Trane Vertical Stack WSHP Catalogue

Product Catalog
Water Source Heat Pump
Axiom™ High Efficiency Vertical Stack — GET
¾–3Tons—60 Hz
November 2013
WSHP-PRC020D-EN

Introduction

The 3/4-ton through 3-ton vertical high-rise water-source heat pump is a floor mounted, “furred-
in” unit, designed to be hidden from view behind drywall to blend with the room’s natural decor. In multi-story buildings, the units may be stacked one on top of the other to minimize piping and electrical costs.Supply, return and condensate riser piping may be factory mounted to simplify job site installation of the equipment.
The high-rise configuration is often used in hotels, dorms and assisted living facilities where a
single unit could provide comfort to a single or multiple room dwelling. Because the units are mounted directly in the space, ductwork is optional.
All water-source heat pumps are commissioned, tested and quality certified prior to leaving the factory.This assures global quality standards from controls, water, refrigeration, and aesthetics to the building owner and installing contractor.
Key features of the water-source, vertical stack heat pump include:
1. Removable/replaceable chassis 8.
2. Ducted and free discharge cabinet selections available
3.
Factory mounted flow control with strainer and isolation valve option
4. Plug-in chassis and plug-in thermostat design 12. Auxiliary drain pan
5. Factory supplied riser options 13. Rust resistant chassis drain pan
6. Maintenance accessibility for coil fin cleaning 14. Intelligent controls Extra quiet design includes enhanced and deluxe sound
7. proofing choice
Through the front high and low pressure service ports accessible
9. Tamper proof hinged acoustical door option
10. Unit mounted switch and fuse option
11. Lower height cabinet for ducted applications
Refrigeration Control TXV
Water-Out Connection
Water-In Connection
Auxiliary Drain Pan
Refrigeration Section Completely Enclosed
Chassis Rails
Trademarks
Axiom, ReliaTel,TOPSS,Tracer,Trane, and theTrane logo are trademarks or registered trademarks ofTrane in the United States and other countries.Trane is a business of Ingersoll Rand. All trademarks referenced in this document are the trademarks of their respective owners.
LonTalk is a registered trademark of Echelon Corporation.
BACnet is a registered trademarks. All trademarks referenced in this document are the trademarks of their respective owners.
Revision Summary
WSHP-PRC020D-EN (09 November 2013): Performance Data (Efficiency Upgrades);WPRD Chassis
© 2013Trane All rights reserved WSHP-PRC020D-EN
Table of Contents
Introduction ......................................................2
Features and Benefits ..............................................4
Application Considerations ..........................................7
Selection Procedures ..............................................13
Model Number Descriptions ........................................14
General Data .....................................................16
Performance Data ................................................ 17
Unit Fan Performance .............................................38
Electrical Data ....................................................42
Dimensional Data .................................................43
Controls ........................................................51
Water-Source Vertical High-Rise ................................. 2
Deluxe 24V Electronic Controls ................................. 51
Deluxe 24V features include: ................................... 51
Tracer ZN510 functions include: ................................ 53
Thermostats and Zone Sensors .....................................55
Accessories ......................................................56
Mechanical Specifications ..........................................57
WSHP-PRC020D-EN 3

Features and Benefits

Unit Description
The vertical high-risewater-source heat pumpis a floor mounted configuration available in a ¾ ton,
1 ton, 1¼ ton, 1½ ton, 2 ton and 3 ton sizes.
The unit cabinet may be ordered for early shipment to aid in early installation of drywall, plumbing
and electrical. See “Model Number Descriptions,” p. 14.The cabinet design is available in either an 88-inch height (free discharge) or 80-inch height (ducted) configuration. As many as 3 supply-air discharges are available for the 1¼ ton-3 ton, free discharge cabinets to provide multiple supply­air through one unit.
Air distribution is made through a rigid bar type extruded aluminum grille mounted to the sheetrock. It is both durable and attractive in design.
The return-air panel is a hinged acoustical door, see Figure 1, p. 4.The door allows for easy access
to the unit’s filter and for maintenance of the equipment.
The hinged acoustical panel provides greater sound attenuation, and is mounted flush to the wall. This panel is easily removed for filter maintenance or chassis removal through the magnetic catch
door. An optional tamper proof latch is available on the hinged door design to impede access if required.
Figure 1. Return-air flush mounted hinged door
Blower/Motor Assembly
The unit’s blower/motor assembly includes double width, double inlet (DWDI) blower with direct
drive PSC motor or optional ECM motor for improved efficiency and power factor. It may be easily removed for cleaning or service after removal of the unit chassis.The PSC motor is a multi-speed design, factory wired to high speed or low speed (order specific).The tap will be wired and capped inside the unit control box for easy field convertibility.The ECM motor is programmed to provide four constant CFM profiles and is shipped on Profile B – the rated CFM of the unit.To change the PSC speed tap or the ECM CFM profile, see installation manualWSHP-SVX03*-EN for instructions.
Controls
Standard controls include a 24V, micro-processor Deluxe controller for a wall-mounted thermostat option.The thermostat is typically placed above the return-air door. Even though the thermostat is considered to be unit mounted, the thermostat is mounted to the dry-wall that covers the front of the unit.
4 WSHP-PRC020D-EN
Features and Benefits
Thermostat selections are provided in the “Thermostats and Zone Sensors,” p. 55 section of the
catalog.They are available in manual or automatic changeover options.
The deluxe controller includes relays for: anti-short cycle compressor protection, random start
delay, brown-out protection low pressure time delay, compressor delay on start and night setback control.These extended control features offer greater system performance to extend the equipment’s life.
Figure 2. Deluxe control box
TheTracer™ ZN510 controller (option) is provided on the vertical stack design for direct digital
control (DDC) systems.This controller offers the building owner innovative ways to optimize heating and cooling energy for the building. Faults and sensors include: random start delay, heating/cooling status, occupied/unoccupied mode, and fan/filter status.
Figure 3. ZN510 control box
TheTracer™ Loop Controller (TLC) may be added to either the Deluxe controls or the ZN510
controls to maintain system loop operation. See WMCA-IOP-1 for more information on the TLC.
The ZN510 controller may also be applied with theTracker and Summit building management
systems to further enhance system operation.
Non-fused switch and fused entrance block may be factory added to the equipment to save installation time of these components in the field where local building codes allow.
Deluxe 24V Electronic Controls
General alarm is accomplished through the lockout relay and is usedto drive light emitting diodes.
This feature will drive dry contacts only, and may not be used to drive field installed control inputs.
Factory Installed Flow Control
Optional factory mounting of the isolation valve and flow control valves is available to speed field equipment installation, and help provide optimum water flow balancing support.
Refrigeration Section
The unit’s compressor is a highly efficient, hermetically sealed with internal vibration isolation.
External isolation is provided between the compressor and mounting plate tohelp reduce radiated noise that is typically associated with compressor start.
The air-to-refrigerant coil is easily accessible for cleaning purposes behind the unit’s removable
return-air door/panel.
The water-to-refrigerantcoil is acopper or cupro-nickel (option)co-axial tube-within-a-tube design. The inner-water tube is deeply fluted to enhance heat transfer and minimize fouling and scaling. The outer refrigerant gas tube is made from steel material.The coil is leak tested to assure there
WSHP-PRC020D-EN 5
Features and Benefits
is no cross leakage between the water tube and the refrigerant gas (steel tube) coil.The ½” (009/ 012/015/018) and ¾”(024/036) threaded water connections to the water-coil are available on the exterior chassis top.A flexible hose connectionwith shut-off istypically used between the riser and water-coil in/out connections on the chassis to reduce water vibration.
The refrigerant flow metering is made through a thermal expansion valve (TXV).TheTXV allows
the unit to operate with an entering fluid temperature from 25°F to 120°F, and an entering air temperature from 40°F to 90°F.The valve precisely meters refrigerant flow through the circuitry to achieve desired heating or cooling.
Unlike cap-tube assemblies, theTXV allows the exact amount of refrigerant required to meet the coil load demands.This precise metering increases the over-all efficiency of the unit.
The unit’s reversing valve is piped to be energized in the cooling mode. All vertical high-rise units
ship in a heat pump configuration with a system reversing valve.
Supply/Return/Condensate Risers
Supply, return and condensate risers are available as a factory mounted and shipped option.The risers are constructed from type L or M copper.The top of each riser is swaged to accept the same size diameter riser from above.This helps facilitate installation of the water supply, return and condensate to and from the unit. Insulation may be factory installed or field installed per order selection.The insulation helps keep moisture from forming on the pipes and damaging building construction.
The riser length may be ordered as standard in 96” to 120” lengths. See “Equipment Risers,” p. 9
for riser application information.
Unit Safety
All unit safety devices are provided to help prevent compressor damage. Low pressure switch and high pressure switch are added to help protect the compressor operation under a low charge (40 psig) or during high discharge (650 psig) pressures. In cases where a low charge, or excessive loss of charge occurs, each compressorcomes equipped withan overload device tohalt the compressor operation.
A safety lockout provides the mechanical communication of the low and high pressure switches to prevent compressor operation if the unit is under low or high refrigerant pressures, or during a condensate overflow condition.The lockout relay may be reset at the thermostat, by cycling power to the unit or through a LonTalk™ front end device (ZN510 control option).
6 WSHP-PRC020D-EN

Application Considerations

Advantages of Geothermal
The advantages of a geothermal heat pump system can literally decrease heating and cooling
operating costs by 30%-40%.The units are durable, and typically last longer than conventional systems.They are protected from harsh outdoor weather conditions, because the unit is installed indoors and the loop underground. According to ASHRAE, the estimated service life for a commercial water-to-air heat pump is 19 years.
Geothermal heat pumps have fewer mechanical components, making them more reliable and less prone to failure.
Geothermal heat pumps work toward the preservation of the environment by reducing the environmental impacts of electric power generation.
Flexibility
The vertical, high-rise water-source heat pump system is versatile for installation in boiler/cooling
tower applications, as well as ground-source (geothermal) applications.The system typically employs a central pumping design.The central pumping design involves a single pump design, usually located within a basement or mechanical room to fulfill pumping requirements for the entire building system. An auxiliary pump is typically applied to lessen the likelihood of system downtime if the main pump malfunctions.
Furring-In the Unit
The vertical high-rise water-source heat
pump is designed to be a furred-in application. Dry-wall (sheetrock) is attached to furring studs (not unit cabinet) until the entire cabinet, exceptthe front access panel, is enclosed. Access to the unit is made entirely through thefront panel which spans approximately one-half of the unit height.
The dry-wall enclosure allows the unit to
blend in with the decor of the room. If renovations are needed, the drywall portion of the unit can simply be re-papered or repainted with the remainder of the room.
With careful design, the high-riseWSHP can
be incorporated into a room design, while occupying minimum floor space.
WSHP
WSHP
WSHP
Cooling Tower
Boiler
WSHP
WSHP
WSHP
Expansion Tank
Water Storage Tank
WSHP
WSHP
WSHP
Central Pumps
Water t o Water Heat Pump
To Fresh Air Ventilation System
Installation Tips
When installing a high-rise water-source heat pump, there are specific installation requirements
that should be taken into consideration.These include:
Noise control
Riser location
Furring-in the unit
Sound Attenuation
The high-rise heat pump is better suited for acoustically sensitive water-source heat pump
applications than other water-source products. Compressor and water noise are attenuated by the filter panel, sheet rock and the acoustically lined door. Air noise is silenced through the extended and insulated duct portion at the top of the vertical cabinet.
WSHP-PRC020D-EN 7
Application Considerations
Figure 4. Installation illustration
Equipment Installation
The vertical high-rise unit is versatile in design to fit numerous applications. It is typically applied
to dorm rooms, hotels and motels where multiple supply air configurations may be required for individual tenantheating and cooling.The equipment requires little space, and is tucked away from sight, and rough handling.The vertical stack design is economical to install, requiring no ductwork for air supply.The riser design may be stacked one on top of another for multi-story applications, or shared between two units (see example B) when architectural design permits. Because the chassis is removable, serviceability to the equipment is enhanced. If service does become a requirement, the chassis is simple to remove from the cabinet, replaced with a back-up chassis, then repaired off-site at a convenient time.
RSD
R
A
SINGLE SUPPLY CORNER SET-UP
SD
B
SINGLE SUPPLY PRIMARY/SECONDARY SET-UP
RSD
C
DUAL SUPPLY DIVIDING WALL SET-UP
8 WSHP-PRC020D-EN
Application Considerations
Equipment Risers
The riser provides an easy way to facilitate the water flow
through a multi-story building and the high-rise heat pump.The high-rise heat pump is best applied to a building with identical zones on each floor, and zones that are typically small. An example building might include a hotel, dorm, condominium or assisted living facility. With these types of buildings, the riser column (external to the unit cabinet) can be stacked one on top of the other.The piping installation for the entire HVAC system becomes very simple to install because it is pre-measured, and pre-fabricated at the factory.
Factory risers are available asType K (design special), L (standard design), and M (standard design).The differences between these types of materials is the wall thickness of the copper. Table 1, p. 9 shows the wall thickness for the most common diameters ofrisers. Itis recommended formost jobs to use type L or Mcopper.Type Krisers are generally notnecessary for most high-rise heat pump applications.
The riser design contains threaded stubouts to facilitate
connection of the supply and return risers to the hose kits.The hose kits are then connected to the water-in/out of the unit’s chassis.
Note: Supply/return/drain risers that are ordered and supplied
through the factory may be ordered as insulated.
Drain risers aregenerallymade of typeM copper.If copper, drain risers are used, the risers should be insulated since the typical temperatures of condensate may cause the riser to sweat.
Table 1. Riser characteristics
Type K (special design)
Riser Size (in.) I.D. (in.) O.D. (in.) Copper Wall Thickness (in.)
1 0.995 1.125 0.065 1¼ 1.245 1.375 0.065 1½ 1.481 1.625 0.072
2 1.959 2.125 0.083 2½ 2.435 2.625 0.095
3 2.907 3.125 0.109
Type L (standard)
1 1.025 1.125 0.05 1¼ 1.265 1.375 0.055 1½ 1.505 1.625 0.06
2 1.985 2.125 0.07 2½ 2.465 2.625 0.08
3 2.945 3.125 0.09
Type M (standard)
Riser Size (in.) I.D. (in.) O.D. (in.) Copper Wall Thickness (in.)
1 1.055 1.125 0.035 1¼ 1.291 1.375 0.042
WSHP-PRC020D-EN 9
Application Considerations
Table 1. Riser characteristics (continued)
Riser Size (in.) I.D. (in.) O.D. (in.) Copper Wall Thickness (in.)
1.527 1.625 0.049
2.495 2.625 0.065
Note: Pressure ratings for risers are typically greater than the maximum pressure rating of the
coaxial water-to-refrigerant heat exchangers.This is true with exception ofType M copper in a 3" diameter.The maximum pressure rating forType M, 3" diameter copper is 380 psig. All other diameters forType M copper, and all 1" through 3"Type L copper are greater than the 400 psig rating on the coaxial water-to-refrigerant heat exchanger.
Riser Sizing
The proper selection of riser diameter is critical when designing a cost effective job. If the riser
diameter is too small, the flow of water to the heat pump may be restricted, making the pumping power requirement excessive. On the other hand, if the riser diameter is too large, the cost of the equipment may become unnecessarily high.
To determine the riser size, calculate the flow at a particular riser. Riser columns will begin with
large diameters at the bottom of the column and decrease diameter as the water travels up toward the top floor.The GPM at the first floor is determined by totaling the GPM of all the units on the riser column.The GPM for the second floor is then determined by taking the total GPM and subtracting the flow from the first floor.
The proper size of the riser is determined by calculating the velocity of the water in the riser.The
maximum water velocity that a riser should experience is about 6 or 7 feet/second. Table 2, p. 10 can be used as a quick reference chart fordetermining the maximum GPMallowed for a given riser size. Riser flow diagram can be found in the used to calculate the precise water velocity for a given riser diameter and flow.
Type M (standard)
2 2.009 2.125 0.058
3 2.981 3.125 0.072
2009 ASHRAE Fundamentals Handbook and may be
Table 2. Maximum riser flow rate
Riser Size (in.) Max. GPM Water Velocity (ft./sec.) Head Loss (ft.100 ft.)
1 16 6.2 15.6 1¼ 24 6.1 11.8 1½ 34 6.1 9.38
2 58 6.0 6.6 2½ 90 6.0 5.1
3 130 6.1 4.2
Note: Table 2, p. 10 is for general design calculation reference. It is not intended to take the place
of an engineered piping design.
10 WSHP-PRC020D-EN
Application Considerations
Riser Size Example
Assume a sixstory building is servedby a high-rise water-source heat pump.When referencing the catalog, determine each high­rise heat pump uses 3 gallons per minute to meet the required capacity of the 1-ton unit. What is the minimum riser diameter that can be used on each floor?
With this arrangement, determine the volume of water used at each floor is 3 GPM.The top floor riser therefore only needs to be sized for 3 GPM. Referring to Table 2, p. 10, we know that a 1­inch type M riser can handle up to 16 GPM, therefore the riser size is determined to be 1-inch.
The first floor will see 18 GPM through the riser. Since 18 GPM
will result in more than 6 ft./second in a 1” riser, it would be advisable to move to a 1¼” riser.
Piping Layout of the Riser
Two methods may be used when piping a riser column.These
include direct return or reverse return.
Advantages may be seen in both types of piping methods. For
a direct return installation, the riser system is straightforward leaving little confusionabout properly sized risers.Thisprovides a more cost effective advantage during the installation process.
The disadvantages of this system is the pressure drop.The total
pressure drop on the unit forthe sixth floor ismuch greater than the total pressure drop on the unit for the first floor.This means that the riser column will require balancing from floor-to-floor during installation.
Piping advantages for the reverse return system include the ability to design the riser column so that the total system pressure drop through each unit is equalized.The overall pressure drop is also lower, allowing some energy savings potential.This piping method however does not eliminate the need for proper balancing at each unit.
The disadvantage of this system relates to cost and complexity. The reverse return method typically costs more because of the
additional pipe required for each riser column.
Central Plant Control
Proper central plant control is critical to the operation of a water-source heat pump system. Loss of waterflow or loop temperatures outside of the recommended range will severely impact the operation of the equipment.The following should be followed as minimum operational recommendation for the central plant:
Heat rejector control (i.e. closed circuit cooling tower, or geothermal loop)
Heat adder (i.e. boiler or geothermal loop)
Circulating pumps
Sensing elements
WSHP-PRC020D-EN 11
Application Considerations
Heat Rejection through a Closed Circuit CoolingTower
Cooling towers serve to reject heat from the condenser water loop to the atmosphere.Two types of cooling towers are used with water-source heat pump systems: open or closed-circuit.The towers themselves are different, but when an open tower is used in conjunction with a water-to­water heat exchanger, the control of the two tower types is essentially the same.
Control for the closed-circuit cooling towers may be made with aTrane®Tracer™ Loop Controller (TLC). With the TLC, up to four stages of cooling tower control are possible.
When the loop supply temperature is 4°F below the loop supply high setpoint, the first stage of
cooling is initiated by opening the closure dampers on the cooling tower.
At 2° F below the setpoint the next stage of cooling is initiated which is the starting of the tower’s
circulating pump. If the amount of heat rejected by the first two stages is not enough, the loop temperature will continue to rise.When the temperature reaches the loop supply high setpoint,the next stage of cooling is initiated.This is the first stage of cooling tower fans.
The differential between the stages now become 3°F and the temperature must remain above the
differential for three minutes. Up to three individual fan stages may be sequenced or the second stage of fan can be the high speed of a multi-speed motor.
There are five different fan arrangements that theTLC supports: A single fan with a single motor,
a single fan with dual motors (pony motors), a maximum of three fans with a maximum of three motors, a variable speed fan with a field supplied variable frequency drive, and a single multi­speed motor.
Multiple cooling towers can be supported only if the cooling towerstages are controlled in parallel.
Boiler Operation
TheTLC will operate a boiler and the mixing valve respectively. Boiler control is traditionally
controlled by a separate boiler controller, provided by the boiler manufacturer.The boiler mixing valve will control the mixture of the boiler water into the main loop to achieve the desired loop supply water.
When the loop temperature falls below the low loop-supply setpoint, theTLC enables the boiler.
The ideal arrangementis for the boiler tohave its own bypass loopso the boiler pump can circulate
water through the heat exchanger. The boiler will maintain the temperature of the water to the desired setting in the packaged boiler control.
The three-way mixing valve is controlled by theTLC to add heat to themain loopby mixingin water
from the boiler loop. A proportional-integral-derivative algorithm controls the valve. The boiler is not disable until the main loop temperature is 5°F greater than the low loop supply setpoint for more than 5 minutes.
TheTLC will also monitor the boiler loop temperature and provide an alarm if the temperature is
below the boiler loop low limit after 30 minutes of run time.The TLC will provide an alarm if the boiler loop temperature exceeds the boiler loop high limit after 30 minutes continually.
Facilities Management
Water-source heat pump systems are naturally decentralized; thus they inherently provide
individual zone control.Typical installations use mechanical thermostats to provide localized control. Central plant control is typically handledby a control panel located in the main mechanical room. Minimal coordination is usually required between the central plant and the individual water­source heat pumps for successful operation of the system. A direct digital control system is recommended to help support coordination efforts between the central plant and the individual water-source heat pumps.This enhanced coordination can result in reductions in operating cost of the entire system.The following items are typical of the additional coordination: Night setback and setup; After hourusage for tracking and billing;Pump cycling foroccupied/unoccupied control; Zone scheduling; Maintenance reporting for monitoring unit fault conditions;Trend logging of the system water temperatures;Monitoring of systemlevels for items such as waterflow, temperature, faults, heat rejector status, heat adder status and circulating pump status.
12 WSHP-PRC020D-EN

Selection Procedures

Model Number
Two model number designators have been defined for the cabinet configuration, and the chassis
configuration. Both model numbers require input for the order to be complete and built to specification.
Typically the vertical stack equipment ships in two sections. (1)The cabinet and riser section ship
first to allow the contractor to furr-in the equipment during sheetrock installation, and (2) the chassis (refrigeration/water) section ship approximately two to four weeks later eliminating storage requirements of the chassis and possible damage at the job site while waiting for installation. For this reason, there are two model number designators specific to the unit chassis, and the cabinet for the equipment.
WSHP-PRC020D-EN 13

Model Number Descriptions

Vertical High-Rise Cabinet WSHP
Digits 1-3: Unit Configuration
GET = High Efficiency Vertical High Rise
Heat Pump
Digit 4: Development Sequence
E = R-410A
Digits 5-7: Nominal Size (Tons)
009=¾Tons 012=1Tons 015=1¼Tons 018=1½Tons 024 = 2Tons 036 = 3Tons
Digit 8: Voltage (Volts/Hz/Phase)
1 = 208/60/1 2 = 230/60/1 7 = 265/60/1
Digit 9: Heat Exchanger
1 = Copper Water Coil 2 = Cupro-Nickel Water Coil 3 = Copper Water Coil with Isolation
Valve and Low Flow Control
4 = Cupro- Nickel Water Coil with
Isolation Valve and Low Flow Control
5 = Copper Water Coil with Isolation
Valve and High Flow Control
6 = Cupro-Nickel Water Coil with Isolation
Valve and High Flow Control
Digit 10: Current Design Sequence
Digit 11: Refrigeration Circuit
0 = Heating and Cooling Circuit
Digit 12: Blower Configuration
1 = Free Discharge - PSC motor 2 = Ducted Discharge - PSC motor 3 = Free Discharge w/1" Flange -
PSC motor
4 = Free Discharge w/3" Flange -
PSC motor 5 = ECM motor w/o flange 6 = ECM motor w/1" flange 7 = ECM motor w/3" flange 8 = Chassis only/No motor (ECM Control) 9 = Chassis only/No motor (PSC Control)
Digit 13: Freeze Protection
A = 20° freezestat B = 35° freezestat
Digit 14: Open Digit
0 = Open S = Special
Digit 15: Supply Air Arrangement
0 = No Supply Air Arrangement 1 = Back and Front Supply Air 2 = Back and Left Supply Air 3 = Back and Right Supply Air 4 = Front and Left Supply Air 5 = Front and Right Supply Air 6 = Left and Right Supply Air 7 = Back, Front and Right Supply Air 8 = Back, Front and Left Supply Air 9 = Front, Right and Left Supply Air B = Back Supply Air L = Left Supply Air R = Right Supply Air
T =Top Supply Air
F = Front Supply Air
Digit 16: Return Air Arrangement
0 = No Return Air Door (Field Provided) 1 = Flush with Wall, Acoustic Hinged
Return Air Door with Keyless Entry
2 = Flush with Wall, Acoustic Hinged
Return Air Door with Keylock Entry
Digit 17: Control Types
D = Deluxe 24V Controls C =Tracer™ ZN510 Controls
Digit 18:Thermostat Sensor Location
0 = Wall Mounted Location
Digit 19: Fault Sensors
0 = No Fault Sensors 1 = Condensate Overflow Sensor 2 = Filter MaintenanceTimer 3 = Condensate Overflow and Filter
MaintenanceTimer
Digit 20-22: Open Digits
Digit 23: Unit Mounted Disconnect
0 = No Unit Mounted Switch C =Toggle Switch Only D =Toggle Switch with Fuses
Digit 24: Filter Type
1 = 1-inch Throwaway Filter
Digit 25: Acoustic Arrangement
0 = Enhanced Sound Attenuation 1 = Deluxe Sound Attenuation
Digit 26: Factory Configuration
3 = R-410A Cabinet
Digit 27: Paint Color
8 = Polar White
Digit 28: Outside Air Option
0 = No Outside Air
Digit 29: Piping Arrangement
B = Back Riser Location L = Left Hand Riser Location R = Right Hand Riser Location
Digit 30: Riser Type
0 = No Riser L =Type L Riser M=Type M Riser
Digit 31: Supply Riser
0 = No Riser B = 1" Dia. Riser with Insulation C = 1¼" Dia. Riser with Insulation D = 1½" Dia. Riser with Insulation E = 2 Dia. Riser with Insulation F = 2½" Dia. Riser with Insulation G = 3" Dia. Riser with Insulation 2 = 1" Dia. Riser 3 = 1¼" Dia. Riser 4 = 1½" Dia. Riser 5 = 2" Dia. Riser 6 = 2½" Dia. Riser 7 = 3" Dia. Riser
Digit 32: Return Riser
0 = No Riser B = 1" Dia. Riser with Insulation C = 1¼" Dia. Riser with Insulation D = 1½" Dia. Riser with Insulation E = 2" Dia. Riser with Insulation F = 2½" Dia. Riser with Insulation G = 3" Dia. Riser with Insulation 2 = 1" Dia. Riser 3 = 1¼" Dia. Riser 4 = 1½" Dia. Riser 5 = 2" Dia. Riser 6 = 2½" Dia. Riser 7 = 3" Dia. Riser
Digit 33: Condensate Riser
0 = No Riser B = 1" Dia. Riser with Insulation C = 1¼" Dia. Riser with Insulation D = 1½" Dia. Riser with Insulation E = 2" Dia. Riser with Insulation F = 2½" Dia. Riser with Insulation G = 3" Dia. Riser with Insulation 2 = 1" Dia. Riser 3 = 1¼" Dia. Riser 4 = 1½" Dia. Riser 5 = 2" Dia. Riser 6 = 2½" Dia. Riser 7 = 3" Dia. Riser
14 WSHP-PRC020D-EN
Model Number Descriptions
Digit 34, 35, 36: Riser Length
000 = No Riser 096 = 96" Riser Length 097 = 97" Riser Length 098 = 98" Riser Length 099 = 99" Riser Length 100 = 100" Riser Length 101 = 101" Riser Length 102 = 102" Riser Length 103 = 103" Riser Length 104 = 104" Riser Length 105 = 105" Riser Length 106 = 106" Riser Length 107 = 107" Riser Length 108 = 108" Riser Length 109 = 109" Riser Length 110 = 110" Riser Length 111 = 111" Riser Length 112 = 112" Riser Length 113 = 113" Riser Length 114 = 114" Riser Length 115 = 115" Riser Length 116 = 116" Riser Length 117 = 117" Riser Length 118 = 118" Riser Length 119 = 119" Riser Length 120 = 120" Riser Length
Vertical High-Rise Chassis WSHP
Digits 1-3: Unit Configuration
GET = High Efficiency Vertical High Rise Heat Pump (cabinet with blower/motor)
Digit 4: Development Sequence
E = R-410A
Digits 5-7: Nominal Size (Tons)
009=¾Tons 012=1Tons 015=1¼Tons 018=1½Tons 024 = 2Tons 036 = 3Tons
Digit 8: Voltage (Volts/Hz/Phase)
1 = 208/60/1 2 = 230/60/1 7 = 265/60/1
Digit 9: Heat Exchanger
1 = Copper Water Coil 2 = Cupro-Nickel Water Coil 3 = Copper Water Coil with Isolation
Valve and Low Flow Control
4 = Cupro- Nickel Water Coil with Isolation
Valve and Low Flow Control
5 = Copper Water Coil with Isolation
Valve and High Flow Control
6 = Cupro-Nickel Water Coil with Isolation
Valve and High Flow Control
Digit 10: Current Design Sequence
Digit 11: Refrigeration Circuit
0 = Heating and Cooling Circuit
Digit 12: Blower Configuration
1 = Free Discharge - PSC motor 2 = Ducted Discharge - PSC motor 3 = Free Discharge w/1" Flange -
PSC motor
4 = Free Discharge w/3" Flange -
PSC motor 5 = ECM motor w/o flange 6 = ECM motor w/1" flange 7 = ECM motor w/3" flange 8 = Chassis only/No motor (ECM Control) 9 = Chassis only/No motor (PSC Control)
Digit 13: Freeze Protection
0 = None or Standard A = 20° Freezestat B = 35° Freezestat
Digit 14: Open Digit
0 = Open
Digit 15: Supply Air Arrangement
0 = No Supply Air Arrangement 1 = Back and Front Supply Air 2 = Back and Left Supply Air 3 = Back and Right Supply Air 4 = Front and Left Supply Air 5 = Front and Right Supply Air 6 = Left and Right Supply Air 7 = Back, Front and Right Supply Air 8 = Back, Front and Left Supply Air 9 = Front, Right and Left Supply Air B = Back Supply Air L = Left Supply Air R = Right Supply Air
T =Top Supply Air
F = Front Supply Air
Digit 16: Return Air Arrangement
0 = No Door (Chassis Only) 1 = Flush with Wall, Acoustic Hinged
Return Air Door with Keyless Entry 2 = Flush with Wall, Acoustic Hinged
Return Air Door with Keylock Entry
Digit 17: Control Types
0 = Basic Controls for WPRD Retrofit
Chassis D = Deluxe 24V Controls C =Tracer™ ZN510 Controls
Digit 18:Thermostat Sensor Location
0 = Wall Mounted Location
Digit 19: Fault Sensors
0= No Fault Sensors 1 = Condensate Overflow Sensor 2 = Filter Maintenance Timer 3 = Condensate Overflow and Filter
MaintenanceTimer
Digit 20-22: Open Digits
Digit 23: Unit Mounted Disconnect
0 = No Unit Mounted Switch C = Switch Only D = Switch with Fuses
Digit 24: Filter Type
1 = 1-inch Throwaway Filter
Digit 25: Acoustic Arrangement
0 = Enhanced Sound Attenuation 1 = Deluxe Sound Attenuation
Digit 26: Factory Configuration
2 = R-410A Chassis R = WPRD Retrofit Chassis
Digit 27: Paint Color
8 = Polar White
Digit 28: Outside Air Option
0 = No Outside Air
Digit 29: Piping Arrangement
B = Back Riser Location L = Left Hand Riser Location R = Right Hand Riser Location
Digit 30: Riser Type
0 = No Riser (Chassis Only)
Digit 31: Supply Riser
0 = No Riser (Chassis Only)
Digit 32: Return Riser
0 = No Riser (Chassis Only)
Digit 33: Condensate Riser
0 = No Riser (Chassis Only)
Digit 34, 35, 36: Riser Length
000 = No Riser (Chassis Only)
WSHP-PRC020D-EN 15

General Data

Table 3. General Data
Model Number 009 012 015 018 024 036
Compressor Type Rotary Rotary Rotary Rotary Scroll Scroll
Cabinet Size Depth (in.)
Height (in.)
Depth (mm)
Height (mm)
Width (mm)
Approximate weight
cabinet with Pallet (lb.)
Approximate weight
cabinet without Pallet (lb.)
Approximate weight
chassis with Pallet (lb.)
Approximate weight
chassis without Pallet (lb.)
Face Area (ft.2)
Face Area (cm2)
Air-to-Refrigerant Coil
Fins Per Inch
Fins Per cm.
Nominal 1”
Filter Size
Water In/Out size NPTI
Condensate Plastic Hose ID (in)
Riser Connection NPTE
PSC Ducted Discharge
PSC Free Discharge
ECM Motor
Refrig. Side (PSIG)
Water-to-Refrigerant
Coil Water Side (PSIG)
Internal Volume
Width (in.)
Rows
Inches
mm
Blower
Motor HP
Blower
Motor HP
Blower
Motor HP
(gal)
16.0 16.0 18.0 18.0 24.0 24.0
88.0 88.0 88.0 88.0 88.0 88.0
16.0 16.0 20.0 20.0 24.0 24.0
406.4 406.4 457.2 457.2 609.6 609.6
2235.2 2235.2 2235.2 2235.2 2235.2 2235.2
406.4 406.4 508.0 508.0 609.6 609.6
135 135 175 175 225 225
115 115 150 150 195 195
88 107 112 117 174 190
78 97 102 107 164 180
1.35 1.35 2.11 2.11 2.88 2.88
1254 1254 1959 1959 2676 2676
244 4 3 4
14 14 14 14 14 14
5.5 5.5 5.5 5.5 5.5 5.5
14 x 20 14 x 20 18 x 25 18 x 25 20 x 30 20 x 30
356 x 508 356 x 508 457 x 635 457 x 635 508 x 762 508 x 762
½" ½" ½" ½" ¾" ¾" ¾" ¾" ¾" ¾" ¾" ¾" ½" ½" ½" ½" ¾" ¾"
90-6TDD 90-6TDD 90-6RDD 100-6TDD 100-6TDD 120-8TDD11
0.05 0.125 0.125 0.2 0.33 0.5
90-6TDD 90-6TDD 90-6RDD 100-6TDD 100-6TDD 120-8TDD11
0.05 0.125 0.125 0.125 0.33 0.5
90-6TDD 90-6TDD 100-6TDD 100-6TDD 120-8TDD11 120-8TDD11
0.33 0.33 0.5 0.5 0.5 0.75 650 650 650 650 650 650
400 400 400 400 400 400
0.081 0.081 0.228 0.228 0.271 0.368
16 WSHP-PRC020D-EN

Performance Data

Table 4. AHRI-ISO performance
Rated
Flow Rate
Unit Size
GET 009 2.1 340 8200 12.8 10800 4.6 9700 18.4 8700 3.8 8800 14.9 6600 3.2 GET 012 2.8 440 11900 13.5 14100 4.6 13100 18.9 11800 4.0 12300 15.1 9000 3.2 GET 015 3.5 540 14700 13.1 17700 4.6 16600 20.1 13700 3.7 15400 14.8 11800 3.3 GET 018 4.2 650 18100 13.0 22900 4.5 19500 18.0 17900 3.7 18700 14.3 14800 3.3 GET 024 5.6 820 23300 13.1 26600 4.3 25600 18.6 23600 3.9 24300 14.9 18700 3.2 GET 036 8.4 1170 33700 13.0 41300 4.3 37900 18.7 34400 3.7 35100 14.6 27300 3.2
GET 009 2.1 340 8300 13.9 10500 4.6 9600 21.1 8500 3.9 8700 16.2 6500 3.2 GET 012 2.8 440 12000 14.2 14300 4.8 14100 23.2 11600 4.0 12600 16.5 8700 3.2 GET 015 3.5 540 14900 15.0 18000 5 17000 23.9 14800 4.3 15600 17.5 11300 3.5 GET 018 4.2 650 18500 14.6 22300 4.6 21100 22.6 18400 4.2 19500 17 14200 3.4 GET 024 5.6 820 24200 16.0 26300 4.8 26800 24 23100 4.4 25200 18.4 17800 3.5 GET 036 8.4 1170 34200 15.2 40200 4.6 38200 24 33500 4.1 35600 17.8 26300 3.3
Note: Certified in accordance with AHRI Water to Air and Brine to Air Heat Pump Certification Program which is based on ISO Standard 13256-1: 1998.
(GPM)
Certified conditions are 80.6°F DB/66.2°F WB EAT in cooling and 68°F DB/59°F WB EAT in heating.
Rated
Air
Flow
(CFM)
Cooling
Capacity
(Mbtuh) EER
Water Loop Ground Water Ground Loop
Heating
Capacity
(Mbtuh) COP
Cooling
Capacity
(Mbtuh) EER
PSC Motor
ECM Motor
Heating
Capacity
(Mbtuh) COP
Cooling
Capacity
(Mbtuh) EER
Heating
Capacity
(Mbtuh) COP
Table 5. GET 009 cooling performance
EWT GPM
45 1.1 10.3 8.0 0.77 11.7 0.41 65.7 2.1 45 1.5 10.4 8.0 0.77 11.8 0.40 60.7 3.4 45 1.8 10.5 8.0 0.76 11.9 0.39 58.2 4.7 45 2.1 10.6 8.1 0.76 12.0 0.39 56.4 6.2 45 2.3 10.8 8.1 0.75 12.1 0.39 55.7 6.9 45 2.4 10.8 8.1 0.75 12.1 0.39 55.1 7.8 45 2.6 10.8 8.1 0.75 12.2 0.39 54.3 9.1 55 1.1 9.8 7.8 0.79 11.3 0.44 75.1 2.0 55 1.5 10.0 7.9 0.79 11.4 0.42 70.2 3.3 55 1.8 10.1 7.9 0.78 11.5 0.42 67.8 4.5 55 2.1 10.2 7.9 0.78 11.6 0.41 66.0 5.9 55 2.3 10.2 7.9 0.78 11.6 0.41 65.3 6.7 55 2.4 10.2 7.9 0.78 11.6 0.41 64.7 7.5 55 2.6 10.3 8.0 0.77 11.7 0.41 63.9 8.7 68 1.1 9.4 7.7 0.82 11.1 0.49 87.7 1.9 68 1.5 9.5 7.7 0.81 11.1 0.47 82.8 3.1 68 1.8 9.6 7.7 0.81 11.1 0.46 80.4 4.3 68 2.1 9.6 7.7 0.80 11.2 0.46 78.6 5.6 68 2.3 9.6 7.8 0.80 11.2 0.45 77.9 6.4 68 2.4 9.7 7.8 0.80 11.2 0.45 77.3 7.1 68 2.6 9.7 7.8 0.80 11.2 0.45 76.5 8.3 75 1.1 9.2 7.6 0.83 11.0 0.53 94.5 1.8 75 1.5 9.3 7.6 0.82 11.0 0.51 89.7 3.1
(Mbtuh)
Total Gross
Gross Sen
(Mbtuh) SHR
Heat of Rej
(Mbtuh)
Comp Pwr
(kW) LWT
WPD
(feet head)
WSHP-PRC020D-EN 17
Performance Data
Table 5. GET 009 cooling performance (continued)
EWT GPM
75 1.8 9.3 7.7 0.82 11.0 0.49 87.2 4.2 75 2.1 9.4 7.7 0.82 11.0 0.49 85.5 5.5 75 2.3 9.4 7.7 0.82 11.0 0.48 84.8 6.2 75 2.4 9.4 7.7 0.82 11.1 0.48 84.2 7.0 75 2.6 9.4 7.7 0.82 11.1 0.48 83.4 8.2 77 1.1 9.1 7.6 0.83 11.0 0.54 96.5 1.8 77 1.5 9.2 7.6 0.83 11.0 0.52 91.6 3.0 77 1.8 9.3 7.6 0.82 11.0 0.51 89.2 4.2 77 2.1 9.3 7.7 0.82 11.0 0.50 87.5 5.5 77 2.3 9.3 7.7 0.82 11.0 0.49 86.8 6.2 77 2.4 9.3 7.7 0.82 11.0 0.49 86.2 6.9 77 2.6 9.3 7.7 0.82 11.0 0.49 85.4 8.1 86 1.1 8.9 7.5 0.85 10.9 0.60 105.4 1.8 86 1.5 8.9 7.5 0.84 10.9 0.57 100.5 3.0 86 1.8 9.0 7.5 0.84 10.9 0.56 98.1 4.1 86 2.1 9.0 7.6 0.84 10.9 0.55 96.4 5.3 86 2.3 9.0 7.6 0.84 10.9 0.55 95.7 6.0 86 2.4 9.0 7.6 0.84 10.9 0.54 95.0 6.7 86 2.6 9.0 7.6 0.84 10.9 0.54 94.3 7.9 95 1.1 8.6 7.4 0.86 10.9 0.67 114.4 1.7 95 1.5 8.7 7.5 0.86 10.8 0.64 109.5 2.8 95 1.8 8.7 7.5 0.86 10.8 0.62 107.0 3.8 95 2.1 8.7 7.5 0.86 10.8 0.61 105.3 5.1 95 2.3 8.7 7.5 0.86 10.8 0.61 104.6 5.7 95 2.4 8.7 7.5 0.86 10.8 0.61 104.0 6.4
95 2.6 8.7 7.5 0.86 10.8 0.60 103.2 7.5 105 1.1 8.4 7.4 0.88 10.9 0.76 124.4 1.6 105 1.5 8.4 7.4 0.88 10.8 0.72 119.5 2.7 105 1.8 8.4 7.4 0.88 10.8 0.71 117.0 3.7 105 2.1 8.4 7.4 0.88 10.8 0.70 115.2 4.9 105 2.3 8.4 7.4 0.88 10.8 0.69 114.6 5.5 105 2.4 8.4 7.4 0.88 10.7 0.69 113.9 6.2 105 2.6 8.4 7.4 0.88 10.7 0.69 113.2 7.3 115 1.1 8.1 7.3 0.90 11.0 0.86 134.6 1.6 115 1.5 8.1 7.3 0.90 10.9 0.83 129.6 2.6 115 1.8 8.1 7.3 0.90 10.9 0.81 127.1 3.6 115 2.1 8.1 7.3 0.90 10.8 0.80 125.3 4.8 115 2.3 8.1 7.3 0.90 10.8 0.80 124.6 5.4 115 2.4 8.1 7.3 0.90 10.8 0.79 124.0 6.1 115 2.6 8.1 7.3 0.90 10.8 0.79 123.2 7.1 120 1.1 8.0 7.3 0.91 11.2 0.94 139.9 1.6 120 1.5 8.0 7.2 0.91 11.0 0.90 134.7 2.6 120 1.8 8.0 7.2 0.91 11.0 0.88 132.2 3.6 120 2.1 8.0 7.2 0.91 10.9 0.87 130.4 4.7
(Mbtuh)
Total Gross
Gross Sen
(Mbtuh) SHR
Heat of Rej
(Mbtuh)
Comp Pwr
(kW) LWT
WPD
(feet head)
18 WSHP-PRC020D-EN
Loading...
+ 42 hidden pages