Trane VCCF04 - 24, VCEF04 - 24, VCWF04 - 24 Installation and Maintenance Manual

VariTrane™ Single-Duct and Fan-Powered Units
All VariTrane VAV models with pneumatic, electronic, DDC controls, and diffusers.
VCCF04 - 24 VCEF04 - 24 VCWF04 - 24
SAFETY WARNING
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment.
September 2014
VAV-SVX08E-EN

Introduction

Read this manual thoroughly before operating or servici ng this unit.

Warnings, Cautions, and Notices

Safety advisories appear throughout this manual as required. Your personal safety and the proper operation of this machine depend upon the strict observance of these precautions.
The three types of advisories are defined as follows:
WARNING
Proper Field Wiring and Grounding Required!
Failure to follow code could result in death or serious injury. All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state electrical codes.
WARNING
CAUTIONs
NOTICE
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
Indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury. It could also be used to alert against unsafe practices.
Indicates a situation that could result in equipment or property-damage only accidents.

Important Environmental Concerns

Scientific research has shown that certain man-made chemicals can affect the earth’s naturally occurring stratospheric ozone layer when released to the atmosphere. In particular, several of the identified chemicals that may affect the ozone layer are refrigerants that contain Chlorine, Fluorine and Carbon (CFCs) and those containing Hydrogen, Chlorine, Fluorine and Carbon (HCFCs). Not all refrigerants containing these compounds have the same potential impact to the environment. Trane advocates the responsible handling of all refrigerants-including industry replacements for CFCs such as HCFCs and HFCs.

Important Responsible Refrigerant Practices

Trane believes that responsible refrigerant practices are important to the environment, our customers, and the air conditioning industry. All technicians who handle refrigerants must be certified. The Federal Clean Air Act (Section 608) sets forth the requirements for handling, reclaiming, recovering and recycling of certain refrigerants and the equipment that is used in these service procedures. In addition, some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants. Know the applicable laws and follow them.
WARNING
Personal Protective Equipment (PPE) Required!
Installing/servicing this unit could result in exposure to electrical, mechanical and chemical hazards.
Before installing/servicing this unit, technicians MUST put on all PPE required for the work being undertaken (Examples; cut resistant gloves/sleeves, butyl gloves, safety glasses, hard hat/bump cap, fall protection, electrical PPE and arc flash clothing). ALWAYS refer to appropriate Material Safety Data Sheets (MSDS)/Safety Data Sheets (SDS) and OSHA guidelines for proper PPE.
When working with or around hazardous chemicals, ALWAYS refer to the appropriate MSDS/SDS and OSHA/GHS (Global Harmonized System of Classification and Labelling of Chemicals) guidelines for information on allowable personal exposure levels, proper respiratory protection and handling instructions.
If there is a risk of energized electrical contact, arc, or flash, technicians MUST put on all PPE in accordance with OSHA, NFPA 70E, or other country-specific requirements for arc flash protection, PRIOR to servicing the unit. NEVER PERFORM ANY SWITCHING, DISCONNECTING, OR VOLTAGE TESTING WITHOUT PROPER ELECTRICAL PPE AND ARC FLASH CLOTHING. ENSURE ELECTRICAL METERS AND EQUIPMENT ARE PROPERLY RATED FOR INTENDED VOLTAGE.
Failure to follow instructions could result in death or serious injury.
© 2014 Trane All rights reserved VAV-SVX08E-EN
WARNING
Fiberglass Wool!
Product contains fiberglass wool. Disturbing the insulation in this product during installation, maintenance or repair will expose you to airborne particles of glass wool fibers and ceramic fibers known to the state of California to cause cancer through inhalation. Glass wool fibers could result in respiratory, skin or eye irritation.

Introduction

This manual describes the installation of VariTrane™ VAV units with recommended wiring, piping, and mounting of single-duct, dual-duct, fan-powered, low-height terminal units, and diffusers.
See also the following reference documents:
BAS-SVX40A-EN —Wireless Comm IOM
BAS-SVX55A-EN — Wireless Comm Network Design Best Practices Guide

Receiving and Handling

VariTrane units are shipped completely assembled with the exceptions of optional attenuators for fan-powered units and accessories.
Upon receiving the equipment, complete the following:
Locate the nameplate and refer to the model and sales order number and check that the correct units have been delivered.
Inspect the control enclosures and air valve casing for dents or punctures.
Verify that all options have been included, such as filters, controls, heating coils, water valves, etc. Also check that the unit voltages agree with the building parameters.
Manually rotate fan (if applicable) to assure that there are no obstructions within the housing.
Claims for in-transit damage must be filed immediately with the delivery carrier.
For hot water re-heat units, check the coil fins and make sure that coils are not damaged.
Locate and verify that the correct zone sensors are with the order. These will be marked with an orange “Accessories Enclosed” label. Store in a secure location until needed. Accessories lost at the job site are NOT covered by Trane’s warranty.
If a discrepancy occurs between what was ordered and what is received, contact you local Trane representative immediately.
Read appropriate section in this manual for installation procedures prior to starting equipment.
Introduction
Upon receiving the equipment, please inspect each unit and components for external or internal damage. Refer to the bill of lading to insure all equipment and accessories have been received. Contact your local Trane sales representative and notify the trucking company immediately of any short ship or damaged equipment.
Copyright
This document and the information in it are the property of Trane, and may not be used or reproduced in whole or in part without written permission. Trane reserves the right to revise this publication at any time, and to make changes to its content without obligation to notify any person of such revision or change.
Trademarks
Trane, VariTrane and the Trane logo are trademarks or registered trademarks of Trane in the United States and other countries. Trane is a business of Ingersoll Rand. All trademarks referenced in this document are the trademarks of their respective owners.
LonTalk is a registered trademarks of Echelon Corporation.
Revision History
VAV-SVX08E-EN (16 Sep 2014)
Updated for universal mount project.
VAV-SVX08D-EN (11 Jul 2013)
Updated model number for Sinro valve.
VAV-SVX08D-EN (27 Jun 2013)
Added Bottom Access with Cam Lock configuration and stand alone control information for UCM 4.2, VV550 LonTalk, UC400, UC210 and WCI.
VAV-SVX08E-EN 3

Table of Contents

Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Warnings, Cautions, and Notices . . . . . . . . 2
Important Environmental Concerns . . . . . 2
Important Responsible Refrigerant
Practices . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Receiving and Handling . . . . . . . . . . . . . . . 3
Model Number Descriptions . . . . . . . . . . . . . . 5
Single-Duct Units . . . . . . . . . . . . . . . . . . . . . . 5
Dual-Duct Units . . . . . . . . . . . . . . . . . . . . . . . 8
Fan-Powered Units . . . . . . . . . . . . . . . . . . . . 9
Unit Information . . . . . . . . . . . . . . . . . . . . . . . . 11
Single-Duct Units . . . . . . . . . . . . . . . . . . . 11
Dual-Duct Units . . . . . . . . . . . . . . . . . . . . 11
Fan-Powered and Fan-Powered
Low-Height Units . . . . . . . . . . . . . . . . . . . 12
Unit Installation . . . . . . . . . . . . . . . . . . . . . . . . 13
Unit Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
(SCR) Motor Speed Control Adjustment
Procedure. . . . . . . . . . . . . . . . . . . . . . . . . . 28
Electrically Commutated Motor (ECM) . . 28
Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . 42
Heaters with Contactors . . . . . . . . . . . . . . . 42
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Installation of Diffusers . . . . . . . . . . . . . . . . . . 53
General . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
T-Bar Ceiling . . . . . . . . . . . . . . . . . . . . . . . 53
Concealed Spline Ceiling . . . . . . . . . . . . . 53
Drywall/Plaster Ceiling . . . . . . . . . . . . . . . 54
4 VAV-SVX08E-EN

Model Number Descriptions

Single-Duct Units

Digit 1, 2 — Unit Type
VC = VariTrane Single Duct
Digit 3—Reheat
C = Cooling Only E = Electric Heat W = Hot Water Heat
Digit 4—Development Sequence
F= Sixth
Digit 5, 6—Primary Air Valve
04 = 4" inlet (225 cfm) 05 = 5" inlet (350 cfm) 06 = 6" inlet (500 cfm) 08 = 8" inlet (900 cfm) 10 = 10" in le t (140 0 cfm ) 12 = 12" inlet (20 00 cfm) 14 = 14" inlet (300 0 cfm) 16 = 16" inlet (40 00 cfm) 24 = 24" x 16" inlet (8000 cfm)
Digit 7, 8, 9—Not Used
000= N/A
Digit 10, 11—Design Sequence
** = Factory Assigned
Digit 12, 13, 14, 15—Controls
DD00 Trane Actuator Only and
Enclosure DD01= UCM4 Cooling Only Control DD02= UCM4 N.C. On/Off Hot Water DD03= UCM4 Prop. Hot Water DD04= UCM4 Staged On/Off E-Heat DD05= UCM4 Pulse Width MOD E-Heat DD07= UCM4 N.O. On/Off Hot Water DD11= VV550 DDC Controller - Cooling
Only DD12= VV550 DDC Ctrl to operate N.C.
On/Off water valve DD13= VV550 DDC Ctrl to operate Prop
water valve DD14= VV550 DDC Ctrl - On/Off Electric
Heat DD15= VV550 DDC Ctrl w/Pulse Width
Modulation DD16= VV550 DDC Controller -
Ventilation Flow DD17= VV550 DDC Ctrl to operate N.O.
On/Off Water Valve DD19= VV550 DDC Controller with Flow
Trac ki ng DD20= VV550 DDC Vent Flow cntrl to
operate N.C. water valve DD21= VV550 DDC - Vent Flow w/ On/Off
Elec Heat DD22= VV550 DDC Vent Flow cntrl to
operate prop water valve DD23= VV550 DDC- Basic plus- Local
(Electric heat- PWM) Remote
(Staged EH) DD24= VV550 DDC-Basic plus- Local
(Water heat- Modulating)
Remote (Water- N.C. 2 position) DD25= VV550 DDC-Basic plus- Local
(Water heat- Modulating)
Remote (Water- N.O. 2 position) DD26= VV550 DDC-Basic plus- Local
VAV-SVX08E-EN 5
DD27= VV550 DDC-Basic plus- Local
DD28= VV550 DDC-Basic plus- Local
DD29= VV550 DDC-Basic plus- Local
DD30= VV550 DDC-Basic plus- Local
DD31= VV550 DDC-Basic plus- Local
DD32= VV550 DDC-Basic plus- Local
DD33= VV550 DDC Vent Flow cntrl to
DD41= UC400 DDC-Basic (No water or
DD42= UC400 DDC-Basic (Water heat-
DD43= UC400 DDC-Basic (Water heat-
DD44= UC400 DDC-Basic (Electric heat-
DD45= UC400 DDC-Basic (Electric heat-
DD46= UC400 DDC Ventilation flow-
DD47= UC400 DDC-Basic (Water heat-
DD49= UC400 DDC-Flow Tracking
DD50= UC400 DDC-Ventilation Flow
DD51= UC400 DDC-Ventilation Flow
DD52= UC400 DDC-Ventilation Flow
DD53= UC400 DDC-Basic plus- Local
DD54= UC400 DDC-Basic plus- Local
DD55= UC400 DDC-Basic plus- Local
DD56= UC400 DDC-Basic plus- Local
DD57= UC400 DDC-Basic plus- Local
DD58= UC400 DDC-Basic plus- Local
DD59= UC400 DDC-Basic plus- Local
DD60= UC400 DDC-Basic plus- Local
DD61= UC400 DDC-Basic plus- Local
(Water heat- N.O. 2-position) Remote (Water- Modulating)
(Water heat- N.C. 2-position) Remote (Water- Modulating)
(Water heat- N.O. 2-position) Remote (Water- N.O. 2-position)
(Water heat- N.C. 2-position) Remote (Water- NC 2-position)
(Water heat- N.O. 2-position) Remote (Water- N.C. 2-position)
(Water heat- N.C. 2-position) Remote (Water- N.O. 2-position)
(Electric heat- Staged) Remote (Staged EH)
operate N.O. On/Off water valve
electric heat)
N.C.- 2 position)
Modulating)
staged)
PWM)
cooling only
N.O.- 2 position)
(Cooling only)
(Water heat- N. C.- 2 position)
(Electric heat- staged)
(Water heat- Modulating)
(Electric heat- PWM) Remote (Staged EH)
(Water heat- Modulating) Remote (Water- N.C. 2 position)
(Water heat- Modulating) Remote (Water- N.O. 2 position)
(Water heat- N.O. 2-position) Remote (Water- Modulating)
(Water heat- N.C. 2-position) Remote (Water- Modulating)
(Water heat- N.O. 2-position) Remote (Water- N.O. 2-position)
(Water heat- N.C. 2-position) Remote (Water- N.C. 2-position)
(Water heat- N.O. 2-position) Remote (Water- N.C. 2-position)
(Water heat- N.C. 2-position)
DD62= UC400 DDC-Basic plus- Local
DD63= UC400 DDC-Ventilation Flow
DD65= UC400 Basic
DD66= UC400 Basic plus-Local
DD67= UC400 Ventilation Flow
DD71= UC210 DDC-Basic (No water or
DD72= UC210 DDC-Basic (Water heat-
DD73= UC400 DDC-Basic (Water heat-
DD74= UC210 DDC-Basic (Electric heat-
DD75= UC210 DDC-Basic (Electric heat-
DD76= UC210 DDC Ventilation flow-
DD77= UC210 DDC-Basic (Water heat-
DD79= UC210 DDC-Flow Tracking
DD80= UC210 DDC-Ventilation Flow
DD81= UC210 DDC-Ventilation Flow
DD82= UC210 DDC-Ventilation Flow
DD83= UC210 DDC-Basic plus- Local
DD84= UC210 DDC-Basic plus- Local
DD85= UC210 DDC-Basic plus- Local
DD86= UC210 DDC-Basic plus- Local
DD87= UC210 DDC-Basic plus- Local
DD88= UC210 DDC-Basic plus- Local
DD89= UC210 DDC-Basic plus- Local
DD90= UC210 DDC-Basic plus- Local
DD91= UC210 DDC-Basic plus- Local
DD92= UC210 DDC-Basic plus- Local
DD93= UC210 Ventilation Flow
DD95= UC210 Basic
DD96= UC210 Basic plus-Local
Remote (Water- N.O. 2-position)
(Electric heat- Staged) Remote (Staged EH)
(Water heat- N.O. 2-position)
(Electric HeatModulating SCR)
(Electric heat-Modulating SCR) Remote (Staged EH)
(Electric heat-Modulating SCR)
electric heat)
N.C.- 2 position)
Modulating)
staged)
PWM)
cooling only
N.O.- 2 position)
(Cooling only)
(Water heat- N. C.- 2 position)
(Electric heat- staged)
(Water heat- Modulating)
(Electric heat- PWM) Remote (Staged EH)
(Water heat- Modulating) Remote (Water- N.C. 2 position)
(Water heat- Modulating) Remote (Water- N.O. 2 position)
(Water heat- N.O. 2-position) Remote (Water- Modulating)
(Water heat- N.C. 2-position) Remote (Water- Modulating)
(Water heat- N.O. 2-position) Remote (Water- N.O. 2-position)
(Water heat- N.C. 2-position) Remote (Water- N.C. 2-position)
(Water heat- N.O. 2-position) Remote (Water- N.C. 2-position)
(Water heat- N.C. 2-position) Remote (Water- N.O. 2-position)
(Electric heat- Staged) Remote (Staged EH)
(Water heat- N.O. 2-position)
(Electric HeatModulating SCR)
Model Number Descriptions
(Electric heat-Modulating SCR)
DD97= UC210 Ventilation Flow
ENCL= Shaft Only in Enclosure ENON= Shaft Out Side for Electric Units FM00= Other Actuator and Control FM01= Trane Supplied Actuator, Other
PC00= N.C. Actuator and Linkage Only PC04= N.C. with DA Stat, 3000 Series PC05= N.C. with RA STAT, 3000 Series PCSS= Normally Closed Special PN00= N.O. Actuator and Linkage Only PN04= N.O. 3000 Series, DA STAT PN05= N.O. 3000 Series, RA STAT PN11= Auto Dual Min. PN32= N.O. PNEU Constant Vol. PN34= N.O. 3000 Series Constant
PNON= Shaft Out Side for Pneumatic
PNSS= Normally Open Special N.C .= Normally-closed N.O. = Normally-opened
DA Stat = Direct-acting pneumatic t-stat
RA Stat = Reverse-acting pneumatic
PN = Pneumatic FM = Factory installation of customer-
PVR = Pneumatic Volume Regulator
Remote (Staged EH)
(Electric heat-Modulating SCR)
Ctrl
Vol.,RA STAT
Units
(by others)
t-stat (by others)
supplied controller
Digit 16—Insulation
A = 1/2" Matte-faced B = 1" Matte-faced D = 1" Foil-faced F = 1" Double-wall G = 3/8" Closed-cell
Digit 17 & 18—Not Used
00 = N/A
Digit 19—Outlet Plenum
(Connection is Slip & Drive)
0= None A= 1 Outlet RH B= 1 Outlet END C = 1 Outlet LH D = 2 Outlets, 1 RH, 1 END E = 2 Outlets, 1 LH, 1 END F = 2 Outlets, 1 RH, 1 LH H = 3 Outlets, 1 LH, 1 RH, 1 END J = 4 Outlets, 1 LH, 1 RH, 2 END
Note: See unit drawings for outlet sizes/
damper information.
Digit 20—Not Used
0= N/A
Digit 21—Water Coil
0= None 1= 1-Row 2= 2-Row 3= 3-Row 4= 4-Row A= 1-Row Premium B = 2-Row Premium C = 3-Row Premium D = 4-Row Premium
Digit 22—Electrical Connections
F = Flippable (can be flipped in the
field for LH or RH connections
- VCEF only)
L = Left (Airflow hitting you in the
face)
R = Right (Airflow hitting you in the
face)
0 = Opposite side connection – coil
and control (VCWF only)
Note: VCCF, VCWF can be flipped in field
for opposite-hand connection
Digit 23—Transformer
0= None 1 = 120/24 volt (50 VA) 2 = 208/24 volt (50 VA) 3 = 240/24 volt (50 VA) 4 = 277/24 volt (50 VA) 5 = 480/24 volt (50 VA) 6 = 347/24 Volt (50 VA) 7 = 380/24 Volt (50 VA) 8 = 575/24 Volt (50 VA)
Note: For VCEF units with transformers
the VA depends on the staging, control, and contactor type (ranges are 50 VA to 75 VA, for 1 and 3 phase)
Digit 24—Disconnect Switch
0= None W= With
Note: VCCF, VCWF – Toggle Disconnect;
VCEF – Door Interlocking Power Disconnect
Digit 25—Power Fuse
0= None W= With
Digit 26—Electric Heat Voltage
0= None A = 208/60/1 B = 208/60/3 C = 240/60/1 D = 277/60/1 E = 480/60/1 F = 480/60/3 G = 347/60/1 H = 575/60/3 J = 380/50/3 K = 120/60/1
Digit 27 - 29—Electric Heat kW
000= None 010 = 1.0 kW 015 = 1.5 kW 460 = 46.0 kW
Note: 0.5 to 8.0 kW – ½ kW increments
8.0 to 18.0 kW – 1 kW increments
18.0 to 46.0 kW – 2 kW increments
Digit 30—Electric Heat Stages
0= None 1 = 1 Stage 2 = 2 Stages Equal 3 = 3 Stages Equal
Digit 31—Electrical Heat
Contactors
0= None 1 = 24-volt magnetic 2 = 24-volt mercury 3 = PE with magnetic 4 = PE with mercury 5 = SCR heat UC400/UC210 6 = SCR heat FMTD/ENCL/DD00 A = 24-volt mercury (left hand) B = 24-volt mercury (right hand) C = PE with mercury (left hand) D = PE with mercury (right hand)
Digit 32 & 33—Not Used
00 = N/A
Digit 34—Actuator
0= Standard A = Spring Return (Normally Open) B = Spring Return (Normally Closed) C = Belimo Actuator
Digit 35—Sensor Options
0 = Standard (Wired) 1 = Factory Mounted Wireless
Receiver (Sensor Accessory)
2 = Wireless Comm Interface
Modular FM
Digit 36—Pre-Wired Factory Solutions
0= None 1 = Factory Mounted DTS 2 = HW Valve Harness 3 = Both DTS & HW Valve Harness 4 = Averaging DTS factory installed
in unit (Required for UC210/UC400 with SCR heat)
Digit 37—Bottom Access with Cam Locks
0= None 1 = Access Left Side Terminal Unit 2 = Access Right Side Terminal Unit 3 = Access Left Side Terminal Unit
with Water Connection on Right
4 = Access Right Side Terminal Unit
with Water Coil Connection on Left
6 VAV-SVX08E-EN
Model Number Descriptions
Digit 38—Piping Package
0= None A = 2-way Automatic Balancing) B = 3-way Automatic Balancing
Digit 39—Water Valve
0= None 1 = Proportional, HW Valve, 0.7 Cv 2 = Proportional, HW Valve, 2.7 Cv 3 = Proportional, HW Valve, 6.6 Cv 4 = Proportional, HW Valve, 8.0Cv
Digit 40—Flow Rate
00 = None A = 0.5 gpm (0.03 l/s) B = 1.0 gpm (0.06 l/s) C = 1.5 gpm (0.09 l/s) D = 2.0 gpm (0.13 l/s) E = 2.5 gpm (0.16 l/s) F = 3.0 gpm (0.19 l/s) G = 3.5 gpm (0.22 l/s) H = 4.0 gpm (0.25 l/s) J = 4.5 gpm (0.28 l/s) K = 5.0 gpm (0.31 l/s) L = 5.5 gpm (0.35 l/s) M = 6.0 gpm (0.38 l/s) N = 6.5 gpm (0.41 l/s) P = 7.0 gpm (0.44 l/s) Q = 7.5 gpm (0.47 l/s) R = 8.0 gpm (0.50 l/s) S = 9.0 gpm (0.57 l/s) T = 10.0 gpm (0.63 l/s) U = 11.0 gpm (0.69 l/s) V = 12.0 gpm (0.76 l/s) W = 13.0 gpm (0.82 l/s) X = 14.0 gpm (0.88 l/s) Y = 15.0 gpm (0.95 l/s) Z = 16.0 gpm (1.01 l/s) 1 = 17.0 gpm (1.07 l/s) 2 = 18.0 gpm (1.14 l/s) 3 = 19.0 gpm (1.20 l/s) 4 = 20.0 gpm (1.26 l/s) 5 = 21.0 gpm (1.32 l/s) 6 = 22.0 gpm (1.39 l/s) 7 = 23.0 gpm (1.45 l/s)
VAV-SVX08E-EN 7
Model Number Descriptions

Dual-Duct Units

Digit 1, 2, 3—Unit Type
VDD= VariTrane dual-duct
Digit 4—Development Sequence
F= Sixth
Digit 5, 6—Primary Air Valve
05 = 5" inlet (350 cfm) 06 = 6" inlet (500 cfm) 08 = 6" inlet (900 cfm) 10 = 10" in le t (140 0 cfm ) 12 = 12" inlet (20 00 cfm) 14 = 14" inlet (300 0 cfm) 16 = 16" inlet (40 00 cfm)
Digit 7, 8—Secondary Air Valve
05 = 5" inlet (350 cfm) 06 = 6" inlet (500 cfm) 08 = 8" inlet (900 cfm) 10 = 10" in le t (140 0 cfm ) 12 = 12" inlet (20 00 cfm) 14 = 14" inlet (300 0 cfm) 16 = 16" inlet (40 00 cfm)
Digit 9—Not Used
0= N/A
Digit 10, 11—Design Sequence
** = Factory Assigned
Digit 12, 13, 14, 15—Controls
DD00= Trane Actuator Only DD01= UCM4 Cooling Only Control DD08= UCM4 Dual Duct
Constant Volume DD11= VV550 DDC Controller -
Cooling Only DD18= VV550 DDC Controller w
Constant Volume DD41= UC400 DDC-Basic (No water or
electric heat) DD48= UC400 DDC-Basic (Constant
Vol ume) DDSS= Digital Special ENON= Shaft Out Side for Electric
Units FM00= Other Actuator and Control FM01= Trane Supplied Actuator, Other
Ctrl PC03= NC Heating Valve, N.O. Cooling
Val ve PCSS= Normally Closed Special PN08= N.O. Heat/Cool Actuators &
Linkage Only PN09= N.O. Heating, N.O. Cooling,
w/PVR’s PN10= N.O. Heating, N.O. Cooling,
w/PVR’s (CV DISCH) PNON= Shaft Out Side for Pneumatic
Units PNSS= Normally Open Special
Notes:
N.C. = Normally-closed N.O. = Normally-opened DA Stat = Direct-acting pneumatic t-stat (by others) RA Stat = Reverse-acting pneumatic t­stat (by others) PN = Pneumatic FM = Factory installation of customer-
supplied controller PVR = Pneumatic Volume Regulator
Digit 16—Insulation
A = 1/2" Matte-faced B = 1" Matte-faced D = 1" Foil-faced F = 1" Double-wall G = 3/8" Closed-cell
Digit 17—Not Used
0= N/A
Digit 18—Not Used
0= N/A
Digit 19—Outlet Plenum (Connection is slip & drive)
0 = none A = 1 outlet–RH B = 1 outlet–END C = 1 outlet–LH D = 2 outlets–1 RH, 1 END E = 2 outlets–1 LH, 1 END F = 2 outlets–1 RH, 1 LH G = 2 outlets - END H = 3 outlets–1 LH, 1 RH, 1 END J = 4 outlets–1 LH, 1 RH, 2 END
Note: See unit drawings for outlet sizes/
damper information.
Digit 20—Not Used
0= N/A
Digit 21—Not Used
0= N/A
Digit 22—Not Used
0= N/A
Digit 23—Transformer
0= None 1 = 120/24 volt (50 VA) 2 = 208/24 volt (50 VA) 3 = 240/24 volt (50 VA) 4 = 277/24 volt (50VA) 5 = 480/24 volt (50 VA) 6 = 347/24 volt (50 VA) 7 = 575/24 volt (50 VA)
Digit 24—Disconnect Switch
0= None W = With Toggle
Digit 25—Power Fuse
0= None W= With
Digit 26—Not Used
0= N/A
Digit 27—Not Used
0= N/A
Digit 28—Not Used
0= N/A
Digit 29—Not Used
0= N/A
Digit 30—Not Used
0= N/A
Digit 31—Not Used
0= N/A
Digit 32—Not Used
0= N/A
Digit 33—Special Options
0= None X = Varies - Factory Assigned
Digit 34—Actuator
A = Belimo Actuator
Digit 35—Wireless Sensor
0 = Sensor/Receiver Standard 1 = Wireless Sensor/Receiver
Mounted
Note: All sensors selected in
accessories
Digit 36—Duct Temp Sensor
0= None 1 = With Duct Temp Sensor
8 VAV-SVX08E-EN
Model Number Descriptions

Fan-Powered Units

Digit 1, 2—Unit Type
VP = VariTrane Fan-Powered Parallel VS = VariTrane Fan-Powered Series LP = VariTrane Fan-Powered
Low-Height Parallel LS = VariTrane Fan-Powered
Low-Height Series
Digit 3—Reheat
C = Cooling Only E = Electric Heat W = Hot Water Heat
Digit 4—Development Sequence
F= Sixth
Digit 5, 6—Primary Air Valve
05 = 5" inlet (350 max cfm) 06 = 6" inlet (500 max cfm) 08 = 8" inlet (900 max cfm) 10 = 10" in le t (140 0 max cf m) 12 = 12" inlet (2000 max cfm) 14 = 14" inlet (3000 max cfm) 16 = 16" inlet (4000 max cfm) RT = 8" x 14" inlet (1800 max CFM)
Note: 10, 12, 14, 16 Not Available on
Low-Height
Digit 7, 8—Secondary Air Valve
00 = N/A
Digit 9—Fan
P = 02SQ fan (500 nominal cfm) Q = 03SQ fan (1100 nominal cfm) R = 04SQ fan (1350 nominal cfm) S = 05SQ fan (1550 nominal cfm) T = 06SQ fan (1850 nominal cfm) U = 07SQ fan (2000 nominal cfm) V = 08SQ Fan (500 nominal cfm) W = 09SQ Fan (900 nominal cfm) X = 10SQ Fan (1800 nominal cfm)
Digit 10, 11—Design Sequence
** = Factory assigned
Digit 12, 13, 14, 15—Controls
DD01= Cooling Only Control DD02= N.C. On/Off Hot Water DD03= Prop. Hot Water DD04= Staged On/Off E-Heat DD05= Pulse Width Mod of E-Heat DD07= N.O. On/Off Hot Water DD11= VV550 DDC Controller - Cooling
Only DD12= VV550 DDC Ctrl w/N.C. On/Off
HW Valve DD13= VV550 DDC Ctrl w/Prop. HW
Valve DD14= VV550 DDC Ctrl - On/Off
Electric Heat DD15= VV550 DDC Ctrl w/Pulse Width
Modulation DD17= VV550 DDC Ctrl w/N.O. On/Off
HW Valve DD23= VV550 DDC- Basic plus- Local
(Electric heat- PWM) Remote
(Staged EH) DD28= VV550 DDC-Basic plus- Local
(Water heat- N.O. 2-position)
Remote (Water- N.O. 2-position)
DD29= VV550 DDC-Basic plus- Local
(Water heat- N.C. 2-position) Remote (Water- N.C. 2-position)
DD30= VV550 DDC-Basic plus- Local
(Water heat- N.O. 2-position) Remote (Water- N.C. 2-position)
DD31= VV550 DDC-Basic plus- Local
(Water heat- N.C. 2-position) Remote (Water- N.O. 2-position)
DD32= VV550 DDC-Basic plus- Local
(Electric heat- Staged) Remote (Staged EH)
DD41= UC400 DDC-Basic (No water or
electric heat)
DD42= UC400 DDC-Basic (Water heat-
Normally Closed- 2 position)
DD43= UC400 DDC-Basic (Water heat-
Modulating)
DD44= UC400 DDC-Basic (Electric heat-
staged)
DD45= UC400 DDC-Basic (Electric heat-
PWM)
DD47= UC400 DDC-Basic (Water heat-
Normally Opened- 2 position)
DD53= UC400 DDC-Basic plus- Local
(Electric heat- PWM) Remote (Staged EH)
DD58= UC400 DDC-Basic plus- Local
(Water heat- N.O. 2-position) Remote (Water- N.O. 2-position)
DD59= UC400 DDC-Basic plus- Local
(Water heat- N.C. 2-position) Remote (Water- N.C. 2-position)
DD60= UC400 DDC-Basic plus- Local
(Water heat- N.O. 2-position) Remote (Water- N.C. 2-position)
DD61= UC400 DDC-Basic plus- Local
(Water heat- N.C. 2-position) Remote (Water- N.O. 2-position)
DD62= UC400 DDC-Basic plus- Local
(Electric heat- Staged) Remote (Staged EH)
DD65= Basic (Electric Heat- Modulating
SCR)
DD66= Basic plus – Local (Electric heat –
Modulating SCR) Remote (Staged EH)
DD71= UC210 DDC-Basic
(Cooling only)
DD72= UC210 DDC-Basic
(Water heat-nc 2pos)
DD73= UC210 DDC-Basic
(Water heat-Modulating)
DD74= UC210 DDC-Basic
(Electric heat-staged) DD75= UC210 DDC-Basic (Electric heat-pwm) DD77= UC210 DDC-Basic
(Water heat-NO 2pos) DD83= UC210 DDC-Basic+ Local
(Electric heat-pwm)
Remote (Staged) DD84= UC210 DDC-Basic+ Local
(Water heat Modulating)
Remote (Water-NC 2pos) DD85= UC210 DDC-Basic+ Local
(Water heat Modulating)
Remote (Water-NO 2pos)
DD86= UC210 DDC-Basic+ Local
(Water heat NO 2pos)
Remote (Water-Modulating)
DD87= UC210 DDC-Basic+ Local
(Water heat NC 2pos) Remote (Water-Modulating)
DD88= UC210 DDC-Basic+ Local
(Water heat NO 2pos) Remote (Water-NO 2pos)
DD89= UC210 DDC-Basic+ Local
(Water heat NC 2pos) Remote (Water-NC 2pos)
DD90= UC210 DDC-Basic+ Local
(Water heat NO 2pos) Remote (Water-NC 2pos)
DD91= UC210 DDC-Basic+ Local
(Water heat NC 2pos) Remote (Water-NO 2pos)
DD92= UC210 DDC-Basic+ Local
(Electric heat-staged) Remote (Staged)
DD95= UC210 DDC-Ctrl w/Modulating
SCR
DD96= UC210 DDC-Space Temp Ctrl w/
Local SCR & Remote Stge Elec
Heat DD00= Trane Actuator Only ENCL= Shaft Only in Enclosure ENON= Shaft Out Side for Electric Units FM00= Other Actuator and Control FM01= Trane supplied actuator,
other control PN00= N.O. Actuator and Linkage Only PN05= N.O. 3000 Series, RA Stat PN51= Pneumatic normally open
w/3011,DPS fan PN52= Pneumatic normally open
w/3011, DPM fan PNON= Shaft Out Side for Pneumatic
Units
Notes:
N.C. = Normally-closed N.O. = Normally-opened DA Stat = Direct-acting pneumatic t-stat
(by others)
RA Stat = Reverse-acting pneumatic
t-stat (by others) PN = Pneumatic FM = Factory installation of customer-
supplied controller PVR = Pneumatic Volume Regulator
Digit 16—Insulation
A = 1/2” Matte-faced B = 1" Matte-faced D = 1" Foil-faced F = 1" Double-wall G = 3/8” Closed-cell
Digit 17—Motor Type
D = PSC Motor E = High-efficiency motor (ECM)
Digit 18—Motor Voltage
1 = 115/60/1 2 = 277/60/1 3 = 347/60/1 4 = 208/60/1 5 = 230/50/1
VAV-SVX08E-EN 9
Model Number Descriptions
Digit 19—Outlet Connection
1 = Flanged 2 = Slip & Drive
Digit 20—Attenuator
0 = No Attenuator W = With Attenuator
Digit 21—Water Coil
0= None 1 = 1-Row–Plenum inlet installed RH 2 = 2-Row–Plenum inlet installed RH 3 = 1-Row–Discharge installed, LH 4 = 1-Row–Discharge installed, RH 5 = 2-Row–Discharge installed, LH 6 = 2-Row–Discharge installed, RH1 A = 1-Row–Premium water coil inlet B = 2-Row–Premium water coil inlet C = 1-Row–Premium hot coil
on discharge, LH
D = 1-Row–Premium hot coil
on discharge, RH
E = 2-Row–Premium hot coil
on discharge, LH
F = 2-Row–Premium hot coil
on discharge, RH
Note: 1- and 2-row not available with
Low-Height
Digit 22—Electrical Connections
L = Left (Airflow hitting you in the
face)
R = Right (Airflow hitting you in the
face)
W = Narrow Corridor LH, Hi-Volt Inlet
Facing
X = Narrow Corridor RH, Hi-Volt Inlet
Facing
Note: (W & X) Fan Powered Series Only
Digit 23—Transformer
0 = N/A (provided as standard)
Digit 24—Disconnect Switch
0= None W= With Electric Reheat w/ door interlocking power disconnect, Cooling Only and Water Reheat w/ toggle disconnect
Digit 25—Power Fuse
0= None W= With
Digit 26—Electric Heat Voltage
0= None A = 208/60/1 B = 208/60/3 C = 240/60/1 D = 277/60/1 E = 480/60/1 F = 480/60/3 G = 347/60/1 H = 575/60/3 J = 380/50/3 K = 120/60/1
Note: K not available with Low Height
Digit 27, 28, 29—Electric Heat kW
000= None 050 = 0.5 kW 010 = 1.0 kW 015 = 1.5 kW 260 = 26.0 kW
Note: Electric Heat Voltage -
0.5 to 8.0 kW–½ kW increments
8.0 to 18.0 kW –1 kW increments
18.0 to 46.0 kW–2 kW increments
Digit 30—Electric Heat Stages
0= None 1 = 1 Stage 2 = 2 Stages Equal 3 = 3 Stages Equal
Note: 3 not available with Low Height
Digit 31—Contactors
0= None 1 = 24-volt magnetic 2 = 24-volt mercury 3 = PE with magnetic 4 = PE with mercury 5 = SCR heat UC400 6 = SCR heat FMTD/ENCL/DD00
Note: SCR cannot be selected with the
following configuration:
KW > 10, 208 volt 3 phase, Low
Height
KW > 22, 480 volt 3 phase, Low
Height
Voltage = 575 volt
Digit 32—Airflow Switch
0= None W= With
Digit 33—Not Used
0= N/A
Digit 34—Actuator
0 = Standard A = Belimo actuator
Digit 35—Wireless Sensors
0= None 1 = Factory Mounted Wireless
Receiver (Sensor Assembly)
2 = Wireless Comm Interface
Modular FM
Note: All sensors selected in
accessories
Digit 36—Pre-Wired Factory Solutions
0= None 1 = Factory Mounted DTS 2 = HW Valve Harness 3 = Both DTS & HW Valve Harness
Digit 37—Bottom Access
0= None W = Access Left Side of Terminal Unit
Digit 38—Piping Package
0= None A = 2-way Automatic Balancing) B = 3-way Automatic Balancing
Digit 39—Water Valve
0= None 1 = Proportional, HW Valve, 0.7 Cv 2 = Proportional, HW Valve, 2.7 Cv 3 = Proportional, HW Valve, 6.6 Cv 4 = Proportional, HW Valve, 8.0Cv
Digit 40—Flow Rate
0= None A = 0.5 gpm (0.03 l/s) B = 1.0 gpm (0.06 l/s) C = 1.5 gpm (0.09 l/s) D = 2.0 gpm (0.13 l/s) E = 2.5 gpm (0.16 l/s) F = 3.0 gpm (0.19 l/s) G = 3.5 gpm (0.22 l/s) H = 4.0 gpm (0.25 l/s) J = 4.5 gpm (0.28 l/s) K = 5.0 gpm (0.31 l/s) L = 5.5 gpm (0.35 l/s) M = 6.0 gpm (0.38 l/s) N = 6.5 gpm (0.41 l/s) P = 7.0 gpm (0.44 l/s) Q = 7.5 gpm (0.47 l/s) R = 8.0 gpm (0.50 l/s) S = 9.0 gpm (0.57 l/s) T = 10.0 gpm (0.63 l/s) U = 11.0 gpm (0.69 l/s) V = 12.0 gpm (0.76 l/s) W = 13.0 gpm (0.82 l/s)
10 VAV-SVX08E-EN

Unit Information

Single-Duct Units

The basic unit consists of a sheet metal casing with an air valve, which is used to modulate the air being delivered into the occupied zone. The unit is designed to modulate either cooling or heating air between the temperatures of 40°F and 140°F. Air enters the air valve through the round or rectangular inlet and exits into the sheet metal casing to be distributed to the zone either through integral round outlets in the casing or through rectangular duct attached to the discharge of the unit.
The basic unit can also be ordered with factory-mounted electric or hot water heating coils attached to the discharge. See Figure 2, p. 11.
These re-heat units are used primarily to reheat air-to-zone temperature when the load in the occupied space is low.
Primary air is modulated through the VariTrane air valve by rotating the damper blade. All air valves have a round/ rectangular inlet for easy fit-up with incoming duct work.
Typical Single-Duct Units
Figure 1. Typical single duct unit — VCCF
Figure 2. Typical single duct unit — VCWF
Figure 3. Typical single duct unit — VCEF

Dual-Duct Units

Dual-duct units provide two air valves: one as heating primary air and the other as cooling primary air. Both discharge into the common outlet, which leads to the zone being controlled. See Figure 4, p. 11.
Units are provided with a slip and drive rectangular duct connection or can be ordered with integral outlet plenum.
Sequencing of hot and cold air valve is dependent on job requirements. One typical control is valves working in conjunction to respond to zone temperature.
When the cooling valve becomes fully closed or reaches a specified minimum, the heating valve will begin to modulate or vice versa. The typical result is that air flowing to the zone varies from maximum down to a minimum and back up to maximum as load varies and controls would cause one air valve to close and the other to open.
Another typical application is when the unit provides a constant volume to the zone. When the zone sensor is tied directly to the heating valve, it will modulate the heating valve according to the zone temperature.
When the heating valve is fully closed or there is a call for cooling in the zone, the cooling valve will be at constant supply. As the space becomes too cool, the heating valve will modulate open, decreasing the cooling valve flow. The typical result is that the air flowing into the zone stays at a constant flow whether the unit is heating or cooling.
Figure 4. Typical dual-duct unit: VDDF
VAV-SVX08E-EN 11
Unit Information
Fan-Powered and Fan-Powered Low­Height Units
VariTrane fan-powered and low-height fan-powered units can be either parallel or series, with or without re-heat. (SeeFigure 5, p. 12 thru Figure 8, p. 12.)
Typical Fan-Powered Units
Figure 5. Parallel fan-powered terminal unit (top) &
series fan-powered terminal units (bottom)
Figure 6. Low height series: LSCF (top) & low height
series: LSWF (bottom)
Figure 7. Low height series: LSEF (top) & low height
parallel: LPCF (bottom)
Figure 8. Low height parallel: LPWF (top) & low height
parallel: LPEF (bottom)
The fan on a series unit runs continuously whenever the main air handler unit is in operation. There are various options for starting the fan. The fan can be started three ways: 1) remotely, 2) by a duct pressure switch, or 3) by a combination of both. The particular fan control method may vary from unit to unit, depending upon job needs.
Typically, heater is off while air valve modulates primary air and responds to zone temperature. If zone temperature decreases to the point where a decrease in primary air will not maintain the desired temperature, the re-heat will be activated to increase the temperature of the discharge air.
On a parallel unit, the VariTrane air valve delivers primary cooling air to the unit outlet. When the space temperature decreases beyond air valve control, the fan is turned on as the first stage of heat. The fan delivers plenum air from above the occupied space to the unit outlet, which is mixed with primary air and delivered to the occupied space.
Note: Either the fan, the air valve, or both can deliver
airflow into the occupied space. In order to prevent primary airflow from exiting through the fan when the fan is not running on a parallel unit, a back draft damper is provided. When the fan is not running, the efficiency of this system is the same as a standard single-duct VAV unit.
Typically, the control systems applied to parallel units cause the air valve to close to zero or a minimum flow before the fan is activated. After the fan is activated, the optional heat will be activated upon further reduction in zone temperature. Therefore, minimal primary air is mixed with the heated air.
VariTrane fan-powered unit fan sizes 02SQ–05SQ and 08SQ–10SQ were performance tested at .12 in. w.g. and sizes 06SQ and 07SQ were tested at .15 in. w.g. Units are not designed to operate unducted and below these tested static pressures.
Note: Fan-powered units are available with rectangular
discharge connection only. The optional heater is mounted on the discharge of the unit. Hot water coils are connected to either the plenum inlet or on the discharge on parallel units, and to the discharge of series units.
12 VAV-SVX08E-EN

Unit Installation

Inlet Size
B C A
1.376" (35 mm)
25.154" (639 mm) 1.376" (35 mm)
37.25" (946 mm)
25.25" (641 mm) 23.154" (588 mm)
12" thru 16"
5" thru 10"
AIR
VALVE
AIR
VALVE
COOLING
HEATING
C
A
B
TOP VIEW
WARNING
Proper Structural Support Required!
Ceiling structure must be strong enough to support the weight of the unit. If unsure, check with a structural engineer. Refer toTable 1, p. 24 thruTable 6, p. 26 for unit weights. Failure to ensure proper structural ceiling support could result in unit failing from its location which could result in death or serious injury.
Due to their weight, the VAV terminal units should be suspended from the uppermost ceiling, independent of the false ceiling grid. Suspension devices are to be supplied by the installer. Units must be installed level and upright. Failure to level the unit properly may prevent proper operation of the controls and/or terminal unit. Units are not designed to be installed vertically. Consequently, this will also void the UL ratings and any warranty on the unit.
Single-Duct
Figure 9. Single-duct hanging recommendations
.
Figure 10. Dual-duct hanger bracket locations
Fan-Powered (Standard and Low-Height)
Fan-powered units should be supported by either hanger straps or by using a threaded rod in conjunction with the hanger brackets that are provided on the unit. Care should be exercised to insure that the hanging straps do not block the side access panel. See Figure 11, p. 16 thru Figure 18,
p. 22.
Depending upon the size and weight of the single-duct unit, it may be capable of being supported by the ductwork that is connected to it. No hanger brackets are provided on these units since the unit should be supported by means of a hanger strap. The hanger strap should be secured directly to the unit casing as shown in Figure 9, p. 13.
For cooling only single-duct units or single-duct units with hot water coil, the unit may be rotated 180° for opposite side connections.
For units with electric heat, the unit can be flipped to either RH or LH connection orientation if model number digit 22 Electrical Connections = F.
Dual-Duct
Dual-duct units should be supported by either hanger straps or by using a threaded rod in conjunction with the hanger brackets that are provided on the unit. See
Figure 10, p. 13.
Duct Connections
All VariTrane units should be provided with a minimum of
1.5-duct diameters of straight duct prior to the inlet of the unit. It is recommended that at least 48 inches of straight duct be provided from the discharge of the units prior to any take-offs or transitions.
Important: This is a requirement for electric heat fan-
powered units used in applications with 100% downward discharge.
Note: In order to maintain good air distribution over the
elements and not create turbulence which could cause a limit cutout there should be four feet of ductwork, consistent of the discharge dimensions of the heater. downstream of the reheat coil prior to any diffuser takeoffs for VariTrane™ electric coils.
1. After all connections are made, check that the entire ductwork system is airtight. In some high-pressure systems, duct sealer may be necessary.
Note: All inlet duct on the VAV boxes are sized
approximately 1/8" smaller in diameter than the nominal size in order to allow the incoming duct to slide over the inlet of the VAV box.
2. Provide insulation around the entire inlet collar (all the way to the unit casing).
VAV-SVX08E-EN 13
Unit Installation
Note: Use caution not to damage the flow tubes when
making ductwork connections or insulating.
3. Cut “slits” in the insulation for the flow tubes and secure with duct tape.
4. If the unit is to be installed in a location with high humidity, external insulation around the heating coil should be installed as required.
Water Coil Connections
Note: The following coils have 3/8” OD water coil piping
connections.
Single Duct 1-row coils (inlet sizes 05, 05, 06, 08 or 10 only)
Low Height Parallel Inlet 1-row
Low Height Parallel Discharge 1-row
All others require a 7/8” OD water coil piping connections.
Note:
1. If necessary, you can change the coil connection from left-handed to right-handed (and vice-versa) by disconnecting the coil from the unit and rotating the coil “like a steering wheel” 180°.
Note: Exception - Coil connection cannot be changed
on parallel fan powered unit with hot water coil on plenum inlet.
2. Use port at the bottom for inlet and top for outlet on single row coils. For multirow coils, always plumb in counter flow orientation.
Water inlet is always on the airflow downstream
side of the hot water coil.
Water outlet is always on the upstream side of the
hot water coil.
3. Care should be taken to properly support the water coil piping connections while connecting the adjoining pipe.
4. It is recommended that piping to the water coil should be done after field-mounted controls, external insulation, and ductwork connections have been completed.
Important: Do not connect water valve or pipe
extensions to the water coil connections unless supported.
Unit Accessibility
Single-duct and dual-duct units provided with hot water reheat have an access panel located on the side of the water coil. All other single-duct and dual-duct units are provided without access, as all functioning components are external to the unit.
Fan-powered terminals are provided with a sliding side access.
Low-height terminal units have a removable bottom panel.
Clearances
For proper service, it is recommended that at least 36” of side clearance be provided to service and access single­duct and dual-duct terminals units.
Fan-powered VAV units have a plenum inlet that must be clear of obstructions. Allow at least 36” of clearance in front of the side access and plenum opening.
Low-height fan-powered terminals require the same plenum clearance requirement that applies to the standard fan-powered units. However the access to the internal components is located on the bottom of the unit.
It is also recommended that 6” of clearance be provided to the top and bottom of all the units.
Note: The minimum clearance for controls and heater
controls should be 36” for all models except units with 575-volt electric heaters, which require 48” of clearance. NEC and/or local codes override all clearance requirements.
Actuator Mounting
Important: When installing or replacing the actuator
tighten the actuator set screw per the manufacturer’s instructions. Failure to follow the manufacturer’s specifications may result in unit malfunction.
Trane offers a factory-mounted actuator with a 90-second drive time. The actuator drives 1 degree per second. A field-installed actuator may be used if desired. The actuator shaft has a ½-inch diameter and is designed to travel clockwise to close the damper and counter­clockwise to open the damper. There is an indicator on the end of the actuator shaft that can be used to determine the position of the damper.
Stand Alone UCM 4.2
When there is no communication to the UCM control and the unit is in the stand alone mode the control action is determined by the auxiliary temperature sensor located on TB3-5 and TB3-6 terminals on the UCM board. In order for the auxiliary sensor to determine the control action (heat, cool) it must be located in the supply duct. The auxiliary temperature is then compared to the zone temperature. If the supply air temperature is 10 degrees above the zone temperature, then the control action will be heat. If the supply air temperature is less than or equal to the zone temperature, then the control action will be cool. If the supply air temperature is between the zone temperature and the zone temperature + 10ºF (5.5°C)(zone temperature < supply air temperature < zone temperature + 10ºF) (5.5°C), the control action remains the same and the UCM controls to the minimum flow set point. If an auxiliary sensor is not installed the UCM will retain the last control action in effect
.
14 VAV-SVX08E-EN
Stand Alone VV550 LonTalk™ Control
When there is no communication to the VV550 control and the unit is in the stand alone mode the control action is determined by the auxiliary temperature sensor located on TB3-5 and TB3-6 terminals on the VV550 board. The control must also be configured through the “Inputs Tab” of Analog Input 4 as “Primary Supply Air Sensor”. In order for the auxiliary sensor to determine the control action (heat, cool) it must be located in the supply inlet of the duct. The auxiliary temperature is then compared to the zone temperature. If the supply air temperature is 10 degrees above the zone temperature, then the control action will be heat. If the supply air temperature is less than or equal to the zone temperature, then the control action will be cool. If the supply air temperature is between the zone temperature and the zone temperature + 10ºF (5.5°C)(zone temperature < supply air temperature < zone temperature + 10ºF) (5.5°C), the control action remains the same and the UCM controls to the minimum flow set point. If an auxiliary sensor is not installed the UCM will retain the last control action in effect.
Stand Alone UC400
When there is no communication to the UC400 control and the unit is in the stand alone mode the control action is determined by the auxiliary temperature sensor located on AI5 terminals on the UC400 control. This input may have to be changed from AI4 (Discharge Air Input) as wired from the factory. In order for the auxiliary sensor to determine the control action (heat, cool) it must be located in the supply inlet of the duct. The auxiliary temperature is then compared to the zone temperature. If the supply air temperature is 10 degrees above the zone temperature, then the control action will be heat. If the supply air temperature is less than or equal to the zone temperature, then the control action will be cool. If the supply air temperature is between the zone temperature and the zone temperature + 10ºF (5.5°C)(zone temperature < supply air temperature < zone temperature + 10ºF) (5.5°C), the control action remains the same and the UCM controls to the minimum flow set point. If an auxiliary sensor is not installed the UCM will retain the last control action in effect.
Unit Installation
VAV-SVX08E-EN 15
Unit Installation
Water
Coil
Airflow
Plenum Inlet
Optional Attenuator
Field Installed
Primary
Airflow
TOP VIEW
Parallel Cooling & Hot Water
Flow Ring
Tubing
Air
Valve
Airflow
Discharge Outlet
A
B
C
D
EF
ADE
F
B
C
FAN SIZE
02SQ
03SQ, 04SQ, 05SQ
06SQ, 07SQ
26.75" (679 mm)
26.75" (679 mm)
26.75" (679 mm)
26.75" (679 mm)
29.75" (756 mm)
36.75" (933 mm)
41.154" (1041 mm)
41.154" (1041 mm)
41.154" (1041 mm)
3.25" (83 mm)
3.25" (83 mm)
3.25" (83 mm)
20.00" (508 mm)
20.00" (508 mm)
20.00" (508 mm)
38.95" (989 mm)
38.95" (989 mm)
38.95" (989 mm)
Airflow
Plenum Inlet
Optional Attenuator
Field Installed
Primary
Airflow
TOP VIEW
Parallel Electric Heat
Flow Ring
Tubing
Air
Val ve
Airflow
Discharge Outlet
A
D
EF
B
C
Heater
Terminal Box
43.546
(1106 mm)
Figure 11. Parallel hanger bracket locations sizes
16 VAV-SVX08E-EN
Figure 12. Series hanger bracket locations
Water
Coil
Airflow
Plenum Inlet
Optional Attenuator
Field Installed
TOP VIEW
Series Cooling & Hot Water
Flow Ring
Tubing
Air
Valve
A
D
B
C
TOP VIEW
Series Electric Heat
1.
1.
2.
1.625"
(41 mm)
All attenuators are the same length and width.
Sizes 01 and 02 units are smaller than attenuators.
Airflow
Plenum Inlet
Optional Attenuator
Field Installed
Flow Ring
Tubing
Air
Valve
A B
Electric
Heater
D
G
F
C
B
B
C
A D E
FAN SIZE
(Elec. Heat Only)
3.25" (83 mm)
3.25" (83 mm)
3.25" (83 mm)
3.25" (83 mm)
41.154" (1041 mm)
41.154" (1041 mm)
41.154" (1041 mm)
41.154" (1041 mm)
41.154" (1041 mm)
41.154" (1041 mm)
41.154" (1041 mm)
26.75" (679 mm)
26.75" (679 mm)
26.75" (679 mm)
26.75" (679 mm) 02SQ
06SQ, 07SQ
03SQ, 04SQ
05SQ 26.75" (679 mm)
20.75" (527 mm)
18.75" (476 mm)
27.25" (692 mm)
35.154 (740 mm)
23.875 (606 mm)
29.875" (759 mm)
28.966" (736 mm)
20.132" (511 mm)
Fan Inlet w/o
Attenuator
Fan Inlet w/o
Attenuator
F
C
E
2.
J
(Elec. Heat Only)
59.750” (1517 mm)
58.250" (1479 mm)
59.750" (1517 mm)
53.750" (1365 mm)
G
(Elec. Heat Only)
19.00" (483 mm)
17.50" (445 mm)
19.00" (483 mm)
19.00" (483 mm)
J
Unit Installation
VAV-SVX08E-EN 17
Unit Installation
31.65"
(804 mm)
23.90"
(607 mm)
13.00"
(330 mm)
19.86"
(504 mm)
Airflow
Plenum Inlet
Optional Attenuator
Field Installed
24.30"
(617 mm)
Primary
Airflow
Airflow
Discharge Outlet
13.80"
(350 mm)
4.00"
(102 mm)
23.10"
(587 mm)
3.35"
(85 mm)
TOP VIEW
TOP VIEW
3.35"
(85 mm)
Airflow
Discharge Outlet
31.65"
(804 mm)
23.90"
(607 mm)
13.00"
(330 mm)
19.86"
(504 mm)
Airflow
Plenum Inlet
Optional Attenuator
Field Installed
24.30"
(617 mm)
Primary
Airflow
13.80"
(350 mm)
4.00"
(102 mm)
23.10"
(587 mm)
3.00"
(76 mm)
Heater
Terminal Box
Figure 13. Low-height parallel 08SQ/09SQ w/hot water or electric heat
18 VAV-SVX08E-EN
Figure 14. Low-height parallel 10SQ
Primary
Airflow
Air
Valve
38.95"
(989 mm)
1.625"
(41 mm)
Flow Ring
Tubing
5.625"
(143 mm)
41.137"
(1045 mm)
Airflow
Discharge Outlet
Optional Heater
Terminal Box
5.625"
(143 mm)
TOP VIEW
38.75"
(984 mm)
Plenum
Inlet
Unit Installation
VAV-SVX08E-EN 19
Unit Installation
g
19.86"
(504 mm)
3.35"
(85 mm)
31.65"
(804 mm)
12.85"
(326 mm)
10.13"
(257 mm)
4.00"
(102 mm)
34.30"
(871 mm)
10.13"
(257 mm)
3.35"
(85 mm)
4.00"
(102 mm)
27.00"
(686 mm)
20.00"
(508 mm)
Primary
Airflow
Air
Valv e
Airflow
Plenum Inlet
Optional Attenuator
Field Installed
Wate r
Coil
Primary
Airflow
Airflow
TOP VIEW
19.86"
(504 mm)
3.35"
(85 mm)
31.65"
(804 mm)
12.85"
(326 mm)
34.30"
(871 mm)
3.35"
(85 mm)
27.00"
(686 mm)
20.00"
(508 mm)
Air
Val ve
Airflow
Plenum Inlet
Optional Attenuator
Field Installed
Optional
Electric Heater
Airflow
TOP VIEW
Figure 15. Low-height series 08SQ/09SQ w/hot water or electric heat
20 VAV-SVX08E-EN
Figure 16. Low-height series 10SQ w/hot water or electric heat
31.65"
(804 mm)
19.86"
(504 mm)
Airflow
Plenum Inlet
Optional Attenuator
Field Installed
31.65"
(804 mm)
Primary
Airflow
Airflow
Discharge Outlet
10.12"
(257 mm)
42.00"
(1067 mm)
30.30"
(770 mm)
3.35"
(85 mm)
TOP VIEW
Optional Attenuator
Field Installed
Airflow
Plenum Inlet
19.45"
(494 mm)
19.45"
(494 mm)
19.86"
(504 mm)
3.35"
(85 mm)
3.50"
(89 mm)
3.50"
(89 mm)
31.65"
(804 mm)
19.86"
(504 mm)
Airflow
Plenum Inlet
Optional Attenuator
Field Installed
31.65"
(804 mm)
Primary
Airflow
Airflow
Discharge Outlet
10.12"
(257 mm)
42.00"
(1067 mm)
30.30"
(770 mm)
3.35"
(85 mm)
TOP VIEW
Optional Attenuator
Field Installed
Airflow
Plenum Inlet
19.45"
(494 mm)
19.45"
(494 mm)
19.86"
(504 mm)
3.35"
(85 mm)
3.50"
(89 mm)
3.50"
(89 mm)
1.92"
(49 mm)
Terminal Box
Plenum Area
Optional
Heater
Unit Installation
VAV-SVX08E-EN 21
Unit Installation
Mounting Bracket
Optional Attenuator Field Installed
1. Attach attenuator as shown with provided mounting brackets.
Optional Attenuator Field Installed
Mounting Bracket
1. Attach attenuator as shown with provided mounting brackets.
Figure 17. Attenuator installation - parallel units
Note: Bottom bracket not shown. Bottom bracket to be installed in same orientation on bottom of unit.
Figure 18. Attenuator installation - series units
Note: Bottom bracket not shown. Bottom bracket to be installed in same orientation on bottom of unit.
22 VAV-SVX08E-EN
Figure 19. Attenuator installation - low-height parallel units
1. Attach attenuator to unit as shown with provided mounting brackets.
MOUNTING BRACKET
OPTIONAL ATTENUATOR
FIELD INSTALLED
1. Attach attenuator to unit as shown with provided mounting brackets.
MOUNTING BRACKET
OPTIONAL ATTENUATOR
FIELD INSTALLED
MOUNTING BRACKET
OPTIONAL ATTENUATOR
FIELD INSTALLED
MOUNTING BRACKET
OPTIONAL ATTENUATOR
FIELD INSTALLED
Notes: Bottom bracket not shown. Bottom bracket to be installed in same orientation on bottom of unit.
Figure 20. Attenuator installation - low-height series units
Unit Installation
Note: Bottom bracket not shown. Bottom bracket to be installed in same orientation on bottom of unit.
Bottom Access
An optional bottom access can be provided in the casing of fan powered series or parallel terminal unit. See
Figure 21.
The 22 ga. door is lined with 1” 26 ga. dual wall insulation and thermally lined with 1” – 1 lb. density fiberglass insulation with a 3.85 R-value.
Each door includes 4 to 6 cam locs that are used to secure the door to the casing.
The cam loc engages a metal encapsulated frame on the unit that encloses the unit insulation to prevent air erosion.
The cam loc engagements are interlocked using a flat head screwdriver. Once unlocked the entire door assembly can be removed for access.
VAV-SVX08E-EN 23
Figure 21. Bottom access
Unit Installation
Table 1. Single-duct units
Unit Size
4 5 6 8
10 12 14 16 24
VCCF
(lbs/kg)
22/10 27/12 32/15 35/16 52/24
16/7 16/7 16/7 16/7
Dual Wall
(lbs/kg)
19/9 19/9 19/9 20/9
27/12 34/15 41/19 46/21 63/29
Table 2. Dual-duct units
Unit Size VDDF (lbs/kg) VDDF w/Dual Wall (lbs/kg)
0505 0506 0606 0508
0608 0510 0808 0610
0810 1010 0612 0812
1012 1212 0814 1014
1214 1414 0816 1016
1216 1416 1616
VCCF w/
VCEF
(lbs/kg)
38/17 38/17 38/17 38/17
46/21 52/24 60/27 69/31 84/38
VCEF w/
Dual Wall
(lbs/kg)
48/22 48/22 48/22 49/22
60/27 68/31 80/36 91/41
106/48
VCWF
1-Row
(lbs/kg)
21/10 21/10 21/10 21/10
29/13 37/17 44/20 49/22 70/32
VCWF
2-Row
(lbs/kg)
22/10 22/10 22/10 24/11
32/15 40/18 48/22 54/24 77/35
54/24 54/24 54/24 55/25
55/25 56/25 56/25 56/25
57/26 61/28 57/26 58/26
59/27 60/27 78/35 79/36
80/36 81/37 79/36 80/36
81/37 82/37 83/38
VCWF
3-Row
(lbs/kg)
23/11 23/11 22/10 24/11
32/15 41/19 51/23 56/25 76/35
VCWF
4-Row
(lbs/kg)
24/11 24/11 24/11 26/12
36/16 45/20 55/25 61/28 82/37
VCWF
1-Row w/
Dual Wall
(lbs/kg)
24/11 24/11 24/11 25/11
34/15 43/20 53/24 60/27 81/37
VCWF 2-Row w/ Dual Wall
(lbs/kg)
25/11 25/11 25/11 28/13
37/17 47/21 57/26 65/29 88/40
68/31 68/31 68/31 68/31
69/31 69/31 70/32 70/32
70/32 74/34 70/32 71/32
72/33
84/38 102/46 103/47
104/47 105/48 103/47 104/47
105/48 105/48 106/48
VCWF 3-Row w/ Dual Wall
(lbs/kg)
26/12 26/12 25/11 28/13
37/17 48/22 60/27 67/30 87/40
VCWF 4-Row w/ Dual Wall
(lbs/kg)
27/12 27/12 27/12 30/14
41/19 52/24 64/29 72/33 93/42
24 VAV-SVX08E-EN
Table 3. Parallel fan-powered units
Unit Installation
Unit Size
0502SQ 0602SQ 0603SQ 0802SQ
0803SQ 0804SQ 1002SQ 1003SQ
1004SQ 1005SQ 1006SQ 1007SQ
1203SQ 1204SQ 1205SQ 1206SQ
1207SQ 1404SQ 1405SQ 1406SQ
1407SQ 1606SQ 1607SQ
VPCF
(lbs/kg)
81/37 80/36 83/38 81/37
83/38 84/38 82/37 84/38
85/39
98/44 114/52 122/55
85/39
86/39
99/45 115/52
123/56
87/39 100/45 116/53
124/56 117/53 125/57
VPCF w/Dual Wall (lbs/kg)
115/52 114/52 117/53 115/52
117/53 118/54 116/53 118/54
119/54 132/60 148/67 156/71
119/54 120/54 133/60 149/68
157/71 121/55 134/61 150/68
158/72 151/68 159/72
VPEF
(lbs/kg)
110/550
109/49 112/51 110/50
112/51 113/51 111/50 113/51
114/52 128/58 144/65 152/69
114/52 115/52 129/59 145/66
153/69 116/53 130/59 146/66
154/70 147/67 155/70
VPEF w/Dual
Wall (lbs/kg)
144/65 143/65 146/66 144/65
146/66 147/67 145/66 147/67
148/67 162/73 178/81 186/84
148/67 149/68 163/74 179/81
187/85 150/68 164/74 180/82
188/85 181/82 189/86
VPWF 1-Row
(lbs/kg)
92/42 91/41
105/48
92/42
105/48 106/48
93/42
106/48 107/49
120/54 127/58 135/61
107/49 108/49 121/55 128/58
136/62 109/49 122/55 129/59
137/62 130/59 138/63
VPWF 2-Row
(lbs/kg)
95/43 94/43
108/49
95/43
108/49 109/49
96/44
109/49 110/50
123/56 130/59 138/63
110/50 111/50 124/56 131/59
139/63 112/51 125/57 132/60
140/64 133/60 141/64
VPWF 1-Row
w/Dual Wall
(lbs/kg)
126/57 125/57 139/63 126/57
139/63 140/64 127/58 140/64
141/64 154/70 161/73 169/77
141/64 142/64 155/70 162/73
170/77 143/65 156/71 163/74
171/78 164/74 172/78
VPWF 2-Row
w/Dual Wall
(lbs/kg)
129/59 128/58 142/64 129/59
142/64 143/65 130/59 143/65
144/65 157/71 164/74 172/78
144/65 145/66 158/72 165/75
173/78 146/66 159/72 166/75
174/79 167/76 175/79
VPxF
Attenuator
(lbs/kg)
46/21 46/21 48/22 46/21
48/22 48/22 46/21 48/22
48/22 48/22 54/24 54/24
48/22 48/22 48/22 54/24
54/24 48/22 48/22 54/24
54/24 54/24 54/24
Table 4. Series fan-powered
VSCF w/
Dual Wall
(lbs/kg)
93/42 93/42
92/42 100/45 111/50
94/43 101/46 112/51
96/44 104/47
115/52 116/53 133/60 146/66 106/48
116/53 118/54 134/61 147/67 117/53
120/54 135/61 148/67 136/62 149/68
Unit Size
0402SQ 0502SQ 0602SQ 0603SQ 0604SQ
0802SQ 0803SQ 0804SQ 1002SQ 1003SQ
1004SQ 1005SQ 1006SQ 1007SQ 1203SQ
1204SQ 1205SQ 1206SQ 1207SQ 1404SQ
1405SQ 1406SQ 1407SQ 1606SQ 1607SQ
VSCF
(lbs/kg)
78/35 78/35 77/35 76/34 87/39
79/36 77/35 88/40 81/37 80/36
91/41
92/42 104/47 117/53
82/37
92/42
94/43 105/48 118/54
93/42
96/44 106/48 119/54 107/49 120/54
VSEF
(lbs/kg)
104/47 104/47 103/47 105/48 116/53
105/48 106/48 117/53 107/49 109/49
120/54 121/55 135/61 148/67 111/50
121/55 123/56 136/62 149/68 122/55
125/57 137/62 150/68 138/63 151/68
VSEF w/
Dual Wall
(lbs/kg)
119/54 119/54 118/54 129/59 140/64
120/54 130/59 141/64 122/55 133/60
144/65 145/66 164/74 177/80 135/61
145/66 147/67 165/75 178/81 146/66
149/68 166/75 179/81 167/76 180/82
VSWF
1-Row
(lbs/kg)
85/39 85/39 84/38 88/40 99/45
86/39 89/40
100/45
88/40 92/42
103/47 104/47 119/54 132/60
94/43
104/47 106/48 120/54 133/60 105/48
108/49 121/55 134/61 122/55 135/61
VSWF
2-Row
(lbs/kg)
87/39 87/39 86/39 92/42
103/47
88/40 93/42
104/47
90/41 96/44
107/49 108/49 124/56 137/62
98/44
108/49 110/50 125/57 138/63 109/49
112/51 126/57 139/63 127/58 140/64
VSWF
1-Row
w/Dual Wall
(lbs/kg)
100/45 100/45
99/45 112/51 123/56
101/46 113/51 124/56 103/47 116/53
127/58 128/58 148/67 161/73 118/54
128/58 130/59 149/68 162/73 129/59
132/60 150/68 163/74 151/68 164/74
VSWF
2-Row
w/Dual Wall
(lbs/kg)
102/46 102/46 101/46 116/53 127/58
103/47 117/53 128/58 105/48 120/54
131/59 132/60 153/69 166/75 122/55
132/60 134/61 154/70 167/76 133/60
136/62 155/70 168/76 156/71 169/77
VSxF
Attenuator
(lbs/kg)
46/21 46/21 46/21 48/22 48/22
46/21 48/22 48/22 46/21 48/22
48/22 48/22 54/24 54/24 48/22
48/22 48/22 54/24 54/24 48/22
48/22 54/24 54/24 54/24 54/24
VAV-SVX08E-EN 25
Unit Installation
Table 5. Low-height parallel units
LPCF w/
Unit Size
0508SQ 0608SQ 0609SQ 0808SQ
0809SQ
0810SQ 14RT09SQ 14RT10SQ
LPCF
(lbs/kg)
69/31 68/31 73/33 69/31
74/34 90/41 83/38 97/44
Dual Wall
(lbs/kg)
89/40 88/40 93/42 89/40
94/43 110/50 103/47 117/53
Table 6. Low-height series units
LSCF w/
Dual Wall
(lbs/kg)
86/39 85/39 95/43 86/39
96/44
120/54 105/48 130/59
Unit Size
0508SQ 0608SQ 0609SQ 0808SQ
0809SQ
0810SQ 14RT09SQ 14RT10SQ
LSCF
(lbs/kg)
71/32 70/32 80/36 71/32
81/37 95/43 90/41
105/48
LPEF
(lbs/kg)
84/38 83/38 88/40 84/38
89/40
105/48
98/44
112/51
LSEF
(lbs/kg)
86/39 85/39 95/43 86/39
96/44 120/54 105/48 130/59
LPEF w/
Dual Wall
(lbs/kg)
104/47 103/47 108/49 104/47
109/49 125/57 118/54 132/60
LSEF w/
Dual Wall
(lbs/kg)
101/45 100/45 110/50 101/46
111/50 145/66 120/54 155/70
LPWF
1-Row
(lbs/kg)
78/35 77/35 82/37 78/35
83/38 99/45 92/42
106/48
LSWF
1-Row
(lbs/kg)
80/36 79/36 89/40 80/36
90/41
111/50
99/45
121/55
LPWF
2-Row
(lbs/kg)
81/37 80/36 85/39 81/37
86/39
102/46
95/43
109/49
LSWF
2-Row
(lbs/kg)
82/37 81/37 91/41 82/37
92/42 115/52 101/46 125/57
LPWF 1-Row w/Dual Wall
(lbs/kg)
98/44 97/44
102/46
98/44
103/47 119/54 112/51 126/57
LSWF 1-Row w/Dual Wall
(lbs/kg)
95/43 94/43
104/47
95/43
105/48 136/62 114/52 146/66
LPWF 2-Row
w/DualWall
(lbs/kg)
101/46 100/45 105/48 101/46
106/48 122/55 115/52 129/59
LSWF 2-Row w/Dual Wall
(lbs/kg)
97/44 96/44
106/48
97/44
107/49 140/64 116/53 150/68
LPxF
Attenuator
(lbs/kg)
10/5 10/5 10/5 10/5
10/5 10/5 10/5 10/5
LSxF
Attenuator
(lbs/kg)
10/5 10/5 10/5 10/5
10/5 20/9 10/5 20/9
26 VAV-SVX08E-EN

Unit Setup

0.01
0.1
1
10
10 100 1,000 10,000
Airflow (CFM)
Flow Sensor Differential Pressure (inches water)
4
6
8"
5
10"
12" 14" 16"
8" x 12"
16" x 24"
Figure 22. Flow sensor P vs. airflow delivery
Fan Motor Amperage
Table 7. Maximum ECM fan motor amperage (FLA)
Fan Size HP VAC 115 VAC 277 VAV
Parallel/Series 03SQ 1/3 4.5 2.4 Parallel/Series 04SQ 1/2 6.5 3.5 Parallel/Series 05SQ 1 10.1 5.4 Parallel/Series 06SQ 19.55.1 Low-height Parallel/
Series 08SQ
Low-height Parallel/
Series 09SQ
Low-height Series 10SQ 2 x 1/2 7.5 4.0
1/2 2.0 1.1
1/2 6.7 3.6
VAV-SVX08E-EN 27
Unit Setup
Table 8. Maximum PSC fan motor amperage (FLA)
Fan Size HP VAC
Parallel/Series 02SQ 1/8 1.6 0.7 .7 -
Parallel/Series 03SQ 1/3 4.3 1.6 1.4 -
Parallel/Series 04SQ 1/3 5.5 2.0 1.8 -
Parallel/Series 05SQ 1/2 6.7 2.4 2.2 -
Parallel/Series 06SQ 1/2 - 3.8 3.3 4.6
Parallel/Series 07SQ 1 - 4.7 3.8 6.6
Low-height Parallel/
Series 08SQ
Low-height Parallel/
Series 09SQ
Series Low-height
10SQ
Parallel Low-Height
10SQ
2 x 1/8 11.0 5.0 3.5 -
2 x 1/8 9.4 3.5 3.0
115
VAC
1/3 5.5 2.5 1.8 -
1/3 5.5 2.5 1.8 -
277 VAV
347
VAC 208

(SCR) Motor Speed Control Adjustment Procedure.

In order to make units more convenient and efficient to balance, an SCR (silicone control rectifier) is provided as standard on all fan-powered units.
The SCR is located on the side of the fan control box. To adjust the speed of the motor, the external knob must be rotated either clockwise or counterclockwise depending on the desired speed adjustment.
There is an internal potentiometer (Figure 23, p. 28) setting on the SCR controller that can be accessed by removing the control box cover. This internal potentiometer is set at the factory to the specific motor voltage.
It may be necessary to adjust this in the field depending on the building’s power factor.
Figure 23. SCR (L) & internal potentiometer (R)

Electrically Commutated Motor (ECM)

Figure 24. ECM control board
Trane offers an energy efficient ECM motor as a motor option. Balancing of an ECM motor is accomplished through electronic control adjustments on the ECM control board (see Figure 24, p. 28). Potentiometer settings for a multitude of CFM settings are given in
Table 9, p. 29 thru Table 21, p. 41. Other potentiometer
settings can be determined either by interpolating from these tables or by using the following equation:
CFMsetting = CFMmin + {(Potentiometer Setting) x [(CFMmax - CFMmin)/100]}
There is an LED on the ECM control board, which will blink one time for every 100 CFM of motor setting. For example, the LED on a unit set for 790 CFM will blink 7 times. The LED on a unit set for 800 CFM will blink 8 times.
Note: This feature only verifies that the CFM is set
properly. This feature does not indicate at what speed the motor is actually running.
The ECM must be “load tested.” In other words, the fan must be connected to properly test the ECM.
120 v
208 v– 277 v
347 v
DO NOT SET THIS POTENTIOMETER BELOW THE VOLTAGE OF THE FAN MOTOR.
Max
Note: Do not set this potentiometer below the voltage of
the fan motor.
28 VAV-SVX08E-EN
Table 9. VPxF 03SQ ECM CFM
Motor Min CFM: 160 Motor Max CFM: 1085
CFM L/sec % Setting
160 170 179 188 198
207 216 226 235 244
254 263 272 282 291
300 310 319 328 338
347 356 366 375 385
394 403 413 422 431
441 450 459 469 478
487 497 506 515 525
534 543 553 562 571
581 590 599 609 618
627 637 646 655 665
76 80 84 89 93
98 102 107 111 115
120 124 129 133 137
142 146 151 155 159
164 168 173 177 181
186 190 195 199 204
208 212 217 221 226
230 234 239 243 248
252 256 261 265 270
274 278 283 287 292
296 300 305 309 314
10 11
12 13 14 15
16 17 18 19 20
21 22 23 24 25
26 27 28 29 30
31 32 33 34 35
36 37 38 39 40
41 42 43 44 45
46 47 48 49 50
51 52 53 54 55
Unit Setup
Table 9. VPxF 03SQ ECM CFM (continued)
Motor Min CFM: 160 Motor Max CFM: 1085
CFM L/sec % Setting
674
1 2 3 4 5
6 7 8 9
683 693 702 711
721 730 739 749 758
767 777 786 795 805
814 823 833 842 852
861 870 880 889 898
908 917 926 936 945
954 964 973 982 992
1001 1010 1020 1029 1038
1048 1057 1066 1076 1085
318 323 327 331 336
340 345 349 353 358
362 367 371 375 380
384 389 393 397 402
406 411 415 419 424
428 433 437 442 446
450 455 459 464 468
472 477 481 486 490
494 499 503 508 512
56 57 58 59 60
61 62 63 64 65
66 67 68 69 70
71 72 73 74 75
76 77 78 79 80
81 82 83 84 85
86 87 88 89 90
91 92 93 94 95
96 97 98 99
100
VAV-SVX08E-EN 29
Unit Setup
Table 10. VPxF 04SQ ECM CFM
Motor Min CFM: 220 Motor Max CFM: 1510
CFM L/sec % Setting
220 233 246 259 272
285 298 311 324 337
350 363 376 389 402
415 429 442 455 468
481 494 507 520 533
546 559 572 585 598
611 624 637 650 663
676 689 702 715 728
741 754 767 780 793
806 819 832 845 859
872 885 898 911 924
104 110 116 122 128
135 141 147 153 159
165 171 178 184 190
196 202 208 215 221
227 233 239 245 251
258 264 270 276 282
288 294 301 307 313
319 325 331 338 344
350 356 362 368 374
381 387 393 399 405
411 417 424 430 436
10 11
12 13 14 15
16 17 18 19 20
21 22 23 24 25
26 27 28 29 30
31 32 33 34 35
36 37 38 39 40
41 42 43 44 45
46 47 48 49 50
51 52 53 54 55
Table 10. VPxF 04SQ ECM CFM (continued)
Motor Min CFM: 220 Motor Max CFM: 1510
CFM L/sec % Setting
937
1 2 3 4 5
6 7 8 9
950 963 976 989
1002 1015 1028 1041 1054
1067 1080 1093 1106 1119
1132 1145 1158 1171 1184
1197 1210 1223 1236 1249
1262 1275 1288 1302 1315
1328 1341 1354 1367 1380
1393 1406 1419 1432 1445
1458 1471 1484 1497 1510
442 448 454 461 467
473 479 485 491 497
504 510 516 522 528
534 540 547 553 559
565 571 577 584 590
596 602 608 614 620
627 633 639 645 651
657 663 670 676 682
688 694 700 706 713
56 57 58 59 60
61 62 63 64 65
66 67 68 69 70
71 72 73 74 75
76 77 78 79 80
81 82 83 84 85
86 87 88 89 90
91 92 93 94 95
96 97 98 99
100
30 VAV-SVX08E-EN
Table 11. VPxF 05SQ ECM CFM
Motor Min CFM: 280 Motor Max CFM: 1850
CFM L/sec % Setting
280 296 312 327 343
359 375 391 407 423
438 454 470 486 502
518 534 549 565 581
597 613 629 645 661
676 692 708 724 740
756 772 787 803 819
835 851 867 883 898
914 930 946 962 978
994 1009 1025 1041 1057
1073 1089 1105 1120 1136
132 140 147 155 162
170 177 184 192 199
207 214 222 229 237
244 252 259 267 274
282 289 297 304 312
319 327 334 342 349
357 364 372 379 387
394 402 409 417 424
431 439 446 454 461
469 476 484 491 499
506 514 521 529 536
10 11
12 13 14 15
16 17 18 19 20
21 22 23 24 25
26 27 28 29 30
31 32 33 34 35
36 37 38 39 40
41 42 43 44 45
46 47 48 49 50
51 52 53 54 55
Unit Setup
Table 11. VPxF 05SQ ECM CFM (continued)
Motor Min CFM: 280 Motor Max CFM: 1850
CFM L/sec % Setting
1152
1 2 3 4 5
6 7 8 9
1168 1184 1200 1216
1231 1247 1263 1279 1295
1311 1327 1342 1358 1374
1390 1406 1422 1438 1454
1469 1485 1501 1517 1533
1549 1565 1580 1596 1612
1628 1644 1660 1676 1691
1707 1723 1739 1755 1771
1787 1802 1818 1834 1850
544 551 559 566 574
581 589 596 604 611
619 626 634 641 649
656 664 671 678 686
693 701 708 716 723
731 738 746 753 761
768 776 783 791 798
806 813 821 828 836
843 851 858 866 873
56 57 58 59 60
61 62 63 64 65
66 67 68 69 70
71 72 73 74 75
76 77 78 79 80
81 82 83 84 85
86 87 88 89 90
91 92 93 94 95
96 97 98 99
100
VAV-SVX08E-EN 31
Unit Setup
Table 12. VPxF 06SQ ECM CFM
Motor Min CFM: 530 Motor Max CFM: 2100
CFM L/sec % Setting
530
546
562
577
593
609
625
641
657
673
688
704
720
736
752
768
784
799
815
831
847
863
879
895
911
926
942
958
974
990 1006
1022 1037 1053 1069
1085 1101 1117 1133 1148
1164 1180 1196 1212 1228
1244 1259 1275 1291 1307
1323 1339 1355 1370 1386
250 258 265 273 280
287 295 302 310 317
325 332 340 347 355
362 370 377 385 392
400 407 415 422 430
437 445 452 460 467
475 482 490 497 505
512 520 527 535 542
549 557 564 572 579
587 594 602 609 617
624 632 639 647 654
10 11
12 13 14 15
16 17 18 19 20
21 22 23 24 25
26 27 28 29 30
31 32 33 34 35
36 37 38 39 40
41 42 43 44 45
46 47 48 49 50
51 52 53 54 55
Table 12. VPxF 06SQ ECM CFM (continued)
Motor Min CFM: 530 Motor Max CFM: 2100
CFM L/sec % Setting
1402
1 2 3 4 5
6 7 8 9
1418 1434 1450 1466
1481 1497 1513 1529 1545
1561 1577 1592 1608 1624
1640 1656 1672 1688 1704
1719 1735 1751 1767 1783
1799 1815 1830 1846 1862
1878 1894 1910 1926 1941
1957 1973 1989 2005 2021
2037 2052 2068 2084 2100
662 669 677 684 692
699 707 714 722 729
737 744 752 759 767
774 782 789 796 804
811 819 826 834 841
849 856 864 871 879
886 894 901 909 916
924 931 939 946 954
961 969 976 984 991
56 57 58 59 60
61 62 63 64 65
66 67 68 69 70
71 72 73 74 75
76 77 78 79 80
81 82 83 84 85
86 87 88 89 90
91 92 93 94 95
96 97 98 99
100
32 VAV-SVX08E-EN
Table 13. VSxF 03SQ ECM CFM
Motor Min CFM: 200 Motor Max CFM: 1100
CFM L/sec % Setting
200
209
218
227
236
246
255
264
273
282
291
300
309
318
327
336
346
355
364
373
382
391
400
409
418
427
436
446
455
464
473
482
491
500
509
518
527
536
546
555
564
573
582
591
600
609
618
627
636
646
655
664
673
682
691
94
99 103 107 112
116 120 124 129 133
137 142 146 150 154
159 163 167 172 176
180 185 189 193 197
202 206 210 215 219
223 227 232 236 240
245 249 253 257 262
266 270 275 279 283
287 292 296 300 305
309 313 318 322 326
10 11
12 13 14 15
16 17 18 19 20
21 22 23 24 25
26 27 28 29 30
31 32 33 34 35
36 37 38 39 40
41 42 43 44 45
46 47 48 49 50
51 52 53 54 55
Unit Setup
Table 13. VSxF 03SQ ECM CFM (continued)
Motor Min CFM: 200 Motor Max CFM: 1100
CFM L/sec % Setting
700
1 2 3 4 5
6 7 8 9
709 718 727 736
745 755 764 773 782
791 800 809 818 827
836 845 855 864 873
882 891 900 909 918
927 936 945 955 964
973 982
991 1000 1009
1018 1027 1036 1045 1055
1064 1073 1082 1091 1100
330 335 339 343 348
352 356 360 365 369
373 378 382 386 390
395 399 403 408 412
416 420 425 429 433
438 442 446 451 455
459 463 468 472 476
481 485 489 493 498
502 506 511 515 519
56 57 58 59 60
61 62 63 64 65
66 67 68 69 70
71 72 73 74 75
76 77 78 79 80
81 82 83 84 85
86 87 88 89 90
91 92 93 94 95
96 97 98 99
100
VAV-SVX08E-EN 33
Unit Setup
Table 14. VSxF 04SQ ECM CFM
Motor Min CFM: 275 Motor Max CFM: 1500
CFM L/sec % Setting
275 288 300 312 325
337 350 362 374 387
399 411 424 436 449
461 473 486 498 510
523 535 548 560 572
585 597 609 622 634
646 659 671 684 696
708 721 733 745 758
770 783 795 807 820
832 844 857 869 882
894 906 919 931 943
130 136 142 147 153
159 165 171 177 183
188 194 200 206 212
218 223 229 235 241
247 253 258 264 270
276 282 288 293 299
305 311 317 323 328
334 340 346 352 358
363 369 375 381 387
393 399 404 410 416
422 428 434 439 445
10 11
12 13 14 15
16 17 18 19 20
21 22 23 24 25
26 27 28 29 30
31 32 33 34 35
36 37 38 39 40
41 42 43 44 45
46 47 48 49 50
51 52 53 54 55
Table 14. VSxF 04SQ ECM CFM (continued)
Motor Min CFM: 275 Motor Max CFM: 1500
CFM L/sec % Setting
956
1 2 3 4 5
6 7 8 9
968
980
993 1005
1018 1030 1042 1055 1067
1079 1092 1104 1117 1129
1141 1154 1166 1178 1191
1203 1215 1228 1240 1253
1265 1277 1290 1302 1314
1327 1339 1352 1364 1376
1389 1401 1413 1426 1438
1451 1463 1475 1488 1500
451 457 463 469 474
480 486 492 498 504
509 515 521 527 533
539 544 550 556 562
568 574 579 585 591
597 603 609 615 620
626 632 638 644 650
655 661 667 673 679
685 690 696 702 708
56 57 58 59 60
61 62 63 64 65
66 67 68 69 70
71 72 73 74 75
76 77 78 79 80
81 82 83 84 85
86 87 88 89 90
91 92 93 94 95
96 97 98 99
100
34 VAV-SVX08E-EN
Table 15. VSxF 05SQ ECM CFM
Motor Min CFM: 350 Motor Max CFM: 2050
CFM L/sec % Setting
350 367 385 402 419
436 453 470 488 505
522 539 556 573 591
608 625 642 659 676
694 711 728 745 762
779 797 814 831 848
865 882 900 917 934
951 968
985 1003 1020
1037 1054 1071 1088 1106
1123 1140 1157 1174 1192
1209 1226 1243 1260 1277
165 173 181 190 198
206 214 222 230 238
246 254 263 271 279
287 295 303 311 319
327 335 344 352 360
368 376 384 392 400
408 416 425 433 441
449 457 465 473 481
489 498 506 514 522
530 538 546 554 562
570 579 587 595 603
10 11
12 13 14 15
16 17 18 19 20
21 22 23 24 25
26 27 28 29 30
31 32 33 34 35
36 37 38 39 40
41 42 43 44 45
46 47 48 49 50
51 52 53 54 55
Unit Setup
Table 15. VSxF 05SQ ECM CFM (continued)
Motor Min CFM: 350 Motor Max CFM: 2050
CFM L/sec % Setting
1295
1 2 3 4 5
6 7 8 9
1312 1329 1346 1363
1380 1398 1415 1432 1449
1466 1483 1501 1518 1535
1552 1569 1586 1604 1621
1638 1655 1672 1689 1707
1724 1741 1758 1775 1792
1810 1827 1844 1861 1878
1895 1913 1930 1947 1964
1981 1998 2016 2033 2050
611 619 627 635 643
651 660 668 676 684
692 700 708 716 724
732 741 749 757 765
773 781 789 797 805
814 822 830 838 846
854 862 870 878 886
895 903 911 919 927
935 943 951 959 967
56 57 58 59 60
61 62 63 64 65
66 67 68 69 70
71 72 73 74 75
76 77 78 79 80
81 82 83 84 85
86 87 88 89 90
91 92 93 94 95
96 97 98 99
100
VAV-SVX08E-EN 35
Unit Setup
Table 16. VSxF 06SQ ECM CFM
Motor Min CFM: 700 Motor Max CFM: 2500
CFM L/sec % Setting
700
718
737
755
773
791
809
827
846
864
882
900
918
937
955
973
991 1009 1027 1046
1064 1082 1100 1118 1137
1155 1173 1191 1209 1227
1246 1264 1282 1300 1318
1336 1355 1373 1391 1409
1427 1446 1464 1482 1500
1518 1536 1555 1573 1591
1609 1627 1646 1664 1682
330 339 348 356 365
373 382 391 399 408
416 425 433 442 451
459 468 476 485 493
502 511 519 528 536
545 554 562 571 579
588 596 605 614 622
631 639 648 656 665
674 682 691 699 708
717 725 734 742 751
759 768 777 785 794
10 11
12 13 14 15
16 17 18 19 20
21 22 23 24 25
26 27 28 29 30
31 32 33 34 35
36 37 38 39 40
41 42 43 44 45
46 47 48 49 50
51 52 53 54 55
Table 16. VSxF 06SQ ECM CFM (continued)
Motor Min CFM: 700 Motor Max CFM: 2500
CFM L/sec % Setting
1700
1 2 3 4 5
6 7 8 9
1718 1736 1755 1773
1791 1809 1827 1846 1864
1882 1900 1918 1936 1955
1973 1991 2009 2027 2046
2064 2082 2100 2118 2136
2155 2173 2191 2209 2227
2245 2264 2282 2300 2318
2336 2355 2373 2391 2409
2427 2445 2464 2482 2500
802 811 820 828 837
845 854 862 871 880
888 897 905 914 922
931 940 948 957 965
974 983
991 1000 1008
1017 1025 1034 1043 1051
1060 1068 1077 1085 1094
1103 1111 1120 1128 1137
1146 1154 1163 1171 1180
56 57 58 59 60
61 62 63 64 65
66 67 68 69 70
71 72 73 74 75
76 77 78 79 80
81 82 83 84 85
86 87 88 89 90
91 92 93 94 95
96 97 98 99
100
36 VAV-SVX08E-EN
Table 17. LPxF 08SQ ECM CFM
Motor Min CFM: 100 Motor Max CFM: 460
CFM L/sec % Setting
100 103 107 111 114
118 121 125 129 132
136 140 143 147 151
154 158 162 165 169
172 176 180 183 187
191 194 198 202 205
209 212 216 220 223
227 231 234 238 242
245 249 253 256 260
263 267 271 274 278
282 285 289 293 296
47 49 50 52 54
56 57 59 61 62
64 66 68 69 71
73 75 76 78 80
81 83 85 87 88
90 92 93 95 97
99 100 102 104 105
107 109 111 112 114
116 117 119 121 123
124 126 128 129 131
133 135 136 138 140
10 11
12 13 14 15
16 17 18 19 20
21 22 23 24 25
26 27 28 29 30
31 32 33 34 35
36 37 38 39 40
41 42 43 44 45
46 47 48 49 50
51 52 53 54 55
Unit Setup
Table 17. LPxF 08SQ ECM CFM (continued)
Motor Min CFM: 100 Motor Max CFM: 460
CFM L/sec % Setting
300
1 2 3 4 5
6 7 8 9
303 307 311 314
318 322 325 329 333
336 340 344 347 351
354 358 362 365 369
373 376 380 384 387
391 394 398 402 405
409 413 416 420 424
427 431 435 438 442
445 449 453 456 460
142 143 145 147 148
150 152 154 155 157
159 160 162 164 166
167 169 171 172 174
176 178 179 181 183
184 186 188 190 191
193 195 196 198 200
202 203 205 207 209
210 212 214 215 217
56 57 58 59 60
61 62 63 64 65
66 67 68 69 70
71 72 73 74 75
76 77 78 79 80
81 82 83 84 85
86 87 88 89 90
91 92 93 94 95
96 97 98 99
100
VAV-SVX08E-EN 37
Unit Setup
Table 18. LPxF 09SQ ECM CFM
Motor Min CFM: 250 Motor Max CFM: 1025
CFM L/sec % Setting
250 258 265 273 281
289 297 305 312 320
328 336 344 352 359
367 375 383 391 399
406 414 422 430 438
446 453 461 469 477
485 493 500 508 516
524 532 540 547 555
563 571 579 587 594
602 610 618 626 634
641 649 657 665 673
118 122 125 129 133
136 140 144 147 151
155 159 162 166 170
173 177 181 184 188
192 196 199 203 207
210 214 218 221 225
229 232 236 240 244
247 251 255 258 262
266 269 273 277 281
284 288 292 295 299
303 306 310 314 317
10 11
12 13 14 15
16 17 18 19 20
21 22 23 24 25
26 27 28 29 30
31 32 33 34 35
36 37 38 39 40
41 42 43 44 45
46 47 48 49 50
51 52 53 54 55
Table 18. LPxF 09SQ ECM CFM (continued)
Motor Min CFM: 250 Motor Max CFM: 1025
CFM L/sec % Setting
680
1 2 3 4 5
6 7 8 9
688 696 704 712
720 727 735 743 751
759 767 774 782 790
798 806 814 821 829
837 845 853 861 868
876 884 892 900 908
915 923 931 939 947
955 962 970 978 986
994 1002 1009 1017 1025
321 325 329 332 336
340 343 347 351 354
358 362 365 369 373
377 380 384 388 391
395 399 402 406 410
414 417 421 425 428
432 436 439 443 447
450 454 458 462 465
469 473 476 480 484
56 57 58 59 60
61 62 63 64 65
66 67 68 69 70
71 72 73 74 75
76 77 78 79 80
81 82 83 84 85
86 87 88 89 90
91 92 93 94 95
96 97 98 99
100
38 VAV-SVX08E-EN
Table 19. LSxF 08SQ ECM CFM
Motor Min CFM: 100 Motor Max CFM: 460
CFM L/sec % Setting
100 103 107 111 114
118 121 125 129 132
136 140 143 147 151
154 158 162 165 169
172 176 180 183 187
191 194 198 202 205
209 212 216 220 223
227 231 234 238 242
245 249 253 256 260
263 267 271 274 278
282 285 289 293 296
47 49 50 52 54
56 57 59 61 62
64 66 68 69 71
73 75 76 78 80
81 83 85 87 88
90 92 93 95 97
99 100 102 104 105
107 109 111 112 114
116 117 119 121 123
124 126 128 129 131
133 135 136 138 140
10 11
12 13 14 15
16 17 18 19 20
21 22 23 24 25
26 27 28 29 30
31 32 33 34 35
36 37 38 39 40
41 42 43 44 45
46 47 48 49 50
51 52 53 54 55
Unit Setup
Table 19. LSxF 08SQ ECM CFM (continued)
Motor Min CFM: 100 Motor Max CFM: 460
CFM L/sec % Setting
300
1 2 3 4 5
6 7 8 9
303 307 311 314
318 322 325 329 333
336 340 344 347 351
354 358 362 365 369
373 376 380 384 387
391 394 398 402 405
409 413 416 420 424
427 431 435 438 442
445 449 453 456 460
142 143 145 147 148
150 152 154 155 157
159 160 162 164 166
167 169 171 172 174
176 178 179 181 183
184 186 188 190 191
193 195 196 198 200
202 203 205 207 209
210 212 214 215 217
56 57 58 59 60
61 62 63 64 65
66 67 68 69 70
71 72 73 74 75
76 77 78 79 80
81 82 83 84 85
86 87 88 89 90
91 92 93 94 95
96 97 98 99
100
VAV-SVX08E-EN 39
Unit Setup
Table 20. LSxF 09SQ ECM CFM
Motor Min CFM: 240 Motor Max CFM: 950
CFM L/sec % Setting
240 247 255 262 269
276 283 290 298 305
312 319 326 333 341
348 355 362 369 376
384 391 398 405 412
419 427 434 441 448
455 462 470 477 484
491 498 505 513 520
527 534 541 548 556
563 570 577 584 592
599 606 613 620 627
113 117 120 123 127
130 134 137 140 144
147 151 154 157 161
164 167 171 174 178
181 184 188 191 195
198 201 205 208 211
215 218 222 225 228
232 235 239 242 245
249 252 255 259 262
266 269 272 276 279
283 286 289 293 296
10 11
12 13 14 15
16 17 18 19 20
21 22 23 24 25
26 27 28 29 30
31 32 33 34 35
36 37 38 39 40
41 42 43 44 45
46 47 48 49 50
51 52 53 54 55
Table 20. LSxF 09SQ ECM CFM (continued)
Motor Min CFM: 240 Motor Max CFM: 950
CFM L/sec % Setting
635
1 2 3 4 5
6 7 8 9
642 649 656 663
670 678 685 692 699
706 713 721 728 735
742 749 756 764 771
778 785 792 799 807
814 821 828 835 842
850 857 864 871 878
885 893 900 907 914
921 928 936 943 950
299 303 306 310 313
316 320 323 327 330
333 337 340 343 347
350 354 357 360 364
367 371 374 377 381
384 387 391 394 398
401 404 408 411 415
418 421 425 428 431
435 438 442 445 448
56 57 58 59 60
61 62 63 64 65
66 67 68 69 70
71 72 73 74 75
76 77 78 79 80
81 82 83 84 85
86 87 88 89 90
91 92 93 94 95
96 97 98 99
100
40 VAV-SVX08E-EN
Table 21. LSxF 10SQ ECM CFM
Motor Min CFM: 400 Motor Max CFM: 1800
CFM L/sec % Setting
400 414 428 443 457
471 485 499 513 527
542 556 570 584 598
612 626 641 655 669
683 697 711 725 740
754 768 782 796 810
824 838 853 867 881
895 909 923 937 952
966 980
994 1008 1022
1036 1051 1065 1079 1093
1107 1121 1135 1150 1164
189 196 202 209 216
222 229 236 242 249
256 262 269 276 282
289 296 302 309 316
322 329 336 342 349
356 362 369 376 382
389 396 402 409 416
422 429 436 442 449
456 462 469 476 482
489 496 502 509 516
523 529 536 543 549
10 11
12 13 14 15
16 17 18 19 20
21 22 23 24 25
26 27 28 29 30
31 32 33 34 35
36 37 38 39 40
41 42 43 44 45
46 47 48 49 50
51 52 53 54 55
Unit Setup
Table 21. LSxF 10SQ ECM CFM (continued)
Motor Min CFM: 400 Motor Max CFM: 1800
CFM L/sec % Setting
1178
1 2 3 4 5
6 7 8 9
1192 1206 1220 1234
1249 1263 1277 1291 1305
1319 1333 1348 1362 1376
1390 1404 1418 1432 1447
1461 1475 1489 1503 1517
1531 1545 1560 1574 1588
1602 1616 1630 1644 1659
1673 1687 1701 1715 1729
1743 1758 1772 1786 1800
556 563 569 576 583
589 596 603 609 616
623 629 636 643 649
656 663 669 676 683
689 696 703 709 716
723 729 736 743 749
756 763 769 776 783
789 796 803 809 816
823 829 836 843 850
56 57 58 59 60
61 62 63 64 65
66 67 68 69 70
71 72 73 74 75
76 77 78 79 80
81 82 83 84 85
86 87 88 89 90
91 92 93 94 95
96 97 98 99
100
VAV-SVX08E-EN 41

Wiring Diagrams

Note: See programming guides listed below for detailed wiring information on the following:
UCM 4.2: VAV-SVX01*-EN UC400: VAV-SVX07*-EN VV550: VAV-SVP01*-EN

Heaters with Contactors

Figure 25. Single-duct units (typical of single phase voltages - 1 leg)
42 VAV-SVX08E-EN
Figure 26. Single-duct units (typical of single phase voltages - 2 leg)
Wiring Diagrams
VAV-SVX08E-EN 43
Wiring Diagrams
Figure 27. Single-duct units (typical of three phase voltages)
44 VAV-SVX08E-EN
Figure 28. Fan-powered units (electronic or DDC/UCM)
Wiring Diagrams
VAV-SVX08E-EN 45
Wiring Diagrams
Figure 29. Fan-powered units (pneumatic controls)
46 VAV-SVX08E-EN
Figure 30. Fan-powered control boxes
FOR SERIES FAN POWERED TERMINAL UNITS ONLY.
EXTERNAL TO CONTROL BOX.
OPTIONAL OR ALTERNATE CIRCUITRY
DISCONNECT SWITCH, FUSE, & SCR ARE LOCATED
DETERMINED BY MOTOR VOLTAGE ON ORDER.
FUSE IS OPTIONAL.
VOLTAGE FOUND ON UNIT NAMEPLATE.
6.
5.
4.
CAPACITOR IS INSTALLED ON FAN HOUSING.
FACTORY INSTALLED BY OTHERS
3.
2.
NOTES:
1.
NO
P.E. SWITCH-2
CC
P.E. SWITCH-1
BK
NC
BK
NC
BK
NO
NO
NC
C
6.
6.
6.
2.
2.
2.
5.
5.
5.
3.
3.
3.
4.
4.
4.
}
BK
24V
1
3
2
4
R
MOTOR
RELAY
BR
TRANSFORMER
FUSE
BK
BK
W
GROUND
SCREW
GREEN
DISCONNECT
SWITCH
BK
W
L1
N
24V
BK
BL
Y
CONTROLLER
CAPACITOR
BR
BR
FAN
MOTOR
BLOCK
TERMINAL
W
BK
BR R
BK
CONTROL
SPEED
MOTOR
W
W
W-COM
BK
LINE VOLTAGE
OR FROM HEATER TERMINAL
TO VAV
Fan-powered Control Box with Electronic or DDC Controls
CAPACITOR
MOTOR
FAN
SWITCH
DISCONNECT
OR FROM HEATER TERMINAL
LINE VOLTAGE
Fan-powered Control Box with Pneumatic Controls Duct Pressure Switch Option
BR
BR
TERMINAL
W-COM
BK
W
BK
BLOCK
R
24V
1
3
TRANSFORMER
MOTOR
BK
BR
RELAY
24V
BK
2
4
GREEN
GROUND
SCREW
CONTROL
SPEED
MOTOR
W
W
FUSE
BK
BK
BK
W
W
BK
L1
N
DUCT PRESSURE
SWITCH
CAPACITOR
MOTOR
FAN
Fan-powered Control Box with Pneumatic Controls
BR
BR
P.E. SWITCH
TERMINAL
W-COM
W
BK
BLOCK
BK
CONTROL
SPEED
MOTOR
W
W
LINE VOLTAGE
SWITCH
DISCONNECT
OR FROM HEATER TERMINAL
GREEN
GROUND
SCREW
FUSE
BK
BK
BK
BK
W
W
L1
N
BK
C
NO
NC
DUCT PRESSURE MAIN CONTROL
FAN CONTROL BOX FAN CONTROL BOX
FAN CONTROL BOX
CAPACITORS BEFORE SERVICING.
DISCHARGE MOTOR START/RUN
FAILURE TO DISCONNECT POWER BEFORE SERVICING CAN CAUSE SEVERE PERSONAL INJURY OR DEATH.
UNIT TERMINALS ARE NOT DESIGNED TO ACCEPT OTHER TYPES OF
FAILURE TO DO SO MAY CAUSE DAMAGE TO THE EQUIPMENT.
USE COPPER CONDUCTORS ONLY!
CONDUCTORS.
SERVICING.
REMOTE DISCONNECTS BEFORE
HAZARDOUS VOLTAGE!
DISCONNECT, LOCK OUT AND TAG ALL ELECTRIC POWER INCLUDING
WARNINGWARNING
CAUTIONCAUTION
}
}
}
Wiring Diagrams
VAV-SVX08E-EN 47
Wiring Diagrams
FOR SERIES FAN POWERED TERMINAL UNITS ONLY.
EXTERNAL TO CONTROL BOX.
OPTIONAL OR ALTERNATE CIRCUITRY
DISCONNECT SWITCH, FUSE, & SCR ARE LOCATED
DETERMINED BY MOTOR VOLTAGE ON ORDER.
FUSE IS OPTIONAL.
VOLTAGE FOUND ON UNIT NAMEPLATE.
5.
4.
3.
FACTORY INSTALLED BY OTHERS
2.
NOTES:
1.
NO
P.E. SWITCH-2
CC
P.E. SWITCH-1
BK
NC
BK
NC
BK
NO
5.
3.
4.
4.
4.
RED
NEUT.
W
BK
G
R
RED
24V
BL
Y
R
BK
NEUT.
RED
G
W
RED
24V
BL
Y
1
24V
3
2
4
RED RED
G
W
BK
R
24VNEUT.
BK
BOARD
ECM
ECM
BOARD
MOTOR RELAY
ECM
BOARD
}
Fan-powered Control Box w/ ECM with Electronic or DDC Controls
(Depending on the size of the unit, the ECM board may or may not be located in the fan control box.)
OR FROM HEATER TERMINAL
LINE VOLTAGE
Fan-powered Control Box with Pneumatic Controls
LINE VOLTAGE
OR FROM HEATER TERMINAL
DUCT PRESSURE MAIN CONTROL
CORRECTION
PRESSURE
SWITCH
DUCT
C
NC
TRANSFORMER
BK
24V
Y
BL
CHOKE
BL
NO
BL
DISCONNECT
BK
SWITCH
3.
FUSE
FACTO R
POWER
W
BK
W
SCREW
2.
GROUND
GREEN
GR
TERMINAL
BK
BLOCK
MOTOR
FAN
Fan-powered Control Box w/ ECM with Pneumatic Controls
Duct Pressure Switch Option
P.E. SWITCH
DISCONNECT SWITCH
C
FUSE
NC
CORRECTION CHOKE
TRANSFORMER
NO
BK
BL
Y
24V
BK
POWER FACTOR
BLOCK
2.
W
BK
W
FAN
MOTOR
TERMINAL
GR
GREEN GROUND SCREW
BK
5.
CORRECTION CHOKE
POWER FACTOR
FAN CONTROL BOX
TRANSFORMER
BK
W
DISCONNECT
FUSE
3.
W
2.
SWITCH
3.
24V
BL
Y
BLOCK
TERMINAL
OR FROM HEATER TERMINAL
GR
L1
GROUND SCREW
GREEN
N
LINE VOLTAGE
BK
W
MOTOR
FAN
CONTROLLER
TO VAV
Y
BK
FAN CONTROL BOX
FAN CONTROL BOX
CAPACITORS BEFORE SERVICING.
DISCHARGE MOTOR START/RUN
FAILURE TO DISCONNECT POWER BEFORE SERVICING CAN CAUSE SEVERE PERSONAL INJURY OR DEATH.
UNIT TERMINALS ARE NOT DESIGNED TO ACCEPT OTHER TYPES OF
FAILURE TO DO SO MAY CAUSE DAMAGE TO THE EQUIPMENT.
USE COPPER CONDUCTORS ONLY!
CONDUCTORS.
SERVICING.
REMOTE DISCONNECTS BEFORE
HAZARDOUS VOLTAGE!
DISCONNECT, LOCK OUT AND TAG ALL ELECTRIC POWER INCLUDING
CAUTION
CAUTION
WARNING
WARNING
}
}
}
Figure 31. Fan-powered units with ECM
48 VAV-SVX08E-EN
Figure 32. Fan-powered low-height units
CAUTION
WARNING
Wiring Diagrams
Fan-Powered Low-Height Control Box with Electronic or DDC Controls
LINE VOLTAGE
OR FROM HEATER TERMINAL
BK
4.
BK
FUSE
BK
5.
}
L1
N
GREEN
GROUND
SCREW
DISCONNECT
W
SWITCH
2.
W
2
1
BK
MOTOR
4
RELAY
BR
24V
3
R
WARNING
HAZARDOUS VOLTAGE!
DISCONNECT, LOCK OUT AND TAG ALL ELECTRIC POWER INCLUDING REMOTE DISCONNECTS BEFORE SERVICING.
DISCHARGE MOTOR START/RUN CAPACITORS BEFORE SERVICING.
FAILURE TO DISCONNECT POWER BEFORE SERVICING CAN CAUSE SEVERE PERSONAL INJURY OR DEATH.
CAUTION
USE COPPER CONDUCTORS ONLY!
UNIT TERMINALS ARE NOT DESIGNED TO ACCEPT OTHER TYPES OF CONDUCTORS.
FAILURE TO DO SO MAY CAUSE DAMAGE TO THE EQUIPMENT.
CAPACITOR
BR
MOTOR
SPEED
CONTROL
TERMINAL
BLOCK
3.
2.
BR
BR
W or BR
FAN
MOTOR
W
W
W
W
BK
TRANSFORMER
CAPACITOR
BR
BK
W
24V
FAN CONTROL BOX
Y
BL
3.
BR
BR
R
MOTOR 2
(SIZE 10 ONLY)
W
DUCT PRESSURE MAIN CONTROL
6.
BK
NC
P.E. SWITCH-2
NO
CC
NO
BK
NC
P.E. SWITCH-1
BK
NOTES:
1.
2.
DISCONNECT SWITCH, FUSE, & SCR ARE LOCATED EXTERNAL TO CONTROL BOX.
3.
CAPACITOR IS INSTALLED ON FAN HOUSING.
4.
FUSE IS OPTIONAL.
5.
DETERMINED BY MOTOR VOLTAGE ON ORDER. VOLTAGE FOUND ON UNIT NAMEPLATE.
6.
FOR SERIES FAN POWERED TERMINAL UNITS ONLY.
FACTORY INSTALLED BY OTHERS OPTIONAL OR ALTERNATE CIRCUITRY
FAN
}
BK
TO VAV
CONTROLLER
Fan-Powered Low-Height Control Box with Pneumatic Controls
Duct Pressure Switch Option
BL
6.
C
DUCT
PRESSURE
SWITCH
NO
NC
LINE VOLTAGE
OR FROM HEATER TERMINAL
L1
N
BK
W
DISCONNECT
W
BK
4.
FUSE
BK
5.
GROUND
SWITCH
TRANSFORMER
GREEN
SCREW
BK
BL
24V
CAPACITOR
MOTOR
SPEED
CONTROL
2.
TERMINAL
BLOCK
2
Y
1
MOTOR
RELAY
Fan-Powered Low-Height Control Box with Pneumatic Controls
LINE VOLTAGE
OR FROM HEATER TERMINAL
FUSE
4.
BK
L1
BK
BK
C
P.E. SWITCH
NO
N
W
NC
}
W
DISCONNECT
5.
GREEN
GROUND
SCREW
SWITCH
BK
BK
2.
BR
MOTOR SPEED
CONTROL
2.
TERMINAL
BLOCK
3.
BR
CAPACITOR
WW
BR
24V
W
BR
2.
BR
MOTOR
W
W
3.
BR
WW
BK
4
BL
3
FAN
BK
FAN CONTROL BOX
FAN
MOTOR
W
BK
W
W
BK
FAN CONTROL BOX
CAPACITOR
CAPACITOR
3.
BR
3.
BR
MOTOR 2
(SIZE 10 ONLY)
BR
FAN
MOTOR 2
(SIZE 10 ONLY)
W
BK
FAN
W
BK
VAV-SVX08E-EN 49
Wiring Diagrams
FOR SERIES FAN POWERED TERMINAL UNITS ONLY.
EXTERNAL TO CONTROL BOX.
OPTIONAL OR ALTERNATE CIRCUITRY
DISCONNECT SWITCH, FUSE, & SCR ARE LOCATED
DETERMINED BY MOTOR VOLTAGE ON ORDER.
FUSE IS OPTIONAL.
VOLTAGE FOUND ON UNIT NAMEPLATE.
5.
4.
3.
FACTORY INSTALLED BY OTHERS
2.
NOTES:
1.
NO
P.E. SWITCH-2
CC
P.E. SWITCH-1
BK
NC
BK
NC
BK
NO
5.
W
G
BK
R
NEUT.
RED
24V
RED
BL
NEUT.
RED
24V
RED
R
BK
W
G
BL
BL
4
W
G
R
BK
NEUT.
RED
BK
24V
RED
24V
3
1
2
BOARD
ECM
BOARD
ECM
MOTOR RELAY
BOARD
ECM
OR FROM HEATER TERMINAL
LINE VOLTAGE
Fan-Powered Low-Height Control Box w/ ECM with Pneumatic Controls
DUCT PRESSURE MAIN CONTROL
Fan-Powered Low-Height Control Box w/ ECM with Pneumatic Controls
Duct Pressure Switch Option
(SIZE 10 ONLY)
DISCONNECT SWITCH
FUSE
3.
TRANSFORMER
BK
BLOCK
TERMINAL
W
2.
24V
BL
Y
BK
W
FAN
MOTOR
GR
GREEN GROUND SCREW
4.
W
BK
BK
W
MOTOR 2
FAN
TO VAV
OR FROM HEATER TERMINAL
LINE VOLTAGE
MOTOR
BL
DUCT
SWITCH
PRESSURE
TRANSFORMER
BL
BK
24V
Y
BL
C
NC
NO
FUSE
3.
BK
BK
DISCONNECT SWITCH
2.
W
W
SCREW
GROUND
GREEN
GR
W
BK
4.
Y
BK
TERMINAL
BLOCK
W
FAN FAN
(SIZE 10 ONLY)
MOTOR 2
CONTROLLER
NO
P.E. SWITCH
C
NC
DISCONNECT SWITCH
FUSE
3.
BK
W
TRANSFORMER
BK
24V
BL
Y
BLOCK
TERMINAL
2.
W
GROUND SCREW
GREEN
BK
W
GR
4. FAN
MOTOR
Y
W
BK
(SIZE 10 ONLY)
MOTOR 2
FAN
LINE VOLTAGE
OR FROM HEATER TERMINAL
5.
Fan-Powered Low-Height Control Box w/ ECM with Electronic or DDC Controls
(Depending on the size of the unit, the ECM board may or may not be located in the fan control box.)
Y
CAUTION
CAUTION
WARNING
WARNING
}
}
FAN CONTROL BOX
FAN CONTROL BOX
FAN CONTROL BOX
CAPACITORS BEFORE SERVICING.
DISCHARGE MOTOR START/RUN
FAILURE TO DISCONNECT POWER BEFORE SERVICING CAN CAUSE SEVERE PERSONAL INJURY OR DEATH.
UNIT TERMINALS ARE NOT DESIGNED TO ACCEPT OTHER TYPES OF
FAILURE TO DO SO MAY CAUSE DAMAGE TO THE EQUIPMENT.
USE COPPER CONDUCTORS ONLY!
CONDUCTORS.
SERVICING.
REMOTE DISCONNECTS BEFORE
HAZARDOUS VOLTAGE!
DISCONNECT, LOCK OUT AND TAG ALL ELECTRIC POWER INCLUDING
}
}
Figure 33. Fan-powered low-height units with ECM
50 VAV-SVX08E-EN

Maintenance

Periodic maintenance of the VariTrane product is minimal, but necessary for efficient operation. Routine maintenance consists of inspecting/replacing the air filter s of the fan-powered terminals.
Motors
Both the PSC (permanent split capacitor) and the ECM (Electrically Commutated Motor) require no lubrication during its normal life of operation.
Fan Wheel
Periodically, the fan wheel should be inspected for dirt or debris and cleaned as necessary.
Filter
The filter on fan-powered terminals will need to be inspected/replaced routinely depending on the environmental conditions of the plenum.
Filter Change Out
To remove the filter, turn each of the filter retaining clips 90° (CW or CCW)
Remove the filter and replace with new filter of the same frame size.
Return the filter clips to their retainng position by turning them 90° (CW or CCW) back to their original position.
Water Coil
Water coils should be inspected and the fins should be cleaned periodically.
Water coils have been provided with an access panel as standard to assist with inspection and cleaning.
Figure 34. Standard motor removal
Standard height fan-powered series and parallel fan motors are replaceable through the filter opening and the standard sliding side access panel. To access the fan motor, the fan housing must be detached by removing the mounting bolts that hold the housing to the fan board. Removing the entire housing allows the fan motor, fan housing, and fan wheel to be re-aligned on a workbench or floor and prevent any possible fan wheel rubbing that may occur. Removing the housing will provide access to the motor shaft set screw that holds the fan wheel to the motor shaft.
Fan Motor Replacement
WARNING
Hazardous Voltage w/Capacitors!
Disconnect all electric power, including remote disconnects and discharge all motor start/run capacitors before servicing. Follow proper lockout/ tagout procedures to ensure the power cannot be inadvertently energized. For variable frequency drives or other energy storing components provided by Trane or others, refer to the appropriate manufacturer’s literature for allowable waiting periods for discharge of capacitors. Verify with an appropriate voltmeter that all capacitors have discharged. Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury.
For additional information regarding the safe discharge of capacitors, see PROD-SVB06A-EN.
VAV-SVX08E-EN 51
Maintenance
Bottom View
The low-height fan assembly was designed with an inlet ring that assists with removal of the fan motor. To access the fan motor assembly, the bottom panel must be removed. The inlet ring is held in place by six bolts and three motor mount bolts. Remove these bolts and the motor and fan wheel will come out of the fan housing.
Figure 35. Low-height motor removal
SCR Assembly
SCR solid state relays are used to switch a single heater stage on and off. An intelligent (Master) relay is used for all single phase applications. For three phase applications, a Master-Slave configuration is used to switch two legs of three phase power to the heater stage. The Master Relay controls one leg independently, and provides a control signal to the Slave Relay, which controls the second leg.
Figure 36. Typical heat sink fin orientation
Every Master or Master/Slave relay combination is mounted on a heat sink to prevent the relays from overheating during normal operation. The SCR assembly must always be mounted with the heat sink fins oriented vertically (See Figure 36, p. 52), with a minimum clearance of ½" on all sides of the heat sink for cooling. Where additional cooling slots are provided in the heater, the VAV unit must be mounted with a minimum of 1" clearance in front of the slots.
When the 0-10 VDC control voltage is present at the Master relay in both single and three phase applications, an "ON" indicating LED light on the Master relay will blink continually (approximately 0.5 seconds on, 1.0 seconds off). If the load side voltage is also present at the relay(s), the Master relay LED and the Slave relay LED blink rate will increase as the control signal increases. When the control signal reaches a maximum of 10VDC, all LEDs will be lit continuously, indicating that the relays are full-open and continuously conducting. If the control signal is present in three phase applications while the load side voltage is not, only the Master relay LED will light and the blink rate will be constant.
If the SCR assembly does not appear to be functioning properly, verify that all required voltages are present and all that all wiring is properly connected. If all these conditions are verified, and the SCR LED(s) does not light and/or the SCR relay(s) does not conduct, the entire SCR heat sink assembly should be changed out. Individual Master or Slave relays should not be replaced.
52 VAV-SVX08E-EN

Installation of Diffusers

General

All units must be installed upright and level as indicated by
the arrow on the side of the units. Return air slots should be placed perpendicular and offset to the slot diffusers to avoid short-circuiting of air distribution patterns.
Place the unit in its approximate final position and check that it is upright and level. For single-slot units, engage the back of the diffuser over the t-bar with an edge and both ends resting on the t-bar. For double-slot units, slide the unit over the t-bar. For center-notch units, place diffuser over the t-bar, straddling it across a t-bar and resting on the units ends.
If the unit has a fire damper, make sure that the damper is still fully open. Diffuser discharge must always be flush with the ceiling tiles to assure the proper airflow (Coanda effect).
Diffusers require specific installation information when mounting to a desired ceiling type. Select the ceiling type that closely matches the job site application and use the following procedures.

T-Bar Ceiling

Finish installation of the diffuser in t-bar ceiling. (See
Figure 37, p. 53.) Follow these procedures before the
ceiling construction is completed.
1. Position the diffuser at each end resting directly on the structural t-bar for support and the t-bar fitting into the channel provided at the unit discharge air throw.
2. A ceiling tile support flange is provided on each side of the discharge slot of the unit. Trim ceiling tile approximately 1½ inches each to allow for width of discharge slot. For revealed edge ceilings, tile must be cut in a “Z” pattern.
3. Install ceiling tiles in usual manner with cut edges resting
on the flanges of the air slot.

Concealed Spline Ceiling

Follow these procedures to finish installation of control and satellite diffusers and concealed spline for suspension ceilings before completing the ceiling construction (Figure 38, p. 53).
Place the units in their approximate final positions. If using the trim angle diffuser, its slots must be even with the spline level. If applying the trim accessory, the bottom of the diffuser must be level with the finished ceiling.
If installing the trim accessory, insert the trim into the ceiling opening from below and engage the diffuser slot to the trim t-bar structure. With bottom flange of trim accessory against the ceiling, and using the pre-drilled holes in the flange as a guide, drill holes in the flange of the diffuser. Join the diffuser and trim accessory with self­taping sheet metal.
Figure 38. Diffuser with trim accessory installation in
concealed spline ceiling
Figure 37. Diffuser installation in t-bar ceiling
VAV-SVX08E-EN 53
Installation of Diffusers

Drywall/Plaster Ceiling

Finish installation of diffusers in plaster ceiling. Follow these procedures before completing the ceiling construction (Figure 39, p. 54).
NOTICE:
Equipment Damage!
Do not install trim frame into ceiling using screws.
When diffuser is placed on the trim frames, it will pull
out.
1. Suspend the units above the intended ceiling level and their approximate horizontal positions and finish running flexible ductwork.
2. After drywall and/or plaster is installed, cut openings to receive the diffuser air outlets. Also, allow for access openings to complete installation and service of the unit.
3. Slide the trim accessory up and into the ceiling opening. four guide holes in the lip of the diffuser slot. Lower unit onto trim frame and attach with sheet metal screws.
Note: The bottom of the throat section must be parallel to
Using the rim accessory as a template, drill
the ceilings for proper air distribution.
Figure 39. Diffuser with trim accessory installation in
plaster ceiling
Diuser Flange
Trim Accessory
Plaster trim frame attaches with 2–4 tension clips on the side of the diffuser.
54 VAV-SVX08E-EN
Trane optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the leader in creating and sustaining safe, comfortable and energy efficient environments, Trane offers a broad portfolio of advanced controls and HVAC systems, comprehensive building services, and parts. For more information, visit www.Trane.com.
Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.
© 2014 Trane All rights reserved
VAV-SVX08E-EN 16 Sep 2014
Supersedes VAV-SVX08D-EN (27 Jun 2013)
We are committed to using environmentally
conscious print practices that reduce waste.
Loading...