T rane vertical stack fan coil units are used in high-rise hotels, condominiums, dormitories, military
barracks, and residential buildings. Trane specializes in flexible response to customers’ needs.
We work closely with engineers at the design stage to ensure optimum use of the units within the
HVAC system.
Figure 1.Fan coil - Model RSGFigure 2.Furred-in f a n coil
18 ga. galvanized cabinet with acoustical liner
Direct-drive centrifugal fan - PSC fan motor
with sealed bearings standard
Piping package factory installed (HW pre-
heat)
CW/HW coils - 2-pipe or 4-pipe
Drain pan - galvanized, positively sloped to
outlet - standard
Optional electric heater (behind panel)
Optional electrical box for unit-mounted
The following is a complete description of
the vertical stack fan coil model number.
Each digit in the model number has a
corresponding code that identifies
specific unit options. Example of model
number:
RS-GF05-86MKX-WWX-R1PDABCDEFGA
Digits 1, 2 – Finished Goods
Identifier
Must always be “RS”
Digit 3 – Spacer
Digits 4, 5 – Unique Part
Identifier - Reserved
Must always be “GF”
Digits 6, 7 – Cabinet Footprint
05 = 17-in. x 17-in. Cabinet footprint (350
and 450 CFM models)
08 = 20-in. x 20-in. Cabinet footprint (600
and 800 CFM models)
12 = 20-in. x 24-in. Cabinet footprint (1000
and 1200 CFM models)
Digit 8 – Spacer
Digits 9, 10 – Unique Part
Identifier - Reserved
Must always be digits “86”
Digits 11, 12, 13 – Unique Part
Identifier – Reserved
P = PSC
D = ECM (Discrete speed)
V = ECM (Variable Speed)
Digit 22 – Water Coil and Fins
Per Inch (FPI)
Note: X/Y format, where X = Number of
Cooling rows and Y = Number of
Heating rows. Function (cooling
only, changeover, etc) is handled
in positions 15 and 16 of the model
number.
3 row coils
K = 3/0 (2-pipe), 12 FPI
L = 3/1 (4-pipe), 12 FPI
M = 3/2 (4-pipe), 12 FPI
N = 3/0 (2-pipe), 14 FPI
P = 3/1 (4-pipe), 14 FPI
Q = 3/2 (4-pipe), 14 FPI
4-row coils
U = 4/0 (2-pipe), 12 FPI
V = 4/1 (4-pipe), 12 FPI
W = 4/2 (2-pipe), 12 FPI
X = 4/0 (2-pipe), 14 FPI
Y = 4/1 (4-pipe), 14 FPI
Z = 4/2 (4-pipe), 14 FPI
Digit 23 – Chilled Water Piping
Packages
Note: Manual air vent, drain cock,
flexible braided hoses and unions
on supply and return are standard
features. Control valves are
mounted on coil return.
A = 2-way control valve, shutoff valves on
supply and return
B = 3-way control valve, shutoff valves on
supply and return
C = 2-way control valve, shutoff valve on
supply, manual balancing valve with
shutoff on return.
D = 3-way control valve, shutoff valve on
supply, manual balancing valve with
shutoff on return.
E = 2-way control valve, combo strainer/
shutoff valve on supply, manual
balancing valve with shutoff on return
F = 3-way control valve, combo strainer/
shutoff valve on supply, manual
balancing valve with shutoff on return
G = 2-way control valve, combo strainer/
shutoff valve on supply, automatic
balancing valve with shutoff on return
H = 3-way control valve, combo strainer/
shutoff valve on supply, automatic
balancing valve with shutoff on return
Digit 24 – Hot Water Piping
Packages
Note: Manual air vent, drain cock,
flexible braided hoses and unions
on supply and return are standard
features. Control valves are
mounted on coil return.
A = 2-way control valve, shutoff valves on
supply and return
B = 3-way control valve, shutoff valves on
supply and return
C = 2-way control valve, shutoff valve on
supply, manual balancing valve with
shutoff on return.
D = 3-way control valve, shutoff valve on
supply, manual balancing valve with
shutoff on return.
E = 2-way control valve, combo strainer/
shutoff valve on supply, manual
balancing valve with shutoff on return
F = 3-way control valve, combo strainer/
shutoff valve on supply, manual
balancing valve with shutoff on return
G = 2-way control valve, combo strainer/
shutoff valve on supply, automatic
balancing valve with shutoff on return
H = 3-way control valve, combo strainer/
shutoff valve on supply, automatic
balancing valve with shutoff on return
Digit 25 – Electric Heat
Note: Must operate at supply voltage,
subject to cabinet size and airflow.
0 = No Electric Heating Coil
A = 0.75 kW
B = 1.0 kW
C = 1.5 kW
D = 2.0 kW
E = 2.5 kW
F = 3.0 kW
G = 3.5 kW
H = 4.0 kW
J = 4.5 kW
K = 5.0 kW
M = 6.0 KW
P = 7.0 KW
R = 8.0 KW
Digit 26 – Control Type
(Provided and installed by factory unless
otherwise noted)
0 = Low-voltage control by Others,
Installed by Others, Terminal Strip
provided.
A = Auto Changeover, NonProgrammable, Fan Speed Switch
B = Auto Changeover, Programmable, Fan
Speed Switch
C = Auto Changeover, NonProgrammable, No Fan Speed Switch
D = Auto Changeover, Programmable, No
Fan Speed Switch
E = Manual Changeover, NonProgrammable, Fan Speed Switch
F = Manual Changeover, Programmable,
Fan Speed Switch
UNT-PRC019-EN5
Model Number Description
G = Manual Changeover, NonProgrammable, No Fan Speed Switch
H = Manual Changeover, Programmable,
No Fan Speed Switch
1 = Tracer™ ZN521 (zone sensor ordered
separately)
2 = Tracer™ UC400 (zone sensor ordered
separately)
Digit 27 – Actuator Operation
(Provided and installed by factory unless
otherwise noted)
0 = None, Low Voltage, installed by
others, outside of unit
C = Control Contractor Supplied, Low
Voltage, installed by factory
L = Line Voltage, 2-position
B = 24 V 2-position (normally closed
spring return)
F = 3-Wire Floating Point
M = 0-10 or 2-10 V Modulating
For a 2-pipe system:
First character: Use to describe the
cooling supply and return (or
heating supply and return)
Second character: Enter “X”
Third character: use to describe
condensate
First character: Use to describe
cooling supply and return.
Second character: Use to describe
heating supply and return.
Third character: Use to describe
condensate.
Raised Base Package
Digit 1, 2, 3, 4 – Raised Base
Package
Must always be “YRBP”
Digit 5 – Spacer
Digit 6 – Unit Foot Print
1 = 350/450 (17 in. x 17 in.)
2 = 600/800 (20 in. x 20 in.)
3 = 1000/1200 (24 in. x 20 in.)
Digit 7, 8 – Raised Base Height
04 = 4 inches
08 = 8 inches
12 = 12 inches
Digit 9 – Access Panel**
0 = None
1 = Yes, front
Digit 10 – Condensate Pump*
(Voltages are connection
voltages)
0= Double deflection, horizontal front
blades with mounting clips
1 = Double deflection, horizontal front
blades with mounting holes
Digit 8, 9 – Height**
XX = round inches
Digit 10 – Color/Finish
W = Nailorhart White
C = Custom color
Note: * Mounting holes are on front
flange of supply grille.
Note: ** Dimensions given for nominal
frame size. These correspond to
the nominal unit opening.
Table 1.Return Air Gr ille Part
Numbers
Return Air Panel Type
Flush MountedFSM 0145XAFSM 0145XB
Hinge MountedGRS 14152WGRS 16154W
Flush MountedFSM 0145XACFSM 0145XBC
Hinge MountedGRS 14152CGRS 16154C
Size 350/450/600/800Size 1000/1200
Standard White
Custom Color
Table 2.Register/Grille Quick
Reference
Nominal
Size
14 x 5GSS 14005WGSR 14005WGSS 14105WGSR 14105W
14 x 8GSS 14008WGSR 14008WGSS 14108WGSR 14108W
14 x 10GSS 14010WGSR 14010WGSS 14110WGSR 14110W
14 x 12GSS 14012WGSR 14012WGSS 14112WGSR 14112W
14 x 14GSS 14014WGSR 14014WGSS 14114WGSR 14114W
16 x 12GSS 16012WGSR 16012WGSS 16112WGSR 16112W
16 x 14GSS 16014WGSR 16014WGSS 16114WGSR 16114W
Note: For custom color grille, replace “W” with “C” at the end of the part number.
Registers and grilles are only available in the sizes list ed in this table.
GrillesRegistersGrillesRegisters
ClipsScrew Holes
Filters
Table 3.Filter Part Numbers
Filter Part Numbers
Size 1000/1200
16 x 25 nominal size
FRX 14125FRX 16125
Filter Type
Pleated - MERV 13FPH 14125FPH 16125
Throwaway Wire Frame - for Units with
Throwaway Cardboard Frame - for Units
Note: All filters are 1-inch thick.
Pleated - MERV 10FPY 14125FPY 16125
Hinged Access Panel
with Flush Mounted Access Panel
Size 350/450/600/800
14 x 25 nominal size
FWX 14125AFWX 16125
UNT-PRC019-EN7
Performance Data
Cooling Capacities
AHRI-certified cooling performance is based on ANSI/AHRI Standard 440-2008: Performance
Rating of Room Fan-Coils: 80/67°F entering air temperature, 45°F entering chilled water
temperature with a 10°F delta T. All performance measured on high speed tap using a 120 V AC
motor, 0.05 inches ESP without filters or grilles.
Table 4.AHRI-certified rating s for cooling capacities
Heating performance is based on 70°F entering air temperature, and listed entering water
temperatures. All performance data measured on high speed tap using a 120 V AC motor, 0.05
inches ESP without filters and grilles. 1-row and 2-row coils are in the preheat configuration as part
of a 4-pipe system. 3-row and 4-row coils are only available as part of a 2-pipe system.
Note: Sound level is measured at a distance of 8 ft. from the return air grille. Measurements are for a typical furnished and
carpeted hotel suite. CFM in the above chart is approximate. Airflow is dependent on the number of coil rows, coil fins
per inch, the amount of condensate on the fins, supply voltage, motor manufacturer, supply air configuration, filter
cleanliness and altitude.
•The heater is located in the reheat position relative to the cooling coil.
•The fan coil unit does not include a fuse or fusible type disconnect. Motor sub-fusing as per
electrical code.
Amps = Watts
Volts
Air temp. rise (Delta T) = kW x 3160
= MBH x 925
CFMCFM
S.A. = Supply Air
FLA = Full Load Amps
= S.A. fan motor Amps + Electric Heater Amps
MCA = Minimum Circuit Ampacity
= FLA x 1.25
MOP = Rating of maximum overcurrent protection device
= (2.25 x S.A. fan motor Amps) + Electric Heater Amps
UNT-PRC019-EN11
Components and Options
Requirements of Standards: UL 1995 and CSA C22.2 No.236
•If the value of the calculated rating does not equal a standard current rating of overcurrent
protective device, the mark ed maximum rating shall be the next lower standard rating.
•Exception No. 1: The marked maximum rating of the overcurrent protective device shall be the
standard rating next higher than the computed value if the next lower standard ratings is less
than 125 percent of the current rating of an electric heater load, when the unit includes an
electric heater.
•Exception No. 2: if the computed value of the overcurrent protective device is less than the
minimum ampacity of the supply circuit, the marked rating of the device shall be increased to
the largest standard overcurrent protective device rating appropriate for the marked minimum
circuit ampacity.
•Exception No. 3: If the marked minimum circuit ampacity does not correspond to a standard
protective device rating, the next higher standard rating of the protective device may be
marked.
12 UNT-PRC019-EN
Fans Curves
0
0.1
0.2
0.3
0.4
0.5
0100200300400
External Static Pressure (in. wg.)
Supply Air Volume (SCFM)
Medium
Low
6 Row
5 Row
4 Row
3 Row
0
0.1
0.2
0.3
0.4
0.5
200300400500600
External Static Pressure (in. wg.)
Supply Air Volume (SCFM)
High
Medium
Low
6 Row
5 Row
4 Row
3 Row
Components and Options
Figure 3.Unit size 350
High
Figure 4.Unit size 450
UNT-PRC019-EN13
Components and Options
0
0.1
0.2
0.3
0.4
0.5
300400500600700
External Static Pressure (in. wg.)
Supply Air Volume (SCFM)
High
Medium
Low
6 Row
5 Row
4 Row
3 Row
0
0.1
0.2
0.3
0.4
0.5
300400500600700800
External Static Pressure (in. wg.)
Supply Air Volume (SCFM)
High
Medium
Low
6 Row
5 Row
4 Row
3 Row
Figure 5.Unit size 600
Figure 6.Unit size 800
14 UNT-PRC019-EN
Figure 7.Unit size 1000
0.5
0.4
Components and Options
Low
0.3
0.2
0.1
External Static Pressure (in. wg.)
6 Row
5 Row
4 Row
3 Row
0
600700800900100011001200
Figure 8.Unit size 1200
0.5
0.4
Low
0.3
Medium
Medium
High
Supply Air Volume (SCFM)
High
0.2
External Static Pressure (in. wg.)
5 Row
4 Row
3 Row
6 Row
0.1
0
8009001000110012001300
Supply Air Volume (SCFM)
Fan curves are based on 120V AC PSC motor at high, medium and low fan speed settings. The
following test conditions apply:
•Centrifugal direct drive fan with double inlet and forward curved impeller.
•Cooling coil is dry.
•One-inch throwaway filter is clean.
UNT-PRC019-EN15
Components and Options
Motor Data
Table 8.Motor data
Size
350
450
600
800
1000
1200
Note: EC motors have been programmed for three (3) discrete speed operation. Variable speed also available (not shown.) Motor nameplate data is show n
in table. Fan motors are single phase and have a minimum of three speeds. Trane has several fan motor suppliers in order to ensure availability . Amp
draws may differ between motors from different manufacturers. Trane reserves the right to change motor HP and therefore amp draws without notice
Connection Voltage
Volts/ph/Hz
120V/1/601/201.21/34.8
208-240V/1/601/140.61/32.8
277V/1/601/120.61/32.6
120V/1/601/61.71/34.8
208-240V/1/601/120.81/32.8
277V/1/601/120.61/32.6
120V/1/601/62.61/34.8
208-240V/1/601/120.81/32.8
277V/1/601/120.61/32.6
120V/1/601/62.61/34.8
208-240V/1/601/61.41/32.8
277V/1/601/60.91/32.6
120V/1/601/44.61/34.8
208-240V/1/601/42.21/32.8
277V/1/601/41.61/32.6
120V/1/601/36.41/26.8
208-240V/1/601/33.11/24.1
277V/1/601/32.11/23.6
Max. Plate RatingsMax. Plate Ratings
HPAmpsHPAmps
PSCECM
Control Packages
T rane offers a range of standard thermostats and controllers for the vertical stack fan coil units. For
applications where a larger BAS is to be installed, T rane can provide factory mounting of the ZN521
or UC400 controllers.
Thermostats
Table 9.Thermostat information
Thermostat
VoltageManufacturerModel
24HoneywellTB8575A1000Automatic or Manual User Selectable3
24HoneywellTB7100A10001Automatic or Manual User Selectable3Residential
120/208/240HoneywellTB6575A1000Automatic or Manual User Selectable3
1. The Honeywell TB7100A1000 is a 7-day programmable thermostat.
2. The HotelTech thermostats feature automatic fan speed switching between the available speeds and off. The thermostat selects speed based on
deviation of the room temperature from set point. The occupant can also manually select between the available speeds.
Heat/Cool
ChangeoverFan Operation
Available Fan
SpeedsApplication
Residential or
Hospitality
Residential or
Hospitality
16 UNT-PRC019-EN
Residential applications include: Condominiums, apartments, student residences/dormitories,
assisted living/retirement facilities, and military barracks.
T rane recommends the remote mounting of low voltage (24V) thermostats to achieve optimal zone
control. When thermostats are remote mounted, a terminal strip is provided inside the unit for field
connection to the remote thermostat. Unit mounting of thermostat is also available, however all
thermostats are shipped loose for field installation after the unit is installed, drywall is applied and
the walls are painted.
The standard standalone thermostats listed above cycle a two position (on/off) valve and feature
discrete speed fan speed operation. If modulating (0-10V DC or 3-wire floating point) valve
actuators or modulating or 0-10V DC EC motors are a requirement, a thermostat or controller with
the necessary analog outputs must be used.
Tracer ZN521 Zone Controller
The T racer ZN521 is a factory-installed LonTalk® control board designed to provi de control of th e
fan-coil products (see Figure 9).
Figure 9. Tracer ZN521 controller
Components and Options
Features include:
•Automatic fan-speed reset
•Automatic ventilation reset
•Manual output test
•Filter maintenance
•Master slave
•Water valve override
•Freeze avoidance
•Interoperability
•Three generic I/O ports
The Tracer ZN521 controller is designed to be used in the following applications:
•As part of the T rane T racer Summit building automation system, the T racer ZN521 becomes an
important part of the Trane Integrated Comfort system (ICS).
•The Tracer ZN521 can function as a completely standalone controller in situations where a
building automation system (BAS) is not present.
•For situations when a non-T rane BAS is present, the T racer ZN521 can be where ever a LonT alk
front-end system is present.
Through building management of the HVAC system, optimizing energy consumption becomes
possible at a zone level. Each unit is capable of functioning independently of one another during
occupied and unoccupied hours of the day. This allows the temperature setpoint and ventilation
setting to be changed automatically based on zone usage (see Figure 10).
UNT-PRC019-EN17
Components and Options
Fan
coil
Fan
coil
To other
building products
To other
Trane products
Security
system
Rover™
(optional)
Tracer
Summit®
System
Lighting
system
Fire safety
system
Figure 10. Tracer ZN521 System
Two Systems in One
In an ICS environment, the Tracer ZN521 is pre-designed to install quickly and easily into the
system. Since the controller is mounted on the unit, the start-up time for the entire system is
minimized. T rane becomes the single source of responsibility for the equipment, unit controls, and
building automation system.
Once power is applied to the controller, it will automatically start up and run based upon the
setpoint on the local zone sensor. The Tracer ZN521 is certified to the interoperable L
Space Comfort Controller profile. This allows the controller to be used with another vendor’ s BAS
and thereby still provide the high quality of factory installation. In addition, the Tracer ZN521
provides one of the most extensive interoperable data lists of any controller of its type in the
industry.
Automatic Fan and Ventilation Reset
With the Tracer ZN521 controller, a multi-speed fan control for the fan coil delivers the airflow
output customized to support the cfm space needs. When less cfm is necessary to meet the load
of the zone (typically 75 to 80 percent of the time), the equipment operates on low speed. However,
if the room temperature rises, the controller will switch to high speed.
18 UNT-PRC019-EN
Manual Output Test
The T racer ZN521 controller includes a manual output test function. This function may be initiated
from the blue test push button on the controller or through the Rover™ service tool. This feature
is used to manually exercise the outputs in a defined sequence.
The purpose of this test sequence is to verify output and end device operation. The manual output
test function may also be used in the following situations:
•Reset latching diagnostics
•Verify output wiring and operation
•Force the water valve(s) open to balance the hydronic system during installation set-up or
service.
ONMARK
®
Components and Options
Filter Maintenance
Filter status for the controller is based on the cumulative run hours of the unit fan. The controller
compares the amount of fan run time against an adjustable fan run hour (stored in the controller)
to determine when maintenance is recommended for the unit. The run-hours value may be user
edited as required (through Rover). The valid range for the fan run hours limit is 0 to 5000 hours
with a default of 600 hours. Once the run hours limit has been exceeded, the controller generates
a maintenance required diagnostic (unit will not shut-down). The user will be notified of th is
diagnostic through the building automa tion system or when a T rane Service T ool is communicating
with the controller.
Master Slave (Data Sharing)
Because the Tracer ZN521 controller utilizes LONW
receive data (setpoint, heat/cool mode, fan request, space temperature, etc.) to and from other
controllers on the communication link with or without the existence of a building automation
system. This applies to applications where multiple units might share one zone sensor for both
stand-alone (with communication wiring between units) and a building automation system.
®
ORKS
technology, the controller can send or
Water Valve Override
The Tracer ZN521 can be commanded via the Rover service tool to open all hydronic valves
100 percent. This allows for the faster water balancing of each unit and the entire system when the
command is sent globally to all controllers. A properly balanced system is essential for proper and
efficient operation.
Fan coil systems in cold climates need to take precautions to avoid hydronic coil freeze-up. The
T racer ZN521 does this from three different aspects. Any of these methods of protections will result
in the unit fan being disabled, the outside air damper being shut , and the hydronic valves being
opened 100 percent.
The three methods of freeze avoidance include:
1 . A binary freeze protection thermostat is mounted on the coil and will cause a latching diagnostic
if the coil temperature falls below 35°F.
2. An analog discharge air sensor monitors the temperature of the air coming off of the coil and
if the temperature falls below 40°F the outside air damper is closed, the fan is turned off and
the valves are fully opened.
3. When in the unoccupied mode the Tracer ZN521 has an adjustable freeze avoidance setpoint.
If the outside air temperature is below the setpoint the unit will open the valves to allow water
to flow through the coils.
Interoperability
Interoperability allows the owner freedom to select multiple vendors, and multiple products. With
this advantage, the owner can choose the best products, the best application, and the best service
from a variety of suppliers to meet their evolving building control needs in a cost effective manner.
Generic Binary Input/Output
The three generic binary inputs/outputs are not part of the normal control, but are actually
controlled through the Tracer Summit system (when present) to issue commands to the Tracer
ZN521 control to turn the generic inpu ts/outputs of add-on equipment (suc h as baseboard heating,
exhaust fans, occupancy sensor, lighting, etc.) on and off. This binary port is not affected when
other binary diagnostics interrupt unit operation.
UNT-PRC019-EN19
Components and Options
Tracer UC400 Controller
The T racer UC400 is a factory-installed BACnet® MS/TP control designed to pro vide control o f the
fan coil (see Figure 11). The Tracer UC400 controller is designed to be used in the following
applications: as stand-alone operation, part of the T rane T racer SC building automation system, or
part of another BACnet MS/TP Building Automation System. The Tracer UC400 can function as a
completely standalone controller in situations where a building automation system (BAS) is not
present.
Figure 11. Tracer UC400 Controller
Features include:
•Single Zone VAV
•Automatic ventilation reset
•Filter maintenance
•Wa t er valve overri de
•Freeze avoidance
•Interoperability
•Unused I/O can be used as generic I/O
The T racer UC400 is designed to install quickly and easily into the system. T rane becomes the single
source of responsibility for the equipment, unit controls, and building automation system. As a
standalone controller, the T racer UC400 is ideally suited for fix-on-fail replacement of units with old
pneumatic controllers, or in situations where a BAS will be added at a later date. Once power is
applied to the controller , it will automatically start up and run based upon the setpoint on the local
zone sensor. An individual time clock can be added to the unit for local scheduling. The Tracer
UC400 is BTL listed as B-ASC profile. This ensures the controller to be use d with other BACnet
building automation systems.
The Tracer UC400 controller delivers single zone VAV control and can be used in a stand-alone
application or as part of a Trane Integrated Comfort™ System (ICS).
In the stand-alone configuration, Tracer UC400 receives operation commands from the zone sensor
and/or the auto changeover sensor (on auto changeover units). The entering water temperature is
read from the auto changeover sensor and determines if the unit is capable of cooling or heating.
The zone sensor module is capable of transmitting the following information to the controller:
•Timed override on/cancel request
•Zone setpoint
•Current zone temperature
•Fan mode selection (off-auto-high-med-low)
For optimal system performance, fan coils can operate as part of an ICS building automation
system controlled by T racer Summit. The controller is linked directly to the Summit control panel
via a twisted pair communication wire, requiring no additional interface device (i.e., a command
unit). The T rane ICS system can monitor or over ride T racer UC400 control points. This includes such
points as temperature and output positions.
®
20 UNT-PRC019-EN
Components and Options
Discharge temp setpoint (°F)
Fan speed command (%)
Single Zone VAV with Fully Modulating Fan Speed
With a single zone VAV with fully modulating fan speed, and EDM with modulating signal is
required. The Tracer UC400 will minimize fan speed, and in turn energy usage, by only delivering
the air flow needed. See Figure 12.
Figure 12. Cool mode nominal hydronic cooling control
Filter Maintenance
Filter status for the controller is based on the cumulative run hours of the unit fan. The controller
compares the amount of fan run time against an adjustable fan run hour (stored in the controller)
to determine when maintenance is recommended for the unit. The run-hours value may be user
edited as required. The valid range for the fan run hours limit is 0 to 5000 hours with a default of
600 hours. Once the run hours limit has been exceeded, the con t roller generates a maintenance
required diagnostic (unit will not shut-down). The user will be no tified of this di agnosti c through
the building automation system or when a Trane
controller.
Fan coil systems in cold climates need to take precautions to avoid hydronic coil freeze-up. The
controller does this from three different aspects. Any of these methods of protections will result
in the unit fan being disabled, the outside air damper being shut , and the hydronic valves being
opened 100 percent.
The three methods of freeze avoidance include:
1 . A binary freeze protection thermostat is mounted on the coil and will cause a latching diagnostic
if the coil temperature falls below 35°F.
2. An analog discharge air sensor monitors the temperature of the air coming off of the coil and
if the temperature falls below 40°F the outside air damper is closed, the fan is turned off and
the valves are fully opened.
3. When in the unoccupied mode, the controller has an adjustable freeze avoidance setpoint. If the
outside air temperature is below the setpoint, the unit will open the valves to allow water to flow
through the coils.
UNT-PRC019-EN21
Interoperability
Interoperability allows the owner freedom to select multiple vendors, and multiple products. With
this advantage, the owner can choose the best products, the best application, and the best service
from a variety of suppliers to meet their evolving building control needs in a cost effective manner.
Dimensions and Weights
FRONT VIEW
SIDE SECTION
(Flush Mounted Panel Option)
TOP VIEW
F. F.L .
SIDE VIEW
(Hinged Panel Option)
E
86 in.
C
36 in.
2 1/8 in.
A
B
8
16
2
3
4
5
6
14
15
7
13
9
6
10
12
11
1
9
6 in.
1/2 in.
1 1/2 in.
D
47 in.
4 in.
Vertical Fan Coil Units
2-Pipe Chilled Water Cooling Unit
Figure 13. 2-pipe chilled water cooling unit - hot water c hangeover coil optional
22 UNT-PRC019-EN
Dimensions and Weights
Table 10. 2-pipe chilled water cooling unit callouts
18 ga. steel cabinet, lined with 1/2-inch fiberglass
insulation coated on air side; 3/8-inch closed-cell
foam optional.
Direct-drive centrifugal fan and PSC moto r; EC motor
optional.
Chilled water coil; hot water changeover optional.Hinged return air grille/access panel (optional).
Acrylic coated galvanized steel drain pan, pitched in
two directions, insulated on the underside; stainless
steel optional.
Drain hose from drain pan to condensate riser. The
flexible hose forms a running trap.
Double deflection steel supply air grille at front, left,
right or back or any combination when there are
multiple openings. Dimension “D” varies with CFM:
5, 8, 10, 12, or 14 inches.
Flush mounted return air grille/access panel
attached by quarter turn fasteners.
One inch disposable filter.
1/2-inch flange on front of unit. Allows direct
application of drywall to the unit.
7/8-inch hole on each side of cabinet for power and
control cable entry points on all units. See CLCHSVX021A-EN installation manual for details.
2 1/8-inch flange on front of unit. Drywall to be
framed out in front of unit.
Unit mounting location for thermostat/controller.
Fan shield, acoustically lined. Identification and
safety caution labels are affixed to this panel.
Vertical centerline of coil connection run outs.
Connections are at the back, left or right sides of the
unit.
T op supply air opening (knock out) for attachment of
ductwork.
Table 11. 2-pipe chilled water cooling unit dimensions (inches)
SizeABCE
35017171452
45017171452
60020201452
80020201452
100020241654
120020241654
UNT-PRC019-EN23
Dimensions and Weights
FRONT VIEW
SIDE SECTION
(Flush Mounted Panel Option)
TOP VIEW
F. F.L .
SIDE SECTION
(Hinged Panel Option)
A
E
86 in.
36 in.
1/2 in.
D
C
B
9
17
3
4
5
6
7
15
16
8
2
14
1
9
7
12
13
10
47 in.
1 1/2 in.
2 1/8 in.
6 in.
11
4 in.
2-Pipe Chilled Water Cooling Unit with Electric Heat
Figure 14. 2-pipe chilled water cooling unit with electric heat
24 UNT-PRC019-EN
Dimensions and Weights
Table 12. 2-pipe chilled water cooling unit with electric heat callouts
18 ga. steel cabinet, lined with 1/2-inch fiberglass
insulation coated on air side; 3/8-inch closed-cell
foam optional.
Electric heater (primary or auxiliary).
Direct-drive centrifugal fan and PSC moto r; EC motor
optional.
Chilled water coil; hot water changeover optional.
Acrylic coated galvanized steel drain pan, pitched in
two directions, insulated on the underside; stainless
steel optional.
Drain hose from drain pan to condensate riser. The
flexible hose forms a running trap.
Double deflection steel supply air grille at front, left,
right or back or any combination when there are
multiple openings. Dimension “D” varies with CFM:
5, 8, 10, 12, or 14 inches.
Flush mounted return air grille/access panel
attached by quarter turn fasteners.
One inch disposable filter.
1/2-inch flange on front of unit. Allows direct
application of drywall to the unit.
7/8-inch hole on each side of cabinet for power and
control cable entry points on all units. See CLCHSVX021A-EN installation manual for details.
Hinged return air grille/access panel (optional).
2 1/8-inch flange on front of unit. Drywall to be
framed out in front of unit.
Unit mounting location for thermostat/controller.
Fan shield, acoustically lined. Identification and
safety caution labels are affixed to this panel.
Vertical centerline of coil connection run outs.
Connections are at the back, left or right sides of the
unit.
T op supply air opening (knock out) for attachment of
ductwork.
Table 13. 2-pipe chilled water cooling unit with electric heat dimensions (inches)
SizeABCE
35017171452
45017171452
60020201452
80020201452
100020241654
120020241654
UNT-PRC019-EN25
Dimensions and Weights
9
17
2
5
6
7
15
16
8
3
4
14
9
7
12
1
1310
FRONT VIEW
SIDE SECTION
(Flush Mounted Panel Option)
TOP VIEW
F. F.L .
SIDE SECTION
(Hinged Panel Option)
6 in.
E
86 in.
36 in.
1 1/2 in.
D
C
B
A
1/2 in.
4 in.
47 in.
2 1/8 in.
11
4-Pipe Chilled Water Cooling and Hot Water Heating Unit
Figure 15. 4-pipe chilled water cooling and hot water heating unit
26 UNT-PRC019-EN
Dimensions and Weights
Table 14. 4-pipe chilled water cooling hot water heating unit callouts
18 ga. steel cabinet, lined with 1/2-inch fiberglass
insulation coated on air side; 3/8-inch closed-cell
foam optional.
Direct-drive centrifugal fan and PSC moto r; EC motor
optional.
Chilled water coil.Hinged return air grille/access panel (optional).
Hot water coil.
Acrylic coated galvanized steel drain pan, pitched in
two directions, insulated on the underside; stainless
steel optional.
Drain hose from drain pan to condensate riser. The
flexible hose forms a running trap.
Double deflection steel supply air grille at front, left,
right or back or any combination when there are
multiple openings. Dimension “D” varies with CFM:
5, 8, 10, 12, or 14 inches.
Flush mounted return air grille/access panel
attached by quarter turn fasteners.
One inch disposable filter.
1/2-inch flange on front of unit. Allows direct
application of drywall to the unit.
7/8-inch hole on each side of cabinet for power and
control cable entry points on all units. See CLCHSVX021A-EN installation manual for details.
2 1/8-inch flange on front of unit. Drywall to be
framed out in front of unit.
Unit mounting location for thermostat/controller.
Fan shield, acoustically lined. Identification and
safety caution labels are affixed to this panel.
Vertical centerline of coil connection run outs.
Connections are at the back, left or right sides of the
unit.
T op supply air opening (knock out) for attachment of
ductwork.
Table 15. 4-pipe chilled water cooling and hot water heating unit dimensions (inches)
SizeABCE
35017171452
45017171452
60020201452
80020201452
100020241654
120020241654
UNT-PRC019-EN27
Dimensions and Weights
B K
C
CWS
HWS
HWR
CWR
B K
C
SR
12 3
4
6
5
2-pipe slave unit
with BK connection
4-pipe slave unit
with BK connection
Stub-out detail - typical
Inside
unit
Outside
unit
36 in.
2 5/8 in.
Condensate
connection
5/8 in. I.D. hose
Supply and return
connections
1/2 in. or 3/4 in. nom.
Copper pipe
3 3/4 in.
5 1/4 in.
3 3/4 in.
86 in.
7"
1 1/2 in.
Fan Coil Units Without Risers
Figure 16. Fan Coil Units Without Risers
Table 16. Fan coil units without risers - 2-pipe and 4-pipe slave units callouts
1/2-inch or 3/4-inch supply and return coil branch copper pipe
Union fitting
Ball valve (shut-off valve)
1/2-inch or 3/4-inch copper tail piece soldered into valve body at factory
28 UNT-PRC019-EN
Insulation lining on interior surface of fan coil cabinet
Fan coil cabinet
Riser Packages
RA
RA
RA
RA
RA
RA
3 1/2 in.
3 1/2 in.
Right risers (RT)
R
CS
Reverse right risers (RR)
R
CS
R
C
S
Back risers (BK)
R
C
S
Reverse back risers (RB)
R
Left risers (LT)
TOP VIEW
CS
R
Reverse left risers (RL)
TOP VIEW
CS
S = Supply riser
R = Return riser
C = Condensate riser
C
L
RARARA
RARARA
3 3/4 in.
2 5/8 in.
3 3/4 in.
2 5/8 in.
HWS
HWR
Cond.
CWR
CWS
HWS
HWR
Cond.
CWR
CWS
HWS
HWR
Cond.
CWR
CWS
Left risers (LT)
Back risers (BK)Right risers (RT)
HWS = Hot Water Supply Riser
HWR = Hot Water Return Riser
CWS = Chilled Water Supply Riser
CWR = Chilled Water Return Riser
Cond. = Condensate Riser
TOP VIEW
C
L
HWS
HWR
Cond.
CWR
CWS
HWS
HWR
Cond.
CWR
CWS
HWS
HWR
Cond.
CWR
CWS
Reverse left risers (RL)
Reverse back risers (RB)
Reverse right risers (RR)
TOP VIEW
Reverse Riser orientations are used to aid in eliminating cross over piping when units on a riser
stack change position from floor to floor or when two units share a common riser (Master/Slave).
R
Reverse right risers (RR)Right risers (RT)
TOP VIEW
C
S
R
C
S
R
C
S
Back risers (BK)
Reverse back risers (RB)
R
C
S
TOP VIEW
Figure 17.Riser 2-Pipe Package
Dimensions and Weights
Figure 18. Riser 4-Pipe Package
UNT-PRC019-EN29
Dimensions and Weights
L = F + 2 inches
Spool Piece Length = F - L + 4 inches
L = F - Spool Length + 4 inches
Standard Installation
Standard Installation Using
Spool Pieces
92 in.
92 in.
F
F
L
L
92 in.
92 in.
F
F
L
L
F - L + 4 in.
Figure 19. Riser Installation Dimensions (inches)
30 UNT-PRC019-EN
Raised Base Options
Available in 4-inch, 8-inch and 12-inch heights (shown)
Side View
12 in.
B
Front View
12 in.
A
Raised Base
Figure 20. Raised base - no access panel
Dimensions and Weights
Table 17. Raised base dimensions (inches)
SizeAB
3501717
4501717
6002020
8002020
10002420
12002420
UNT-PRC019-EN31
Dimensions and Weights
Front ViewLeft Side View
Side ViewFront View
1
12 in.
8
6
7
Drywall
F. F.L .
2
3
4
5
3
Available only with 12 inch raised base.
Raised Base with Condensate Pump and Front Access Panel
Figure 21. Raised base with condensate pump and front access panel
32 UNT-PRC019-EN
Table 18. Raised base with condensate pump and front access panel callouts
3/8-inch I.D. outlet tube by contractorScrews for front access panel
12 inch raised baseOpening for condensate hose running in and out
Note: If the supply is 277V, an appropriately sized step-down transformer is included for condensate pump.
Front access panel (350 - 800 - 16 in. x 10 in.,
1000, 1200 - 18 in. x 10 in.
Return Air Panels
1
9
2
4
5
6
7
8
3
10
10
3
2
Bottom side section
Top side section
Up arrow indicates
locked position
Return Air Panel with Flush Mount
Figure 22. Return air panel - flush mount with quarter turn fasteners
Dimensions and Weights
Table 19. Return air panel - flush mount with quarter turn fasteners callouts
Return air grille/access panel with quarter turn
Features
•Drywall attached directly to front of the unit
fasteners
Throwaway 1-inch filter.Plastic washer
1/2-inch deep collar around return air opening on fan
coil unit
1/4 turn fastener with slotted head and square shaftBottom hook of access panel
Pawl of the 1/4 turn fastener1/2-inch drywall
Pawl lock screw
Spring retainer
•Industry standard
•Fast access with quarter turn fasteners
•Easily removable for filter changing
UNT-PRC019-EN33
Dimensions and Weights
1
2
3
4
5
6
6
6
2-in. collar on
front of fan coil unit
Return air panel
Fan coil unit
Front of
fan coil
unit
Drywall stud
by others
Drywall
by others
Return Air Panel with Framed Out Drywall with Hinged Filter Access
Figure 23. Return air panel - framed out drywall with hinged filter access
Table 20. Return air panel with framed out drywall with hinged access filter access callouts
Hinged filter access door
Access panel retaining clip
Throwaway 1-inch filter
Grille frame
Filter channel
Sheet metal screw by contractor
Features
No exposed fasteners
34 UNT-PRC019-EN
Improved aesthetics
Easy filter changing - no tools required
Drywall is framed out around two-inch collar/flange
Fan Coil Weights
Table 21. Weights for fan coil units
The weights are approximate. Risers, external sheet metal accessories and supply air grilles are not
included in the weight.
Dimensions and Weights
SizeWeight
350140 lbs (63 kg)
450150 lbs (68 kg)
600170 lbs (77 kg)
800180 lbs (82 kg)
1000210 lbs (95 kg)
1200220 lbs (100 kg)
UNT-PRC019-EN35
Mechanical Specifications
Certifications
Performance: Unit per formance is certified by AHRI in accordance with ANSI/AHRI 440-2008:
Performance Rating of Room Fan-Coils.
Safety: All standard units are agency listed in the United States and Canada and comply with the
requirements of the current editions of UL 1995/CSA C22.2 No. 236.
Construction
The cabinets shall be fabricated from 18 g age steel lined with ½-inc h fiberglass insulation bonded
with a thermosetting resin and coated on the airstream side with an acrylic facing. In addition, there
is an option available for 3/8-inch closed cell cabinet insulation.
The drain pan shall be an acrylic (black polyester powder) coated 20 gauge galvanized steel
positively sloped in two directions towards the outlet. The drain pan shall be insulated on the
underside with ½-inch fiberg lass insulation (same as cabinet). The drain hose from the outlet to the
condensate riser shall form a running trap. An optional Stainless Steel drain pan is also available.
A drain pan float switc h is also available. The float switc h will close CW control valve upon detection
of high water level in condensate drain pan.
Fan
The galvanized metal fan wh eels are centrifugal forward-curv ed and double-width. Fan wheels and
housings are corrosion resistant.
Motors
The fan motor shall be a three speed P.S.C. type with internal thermal protection and sealed
bearings. All motors have a maximum ambient operating temperature of 104°F and are
permanently lubricated.
An optional ECM type brushless fan motor is ava ilable. The motor is available, programmed at the
factory for three (3) discrete speed operation. A variable speed EC motor is also available for use
with a 2-10V DC signal.
An unfused service disconnect switch shall be included, mounted inside the unit behind the motor
cover.
Coils
The coil shall have aluminum fins mechanic al ly b onded to ½-in ch copper tube. The coil shall be
factory pressure tested at not less than 300 psig. A manual air vent shall be incorporated at the high
point, and a drain cock at the low point of the connecting pipework to the coil.
Piping Packages
The piping package shall include: Ball type shut-off valves on the coil supply and returns (combined
with balancing valves or strainers when used), and a two- or three-way control valve with twoposition actuator. Chilled water and hot water valves are normally closed.
Control valves are also available in 3 wire floating point or 2-10V DC modulating valves.
Additionally balancing valves (manual or automatic) and strainers supplied as riser system
dictates. These devices are provided as combo-valves with the shut-off on supply and ret urn and
can be equipped with PT ports.
Electric Heat
Units with electric heat shall be wired for single-stage operation with an open wire nickel-c hrome
element. An auto-reset high limit device shall be included.
36 UNT-PRC019-EN
Filters
Controls
Mechanical Specifications
A one-inch disposable filter shall be shipped loose with the return air access panel.
Units equipped with one inc h MER V 10 filters have a rating based on ASHRAE Standard 52.2. The
average dust spot efficiency is no less than 35 to 40 percent when tested in accordance with
ASHRAE 52.1 atmospheric dust spot method.
Units equipped with one inch MERV 13 filters have a rating based on A SHRAE Standard 52.2. The
average dust spot efficiency is no less than 90 percent efficiency on 1–3 micron particles and greater
than 90 percent efficiency on 3–10 micron particles when tested in accordance with ASHRAE Test
Standard 52.2.
Thermostat (option)
The fan coil manufacturer shall supply a low voltage (24V) thermostat for remote mounting, or
optionally unit mounted. Remote mounted thermostats are connected to a terminal strip that is
mounted inside the unit. The thermostat is ship ped loose for installation af ter the unit is installed,
dry-wall is applied and the walls are painted.
Line voltage controls for unit mounting is also available. Thermostat quick-connect plug provided;
thermostat ships loose for installation after drywall is applied and walls are painted.
Tracer ZN521 (option)
The T racer ZN521 discrete speed controller can be used in a stand-alone application or used as part
of a T rane Integrated Comfort S ystem (ICS) with LonT alk® communication. The T racer ZN521 offers
the combined advantages of simple and dependable operation. Standard control features include
options normally available on more elaborate control systems. All control options are available
factory-mounted and can be field-configured using a service tool.
Riser Package
Tracer UC400 (option)
The T racer UC400 controller delivers single zone VA V control in a stand-alone application or as part
of a Trane Integrated Comfort system with BACnet® communication. Standard control features
include options normally available on more elaborate control systems.
Risers are available in both type “L” and type “M” copper for supply, return and condensate pipes.
Riser insulation is available in ½-inch and one-inch wall thic kness for closed cell foam (polyolefin),
closed cell elastomeric (similar to Armaflex®) and fiberglass (wrapped with vapor barrier).
Riser diameter and insulation thickness are subject to physical limitations. Contact Trane when
risers are larger than 2 1/2 inches in diameter. The risers shall have an approximately 2 1/2 inch
swaged expansion at the top end to allow a 2 inch insertion of the riser from above without the use
of couplings. Risers may be provided plain ended in lieu of swaged for field supplied/installed
fittings (similar to Pro-Press®).
The riser insulation shall have a flame spread rating of 25 or less and a smoke dev eloped rating
of 50 or less in compliance with AST M E 84. The insulation shall be continuous over the riser length
within the height of the cabinet. Provision for insulation beyond the ends of the cabinet shall be
the responsibility of the installing contractor.
The specification of riser anchoring, expansion loops and fire stopping requirements are not
detailed in this specification and are not part of the Trane fan coils scope. Trane can provide
expansion loops installed on the risers at the factory as per the engineers specification.
Hot water risers which are continuous over twelve or more floors may incorporate expansion
compensation loops within the fan coil cabinet, location and spacing of expansion joints are the
responsibility of the design engineer.
UNT-PRC019-EN37
Mechanical Specifications
Return Air Access Panel
The return air access panel shall have a fixed blade return air grille in the lower portion with filter
access achieved by removal of the panel. The panel installs flush on to the drywall which has been
applied directly to the front of the unit. The panel is of stamped steel construction and shall be
finished in standard white baked enamel. The panel secures to the unit by a hook on the bottom
edge and two quarter -turn fasteners in the upper corners. The panel is shipped loose for installation
after the unit is installed, dry-wall is applied and the walls are painted.
There is also a return air access panel with hinged filter access as an option. Stamped steel
construction with return air grille in lower portion of grille and hinged filter access in the top
portion. Secured to the two-inch flange on the front of the unit with sheet metal screws. Drywall
is framed out in front of the unit and is not applied directly to the unit face.
Supply Air Grilles and Registers
Supply air grilles and registers shall be provided for unit mounting locations. The grilles shall be
steel, have double deflection ai rfoil blade s and shall be finished in standard white baked enamel.
The grilles shall attach to the collar of the fan coil uni t by spring clips. When a unit has more than
one supply air opening a balancing dam p er (horizontal in the front) is included with the grille
(register) to balance the air flow (screw holes optional). Any supply air grilles which are part of
supply air ductwork shall be provided by the sheet metal contractor. Grilles are shipped loose for
installation after the unit is installed, dry-wall applied and the walls are painted.
A line of sight baffle with acoustical wrap shall be included in units which have left and right or front
and back supply air openings.
There is also an option to upgrade the supply air grille material to aluminum as well as the option
to provide custom colors for return air panels and supply air grilles/registers.
Raised Bases
Raised bases are available in heights of 4 inches, 8 inches or 12 inc hes. An access panel is available
only in the 12-inc h hei ght option. If a co ndensate pump is required, 12-inch high raised base with
access panel is required.
38 UNT-PRC019-EN
Notes
Notes
UNT-PRC019-EN39
4008161
ETL LISTED
CONFORMS TO
UL STD 1995
CERTIFIED TO
CSA STD C22.2 NO. 236
Trane optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the leader in
creating and sustaining safe, comfortable and energy efficient environments, Trane offers a broad portfolio of advanced
controls and HVAC systems, comprehensive building services, and parts. For more information, visit www.Trane.com.
Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.