Trane Vertical Stack Fan Coil Units Model RSG Catalogue

Catalog
Vertical Stack Fan Coil Units Model RSG
3/4 through 4 ton capacity
July 2013
UNT-PRC019-EN
6
2
4
5
8
1
7
3
T rane vertical stack fan coil units are used in high-rise hotels, condominiums, dormitories, military barracks, and residential buildings. Trane specializes in flexible response to customers’ needs.
We work closely with engineers at the design stage to ensure optimum use of the units within the HVAC system.
Figure 1. Fan coil - Model RSG Figure 2. Furred-in f a n coil
18 ga. galvanized cabinet with acoustical liner Direct-drive centrifugal fan - PSC fan motor
with sealed bearings standard Piping package factory installed (HW pre-
heat) CW/HW coils - 2-pipe or 4-pipe Drain pan - galvanized, positively sloped to
outlet - standard Optional electric heater (behind panel) Optional electrical box for unit-mounted
thermostat Supply air opening (multiple openings
available)
Also available but not shown:
•Risers
Double deflection supply air grille/ registers
Return air panel
•Filter
Fan shield/motor cover
standard color is white.
Grille and return air panel
2 UNT-PRC019-EN
Table of Contents
Vertical Stack Fan Coil Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Model Number Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Riser Package . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Raised Base Package . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Supply Air Grille/Registers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Cooling Capacities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Heating Capacities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Sound Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Components and Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Electric Heat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Fans Curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Motor Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Control Packages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Thermostats . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Tracer ZN521 Zone Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Tracer UC400 Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Dimensions and Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Vertical Fan Coil Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
2-Pipe Chilled Water Cooling Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
2-Pipe Chilled Water Cooling Unit with Electric Heat . . . . . . . . . . . . . . . . 24
4-Pipe Chilled Water Cooling and Hot Water Heating Unit . . . . . . . . . . . 26
Fan Coil Units Without Risers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Riser Packages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Raised Base Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Raised Base . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Raised Base with Condensate Pump and Front Access Panel . . . . . . . . . 32
Return Air Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Return Air Panel with Flush Mount . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Return Air Panel with Framed Out Drywall with Hinged Filter Acce ss . . 34
Fan Coil Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Mechanical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Certifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Construction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Motors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Coils . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Piping Packages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
UNT-PRC019-EN 3
Electric Heat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Riser Package . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Return Air Access Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Supply Air Grilles and Registers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Raised Bases . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
4 UNT-PRC019-EN
Model Number Description
The following is a complete description of the vertical stack fan coil model number. Each digit in the model number has a corresponding code that identifies specific unit options. Example of model number: RS-GF05-86MKX-WWX-R1PDABCDEFGA
Digits 1, 2 – Finished Goods Identifier
Must always be “RS”
Digit 3 – Spacer Digits 4, 5 – Unique Part
Identifier - Reserved
Must always be “GF”
Digits 6, 7 – Cabinet Footprint
05 = 17-in. x 17-in. Cabinet footprint (350 and 450 CFM models) 08 = 20-in. x 20-in. Cabinet footprint (600 and 800 CFM models) 12 = 20-in. x 24-in. Cabinet footprint (1000 and 1200 CFM models)
Digit 8 – Spacer Digits 9, 10 – Unique Part
Identifier - Reserved
Must always be digits “86”
Digits 11, 12, 13 – Unique Part Identifier – Reserved
Must always be entered as “MKX”
Digit 14 – Spacer Digit 15 – Pr imary Cooling Means
C = Chilled Water (Single Purpose Coil) W = Chilled Water (2-pipe Changeover Coil - requires a change-over sensor) X = No Cooling Coil
Digit 16 – P rimar y Heating Means
H = Hot Water (Single Purpose Coil) W = Hot Water (2-pipe Changeover Coil) E = Electric Resistance X = No Heating Coil
Digit 17 – Auxiliary Heating Means
E = Electric Resistance (requires additional change-over sensor) X = No Heating Coil
Digit 18 – Spacer Digit 19 – Cabinet Nominal CFM
E = 350 G = 450 K = 600 M = 800 P = 1000 R = 1200
Digit 20 – Unit Connection Voltage
1 = 120/1/60 2 = 208/1/60 3 = 240/1/60 4 = 277/1/60
Digit 21 – Motor Type
P = PSC D = ECM (Discrete speed) V = ECM (Variable Speed)
Digit 22 – Water Coil and Fins Per Inch (FPI)
Note: X/Y format, where X = Number of
Cooling rows and Y = Number of Heating rows. Function (cooling only, changeover, etc) is handled in positions 15 and 16 of the model number.
3 row coils
K = 3/0 (2-pipe), 12 FPI L = 3/1 (4-pipe), 12 FPI M = 3/2 (4-pipe), 12 FPI N = 3/0 (2-pipe), 14 FPI P = 3/1 (4-pipe), 14 FPI Q = 3/2 (4-pipe), 14 FPI
4-row coils
U = 4/0 (2-pipe), 12 FPI V = 4/1 (4-pipe), 12 FPI W = 4/2 (2-pipe), 12 FPI X = 4/0 (2-pipe), 14 FPI Y = 4/1 (4-pipe), 14 FPI Z = 4/2 (4-pipe), 14 FPI
Digit 23 – Chilled Water Piping Packages
Note: Manual air vent, drain cock,
flexible braided hoses and unions on supply and return are standard features. Control valves are mounted on coil return.
A = 2-way control valve, shutoff valves on supply and return B = 3-way control valve, shutoff valves on supply and return C = 2-way control valve, shutoff valve on supply, manual balancing valve with shutoff on return. D = 3-way control valve, shutoff valve on supply, manual balancing valve with shutoff on return. E = 2-way control valve, combo strainer/ shutoff valve on supply, manual balancing valve with shutoff on return F = 3-way control valve, combo strainer/ shutoff valve on supply, manual balancing valve with shutoff on return G = 2-way control valve, combo strainer/ shutoff valve on supply, automatic balancing valve with shutoff on return H = 3-way control valve, combo strainer/ shutoff valve on supply, automatic balancing valve with shutoff on return
Digit 24 – Hot Water Piping Packages
Note: Manual air vent, drain cock,
flexible braided hoses and unions on supply and return are standard features. Control valves are mounted on coil return.
A = 2-way control valve, shutoff valves on supply and return B = 3-way control valve, shutoff valves on supply and return C = 2-way control valve, shutoff valve on supply, manual balancing valve with shutoff on return. D = 3-way control valve, shutoff valve on supply, manual balancing valve with shutoff on return. E = 2-way control valve, combo strainer/ shutoff valve on supply, manual balancing valve with shutoff on return F = 3-way control valve, combo strainer/ shutoff valve on supply, manual balancing valve with shutoff on return G = 2-way control valve, combo strainer/ shutoff valve on supply, automatic balancing valve with shutoff on return H = 3-way control valve, combo strainer/ shutoff valve on supply, automatic balancing valve with shutoff on return
Digit 25 – Electric Heat
Note: Must operate at supply voltage,
subject to cabinet size and airflow.
0 = No Electric Heating Coil A = 0.75 kW B = 1.0 kW C = 1.5 kW D = 2.0 kW E = 2.5 kW F = 3.0 kW G = 3.5 kW H = 4.0 kW J = 4.5 kW K = 5.0 kW M = 6.0 KW P = 7.0 KW R = 8.0 KW
Digit 26 – Control Type
(Provided and installed by factory unless otherwise noted) 0 = Low-voltage control by Others, Installed by Others, Terminal Strip provided. A = Auto Changeover, Non­Programmable, Fan Speed Switch B = Auto Changeover, Programmable, Fan Speed Switch C = Auto Changeover, Non­Programmable, No Fan Speed Switch D = Auto Changeover, Programmable, No Fan Speed Switch E = Manual Changeover, Non­Programmable, Fan Speed Switch F = Manual Changeover, Programmable, Fan Speed Switch
UNT-PRC019-EN 5
Model Number Description
G = Manual Changeover, Non­Programmable, No Fan Speed Switch H = Manual Changeover, Programmable, No Fan Speed Switch 1 = Tracer™ ZN521 (zone sensor ordered separately) 2 = Tracer™ UC400 (zone sensor ordered separately)
Digit 27 – Actuator Operation
(Provided and installed by factory unless otherwise noted) 0 = None, Low Voltage, installed by others, outside of unit C = Control Contractor Supplied, Low Voltage, installed by factory L = Line Voltage, 2-position B = 24 V 2-position (normally closed spring return) F = 3-Wire Floating Point M = 0-10 or 2-10 V Modulating
Digit 28 – Cabinet Type/ Thermostat Location/Insulation
1 = Flush Mounted RA panel, remote mounted thermostat (Fiberglass insulation) 2 = Flush Mounted RA panel unit mounted thermostat (Fiberglass insulation) 3 = Hinge Mounted RA panel, remote mounted thermostat (Fiberglass insulation) 4 = Hinge Mounted RA panel unit mounted thermostat (Fiberglass insulation) 5 = Flush Mounted RA panel, remote mounted thermostat (Closed Cell Insulation) 6 = Flush Mounted RA panel unit mounted thermostat (Closed Cell Insulation) 7 = Hinge Mounted RA panel, remote mounted thermostat (Closed Cell Insulation) 8 = Hinge Mounted RA panel unit mounted thermostat (Closed Cell Insulation)
Digit 29 – Drain Pan
0 = None (Heating Only Unit) 1 = Acrylic coated galvanized steel double sloped drain pan 2 = Acrylic coated galvanized steel double sloped drain pan CW float switch 3 = Stainless Steel double sloped drain pan 4 = Stainless Steel double sloped drain pan CW float switch
Digit 30 – Design Sequence
Current design sequence is “A”
Riser Package
Digit 1, 2, 3 – Riser Package
Must always be “YRP”
Digit 4 – Configuration
A = 2-pipe system S = 4-pipe system
Digit 5 – Spacer Digit 6 – Riser Type
1 = Single 2 = Master
Digit 7 – Copper Pipe Type
1 = All risers - type “M” 2 = All risers - type “L” 3 = Supply, Return - type “L”, Condensate ­type “M” 4 = Supply, Return - type “M”, No Condensate
Digit 8, 9, 10 – Riser Insulation Type*
0 = None 1 = Closed cell polyolefin 2 = Closed cell elastomeric 4 = Fiberglass X = n/a
Digit 11 – Spacer Digit 12, 13, 1 4 – Riser Insulation
Thickness*
0 = None 2 = 1/2 inch 4 = 1 inch X = n/a
Note:
Note: *For a 4-pipe system:
*
For a 2-pipe system: First character: Use to describe the cooling supply and return (or heating supply and return) Second character: Enter “X” Third character: use to describe condensate
First character: Use to describe cooling supply and return. Second character: Use to describe heating supply and return. Third character: Use to describe condensate.
Raised Base Package
Digit 1, 2, 3, 4 – Raised Base Package
Must always be “YRBP”
Digit 5 – Spacer Digit 6 – Unit Foot Print
1 = 350/450 (17 in. x 17 in.) 2 = 600/800 (20 in. x 20 in.) 3 = 1000/1200 (24 in. x 20 in.)
Digit 7, 8 – Raised Base Height
04 = 4 inches 08 = 8 inches 12 = 12 inches
Digit 9 – Access Panel**
0 = None 1 = Yes, front
Digit 10 – Condensate Pump* (Voltages are connection voltages)
0 = No pump 1 = 120V 2 = 208V 3 = 240V 4 = 277V (c/w Transformer)
Note: Raised base is not insulated.
Optional access panel only available on the front side.
Note: *If condensate pump is required,
raised base with condensate pump must be factory installed. Electrical connections to the pump are by Trane.
Note: **Access panel is only available
with a 12-inch raised base.
6 UNT-PRC019-EN
Model Number Description
Supply Air Grille/ Registers
Digit 1, 2, 3 – Grille Supply
GSS = Grille Supply Steel GSR = Grille Supply Steel with Register GSA = Grille Supply Aluminum GSB = Grille Supply Aluminum with Register
Digit 4 – Spacer Digit 5, 6 – Width**
XX = Round inches
Digit 7 – Type
0= Double deflection, horizontal front blades with mounting clips 1 = Double deflection, horizontal front blades with mounting holes
Digit 8, 9 – Height**
XX = round inches
Digit 10 – Color/Finish
W = Nailorhart White C = Custom color
Note: * Mounting holes are on front
flange of supply grille.
Note: ** Dimensions given for nominal
frame size. These correspond to the nominal unit opening.
Table 1. Return Air Gr ille Part
Numbers
Return Air Panel Type
Flush Mounted FSM 0145XA FSM 0145XB
Hinge Mounted GRS 14152W GRS 16154W
Flush Mounted FSM 0145XAC FSM 0145XBC
Hinge Mounted GRS 14152C GRS 16154C
Size 350/450/600/800 Size 1000/1200
Standard White
Custom Color
Table 2. Register/Grille Quick
Reference
Nominal
Size
14 x 5 GSS 14005W GSR 14005W GSS 14105W GSR 14105W
14 x 8 GSS 14008W GSR 14008W GSS 14108W GSR 14108W 14 x 10 GSS 14010W GSR 14010W GSS 14110W GSR 14110W 14 x 12 GSS 14012W GSR 14012W GSS 14112W GSR 14112W 14 x 14 GSS 14014W GSR 14014W GSS 14114W GSR 14114W 16 x 12 GSS 16012W GSR 16012W GSS 16112W GSR 16112W 16 x 14 GSS 16014W GSR 16014W GSS 16114W GSR 16114W
Note: For custom color grille, replace “W” with “C” at the end of the part number.
Registers and grilles are only available in the sizes list ed in this table.
Grilles Registers Grilles Registers
Clips Screw Holes
Filters
Table 3. Filter Part Numbers
Filter Part Numbers
Size 1000/1200
16 x 25 nominal size
FRX 14125 FRX 16125
Filter Type
Pleated - MERV 13 FPH 14125 FPH 16125
Throwaway Wire Frame - for Units with Throwaway Cardboard Frame - for Units
Note: All filters are 1-inch thick.
Pleated - MERV 10 FPY 14125 FPY 16125
Hinged Access Panel
with Flush Mounted Access Panel
Size 350/450/600/800
14 x 25 nominal size
FWX 14125A FWX 16125
UNT-PRC019-EN 7
Performance Data
Cooling Capacities
AHRI-certified cooling performance is based on ANSI/AHRI Standard 440-2008: Performance Rating of Room Fan-Coils: 80/67°F entering air temperature, 45°F entering chilled water temperature with a 10°F delta T. All performance measured on high speed tap using a 120 V AC motor, 0.05 inches ESP without filters or grilles.
Table 4. AHRI-certified rating s for cooling capacities
Size Coil
350
450
600
800
1000
1200
Note: EC motor also available.
3HC 300 8.5 5.3 2.3 5.2 132 4HC 300 9.2 5.6 2.4 5.3 132 3HC 470 11.8 7.7 3.1 10.0 175 4HC 470 12.9 8.3 3.4 7.5 175 3HC 620 19.8 12.6 4.7 18.6 259 4HC 620 22.4 13.7 5.3 19.1 259 3HC 700 21.6 13.8 5.1 19.7 290 4HC 700 24.6 15.1 5.8 17.9 290 3HC 1010 31.6 20.0 7.4 18.9 446 4HC 1010 36.3 22.1 8.5 16.5 446 3HC 1140 34.3 22.1 8.0 20.4 621 4HC 1140 39.7 24.4 9.3 18.9 621
Airflow
(cfm)
Total Capacity
(MBh)
Cooling Power Input (W)
Sensible Capacity
(MBh)
Water Flow
(GPM)
WPD
(ft H2O)
PSC
8 UNT-PRC019-EN
Heating Capacities
Heating performance is based on 70°F entering air temperature, and listed entering water temperatures. All performance data measured on high speed tap using a 120 V AC motor, 0.05 inches ESP without filters and grilles. 1-row and 2-row coils are in the preheat configuration as part of a 4-pipe system. 3-row and 4-row coils are only available as part of a 2-pipe system.
Table 5. Heating capacities
Performance Data
Size
350
450
600
800
1000
1200
Size
350
450
600
800
1000
1200
Total
Rows
Heating
1-row
Preheat
2-row
Preheat
1-row
Preheat
2-row
Preheat
1-row
Preheat
2-row
Preheat
1-row
Preheat
2-row
Preheat
1-row
Preheat
2-row
Preheat
1-row
Preheat
2-row
Preheat
Rows
Heating
3-row
Heating
4-row
Heating
3-row
Heating
4-row
Heating
3-row
Heating
4-row
Heating
3-row
Heating
4-row
Heating
3-row
Heating
4-row
Heating
3-row
Heating
4-row
Heating
Capacity
Capacity
WPD
(MBh)
(ft H
0)
2
0.5 GPM 1.0 GPM 2.0 GPM 3.0 GPM 4.0 GPM 5.0 GPM
10.2 0.5 118 13.1 1.8 133 15.3 6.7 144 16.2 14.5 149 - - - - - -
12.5 0.2 109 17.2 0.7 125 20.8 2.6 139 22.3 5.7 145 - - - - - -
11.5 0.5 113 15.6 1.8 128 19.0 6.7 141 20.4 14.5 146 - - - - - -
14.1 0.2 102 20.6 0.7 118 26.6 2.6 133 29.3 5.7 140 - - - - - -
- - - 19.5 0.6 120 25.2 2.3 134 27.9 5.1 141 29.5 8.8 145 - - -
- - - 26.6 0.9 106 35.9 3.3 123 40.3 7.1 133 42.8 12.2 138 - - -
- - - 20.2 0.6 119 26.4 2.3 133 29.4 5.1 140 31.2 8.8 144 32.4 13.6 147
- - - 27.5 0.9 104 38.0 3.3 121 43.0 7.1 131 45.9 12.2 137 - - -
- - - 24.5 0.4 110 33.6 1.6 126 38.3 3.4 134 41.1 5.8 139 43.0 8.8 142
- - - 32.0 0.8 95 47.2 2.7 112 55.3 5.7 122 60.2 9.7 129 63.5 14.7 134
- - - 25.3 0.4 108 35.3 1.6 124 40.5 3.4 132 43.7 5.8 138 45.8 8.8 141
- - - 33.0 0.8 93 49.6 2.7 109 58.9 5.7 120 64.6 9.7 127 68.5 14.7 132
Total
WPD
(MBh)
(ft H
0)
2
0.5 GPM 1.0 GPM 2.0 GPM 3.0 GPM 4.0 GPM 5.0 GPM
10.5 0.2 97 14.7 0.9 110 18.0 3.3 122 19.3 7.2 127 - - - - - -
11.9 0.1 92 16.1 0.5 107 19.7 2.0 120 20.9 4.5 126 - - - - - -
11.7 0.2 93 17.6 0.9 104 23.3 3.3 116 25.9 7.2 122 - - - - - -
13.2 0.1 86 19.2 0.5 101 25.7 2.0 114 28.6 4.5 121 - - - - - -
- - - 22.9 0.6 93 31.8 2.2 108 36.0 4.7 116 38.2 8.2 121 - - -
- - - 24.5 0.4 90 34.7 1.7 105 39.3 3.8 113 41.6 6.6 119 - - -
- - - 23.7 0.6 92 33.7 2.2 106 38.5 4.7 114 41.3 8.2 119 43.0 12.6 123
- - - 25.3 0.4 89 36.7 1.7 103 42.2 3.8 111 45.1 6.6 117 46.9 10.2 121
- - - 27.0 0.4 85 41.5 1.4 98 49.4 3.0 107 54.3 5.1 112 57.4 7.7 117
- - - 28.4 0.2 82 44.9 0.9 94 54.2 1.9 103 59.7 3.3 110 63.1 5.1 114
- - - 27.7 0.4 84 43.6 1.4 96 52.7 3.0 104 58.4 5.1 110 62.3 7.8 115
- - - 29.0 0.2 81 47.2 0.9 92 57.7 2.0 101 64.4 3.3 107 68.7 5.1 112
LWT (°F)
LWT (°F)
Total
Capacity
(MBh)
Total
Capacity
(MBh)
WPD
(ft H
WPD
(ft H
LWT (°F)
0)
2
LWT (°F)
0)
2
Entering Water Temp. 160°F
Total
Capacity
Capacity
WPD
WPD
LWT (°F)
0)
2
LWT (°F)
0)
2
(MBh)
(ft H
Entering Water Temp. 140°F
Total
(MBh)
(ft H
Total
Capacity
(MBh)
Total
Capacity
(MBh)
WPD
(ft H
WPD
(ft H
Total
Capacity
LWT (°F)
0)
2
Capacity
LWT (°F)
0)
2
(MBh)
Total
(MBh)
WPD
(ft H
WPD
(ft H
0)
2
0)
2
LWT (°F)
LWT (°F)
Total
Capacity
(MBh)
Total
Capacity
(MBh)
WPD
(ft H
WPD
(ft H
LWT (°F)
0)
2
LWT (°F)
0)
2
UNT-PRC019-EN 9
Performance Data
Sound Data
Table 6. Sound data for vertical stack fan coils
Unit Size CFM Fan Speed
325 High 31
350
450
600
800
1000
1200
Note: Sound level is measured at a distance of 8 ft. from the return air grille. Measurements are for a typical furnished and
carpeted hotel suite. CFM in the above chart is approximate. Airflow is dependent on the number of coil rows, coil fins per inch, the amount of condensate on the fins, supply voltage, motor manufacturer, supply air configuration, filter cleanliness and altitude.
275 Medium 29 225 Low 28 500 High 37 425 Medium 34 325 Low 31 650 High 39 500 Medium 37 425 Low 35 725 High 41 600 Medium 39 500 Low 37
1050 High 45
950 Medium 43
800 Low 41 1175 High 50 1100 Medium 47 1000 Low 44
dBA
Sound Pressure Level -
10 UNT-PRC019-EN
Components and Options
Electric Heat
Table 7. Kilowatts (kW) per model
kW 0.75 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 6.0 7.0 8.0
Model
350/450
600/800
1000/1200
Volts/ph/Hz Heater Amps
120V/1/60 6.3 8.3 12.5 16.7 208V/1/60 4.8 7.2 9.6 12.0 14.4 16.8 240V/1/60 4.2 6.3 8.3 10.4 12.5 14.6 277V/1/60 3.6 5.4 7.2 9.0 10.8 12.6 120V/1/60 6.3 8.3 12.5 16.7 208V/1/60 4.8 7.2 9.6 12.0 14.4 16.8 19.2 21.6 24.0 28.8 240V/1/60 4.2 6.3 8.3 10.4 12.5 14.6 16.7 18.8 20.8 25.0 277V/1/60 3.6 5.4 7.2 9.0 10.8 12.6 14.4 16.2 18.1 21.7 120V/1/60 6.3 8.3 12.5 16.7 208V/1/60 4.8 7.2 9.6 12.0 14.4 16.8 19.2 21.6 24.0 28.8 33.7 38.5 240V/1/60 4.2 6.3 8.3 10.4 12.5 14.6 16.7 18.8 20.8 25.0 29.2 33.3 277V/1/60 3.6 5.4 7.2 9.0 10.8 12.6 14.4 16.2 18.1 21.7 25.3 28.9
Heaters are wired for single stage operation.
An auto-reset high limit device is included.
Power connection is single point.
The heater is located in the reheat position relative to the cooling coil.
The fan coil unit does not include a fuse or fusible type disconnect. Motor sub-fusing as per electrical code.
Amps = Watts
Volts
Air temp. rise (Delta T) = kW x 3160
= MBH x 925
CFM CFM
S.A. = Supply Air FLA = Full Load Amps = S.A. fan motor Amps + Electric Heater Amps MCA = Minimum Circuit Ampacity = FLA x 1.25 MOP = Rating of maximum overcurrent protection device = (2.25 x S.A. fan motor Amps) + Electric Heater Amps
UNT-PRC019-EN 11
Components and Options
Requirements of Standards: UL 1995 and CSA C22.2 No.236
If the value of the calculated rating does not equal a standard current rating of overcurrent protective device, the mark ed maximum rating shall be the next lower standard rating.
Exception No. 1: The marked maximum rating of the overcurrent protective device shall be the standard rating next higher than the computed value if the next lower standard ratings is less than 125 percent of the current rating of an electric heater load, when the unit includes an electric heater.
Exception No. 2: if the computed value of the overcurrent protective device is less than the minimum ampacity of the supply circuit, the marked rating of the device shall be increased to the largest standard overcurrent protective device rating appropriate for the marked minimum circuit ampacity.
Exception No. 3: If the marked minimum circuit ampacity does not correspond to a standard protective device rating, the next higher standard rating of the protective device may be marked.
12 UNT-PRC019-EN
Fans Curves
0
0.1
0.2
0.3
0.4
0.5
0 100 200 300 400
External Static Pressure (in. wg.)
Supply Air Volume (SCFM)
Medium
Low
6 Row 5 Row 4 Row 3 Row
0
0.1
0.2
0.3
0.4
0.5
200 300 400 500 600
External Static Pressure (in. wg.)
Supply Air Volume (SCFM)
High
Medium
Low
6 Row 5 Row 4 Row 3 Row
Components and Options
Figure 3. Unit size 350
High
Figure 4. Unit size 450
UNT-PRC019-EN 13
Components and Options
0
0.1
0.2
0.3
0.4
0.5
300 400 500 600 700
External Static Pressure (in. wg.)
Supply Air Volume (SCFM)
High
Medium
Low
6 Row 5 Row 4 Row 3 Row
0
0.1
0.2
0.3
0.4
0.5
300400500600700800
External Static Pressure (in. wg.)
Supply Air Volume (SCFM)
High
Medium
Low
6 Row 5 Row 4 Row 3 Row
Figure 5. Unit size 600
Figure 6. Unit size 800
14 UNT-PRC019-EN
Figure 7. Unit size 1000
0.5
0.4
Components and Options
Low
0.3
0.2
0.1
External Static Pressure (in. wg.)
6 Row 5 Row 4 Row 3 Row
0
600 700 800 900 1000 1100 1200
Figure 8. Unit size 1200
0.5
0.4
Low
0.3
Medium
Medium
High
Supply Air Volume (SCFM)
High
0.2
External Static Pressure (in. wg.)
5 Row 4 Row 3 Row
6 Row
0.1
0
800 900 1000 1100 1200 1300
Supply Air Volume (SCFM)
Fan curves are based on 120V AC PSC motor at high, medium and low fan speed settings. The following test conditions apply:
Centrifugal direct drive fan with double inlet and forward curved impeller.
Cooling coil is dry.
One-inch throwaway filter is clean.
UNT-PRC019-EN 15
Components and Options
Motor Data
Table 8. Motor data
Size
350
450
600
800
1000
1200
Note: EC motors have been programmed for three (3) discrete speed operation. Variable speed also available (not shown.) Motor nameplate data is show n
in table. Fan motors are single phase and have a minimum of three speeds. Trane has several fan motor suppliers in order to ensure availability . Amp draws may differ between motors from different manufacturers. Trane reserves the right to change motor HP and therefore amp draws without notice
Connection Voltage
Volts/ph/Hz
120V/1/60 1/20 1.2 1/3 4.8
208-240V/1/60 1/14 0.6 1/3 2.8
277V/1/60 1/12 0.6 1/3 2.6 120V/1/60 1/6 1.7 1/3 4.8
208-240V/1/60 1/12 0.8 1/3 2.8
277V/1/60 1/12 0.6 1/3 2.6 120V/1/60 1/6 2.6 1/3 4.8
208-240V/1/60 1/12 0.8 1/3 2.8
277V/1/60 1/12 0.6 1/3 2.6 120V/1/60 1/6 2.6 1/3 4.8
208-240V/1/60 1/6 1.4 1/3 2.8
277V/1/60 1/6 0.9 1/3 2.6 120V/1/60 1/4 4.6 1/3 4.8
208-240V/1/60 1/4 2.2 1/3 2.8
277V/1/60 1/4 1.6 1/3 2.6 120V/1/60 1/3 6.4 1/2 6.8
208-240V/1/60 1/3 3.1 1/2 4.1
277V/1/60 1/3 2.1 1/2 3.6
Max. Plate Ratings Max. Plate Ratings
HP Amps HP Amps
PSC ECM
Control Packages
T rane offers a range of standard thermostats and controllers for the vertical stack fan coil units. For applications where a larger BAS is to be installed, T rane can provide factory mounting of the ZN521 or UC400 controllers.
Thermostats
Table 9. Thermostat information
Thermostat
Voltage Manufacturer Model
24 Honeywell TB8575A1000 Automatic or Manual User Selectable 3 24 Honeywell TB7100A10001Automatic or Manual User Selectable 3 Residential
120/208/240 Honeywell TB6575A1000 Automatic or Manual User Selectable 3
24 HotelTech LT24A Automatic see Note 2 2 Hotel 24 HotelTech LT24A3 Automatic see Note 2 3 Hotel
120 HotelTech LT120A Automatic see Note 2 2 Hotel
208-230 HotelTech LT220A Automatic see Note 2 2 Hotel
277 HotelTech LT277A Automatic see Note 2 2 Hotel
1. The Honeywell TB7100A1000 is a 7-day programmable thermostat.
2. The HotelTech thermostats feature automatic fan speed switching between the available speeds and off. The thermostat selects speed based on
deviation of the room temperature from set point. The occupant can also manually select between the available speeds.
Heat/Cool
Changeover Fan Operation
Available Fan
Speeds Application
Residential or
Hospitality
Residential or
Hospitality
16 UNT-PRC019-EN
Residential applications include: Condominiums, apartments, student residences/dormitories, assisted living/retirement facilities, and military barracks.
T rane recommends the remote mounting of low voltage (24V) thermostats to achieve optimal zone control. When thermostats are remote mounted, a terminal strip is provided inside the unit for field connection to the remote thermostat. Unit mounting of thermostat is also available, however all thermostats are shipped loose for field installation after the unit is installed, drywall is applied and the walls are painted.
The standard standalone thermostats listed above cycle a two position (on/off) valve and feature discrete speed fan speed operation. If modulating (0-10V DC or 3-wire floating point) valve actuators or modulating or 0-10V DC EC motors are a requirement, a thermostat or controller with the necessary analog outputs must be used.
Tracer ZN521 Zone Controller
The T racer ZN521 is a factory-installed LonTalk® control board designed to provi de control of th e fan-coil products (see Figure 9).
Figure 9. Tracer ZN521 controller
Components and Options
Features include:
Automatic fan-speed reset
Automatic ventilation reset
Manual output test
Filter maintenance
Master slave
Water valve override
Freeze avoidance
Interoperability
Three generic I/O ports
The Tracer ZN521 controller is designed to be used in the following applications:
As part of the T rane T racer Summit building automation system, the T racer ZN521 becomes an important part of the Trane Integrated Comfort system (ICS).
The Tracer ZN521 can function as a completely standalone controller in situations where a building automation system (BAS) is not present.
For situations when a non-T rane BAS is present, the T racer ZN521 can be where ever a LonT alk front-end system is present.
Through building management of the HVAC system, optimizing energy consumption becomes possible at a zone level. Each unit is capable of functioning independently of one another during occupied and unoccupied hours of the day. This allows the temperature setpoint and ventilation setting to be changed automatically based on zone usage (see Figure 10).
UNT-PRC019-EN 17
Components and Options
Fan coil
Fan coil
To other building products
To other Trane products
Security system
Rover™ (optional)
Tracer Summit® System
Lighting system
Fire safety system
Figure 10. Tracer ZN521 System
Two Systems in One
In an ICS environment, the Tracer ZN521 is pre-designed to install quickly and easily into the system. Since the controller is mounted on the unit, the start-up time for the entire system is minimized. T rane becomes the single source of responsibility for the equipment, unit controls, and building automation system.
Once power is applied to the controller, it will automatically start up and run based upon the setpoint on the local zone sensor. The Tracer ZN521 is certified to the interoperable L Space Comfort Controller profile. This allows the controller to be used with another vendor’ s BAS and thereby still provide the high quality of factory installation. In addition, the Tracer ZN521 provides one of the most extensive interoperable data lists of any controller of its type in the industry.
Automatic Fan and Ventilation Reset
With the Tracer ZN521 controller, a multi-speed fan control for the fan coil delivers the airflow output customized to support the cfm space needs. When less cfm is necessary to meet the load of the zone (typically 75 to 80 percent of the time), the equipment operates on low speed. However, if the room temperature rises, the controller will switch to high speed.
18 UNT-PRC019-EN
Manual Output Test
The T racer ZN521 controller includes a manual output test function. This function may be initiated from the blue test push button on the controller or through the Rover™ service tool. This feature is used to manually exercise the outputs in a defined sequence.
The purpose of this test sequence is to verify output and end device operation. The manual output test function may also be used in the following situations:
Reset latching diagnostics
Verify output wiring and operation
Force the water valve(s) open to balance the hydronic system during installation set-up or service.
ONMARK
®
Components and Options
Filter Maintenance
Filter status for the controller is based on the cumulative run hours of the unit fan. The controller compares the amount of fan run time against an adjustable fan run hour (stored in the controller) to determine when maintenance is recommended for the unit. The run-hours value may be user edited as required (through Rover). The valid range for the fan run hours limit is 0 to 5000 hours with a default of 600 hours. Once the run hours limit has been exceeded, the controller generates a maintenance required diagnostic (unit will not shut-down). The user will be notified of th is diagnostic through the building automa tion system or when a T rane Service T ool is communicating with the controller.
Master Slave (Data Sharing)
Because the Tracer ZN521 controller utilizes LONW receive data (setpoint, heat/cool mode, fan request, space temperature, etc.) to and from other controllers on the communication link with or without the existence of a building automation system. This applies to applications where multiple units might share one zone sensor for both stand-alone (with communication wiring between units) and a building automation system.
®
ORKS
technology, the controller can send or
Water Valve Override
The Tracer ZN521 can be commanded via the Rover service tool to open all hydronic valves 100 percent. This allows for the faster water balancing of each unit and the entire system when the command is sent globally to all controllers. A properly balanced system is essential for proper and efficient operation.
Hydronic Coil Freeze Protection (Freeze Avoidance)
Fan coil systems in cold climates need to take precautions to avoid hydronic coil freeze-up. The T racer ZN521 does this from three different aspects. Any of these methods of protections will result in the unit fan being disabled, the outside air damper being shut , and the hydronic valves being opened 100 percent.
The three methods of freeze avoidance include: 1 . A binary freeze protection thermostat is mounted on the coil and will cause a latching diagnostic
if the coil temperature falls below 35°F.
2. An analog discharge air sensor monitors the temperature of the air coming off of the coil and if the temperature falls below 40°F the outside air damper is closed, the fan is turned off and the valves are fully opened.
3. When in the unoccupied mode the Tracer ZN521 has an adjustable freeze avoidance setpoint. If the outside air temperature is below the setpoint the unit will open the valves to allow water to flow through the coils.
Interoperability
Interoperability allows the owner freedom to select multiple vendors, and multiple products. With this advantage, the owner can choose the best products, the best application, and the best service from a variety of suppliers to meet their evolving building control needs in a cost effective manner.
Generic Binary Input/Output
The three generic binary inputs/outputs are not part of the normal control, but are actually controlled through the Tracer Summit system (when present) to issue commands to the Tracer ZN521 control to turn the generic inpu ts/outputs of add-on equipment (suc h as baseboard heating, exhaust fans, occupancy sensor, lighting, etc.) on and off. This binary port is not affected when other binary diagnostics interrupt unit operation.
UNT-PRC019-EN 19
Components and Options
Tracer UC400 Controller
The T racer UC400 is a factory-installed BACnet® MS/TP control designed to pro vide control o f the fan coil (see Figure 11). The Tracer UC400 controller is designed to be used in the following applications: as stand-alone operation, part of the T rane T racer SC building automation system, or part of another BACnet MS/TP Building Automation System. The Tracer UC400 can function as a completely standalone controller in situations where a building automation system (BAS) is not present.
Figure 11. Tracer UC400 Controller
Features include:
Single Zone VAV
Automatic ventilation reset
Filter maintenance
Wa t er valve overri de
Freeze avoidance
Interoperability
Unused I/O can be used as generic I/O
The T racer UC400 is designed to install quickly and easily into the system. T rane becomes the single source of responsibility for the equipment, unit controls, and building automation system. As a standalone controller, the T racer UC400 is ideally suited for fix-on-fail replacement of units with old pneumatic controllers, or in situations where a BAS will be added at a later date. Once power is applied to the controller , it will automatically start up and run based upon the setpoint on the local zone sensor. An individual time clock can be added to the unit for local scheduling. The Tracer UC400 is BTL listed as B-ASC profile. This ensures the controller to be use d with other BACnet building automation systems.
The Tracer UC400 controller delivers single zone VAV control and can be used in a stand-alone application or as part of a Trane Integrated Comfort™ System (ICS).
In the stand-alone configuration, Tracer UC400 receives operation commands from the zone sensor and/or the auto changeover sensor (on auto changeover units). The entering water temperature is read from the auto changeover sensor and determines if the unit is capable of cooling or heating. The zone sensor module is capable of transmitting the following information to the controller:
Timed override on/cancel request
Zone setpoint
Current zone temperature
Fan mode selection (off-auto-high-med-low)
For optimal system performance, fan coils can operate as part of an ICS building automation system controlled by T racer Summit. The controller is linked directly to the Summit control panel via a twisted pair communication wire, requiring no additional interface device (i.e., a command unit). The T rane ICS system can monitor or over ride T racer UC400 control points. This includes such points as temperature and output positions.
®
20 UNT-PRC019-EN
Components and Options
Discharge temp setpoint (°F)
Fan speed command (%)
Single Zone VAV with Fully Modulating Fan Speed
With a single zone VAV with fully modulating fan speed, and EDM with modulating signal is required. The Tracer UC400 will minimize fan speed, and in turn energy usage, by only delivering the air flow needed. See Figure 12.
Figure 12. Cool mode nominal hydronic cooling control
Filter Maintenance
Filter status for the controller is based on the cumulative run hours of the unit fan. The controller compares the amount of fan run time against an adjustable fan run hour (stored in the controller) to determine when maintenance is recommended for the unit. The run-hours value may be user edited as required. The valid range for the fan run hours limit is 0 to 5000 hours with a default of 600 hours. Once the run hours limit has been exceeded, the con t roller generates a maintenance required diagnostic (unit will not shut-down). The user will be no tified of this di agnosti c through the building automation system or when a Trane controller.
®
service tool is communicating with the
Hydronic Coil Freeze Protection (Freeze Avoidance)
Fan coil systems in cold climates need to take precautions to avoid hydronic coil freeze-up. The controller does this from three different aspects. Any of these methods of protections will result in the unit fan being disabled, the outside air damper being shut , and the hydronic valves being opened 100 percent.
The three methods of freeze avoidance include: 1 . A binary freeze protection thermostat is mounted on the coil and will cause a latching diagnostic
if the coil temperature falls below 35°F.
2. An analog discharge air sensor monitors the temperature of the air coming off of the coil and if the temperature falls below 40°F the outside air damper is closed, the fan is turned off and the valves are fully opened.
3. When in the unoccupied mode, the controller has an adjustable freeze avoidance setpoint. If the outside air temperature is below the setpoint, the unit will open the valves to allow water to flow through the coils.
UNT-PRC019-EN 21
Interoperability
Interoperability allows the owner freedom to select multiple vendors, and multiple products. With this advantage, the owner can choose the best products, the best application, and the best service from a variety of suppliers to meet their evolving building control needs in a cost effective manner.
Dimensions and Weights
FRONT VIEW
SIDE SECTION
(Flush Mounted Panel Option)
TOP VIEW
F. F.L .
SIDE VIEW
(Hinged Panel Option)
E
86 in.
C
36 in.
2 1/8 in.
A
B
8
16
2
3
4
5
6
14
15
7
13
9
6
10
12
11
1
9
6 in.
1/2 in.
1 1/2 in.
D
47 in.
4 in.
Vertical Fan Coil Units
2-Pipe Chilled Water Cooling Unit
Figure 13. 2-pipe chilled water cooling unit - hot water c hangeover coil optional
22 UNT-PRC019-EN
Dimensions and Weights
Table 10. 2-pipe chilled water cooling unit callouts
18 ga. steel cabinet, lined with 1/2-inch fiberglass insulation coated on air side; 3/8-inch closed-cell foam optional.
Direct-drive centrifugal fan and PSC moto r; EC motor optional.
Chilled water coil; hot water changeover optional. Hinged return air grille/access panel (optional). Acrylic coated galvanized steel drain pan, pitched in
two directions, insulated on the underside; stainless steel optional.
Drain hose from drain pan to condensate riser. The flexible hose forms a running trap.
Double deflection steel supply air grille at front, left, right or back or any combination when there are multiple openings. Dimension “D” varies with CFM: 5, 8, 10, 12, or 14 inches.
Flush mounted return air grille/access panel attached by quarter turn fasteners.
One inch disposable filter.
1/2-inch flange on front of unit. Allows direct application of drywall to the unit.
7/8-inch hole on each side of cabinet for power and control cable entry points on all units. See CLCH­SVX021A-EN installation manual for details.
2 1/8-inch flange on front of unit. Drywall to be framed out in front of unit.
Unit mounting location for thermostat/controller.
Fan shield, acoustically lined. Identification and safety caution labels are affixed to this panel.
Vertical centerline of coil connection run outs. Connections are at the back, left or right sides of the unit. T op supply air opening (knock out) for attachment of ductwork.
Table 11. 2-pipe chilled water cooling unit dimensions (inches)
Size A B C E
350 17 17 14 52 450 17 17 14 52 600 20 20 14 52
800 20 20 14 52 1000 20 24 16 54 1200 20 24 16 54
UNT-PRC019-EN 23
Dimensions and Weights
FRONT VIEW
SIDE SECTION
(Flush Mounted Panel Option)
TOP VIEW
F. F.L .
SIDE SECTION
(Hinged Panel Option)
A
E
86 in.
36 in.
1/2 in.
D
C B
9
17
3
4
5
6
7
15
16
8
2
14
1
9
7
12
13
10
47 in.
1 1/2 in.
2 1/8 in.
6 in.
11
4 in.
2-Pipe Chilled Water Cooling Unit with Electric Heat
Figure 14. 2-pipe chilled water cooling unit with electric heat
24 UNT-PRC019-EN
Dimensions and Weights
Table 12. 2-pipe chilled water cooling unit with electric heat callouts
18 ga. steel cabinet, lined with 1/2-inch fiberglass insulation coated on air side; 3/8-inch closed-cell foam optional.
Electric heater (primary or auxiliary).
Direct-drive centrifugal fan and PSC moto r; EC motor optional.
Chilled water coil; hot water changeover optional. Acrylic coated galvanized steel drain pan, pitched in
two directions, insulated on the underside; stainless steel optional.
Drain hose from drain pan to condensate riser. The flexible hose forms a running trap.
Double deflection steel supply air grille at front, left, right or back or any combination when there are multiple openings. Dimension “D” varies with CFM: 5, 8, 10, 12, or 14 inches.
Flush mounted return air grille/access panel attached by quarter turn fasteners.
One inch disposable filter.
1/2-inch flange on front of unit. Allows direct application of drywall to the unit.
7/8-inch hole on each side of cabinet for power and control cable entry points on all units. See CLCH­SVX021A-EN installation manual for details.
Hinged return air grille/access panel (optional). 2 1/8-inch flange on front of unit. Drywall to be
framed out in front of unit.
Unit mounting location for thermostat/controller.
Fan shield, acoustically lined. Identification and safety caution labels are affixed to this panel.
Vertical centerline of coil connection run outs. Connections are at the back, left or right sides of the unit.
T op supply air opening (knock out) for attachment of ductwork.
Table 13. 2-pipe chilled water cooling unit with electric heat dimensions (inches)
Size A B C E
350 17 17 14 52
450 17 17 14 52
600 20 20 14 52
800 20 20 14 52 1000 20 24 16 54 1200 20 24 16 54
UNT-PRC019-EN 25
Dimensions and Weights
9
17
2
5
6
7
15
16
8
3
4
14
9
7
12
1
1310
FRONT VIEW
SIDE SECTION
(Flush Mounted Panel Option)
TOP VIEW
F. F.L .
SIDE SECTION
(Hinged Panel Option)
6 in.
E
86 in.
36 in.
1 1/2 in.
D
C B
A
1/2 in.
4 in.
47 in.
2 1/8 in.
11
4-Pipe Chilled Water Cooling and Hot Water Heating Unit
Figure 15. 4-pipe chilled water cooling and hot water heating unit
26 UNT-PRC019-EN
Dimensions and Weights
Table 14. 4-pipe chilled water cooling hot water heating unit callouts
18 ga. steel cabinet, lined with 1/2-inch fiberglass insulation coated on air side; 3/8-inch closed-cell foam optional.
Direct-drive centrifugal fan and PSC moto r; EC motor optional.
Chilled water coil. Hinged return air grille/access panel (optional).
Hot water coil. Acrylic coated galvanized steel drain pan, pitched in
two directions, insulated on the underside; stainless steel optional.
Drain hose from drain pan to condensate riser. The flexible hose forms a running trap.
Double deflection steel supply air grille at front, left, right or back or any combination when there are multiple openings. Dimension “D” varies with CFM: 5, 8, 10, 12, or 14 inches.
Flush mounted return air grille/access panel attached by quarter turn fasteners.
One inch disposable filter.
1/2-inch flange on front of unit. Allows direct application of drywall to the unit.
7/8-inch hole on each side of cabinet for power and control cable entry points on all units. See CLCH­SVX021A-EN installation manual for details.
2 1/8-inch flange on front of unit. Drywall to be framed out in front of unit.
Unit mounting location for thermostat/controller.
Fan shield, acoustically lined. Identification and safety caution labels are affixed to this panel.
Vertical centerline of coil connection run outs. Connections are at the back, left or right sides of the unit.
T op supply air opening (knock out) for attachment of ductwork.
Table 15. 4-pipe chilled water cooling and hot water heating unit dimensions (inches)
Size A B C E
350 17 17 14 52
450 17 17 14 52
600 20 20 14 52
800 20 20 14 52 1000 20 24 16 54 1200 20 24 16 54
UNT-PRC019-EN 27
Dimensions and Weights
B K
C
CWS
HWS
HWR
CWR
B K
C
SR
12 3
4
6
5
2-pipe slave unit with BK connection
4-pipe slave unit with BK connection
Stub-out detail - typical
Inside unit
Outside unit
36 in.
2 5/8 in.
Condensate
connection
5/8 in. I.D. hose
Supply and return
connections
1/2 in. or 3/4 in. nom.
Copper pipe
3 3/4 in.
5 1/4 in.
3 3/4 in.
86 in.
7"
1 1/2 in.
Fan Coil Units Without Risers
Figure 16. Fan Coil Units Without Risers
Table 16. Fan coil units without risers - 2-pipe and 4-pipe slave units callouts
1/2-inch or 3/4-inch supply and return coil branch copper pipe
Union fitting
Ball valve (shut-off valve)
1/2-inch or 3/4-inch copper tail piece soldered into valve body at factory
28 UNT-PRC019-EN
Insulation lining on interior surface of fan coil cabinet
Fan coil cabinet
Riser Packages
RA
RA
RA
RA
RA
RA
3 1/2 in.
3 1/2 in.
Right risers (RT)
R
CS
Reverse right risers (RR)
R
CS
R C
S
Back risers (BK)
R
C
S
Reverse back risers (RB)
R
Left risers (LT)
TOP VIEW
CS
R
Reverse left risers (RL)
TOP VIEW
CS
S = Supply riser R = Return riser C = Condensate riser
C
L
RARARA
RARARA
3 3/4 in.
2 5/8 in.
3 3/4 in.
2 5/8 in.
HWS
HWR
Cond.
CWR
CWS
HWS
HWR
Cond.
CWR
CWS
HWS HWR
Cond. CWR CWS
Left risers (LT)
Back risers (BK) Right risers (RT)
HWS = Hot Water Supply Riser HWR = Hot Water Return Riser CWS = Chilled Water Supply Riser CWR = Chilled Water Return Riser Cond. = Condensate Riser
TOP VIEW
C
L
HWS
HWR
Cond.
CWR
CWS
HWS
HWR
Cond.
CWR
CWS
HWS
HWR
Cond.
CWR
CWS
Reverse left risers (RL)
Reverse back risers (RB)
Reverse right risers (RR)
TOP VIEW
Reverse Riser orientations are used to aid in eliminating cross over piping when units on a riser stack change position from floor to floor or when two units share a common riser (Master/Slave).
R
Reverse right risers (RR)Right risers (RT)
TOP VIEW
C S
R C
S
R
C
S
Back risers (BK)
Reverse back risers (RB)
R
C
S
TOP VIEW
Figure 17. Riser 2-Pipe Package
Dimensions and Weights
Figure 18. Riser 4-Pipe Package
UNT-PRC019-EN 29
Dimensions and Weights
L = F + 2 inches
Spool Piece Length = F - L + 4 inches
L = F - Spool Length + 4 inches
Standard Installation
Standard Installation Using
Spool Pieces
92 in.
92 in.
F
F
L
L
92 in.
92 in.
F
F
L
L
F - L + 4 in.
Figure 19. Riser Installation Dimensions (inches)
30 UNT-PRC019-EN
Raised Base Options
Available in 4-inch, 8-inch and 12-inch heights (shown)
Side View
12 in.
B
Front View
12 in.
A
Raised Base
Figure 20. Raised base - no access panel
Dimensions and Weights
Table 17. Raised base dimensions (inches)
Size A B
350 17 17
450 17 17
600 20 20
800 20 20 1000 24 20 1200 24 20
UNT-PRC019-EN 31
Dimensions and Weights
Front View Left Side View
Side ViewFront View
1
12 in.
8
6 7
Drywall
F. F.L .
2
3
4
5
3
Available only with 12 inch raised base.
Raised Base with Condensate Pump and Front Access Panel
Figure 21. Raised base with condensate pump and front access panel
32 UNT-PRC019-EN
Table 18. Raised base with condensate pump and front access panel callouts
Condensate riser (if applicable) 120V - 208V condensate pump
Drain tube factory installed
3/8-inch I.D. outlet tube by contractor Screws for front access panel
12 inch raised base Opening for condensate hose running in and out
Note: If the supply is 277V, an appropriately sized step-down transformer is included for condensate pump.
Front access panel (350 - 800 - 16 in. x 10 in., 1000, 1200 - 18 in. x 10 in.
Return Air Panels
1
9
2
4
5
6
7
8
3
10
10
3
2
Bottom side section
Top side section
Up arrow indicates locked position
Return Air Panel with Flush Mount
Figure 22. Return air panel - flush mount with quarter turn fasteners
Dimensions and Weights
Table 19. Return air panel - flush mount with quarter turn fasteners callouts
Return air grille/access panel with quarter turn
Features
Drywall attached directly to front of the unit
fasteners Throwaway 1-inch filter. Plastic washer 1/2-inch deep collar around return air opening on fan
coil unit 1/4 turn fastener with slotted head and square shaft Bottom hook of access panel
Pawl of the 1/4 turn fastener 1/2-inch drywall
Pawl lock screw
Spring retainer
Industry standard
Fast access with quarter turn fasteners
Easily removable for filter changing
UNT-PRC019-EN 33
Dimensions and Weights
1
2
3
4
5
6
6
6
2-in. collar on front of fan coil unit
Return air panel
Fan coil unit
Front of fan coil unit
Drywall stud by others
Drywall by others
Return Air Panel with Framed Out Drywall with Hinged Filter Access
Figure 23. Return air panel - framed out drywall with hinged filter access
Table 20. Return air panel with framed out drywall with hinged access filter access callouts
Hinged filter access door
Access panel retaining clip
Throwaway 1-inch filter
Grille frame
Filter channel
Sheet metal screw by contractor
Features
No exposed fasteners
34 UNT-PRC019-EN
Improved aesthetics Easy filter changing - no tools required Drywall is framed out around two-inch collar/flange
Fan Coil Weights
Table 21. Weights for fan coil units
The weights are approximate. Risers, external sheet metal accessories and supply air grilles are not included in the weight.
Dimensions and Weights
Size Weight
350 140 lbs (63 kg)
450 150 lbs (68 kg) 600 170 lbs (77 kg)
800 180 lbs (82 kg) 1000 210 lbs (95 kg) 1200 220 lbs (100 kg)
UNT-PRC019-EN 35
Mechanical Specifications
Certifications
Performance: Unit per formance is certified by AHRI in accordance with ANSI/AHRI 440-2008: Performance Rating of Room Fan-Coils.
Safety: All standard units are agency listed in the United States and Canada and comply with the requirements of the current editions of UL 1995/CSA C22.2 No. 236.
Construction
The cabinets shall be fabricated from 18 g age steel lined with ½-inc h fiberglass insulation bonded with a thermosetting resin and coated on the airstream side with an acrylic facing. In addition, there is an option available for 3/8-inch closed cell cabinet insulation.
The drain pan shall be an acrylic (black polyester powder) coated 20 gauge galvanized steel positively sloped in two directions towards the outlet. The drain pan shall be insulated on the underside with ½-inch fiberg lass insulation (same as cabinet). The drain hose from the outlet to the condensate riser shall form a running trap. An optional Stainless Steel drain pan is also available. A drain pan float switc h is also available. The float switc h will close CW control valve upon detection of high water level in condensate drain pan.
Fan
The galvanized metal fan wh eels are centrifugal forward-curv ed and double-width. Fan wheels and housings are corrosion resistant.
Motors
The fan motor shall be a three speed P.S.C. type with internal thermal protection and sealed bearings. All motors have a maximum ambient operating temperature of 104°F and are permanently lubricated.
An optional ECM type brushless fan motor is ava ilable. The motor is available, programmed at the factory for three (3) discrete speed operation. A variable speed EC motor is also available for use with a 2-10V DC signal.
An unfused service disconnect switch shall be included, mounted inside the unit behind the motor cover.
Coils
The coil shall have aluminum fins mechanic al ly b onded to ½-in ch copper tube. The coil shall be factory pressure tested at not less than 300 psig. A manual air vent shall be incorporated at the high point, and a drain cock at the low point of the connecting pipework to the coil.
Piping Packages
The piping package shall include: Ball type shut-off valves on the coil supply and returns (combined with balancing valves or strainers when used), and a two- or three-way control valve with two­position actuator. Chilled water and hot water valves are normally closed.
Control valves are also available in 3 wire floating point or 2-10V DC modulating valves. Additionally balancing valves (manual or automatic) and strainers supplied as riser system dictates. These devices are provided as combo-valves with the shut-off on supply and ret urn and can be equipped with PT ports.
Electric Heat
Units with electric heat shall be wired for single-stage operation with an open wire nickel-c hrome element. An auto-reset high limit device shall be included.
36 UNT-PRC019-EN
Filters
Controls
Mechanical Specifications
A one-inch disposable filter shall be shipped loose with the return air access panel. Units equipped with one inc h MER V 10 filters have a rating based on ASHRAE Standard 52.2. The
average dust spot efficiency is no less than 35 to 40 percent when tested in accordance with ASHRAE 52.1 atmospheric dust spot method.
Units equipped with one inch MERV 13 filters have a rating based on A SHRAE Standard 52.2. The average dust spot efficiency is no less than 90 percent efficiency on 1–3 micron particles and greater than 90 percent efficiency on 3–10 micron particles when tested in accordance with ASHRAE Test Standard 52.2.
Thermostat (option)
The fan coil manufacturer shall supply a low voltage (24V) thermostat for remote mounting, or optionally unit mounted. Remote mounted thermostats are connected to a terminal strip that is mounted inside the unit. The thermostat is ship ped loose for installation af ter the unit is installed, dry-wall is applied and the walls are painted.
Line voltage controls for unit mounting is also available. Thermostat quick-connect plug provided; thermostat ships loose for installation after drywall is applied and walls are painted.
Tracer ZN521 (option)
The T racer ZN521 discrete speed controller can be used in a stand-alone application or used as part of a T rane Integrated Comfort S ystem (ICS) with LonT alk® communication. The T racer ZN521 offers the combined advantages of simple and dependable operation. Standard control features include options normally available on more elaborate control systems. All control options are available factory-mounted and can be field-configured using a service tool.
Riser Package
Tracer UC400 (option)
The T racer UC400 controller delivers single zone VA V control in a stand-alone application or as part of a Trane Integrated Comfort system with BACnet® communication. Standard control features include options normally available on more elaborate control systems.
Risers are available in both type “L” and type “M” copper for supply, return and condensate pipes. Riser insulation is available in ½-inch and one-inch wall thic kness for closed cell foam (polyolefin), closed cell elastomeric (similar to Armaflex®) and fiberglass (wrapped with vapor barrier).
Riser diameter and insulation thickness are subject to physical limitations. Contact Trane when risers are larger than 2 1/2 inches in diameter. The risers shall have an approximately 2 1/2 inch swaged expansion at the top end to allow a 2 inch insertion of the riser from above without the use of couplings. Risers may be provided plain ended in lieu of swaged for field supplied/installed fittings (similar to Pro-Press®).
The riser insulation shall have a flame spread rating of 25 or less and a smoke dev eloped rating of 50 or less in compliance with AST M E 84. The insulation shall be continuous over the riser length within the height of the cabinet. Provision for insulation beyond the ends of the cabinet shall be the responsibility of the installing contractor.
The specification of riser anchoring, expansion loops and fire stopping requirements are not detailed in this specification and are not part of the Trane fan coils scope. Trane can provide expansion loops installed on the risers at the factory as per the engineers specification.
Hot water risers which are continuous over twelve or more floors may incorporate expansion compensation loops within the fan coil cabinet, location and spacing of expansion joints are the responsibility of the design engineer.
UNT-PRC019-EN 37
Mechanical Specifications
Return Air Access Panel
The return air access panel shall have a fixed blade return air grille in the lower portion with filter access achieved by removal of the panel. The panel installs flush on to the drywall which has been applied directly to the front of the unit. The panel is of stamped steel construction and shall be finished in standard white baked enamel. The panel secures to the unit by a hook on the bottom edge and two quarter -turn fasteners in the upper corners. The panel is shipped loose for installation after the unit is installed, dry-wall is applied and the walls are painted.
There is also a return air access panel with hinged filter access as an option. Stamped steel construction with return air grille in lower portion of grille and hinged filter access in the top portion. Secured to the two-inch flange on the front of the unit with sheet metal screws. Drywall is framed out in front of the unit and is not applied directly to the unit face.
Supply Air Grilles and Registers
Supply air grilles and registers shall be provided for unit mounting locations. The grilles shall be steel, have double deflection ai rfoil blade s and shall be finished in standard white baked enamel. The grilles shall attach to the collar of the fan coil uni t by spring clips. When a unit has more than one supply air opening a balancing dam p er (horizontal in the front) is included with the grille (register) to balance the air flow (screw holes optional). Any supply air grilles which are part of supply air ductwork shall be provided by the sheet metal contractor. Grilles are shipped loose for installation after the unit is installed, dry-wall applied and the walls are painted.
A line of sight baffle with acoustical wrap shall be included in units which have left and right or front and back supply air openings.
There is also an option to upgrade the supply air grille material to aluminum as well as the option to provide custom colors for return air panels and supply air grilles/registers.
Raised Bases
Raised bases are available in heights of 4 inches, 8 inches or 12 inc hes. An access panel is available only in the 12-inc h hei ght option. If a co ndensate pump is required, 12-inch high raised base with access panel is required.
38 UNT-PRC019-EN
Notes
Notes
UNT-PRC019-EN 39
4008161
ETL LISTED
CONFORMS TO
UL STD 1995
CERTIFIED TO
CSA STD C22.2 NO. 236
Trane optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the leader in creating and sustaining safe, comfortable and energy efficient environments, Trane offers a broad portfolio of advanced controls and HVAC systems, comprehensive building services, and parts. For more information, visit www.Trane.com.
Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.
© 2013 Trane All rights reserved UNT-PRC019-EN 15 July 201 3 (NEW)
We are committed to using environmentally conscious print practices that reduce waste.
Loading...