field connection diagram for the sensors and
other options are shown in the following section “Remote
Panels and Se nsors”. These diagrams are representative of
standard applications and are provided for general
reference only. Always refer to the wiring diagram that
shipped with the unit for specific electrical schematic and
connection information.
Note: All field wiring must conform to NEC guidelines as
well as state and local codes.
Control Power Transformer
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote
disconnects before servicing . Follow proper lock out/
tagout procedures to ensure the power can not be
inadvertently energized. Failure to disconnect power
before servicing could result in death or serious injury.
The 24 volt control power transformers are equipped with
internal circuit breakers. They are to be used only with the
accessories called out in this manual. If a circuit breaker
trips, be sure to turn off all power to the unit before
attempting to reset it.
On units equipped with the VFD option, an additional
control power transformer is used. The secondary is
protected with fuses. Should the fuse blow, be sure to turn
off all power to the unit before attempting to replace it.
Field Installed AC Control Wiring
WARNING
Proper Field Wiring and Grounding
Required!
All field wiring MUST be performed by qualified
personnel. Improperly installed and grounded field
wiring poses FIRE and ELECTROCUTION hazards. To
avoid these hazards, y ou MUST follo w requir ements for
field wiring installation and grounding as described in
NEC and your local/state electrical codes. Failure to
follow code could result in death or serious injury.
NOTICE:
Use Copper Conductors Only!
Unit terminals ar e not designed t o accept other types of
conductors. Failure to use copper conductors could
result in equipment damage.
Before installing any connecting wiring, refer to Table 13,
p. 30for conductor sizing guidelines and;
• Use copper conductors unless otherwise specified.
• Ensure that the AC control voltage wiring between
the controls and the unit's termination point does
not exceed three (3) ohms/conductor for the length
of the run.
Note: Resistance in excess of 3 ohms per conduct or may
cause component failure due to insufficient AC
voltage supply.
• Refer to dimensional information beginning with
Figure 1, p. 14 for the electrical access locations
provided on the unit.
• Do not run the AC low voltage wiring in the same
conduit with the high voltage power supply wiring.
Be sure to check all loads and conductors for grounds,
shorts, and miswiring. After cor recting any discrepancies,
reset the circuit breakers by pressing the black button
located on the left side of the transformer.
Table 13. AC conductors
Distance from unit to controlRecommended wire size